Você está na página 1de 12

BC

Actuators for heating,


ventilation, air-conditioning

2. LM-5
Product Information
Damper actuators LM

i0026809
BC
The complete range of damper actuators for general use in HVAC systems

i0084803
Type LM NM SM AM GM LF AF(R)
Torque

4 Nm 8 Nm 15 Nm 18 Nm 30 Nm 4 Nm 15 Nm
For dampers Spring return
function

– – – – –
up to approx.

0.8 m2 1.5 m2 3 m2 3.6 m2 6 m2 0.8 m2 3 m2

For more information, please contact your Belimo Representative or order any brochures you need by fax.

Fax to: BELIMO (address overleaf)

Please send us product brochures on the following damper actuators:


䡺 NM... 䡺 SM... 䡺 AM... 䡺 GM... 䡺 LF... 䡺 AF... 䡺 AFR… 䡺 Electrical accessories

Please send also information on:


䡺 Motorized fire and smoke dampers
䡺 Variable air-volume control (VAV-Control)
䡺 Rotary-motion actuators and valves

ENG-93001-93221-05.02-2M · Printed in Switzerland · ZSD · Subject to technical changes


䡺 Linear-motion actuators and valves

䡺 Please call us back

Sender

Company:

Name:

Address:

Post Code: Country:

Tel.: Fax:

E-Mail: Date:
2
BC Contents

Selection table
LM LM LM LM LM
Torque 4 Nm 24 24 23 23 24
-S 0 0-S -S
R

Nominal voltage AC 24 V • • •
DC 24 V • • •
AC 230 V • •
Running time 80...110 s • • • • •
Control Open/Close Single-wire • • • •
2-wire • •
Modulating DC 0...10 V •
Direction of rotation reversible (right/left) • • • • •
Manual operation by pushbutton • • • • •
Auxiliary switch potential-free • •
Mechanical angle of rotation limiting • • • •
Electronic angle of rotation limiting •
Continuous position feedback •
Damper rotation with universal spindle clamp • • • • •

Actuators with damper rotation for square form-fit spindles (8 mm), actuators with running time (25…35 s), 60 mm linear adapter and actuators
conforming to US standards on request.

Damper actuators, Open/Close


ENG-93001-93221-05.02-2M · Printed in Switzerland · ZSD · Subject to technical changes

LM24 4

LM24-S 4

LM230 5

LM230-S 5

Mounting instructions 6
Note
Adjusting the auxiliary switch 7

Using BELIMO damper actuators


The actuators listed in this catalogue are
intended for the operation of air dampers in Damper actuator, modulating
HVAC systems.
LM24-SR 8
Torque requirements
When calculating the torque required to operate
dampers, it is essential to take into account all Mounting instructions 9
the data supplied by the damper manufacturer
concerning cross sectional area, design, mount- Control and monitoring functions 10
ing and air flow conditions.
3
LM24, LM24-S damper actuators 4 Nm BC
Dampers up to approx. 0.8 m2
Open/Close actuator
(AC/DC 24 V)
Single-wire or 2-wire control

Application
The type LM24(-S) is intended for the
operation of air control dampers in venti-
lation and air-conditioning systems.

Mode of operation
Open/Close control by single-wire or
2-wire system.

p0001707
Product features
Simple direct mounting on the damper
spindle by universal spindle clamp. An
antirotation device is supplied to prevent
unwanted rotation of the whole unit.

Manual operation by self-resetting push-


button when necessary (the gearing is
Wiring diagram disengaged while the pushbutton is held
Single-wire control 2-wire control depressed).
T ~ AC 24 V Connect via T ~ AC 24 V
! safety isolating Adjustable angle of rotation with me-
- + DC 24 V transformer
- + DC 24 V
chanical stops.

High functional reliability


The actuator is overload-proof, needs no
limit switches and halts automatically at
1 2 3 S1 S2 S3 1 2 3 S1 S2 S3 the end stops.

T ~~ T ~~ Flexible signalling 0…100%, with adjust-


LM24-S LM24-S able auxiliary switch (LM24-S only).
- + + 0...100% - + + 0...100%
Mounting instructions, page 6
w0226205

T ~~ Parallel connection of several T ~~


+ + LM24 + + LM24
actuators is possible. Power
- consumption must be observed! - Adjusting auxiliary switch LM24-S,
page 7.

