Escolar Documentos
Profissional Documentos
Cultura Documentos
Total
Rebate if any
Grand Total
NOTE :- Quoted Rate shall be exclusive of GST.
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
Part-A(Building works)
Item
Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
no.
Single pile
b All works from plinth level upto floor V level Cum 120.00
Providing and laying in position machine batched
and machine mixed design mix M-30 grade
cement concrete for reinforced cement concrete
work, using cement content as per approved design
mix, including pumping of concrete to site of laying
11 but excluding the cost of centering, shuttering,
finishing and reinforcement, including admixtures in
recommended proportions as per IS: 9103 to
accelerate, retard setting of concrete, improve
workability without impairing strength and durability
as per direction of Engineer-in-charge.
b All works from plinth level upto floor V level Cum 4758.00
FLOORING
Providing flat brick soling under foundation, floor,
plinth beam including packing with coarse sand and
watering etc complete as directed with bricks class
18 sqm 500.00
designation-75 in cement mortar in proportion 1:4
including curing complete as specified and as
directed.
28 DADO
Providing and fixing 1st class degital ceramic tiles
of approved designs and makes of minimum
thickness 5.6 mm in dado in any pattern over 12
mm thick cement plaster 1:3 (1 cement : 3 coarse
sand) and jointed with tile jointing compound of
approved manufacturer complete as directed.
57 Providing and fixing ball bearing for rolling shutters. Each 6.00
Extra for providing grilled rolling shutters
manufactured out of 8 mm dia M.S. bar instead of
58 Sqm 4.00
laths as per design approved by Engineer-in-
charge, (area of grill to be measured).
a 10 x 60 mm Each 2400.00
FINISHING
82 WATER PROOFING
Providing water proofing treatment with best quality
acrylic polymer modified cementitious composite
slurry coating and fibre glass cloth of approved
brand over sunken floors & terraces as per
manufacturer’s specifications and as approved by
Engineer-in-charge. The waterproofing membrane
applied shall be subjected to water ponding test by
a Sqm 1152.00
filling minimum 50 mm water for 2-3 days or as
specified by Engineer - In charge. Areas to be
observed from bottom and all wet spots & water
leakage area should be marked for treatment. If the
wet areas are observed, they should be treated by
reapplication of waterproofing membrane.(sunken
floor of toilet & kitchen, tiolet walls, )
MISCELLANEOUS ITEMS
Providing and fixing 40mm dia G.I. pipe for spout
85 including cutting holes in walls and making good the
same.
ALUMINIUM WORKS
91 EXPANSION JOINT
Expansion Joints Treatment with Sikadur Combiflex
a
System
Total of Part-A
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
Part-B(Sanitary and water supply works)
Item
Description Unit Quantity Rate in figure (Rs.) Rate in words Total Amount(Rs.)
no.
(b) 110 mm inlet and 63 mm outlet (Floor Drains only) each 40.00
Total of Part-C
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
PART - D(i) : Fire Fighting works
Item
Description Unit Quantity Rate in figure (Rs.) Rate in words
no.
Sub-head -I Hydrants & Spinklers
Supplying and Fixing Single Headed Internal Hydrant Valve
oblique pattern with intantanneous S S coupling of 63 mm dia
with cast iron wheel ISI marked, conforming to IS: 5290 (Type A),
1 each 8
with 80 mm dia flanged inlet,with ABS cap and chain complete
with all accessroies etc. as required.
Make : GETECH/NEWAGE/SAFEX
Providing RRL Hose with ISI Marked (IS:636) 63 mm dia X15 M long
complete with instantaneous type Gun Metal 3 mm dia ISI Marked
2 male & female couplings (IS:903) bound & riveted to hose pipes with each 16
copper rivets and copper wire complete as reqd.
( MAKE: NIRMAL RUBBER/NEWAGE/BRG)
Supplying and Fixing First Aid Hose Reel, wall mounting swinging
type complete with drum & bracket of MS construction, spray
painted in Post office Red, confirming to IS 884/1995 with upto date
amendments, complete with the following as required. 36 Meter long
4 20 mm dia water hose Thermoplastic (Textile reinforced) Type - 2 each 16
as per IS : 12585 20 mm dia gun metal globe valve & nozzle. Drum
and brackets for fixing the quimpments on wall. Connection from riser
with stop valve (gun metal) & M.S. Pipe
MAKE : GETECH/NEWAGE/SAFEX
Supplying and Fixing of Weather Proof Hose Cabinet suitable for
external yard hydrant / FBIC fabricated out of 2 mm thick M.S.