ENG-93001-93221-05.02-2M · Printed in Switzerland · ZSD · Subject to technical changes


Technical data LM24, LM24-S Important
Nominal voltage AC 24 V 50/60 Hz, DC 24 V Read the notes about the use and torque
Nominal voltage range AC/DC 19.2…28.8 V requirements of the damper actuators on
For wire sizing 3 VA page 2.
Power consumption 2W
Connecting cable – motor 1 m long, 3 × 0.75 mm2
– auxiliary switch (LM24-S) 1 m long, 3 × 0.75 mm2
Auxiliary switch (LM24-S) 1 × SPDT 5(2.5) A, AC 250 V (adjustable 0…100% )
Direction of rotation selected with L/R switch Dimensions
Manual operation Pushbutton, self-resetting
Torque min. 4 Nm (at rated voltage) 6...16
Angle of rotation max. 95° (adjustable by mechanical stops)
59

Running time 80…110 s (0…4 Nm)


33.5

Sound power level max. 35 dB(A)


Position indication mechanical
89
Protection class III(safety low voltage) 116.2
Degree of protection IP 54 (bottom cable entry)
Ambient temperature range – 30… + 50 °C
1

Non-operating temperature – 40… + 80 °C


66.2

Humidity test to EN 60335-1


EMC CE according to 89/336/EEC, 92/31/EEC, 93/68/EEC
5.2

Low Voltage Directive CE according to 73/23/EEC


d0001805
0

Maintenance maintenance-free
22.1 94.1
Weight 650 g

4
BC LM230, LM230-S damper actuators 4 Nm

Dampers up to approx. 0.8 m2


Open/Close actuator (AC 230 V)
Control by single-pole contact
(single-wire control)

Application
The type LM230(-S) is intended for the
operation of air control dampers in venti-
lation and air-conditioning systems.

Mode of operation
Open/Close control by single-wire sys-
tem.

p0002707
Product features
Simple direct mounting on the damper
spindle by universal spindle clamp. An
Wiring diagram
antirotation device is supplied to prevent
N L1 AC 230 V To isolate from the main power supply, the system
must incorporate a device which disconnects the
unwanted rotation of the whole unit.
phase conductors (with at least a 3 mm contact gap).
Manual operation by self-resetting push-
button when necessary (the gearing is
disengaged while the pushbutton is held
depressed).
1 2 3 S1 S2 S3
Adjustable angle of rotation with me-
chanical stops.
0...100%
LM230-S
High functional reliability
The actuator is overload-proof, needs no
w0228803

Parallel connection of several actuators


limit switches and halts automatically at
LM230 with 1-wire control possible.
Power consumption must be observed. the end stops.

Flexible signalling 0…100%, with adjust-


Technical data LM230, LM230-S able auxiliary switch (LM230-S only).
Nominal voltage AC 230 V 50/60 Hz
Nominal voltage range AC 198…264 V Mounting instructions, page 6
For wiring sizing 12 VA Adjusting auxiliary switch LM230-S,
ENG-93001-93221-05.02-2M · Printed in Switzerland · ZSD · Subject to technical changes

Power consumption 1W page 7.


Connecting cable – motor 1 m long, 3 × 0.75 mm2
– auxiliary switch (LM230-S) 1 m long, 3 × 0.75 mm2 Important
Auxiliary switch (LM230-S) 1 × SPDT 5(2,5) A, AC 250 V Read the notes about the use and
– Switching point adjustable 0…100%  torque requirements of the damper
Direction of rotation selected with L/R switch actuators on page 2.
Manual operation pushbutton, self-resetting
Torque min. 4 Nm (at rated voltage)
Dimensions
Angle of rotation max. 95° (adjustable by mechanical stops)
Running time 80… 110 s (0… 4 Nm) 6...16

Sound power level max. 35 dB(A)


59
33.5

Position indication mechanical


Protection class II (all insulated)
89
Degree of protection IP 54 (bottom cable entry) 116.2
Ambient temperature range – 30… + 50 °C
Non-operating temperature – 40… + 80 °C
1

Humidity test to EN 60335-1


66.2

EMC CE according to 89/336/EEC, 92/31/EEC, 93/68/EEC


Low Voltage Directive CE according to 73/23/EEC
5.2
d0001805

Maintenance maintenance-free
0

Weight 650 g 22.1 94.1

5
6
6...16
m
in
.3
5
m
m

4
2
Mounting instructions LM24(-S), LM230(-S)

≈ 1 mm
2
1
3

3
5...6Nm

5
3
1
BC

m0001707

ENG-93001-93221-05.02-2M · Printed in Switzerland · ZSD · Subject to technical changes


BC Adjusting the auxiliary switch LM24-S, LM230-S

a) Referring to end stop 0


Option 1: Actuator at Procedure: – Turn the scale knob of the auxiliary switch clockwise (cw) from
left-hand end stop 0 until the tip of the arrow is pointing to the required switching
position. The switch in the example is set to .6 (2 scale divisions cw
from 0 correspond to 60% rotation).

S2 S2
S1 S1
S3 S3
0 .2
.4
.6
0 1 1 .8

– Now, when the actuator rotates clockwise, the switch will operate
at 60% angle of rotation. (Connection S1 to S3 made)

Option 2: Actuator at Procedure: – Depress the manual-operation pushbutton and move the actu-
switching position ator to the position where the auxiliary switch is needed to
operate (e.g. at 60% angle of rotation).
S2 S2
S1 S1
S3 S3
0 .2
.4
.6

m0003707
1 .8
0 1
m0002707

– Turn the scale knob of the auxiliary switch anticlockwise (ccw)


until the tip of the arrow is just past the scale zero. (Connection S1
to S3 made and switching position set for 60% angle of rotation)

b) Referring to end stop 1


Option 1: Actuator at Procedure: – Turn the scale knob of the auxiliary switch anticlockwise (ccw)
right-hand end stop from 1 until the tip of the arrow is pointing to the required
switching position. The switch in the example is set to .4 (6 scale divi-
sions ccw from 1 correspond to 60% rotation).
ENG-93001-93221-05.02-2M · Printed in Switzerland · ZSD · Subject to technical changes

S2 S2
S1 S1
S3 S3
0 .2
.4
.6
1 .8
0 1

– Now, when the actuator rotates anticlockwise, the switch will


operate at 60% angle of rotation. (Connection S1 to S3 made)

Option 2: Actuator at Procedure: – Depress the manual-operation pushbutton and move the
switching position actuator to the position where the auxiliary switch is needed to
operate (e.g. at 60% angle of rotation).
S2 S2
S1 S1
S3 S3
0 .2
.4
.6
m0005707

1 .8

0 1
m0004707

– Turn the scale knob of the auxiliary switch clockwise until the tip
of the arrow is just past the 1 on the scale. (Connection S1 to S3
made and switching position set for 60% angle of rotation)

7
LM24-SR damper actuator 4 Nm BC
Dampers up to approx. 0.8 m2
Modulating damper actuator
(AC/DC 24 V)
Control DC 0…10 V and posi-
tion feedback DC 2…10 V

Application
The type LM24-SR is intended for the
operation of air control dampers in venti-
lation and air-conditioning systems.
Mode of operation
The actuator is controlled by a standard
DC 0…10 V signal and runs to whatever
position is specified by the signal. The

p0003707
purpose of measuring voltage U is to
provide 0…100% electrical indication of
damper position and to act as a master-
slave control signal for other actuators.