sheet with 4 mm thick glazed glass door in front having locking
arrangements, suitable to accommodate external hydrant with
valve, hose reels, branch pipe / FBIC with all the necessary
5 pipes, accessories, fittings etc., mounted on wall or raised brick each 16
platform and duly painted with PO Red externally and white
internally with synthetic enamel paint, sign writing etc. complete in
all respects as required at site and having minimum following
dimensions. 900 mm x 600 mm x 450 mm deep
MAKE:GETECH OR SELF FEBRICATED
c 80 mm dia mtr. 75
f 40 mm dia mtr. 10
d 80 mm dia each 8
d 65 mm dia nos. 8
e 50 mm dia nos. 4
c 80 mm dia each 4
18 JOCKEY PUMPS:
Supply, Erection, Testing & commissioning of Jockey Pump
Horizontal end section single stage centrifugal type pump
complete with bronze impeller, mechanical seal capable of
delivering 180 liters/minute against a total head of 70 metres,
induction motor suitable for 415V, 50 Hz, Min 15 HP with 2900 RPM, set 1
TEFC type conforming to IP: 55, flexible coupling, coupling guard.
Common bedplate fabricated from mild steel channel, vibration
pads, isolation arrangement & RCC foundation.
MAKE:KIRLORKAR OR EQUIV.
19 TERRACE PUMPS:
a 80 mm dia mtr. 40
Supply & Erection of M.S.Fire Hose Box of size 900 x 600x 450 mm
approx.) fabricated from 16 SWG. M.S. Sheet of fully welded
construction with hinge front door with locking arrangement & partially
glazed with 5 mm thick glass powder coated fire red
26 nos. 8
finish paint with Fire Hose Box written on the front side of the glass
for internal hydrants to house 2 nos. hose pipes, 1 no. Branch pipe,
1 no. Hose reel & Landing valve 1 No.
MAKE:GETECH/NEWAGE/SAFEX
Supply, Erection, Testing & commissioning of Drawl of connection
with CI foot valve 150 mm dia (for fire tank)and 3 Meter G.I. 100 mm
27 nos. 1
dia (H) pipe, nuts, bolts, washers & 5mm thick rubber gasket etc.
MAKE:GETECH/NEWAGE/SAFEX
Fire brigade Two Way Inlet Valve with 2 nos. G.M 63 mm dia Male
instantaneous coupling with 100 mm flanged out let connection and
28 nos. 4
built in check valves
MAKE:GETECH/NEWAGE/SAFEX
Main Fire Pump Panel
set 1
Outgoing
1)200 Amps MCB , -2 Nos
2) 100 Amps MCB - 1 No
3) Fully Automatic delta starter (60 hp ) with LED illuminated
set 1
ON-OFF push button -2Nos.
4) Fully Automatic delta starter (15hp ) with LED illuminated
ON-OFF push button - 1 No.
5)Auxillary contactors for main, sprinkler and jockey pumps
6) Auto/ manual selector switch with control wiring for main,
sprinkler and jockey pump
7) Annunciator with hooter, accept/ reset push button with
control wiring
8) Currect Transformer (200/5A) --6 Nos
9) Currect Transformer (100/5A) --3 Nos
10) Ammeter 0-150 --3 Nos
11) Volt Meter 0-500--3 Nos
12) Single phase preventer--3 Nos
13) 3 Set Phase indication Lamps with Phuses
Supply of fire buckets Set of four nos. with MS stand with sand etc. as
31 Nos. 20
required.
Supply, Installation, Fixing of ABC stored Pressure Fire Extinguisher
with built – In Pressure Gauge to know the Ready ness of the
32 Extinguisher Squeeze Grip Handle as per IS:15683 with ISI mark. Nos 46
(6 kg capacity)
BRAND : GETECH / MINIMAX/ SAFEX
34 Manual Call Point & Hooter each floor area. Make:Agni Suraksha Nos 16
35 12 Zone Panel for Manual Call Box & Hooter to identify the Nos 4
36 Exit Board Auto Glow type for easy evcuation floor wise. Nos 24
Providing & fixing angle iron (40mm x 40mm x 5mm) door frame and
M.S sheet (2mm thick) sum glass shutter of size 2.1 mtr. X 1.2 mtr.
(N.S) with 25 mm x 3 mm angleframe all around & stiffenced in
37 between i/c hinges, handle, locking arrangement, painting with each 44
approved synthetic enamle paint i/c sign writing on glass at internal
hydrant including providing & fixing M.S. Sheet 2 mm thick on remaing
portion above door to close opening i/c painting etc. as required.
Nos 49
Each 670
Each 694
6 Supplying, fitting & fixing Duck Dectector.
Each 24
Each 6
Rm 5347
Nos 23
Each 8
Nos 330
Nos 342
Kitchen Nos 6
Each 20
Each 8
Supply , installation, testing & commissioning of M.S.
9 NOS 20
Junction Boxes.