Product features
Wiring diagram
Simple direct mounting on the damper

w0230803
T ~ AC 24 V Connect via Control manufacturers: ABB, AEG, Bälz, Centra, Con- spindle by universal spindle clamp. An
- + DC 24 V ! safety isolating
transformer
trolli, C.S.I., Danfoss, DIGI'Control, Elesta, GA, H.C.Sys-
tem, Honeywell, Inel, IWK, Johnson, Kieback & Peter,
antirotation device is supplied to prevent
unwanted rotation of the whole unit.
Y DC 0…10 V Landis & Staefa, Messner, Priva, RAM, R+S, Samson,
Satchwell, Sauter, SE-Electronic, Siemens, TA, Trend.
Steplessly adjustable angle of rotation
Measuring voltage U for position indicating or by integral potentiometer. Range match-
U DC 2…10 V
as master-slave control signal. ing of the working range and measuring
signal U is performed automatically by
% of set angle Reversing Reversing
switch L switch R the actuator.
100 Y=0 Y=0
Open Open
Manual operation by self-resetting push-
1 2 3 5
button when necessary (the gearing is
disengaged while the pushbutton is held
50 Closed Closed depressed).
T ~ Y U LM24-SR anticlock- clockwise- High functional reliability
- + wise-closing
damper
closing
damper The actuator is overload-proof, needs no
Parallel connection of several 0 Y
actuators is possible. Power 0 2 5 10 [ V ] limit switches and halts automatically at
consumption must be observed.
the end stops.
Electrical accessories (see Doc. 2.Z-.)
Technical data LM24-SR
SG..24 Positioners

ENG-93001-93221-05.02-2M · Printed in Switzerland · ZSD · Subject to technical changes


Nominal voltage AC 24 V 50/60 Hz, DC 24 V ZAD24 Digital position indicator
Nominal voltage range AC 19.2…28.8 V, DC 21.6…28.8 V
For wire sizing 4 VA Control and monitoring functions,
Power consumption 2W page 10
Connecting cable 1 m long, 4 × 0.75 mm2 Important
Control signal Y DC 0…10 V @ input resistance = 100 kΩ Read the notes about the use and torque
Operating range DC 2…10 V (for set angle of rotation) requirements of the damper actuators on
Measuring voltage U DC 2…10 V @ ≤ 0.5 mA (for set angle of rotation) page 2.
Synchronism tolerance ± 5%
Direction of rotation selected with L/R switch Dimensions
(at Y = 0 V) at switch position L  resp. R 
Manual operating Pushbutton, self resetting 6...16
Torque min. 4 Nm (at rated voltage)
59

Angle of rotation max. 95° (adjustable with potentiometer 20…100%)


33.5

Running time 80…110 s for  95° (0…4 Nm)


Sound power level max. 35 dB (A)
89
Position indication mechanical 116.2
Protection class III (safety low voltage)
Degree of protection IP 54 (bottom cable entry)
1

Ambient temperature range – 30... + 50 °C


66.2

Non-operating temperature – 40... + 80 °C


Humidity test to EN 60335-1
5.2

EMC CE according to 89/336/EEC, 92/31/EEC, 93/68/EEC


d0002805
0

Maintenance maintenance-free
22.1 94.1
Weight 620 g

8
BC Mounting instructions for LM24-SR

Mounting on anticlockwise-closing damper

m0006707
m
in
2
.3
5
m
m
3
6...16

1 1 2

5...6Nm
2 3
100%

1
20%

3 4 5

Mounting on clockwise-closing damper

m0007707
ENG-93001-93221-05.02-2M · Printed in Switzerland · ZSD · Subject to technical changes

m
in
.3
5

2
m
m

6...16

1
1 2

5...6Nm
2 3
100%

1
20%

3 4 5
9
LM24-SR Control and monitoring functions BC
Remote control 0...100% Minimum position

w0232205
Connect via Connect via
AC 24 V safety isolating AC 24 V safety isolating
T ~ ! transformer
T ~ ! transformer

T ~ Y Z SGA24, SGF24 T ~ SGA24, SGF24 Y[V]


Y Z
1 2 3 4 SGE24 1 2 3 4 SGE24
10 V
Positioner Positioner
Y DC 0...10 V
(from controller)
min.

1 2 3 5 1 2 3 5

T ~ T ~ 0V
Y U LM24-SR Y U LM24-SR 0% 100%
- + - + Angle of rotation

Parallel connection of further Parallel connection of further


actuators is possible (up to 10). actuators is possible (up to 10).

Override control Position indication


T ~ AC 24 V Connect via
T ~ AC 24 V Connect via
safety isolating safety isolating
! !
- + DC 24 V transformer transformer
- +
Y DC 0...10 V ZAD24
1 2 3 4
b a
Direction of
rotation

Reversing Reversing
a b switch L switch R
1 2 3 5
1 2 3 5
T ~
Y U LM24-SR
- + control mode T ~
Y U LM24-SR
Parallel connecting of further actuators is
possible. Note power consumption data. - +

Master-slave control (depending on position)


T ~ AC 24 V Connect via
safety isolating
!
- + DC 24 V transformer

ENG-93001-93221-05.02-2M · Printed in Switzerland · ZSD · Subject to technical changes


Y DC 0...10 V
Note ± 5% synchronism
tolerance between actuators

to next actuator

1 2 3 5 1 2 3 5

T ~ T ~
Y U LM24-SR Master Y U LM24-SR Slave
- + actuator - + actuator

Function monitoring
T ~ AC 24 V Connect via Procedure
safety isolating
!
- + DC 24 V transformer AC 24 V at terminals 1 and 2
Disconnect terminal 3:
– For direction of rotation "L":
actuator runs

1 2 3 5 – For direction of rotation "R":


actuator runs

T ~ Y U LM24-SR link terminals 2 and 3:


– actuator runs in the opposite direction
- +

10
BC

11
BC

Innovation, Quality and Consultancy:


A partnership for motorizing HVAC actuators

Air applications Water applications

Standard actuators and Safety actuators for VAV systems for indi- Mixing actuators and Globe valves and intelli-
spring-return actuators motorizing fire and vidual room air control motorized ball valves gent linear actuators –
for air control dampers smoke extraction for HVAC water circuits also for leading makes
in HVAC systems dampers of valve

Contact the following for further information:


Belimo Headquarters GB BELIMO Automation UK Limited CN BELIMO Actuators Ltd. IL Shemer Representations RO Mano Construct srl
The Lion Centre 18 FA3, 585 Longhua West-Road P.O. Box 296 Dr Felix 53, ap 14, sector 1
CH BELIMO Holding AG Hampton Road West 200232 Shanghai, China 56101 Yehud, Israel Bucuresti, Romania
Guyer-Zeller-Strasse 6 Feltham, Middlesex, Great Britain Tel. ++86 21 6469 2895 Tel. ++972 3 536 51 67 Tel. ++401 220 05 78
8620 Wetzikon, Switzerland TW 13 6DS Telefax ++86 21 6469 2909 Telefax ++972 3 536 05 81 Telefax ++401 221 59 95
Tel. ++41 (0)1 933 11 11 Tel. ++44 (0)20 8755 4411 E-Mail: shanghai@belimo.com.hk E-Mail: shemer@shemerep.co.il E-Mail: manoconstruct@fx.ro
Telefax ++41 (0)1 933 12 68 Telefax ++44 (0)20 8755 4042
E-Mail: info@belimo.ch CN BELIMO Beijing IN BELIMO Vitek Air Controls RU BELIMO Servomotors
E-Mail: belimo@belimo.co.uk
Internet: http://www.belimo.ch Rm 605, Beijing Hai Chang C-114 Lancelot, First Floor Russia Ltd.
HK BELIMO Actuators Ltd. Edifice, 44, Liang Ma Qiao Road S.V. Road, Borivali (West) Nizhnyaya Pervomaiskaya,
Room 208, 2/F Chao Yang District Mumbai 400 092, India 46 Bld.1, Office 303
New Commerce Centre 100016 Beijing, China Tel. ++91 22 806 21 63 105203 Moscow, Russia
Belimo Subsidiaries 19 On Sum Street, Shatin, N.T. Tel. ++86 10 6462 1382 Telefax ++91 22 806 21 63 Tel. ++7 095 965 74 64
AT/ BELIMO Automation Hong Kong Telefax ++86 10 6462 1383 E-Mail: bvac@bom2.vsnl.net.in Telefax ++7 095 965 74 73
HR/ Handelsgesellschaft m.b.H. Tel. ++852 26 87 17 16 E-Mail: beijing@belimo.com.hk IS Hitatækni ehf. E-Mail: belimo.russia@mtu-net.ru
HU/ Geiselbergstrasse 26–32 Telefax ++852 26 87 17 95 CY R.E.S. Ltd. Langholtsvegi 109 SE BELIMO Spjällmotorer AB