Rm 3581.3
Each 222
Each 136
Wiring for light point/ fan point/ exhaust fan point/ call bell point
with 1.5 sq.mm FRLS PVC insulated copper conductor single core
cable in surface / recessed medium class PVC conduit, with
1 modular switch, modular plate, suitable GI box and earthing the
point with 1.5 sq.mm FRLS PVC insulated copper conductor single
core cable etc. as required.
Wiring for circuit/ submain wiring alongwith earth wire with the
2 following sizes of FRLS PVC insulated copper conductor, single core -
cable in surface/ recessed medium class PVC conduit as required.
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction Each
8 3.00
box/ wooden block including connections etc. as required.
Supplying and fixing following way, single pole and neutral, sheet
steel, MCB distribution board, 240 V, on surface/ recess, complete
10 with tinned copper bus bar, neutral bus bar, earth bar, din bar, -
interconnections, powder painted including earthing etc. as
required. (But without MCB/RCCB/Isolator)
13.3 Supplying and fixing single pole blanking plate in the existing Each 4.00
MCB DB complete etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for meter
19.7 1,060.00
loop earthing as required.
21.3 Above 185 sq. mm and upto 400 sq. mm meter 1,796.00
22.3 Above 185 sq. mm and upto 400 sq. mm meter 40.00
24.1 Upto 35 sq. mm (clamped with 1mm thick saddle) meter 2,238.00
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm meter
24.3 600.00
MS flat clamp)
-
CHAPTER 14- MISC. CIVIL ITEMS -
Providing, laying and fixing following dia G.I. pipe (medium class)
26 in ground complete with G.I. fittings including trenching (75 cm -
deep) and re-filling etc. as required
Providing, laying and fixing following dia RCC pipe NP2 class (light
duty) in ground complete with RCC collars, jointing with cement
27 -
mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm
deep) and refilling etc. as required.
vi) All ammeters with C.T's and voltmeter and energy meters with
necessary fuses.
vii) Panel components as specified.
viii) MS base frame.
ix) All switch gear to have short circuit levels as specified.
2.00 MV CABLE
Supply of heavy duty 1100V grade LT XLPE insulated sheathed &
2.1 armoured cables with aluminium / copper conductors as specified
and required.
2.1.1 4C X 10sq.mm. Al. Ar. XLPE Cable rm 2,324.00
Supply and fixing of shock treatment chart with glass and each
5.2 2.00
aluminium frame on wall in Bengali, Hindi and English
5.3 Supply of First Aid box with all necessary materials and medicines each 1.00
6 EXTERNAL LIGHTING -
Supply & fixing of Junction box with clamp on street light pole /
recessed in gate pillars, comprising of 6A SP MCB with elmex
terminals suitable for terminating incoming and out going cables
6.4 no. 44.00
of upto 3 core 10 sq.mm 1.1 kV grade armoured PVC insulated and
covered cables including bolt,nut & screws, D - clamp etc. as
complete and as directed by Engineer - in - charge.
Supply and fixing of integral LED AVIATION Light with double lamp
6.6 nos 1.00
including all necessary accessories as required.
18.11 Supply testing commessioning of KTS reception phone of REPUTED pcs 2.00
make
18.13 Supply testing commessioning of Desktop Computer For Viewing pcs 2.00
Cameras from the reception for intercom of REPUTED make
18.21 Accessories for keeping camera /network switch accessories at the pcs 80.00
place of installation
DIESEL GENERATOR
4.00 DIESEL GENERATOR SET
4.1,1 160 KVA (with Auto mains failure Panel) each 1.00
4.1.2 1250 KVA each 1.00
1250 KVA Auto mains failure, Auto load sharing & Auto
4.1.2.1 synchronization Panel
4.1.3 500 KVA (with Auto mains failure Panel) each 1.00
7.00 LIFT
Wiring for circuit/ submain wiring alongwith earth wire with the
2 following sizes of FRLS PVC insulated copper conductor, single core
cable in surface/ recessed medium class PVC conduit as required.
Supplying and fixing following way, horizontal type three pole and
neutral, sheet steel, MCB distribution board, 415 V, on surface/
11 recess, complete with tinned copper bus bar, neutral bus bar,
earth bar, din bar, interconnections, powder painted including
earthing etc. as required. (But without MCB/RCCB/Isolator)
v) Brass glands and crimping lugs for sending and receiving ends.
vi) All ammeters with C.T's and voltmeter and energy meters with
necessary fuses.
vii) Panel components as specified.
viii) MS base frame.
ix) All switch gear to have short circuit levels as specified.