ENG-93001-93221-05.02-2M · Printed in Switzerland · ZSD · Subject to technical changes


SK/ 1110 Wien, Austria E-Mail: info@belimo.com.hk P.O. Box 8297 104 Reykjavik, Iceland Hägerstens Allé 88
SL Tel. ++43 (0)1 749 03 61-0 PL BELIMO Silowniki S.A. Nicosia, Cyprus Tel. ++354 5 88 60 70 129 37 Hägersten, Sweden
Telefax ++43 (0)1 749 03 61-99 ul. Zagadkl 21 Tel. ++357 (0)2 51 10 07 Telefax ++354 5 88 60 71 Tel. ++46 (0)8 88 07 00
E-Mail: info@belimo.at 02-227 Warszawa, Poland Telefax ++357 (0)2 49 65 47 E-Mail: fridmar@hitataekni.is Telefax ++46 (0)8 97 85 75
AU BELIMO Actuators Pty. Ltd. Tel. ++48 (0)22 817 35 10 E-Mail: IT BELIMO Servomotori S.r.l. E-Mail: info@belimo.se
Unit 10, 266 Osborne Avenue Telefax ++48 (0)22 817 35 06 reliance@spidernet.com.cy Via Stezzano, 5 SY Philippe A. Jebran
Clayton South, VIC 3169 E-Mail: info@belimo.pl CZ BELIMO CZ (Ing. Ivar Mentzl) 24050 Zanica BG, Italy P.O. Box 7791
Australia SG BELIMO Actuators Pte Ltd Charkovská 16 Tel. ++39 035 67 26 82 Damascus, Syria
Tel. ++61 (0)3 9551 0201 2, Jurong East Street 21 10100 Praha 10, Czech Republic Telefax ++39 035 67 02 00 Tel. ++963 11 231 6586
Telefax ++61 (0)3 9551 0215 #04-31F IMM Building Tel. ++420 (0)2 717 4 0 311 E-Mail: info@belimo.it Telefax ++963 11 231 4052
E-Mail: belimo@belimoactuators.com Singapore 609601 Telefax ++420 (0)2 717 43 057 E-Mail:
KR HANMO Corporation
CA BELIMO Aircontrols (CAN), Inc. Tel. ++65 6564 9828 E-Mail: info@belimo.cz 3rd Floor, Yeosam Bldg. 648-23 belimome@emirates.net.ae
5716 Coopers Ave., Units 14&15 Telefax ++65 6564 9038 DK BELIMO A/S Gangnam-Ku, Seoul, Korea TR BELIMO Otomasyon A.S.
Mississauga, Ontario L4Z 2E8 E-Mail: info@belimo.com.sg Thomas Helstedsvej 7A Tel. ++822 3453 8225 Hayriye Caddesi No. 16
Canada US BELIMO Aircontrols (USA), Inc. 8660 Skanderborg, Denmark Telefax ++822 3453 8228 TR-80060 Galatasaray-Istanbul
Tel. ++1 (1)905 712 31 18 43 Old Ridgebury Road Tel. ++45 86 52 44 00 Turkey
Telefax ++1 (1)905 712 31 24 LB Energy Center (EC)
P.O. Box 2928 Telefax ++45 86 52 44 88 Hamra, Leon Street, Shatilla, Tel. ++90 (0)212 249 76 43
E-Mail: webmaster@belimo.com Danbury, CT 06810 USA E-Mail: info@belimo.dk Telefax ++90 (0)212 243 02 58
Bldg. 4th Floor,
CH BELIMO Automation AG Tel. ++1 (1)203 791 99 15 E-Mail: info@belimo.com.tr
EE BELIMO Balticum AS P.O. Box 113-6955
Sales Switzerland Telefax ++1 (1)203 792 29 67 Töri 10 d Beirut, Lebanon TW Chianseng Enterprise Co. Ltd.
Guyer-Zeller-Strasse 6 E-Mail: webmaster@belimo.com 11313 Tallinn, Estonia Tel. ++961 (0)1 35 38 23 2F, No. 21, Tong Fong Street
8620 Wetzikon, Switzerland Internet: http://www.belimo.com Tel. ++372 6 140 811 Telefax ++961 (0)1 35 38 23 Taipei, Taiwan