1.9 LAB BLOCK LIGHTING & POWR FLOOR PANEL (L1, L2, L3) each 2.00
1.10 APARTMENT BLOCK LIGHTING & POWR FLOOR PANEL A1 each 1.00
1.11 APARTMENT BLOCK LIGHTING & POWR FLOOR PANEL A2, A3 each 1.00
8 LAN SYSTEM
LAN NETWORK SYSTEM
PoE+ 24 Port Switch
The switch should have 24 x 10/100/1000Base t ports plus 4x
1000x SFP ports .Min 370 Watt PoE power budget and support for
IEEE 802.3af and IEEE 802.3at, Switch should have 16K MAC
entries table.Should have 8 Hardware QOS Queues per port ,OS
should support individual process (eg ssh , snmp, telnet, dhcp etc)
restart to prevent reboot in case of Software Process Crash by
running processes on top of Kernel.Switch should have switching NOS
8.1 21.00
fabric performance of minimum 56Gbps switch fabric. Layer 2, IP
v4 & IP v6 - Switch should be upgradeable to Open Shortest Path
First (OSPF) and VRRP.Should support less than 50 Millisecond
convergance for ring based architecture based on RFC
3619/REP/ERPS/G.8032 etc, Switch should have Port, vlan, IPv4,
IPv6, and time based Access Control Lists for both directions.
Switch should have Operating temperature: 32 to 122°F (0°C
to 45°C). Preffered Make : CISCO/Extreme /Juniper /Avaya
Core Switch
Switch should support stacking up to 8 switches or more with
stacking bandwidth of 40Gbps . The switch should have24x
10/100/1000Base t ports with 8x 1000x SFP ports .Min 4 10 G
based SFP+ port , Scalable to min 2 QSFP+ port , The switch should
be upgraded to 4 x SFP+ ports in future without changing the
base hardware . Should have min 2x Stacking port with min 40 NOS
8.2 1.00
Gbps stacking bandwidth from day 1 .Stacking should be ready
from day 1 with accessorries /cables.Stacking mechanism could be
achieved over a diversified location as minimum 800 Meters .
Switch should have dedicated 1 x 10/100/1000 BaseT port for Out
of band Management port. Switch should have Operating
temperature: 32 to 122°F (0°C to 50°C). Preffered Make :
CISCO/Extreme /Juniper /Avaya
CAT6 UTP cable - 4 pairs PVC - 23 AWG - 305 mtr Box
4 Pair CAT6 Unshielded, Twisted Pair (U/UTP) Cable 305
mtr per Box. Blue/Orange/White/Green in colour conforming
8.3 to the following standards like 23AWG, ANSI EIA/TIA 568 Box 46.00
C.2, EN50173, IEC 11801 3rd ED, frequency tested upto
700Mhz with Third Party Certificate etc. Cable Dia 6.1 ± 0.3,
Cross-member (+) fluted Spine/isolator for uniform
separation for all pairs. (Make : Legrand /Systemax/Hubbel)
11.1.1 1600 amps (S.C. rating for 1 sec - 50 KA) meter 22.50
11.1.2 630 amps (S.C. rating for 1 sec - 50 KA) meter 13.50
11.1.7 1600A Braided Cu Flexible ( electro-tinned with silver coated SETS 2.00
Socket) TPN
11.1.8 630A Braided Cu Flexible ( electro-tinned with silver coated SETS 1.00
Socket) TPN
12.1 Tap-off-Box with 250A, FP, ( I cs = Icu = 36kA ) , incomer MCCB each 4.00
12.2 Tap-off-Box with 100A, FP, ( I cs = Icu = 36kA ) , incomer MCCB each 2.00
13.1 20 amps switch WITH 6 pin 20 amp socket outlet each 32.00
Total of Part-E
Bill of Quantity
Name of Work: Construction of Research Park at IITG Campus.
Part-F(HVAC works)
Item Rate in figure
Description Unit Quantity Rate in words Amount (Rs.)
no. (Rs.)
Sub Head-A
VRF Airconditioning system
VRF/ VRV -IVth generation Outdoor units
4.00 SITC of Refnet joints for proper distribution of refrigernt through the
complete circuit for indoor and Outdoor
11.1 22 G Sq Mt 170
11.2 24 G Sq Mt 410
Sub Head-B
CHAPTER 7-MV CABLE LAYING
Laying and fixing of one number PVC insulated and PVC
1 sheathed / XLPE power cable of 1.1 kV grade of following size on
cable tray as required.
1.1 Upto 35 sq. mm (clamped with 1mm thick saddle) meter 2472
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm
1.3 MS flat clamp) meter 280
CHAPTER-4-CABLE TRAYS
CHAPTER-5-EARTHING
Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including
accessories, and providing masonry enclosure with cover plate
6.1 having locking arrangement and watering pipe etc. with Each 4
charcoal/coke and salt as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for
6.4 loop earthing as required. meter 80
Total of Part-F