Tel. ++41 (0)1 933 12 12 Telefax ++372 6 140 812 E-Mail: Tel. ++886 2 27 08 77 80
Telefax ++41 (0)1 933 12 66 E-Mail: info@belimo.ee belimome@emirates.net.ae Telefax ++886 2 27 02 90 90
E-Mail: verkch@belimo.ch Belimo Representatives and E-Mail: taiwan@belimo.com.hk
Internet: http://www.belimo.ch FI Oy Suomen BELIMO Ab NL BELIMO Servomotoren B.V.
Agencies Insinöörinkatu 2 Radeweg 25, 8171 MD Vaassen UA BELIMO Ukraine S.A.R.
DE BELIMO Stellantriebe AE BELIMO Automation 00810 Helsinki, Finland Postbus 300, 8160 AH Epe, 34-A, Ul. Yurkovskaya, Appt.No 2
Vertriebs GmbH Middle East Office Tel. ++358 (0)9 75 11 65 00 Netherlands 254080 Kiev, Ukraine
Welfenstr. 27, Postfach 72 02 30 P.O. Box 55427 Telefax ++358 (0)9 75 11 65 31 Tel. ++31 5 78 57 68 36 Tel./Telefax ++380 44 463 7586
70599 Stuttgart, Germany Dubai, U.A.E. E-Mail: belimo@belimo.fi Telefax ++31 5 78 57 69 15 E-Mail: comaster@belimo.kiev.ua
Tel. ++49 (0)711 1 67 83-0 Tel. ++971 (0)4 387 417 E-Mail: info@belimo.nl
Telefax ++49 (0)711 1 67 83-73 GR BELIMO Air Controls ZA BELIMO Actuators Southern Africa cc
Telefax ++971 (0)4 387 415 29, Tagm. Plessa, Kallithea NO BELIMO Spjeldmotorer A/S P. O. Box 2483
E-Mail: info@belimo.de E-Mail:
Internet: http://www.belimo.de GR 17674 Athens, Greece Konowsgate 5 Alberton 1450, South Africa
belimome@emirates.net.ae Tel. ++30 (0)1 94 00 766 0192 Oslo 1, Norway Tel. ++27 (0)11 868 5681
ES BELIMO Ibérica BE BELIMO Automation N.V.-S.A. Telefax ++30 (0)1 94 00 767 Tel. ++47 22 70 71 71 Telefax ++27 (0)11 900 2673
de Servomotores, S.A. Leuvensesteenweg 613 E-Mail: belimogr@tee.gr Telefax ++47 22 70 71 70 E-Mail: belimo@mega.co.za
C/San Romualdo, 12–14 1930 Zaventem, Belgium E-Mail: info@belimo.no
28037 Madrid, Spain IE Safegard Systems Ltd.
Tel. ++32 (0)2 757 92 95 Systems House, Unit 34 PH BELIMO Actuators Philippines
Tel. ++34 91 304 11 11 Telefax ++32 (0)2 757 90 36
Telefax ++34 91 327 25 39 Southern Cross Business Park Rm.# 507 Anita Build., 5th Floor
E-Mail: info@belimo.be Bray, Co Wicklow, Ireland 1300 Quezon Ave.,Cor.South Ave.
E-Mail: info@belimo.es
BG BELIMO Bulgaria Ltd. Tel. ++353 (0)1 2761600 1103 Quezon City, Philippines
FR BELIMO Servomoteurs j.k. Lagera, 3 Smolyanska Str. Telefax ++353 (0)1 2761611 Tel. ++63 (2) 373 5440
Z.A. de Courtry bl. 56, entr. B, ap. 50 E-Mail: info@safegard.ie Telefax ++63 (2) 373 5424
33, Rue de la Régale 1612 Sofia, Bulgaria E-Mail: philippines@belimo.com.hk
77181 Courtry, France Tel. ++3592 952 3470/1
Tél. ++33 (0)1 64 72 83 70 Telefax ++3592 545 995
Téléfax ++33 (0)1 64 72 94 09 E-Mail: belimo@intech.bg
E-Mail: mail@belimo.fr

Você também pode gostar