Escolar Documentos
Profissional Documentos
Cultura Documentos
A H Chowdhury, PhD
Professor
EEE, BUET
July 2018
Protection of Transmission Lines
2. Measuring elements
3. Timer elements
• Relaying provided at
each station A, B, C
• Arrow pointing
1.3
towards both
directions
indicates relays
operate for faults on
either sides
• Time lag indicated on
1.3 sec
arrow head
• Suitable for radial
1.3 sec
feeder in which
power flow is only in
one direction Graded time lag overcurrent protection of a radial feeder
Non-directional Time Graded Overcurrent
Protection
• Fault beyond C circuit breaker at C operates first, i.e., with relay time of
0.3 second
– Relays at B and A start operating but after about 0.3 second fault is cleared
and relays at A and B get reset
– If relay at C fails to operate, relay at B provides back-up protection
• For faults between B and C only CB at B operates and likewise
Transformers
1.3
Time setting
of relays in these
feeders should be
less than setting
of relays on main
1.3 sec
feeder
1.3 sec
Non-directional Time Graded Overcurrent
Protection
• Inverse definite minimum time delay relays used for obtaining
combination of current and time gradings
• Operating times of relays in consecutive stations can be 0.3, 0.8, 1.3, 1.8,
sec.
Non-directional Time Graded Overcurrent
Protection
• Earth fault relay is residually connected
• Two relays are employed for phase faults and one for earth fault
• Phase fault and earth fault relays are set for short circuits do not detect
over-loads of small magnitude
• Suppose Tm = 2 sec.
• From relay co-ordination point of view desired operating time To is say 1
sec.
• Time multiplier (TSM) is set to
Non-directional Time Graded Overcurrent
Protection
Disadvantages of Graded Time lag Overcurrent Relaying
1. Time lag has to be provided time lag not desirable on short circuits
2. Not suitable for ring mains or interconnected lines suitable for radial
lines with supply at one end only
4. Not suitable for important, long distance transmission lines where rapid
fault clearing necessary to ensure stability of systems
Directional Time and Current Graded
Overcurrent Protection
• Directional time and current graded systems suitable, where power can flow
to fault from both directions
– Circuit breakers on both sides should trip, so as to disconnect faulty line
– Such case occurs in parallel feeders, ring mains, T feeders, interconnected lines
• Long time delays occurring in graded time lag system can be partly
avoided
Employ high speed high set overcurrent relays
b) Fault currents for different types of fault are different brings a certain
difficulty in relay setting
c) For ring mains, T-feeders, parallel feeders etc. power can flow to fault
from either directions directional control is needed
Instantaneous and IDMT Protection
• Instantaneous + inverse definite minimum time (IDMT) relays for high
speed protection of radial lines
Coils of instantaneous element and IDMT element connected in series
Instantaneous overcurrent
protection of line
Characteristics of combined
instantaneous and IDMT
protection
Instantaneous and IDMT Protection
• Such protection can be effectively applied only if following conditions are
satisfied:
Fault level at sending end of line at least thrice that at receiving end of line
• Reach of over-current
relay depends on type
of fault and on source
impedance
Over-reaches to B2 if source
impedance decreases to Zs1
Plain Impedance Relay
Performance of simple impedance relay during normal load flow
• Impedance seen by relay during normal power flow is large and falls
outside trip area of relay operating characteristics
Plain impedance relay stable during normal operating conditions
Impedance seen
by relay during
normal load flow
Plain Impedance Relay
Effect of Arc Resistance on Reach of Simple Impedance Relay
• Under-reach in figure
Plain Impedance Relay
Reactance Relay
• Trip law of reactance relay:
Relay sensitive only to reactive part of impedance seen, and trips if reactive `
part less than a particular set value Xn
Let, (k1/k2) = Zn
• Flux due to operating voltage coil interacts with induced current due to current
coil to produce operating torque proportional to cos ( – τ)
• Restraining torque produced because
of fluxes created by operating and
polarizing voltage coils
• 3 phase fault-
measuring units can
cater for all 7 phase
faults [a-b, a-b-g, b-c,
b-c-g, c-a, c-a-g, a-b-c]
• 3 ground fault-
measuring units can
cater for all 3 ground
faults [a-g, b-g, c-g]
Distance Protection of a Three-phase Line
• 3 phase fault-measuring units can cater for all 7 phase faults [a-b, a-b-g, b-c,
b-c-g, c-a, c-a-g, a-b-c]
• 3 ground fault-measuring units can cater for all 3ground faults [a-g, b-g, c-g]
Problem: Sequence components of voltage and current not readily available at relay
location; only line voltages and currents readily available
Distance Protection of a Three-phase Line
Solution
• A distance measuring unit with voltage of (Vb - Vc = Vbc) and current of (Ib - Ic) will measure
positive sequence impedance up to fault point Z1, in case of phase b-to-c faults
• Similarly, two more units with inputs of Vab, (Ia - Ib) and Vca, (Ic - Ia) cater for phase a-to-b and
phase c-to-a faults
• Distance measuring units which cater for phase a-b, b-c and c-a faults are called phase fault
units
Ground Faults
Ground Faults
will be needed for catering to all three single line to ground faults
First Step
• Set distance protection to reach up to 80 to 90% of length of line section
• This is an instantaneous protection, i.e. there is no intentional time delay
Second Step
• Provide primary protection to remaining to 10% of line
In addition, it cover up to 50% of next line section
Three-stepped distance
protection
Three-stepped distance
protection simplified
representation
Three-stepped Distance Protection
Second step should extend up to 50% into the shortest adjoining line
Third Step
• Give full back-up to adjoining line section
• Covers the line section under consideration, 100% of next line section and
further
• To give full back-up to next line section in spite of the maximum under-
reach of third step
Three-stepped Distance Protection
Three-stepped distance protection using mho relay
• There is an additional distance measuring unit whose reach is beyond third zone
reach
• Operating time of this unit is instantaneous
• This unit is known as a fault detector or starter unit
Trip Contact Configuration for Three-stepped
Distance Protection
Trip contact circuit which implements the three-stepped
distance protection scheme
Trip Contact Configuration for Three-stepped
Distance Protection
• Fault detector initiates timer in case it detects
a fault within its reach setting
Simultaneous reclosure
• Distance relays used in conjunction with carrier channel can achieve these
Carrier Assisted Distance Protection
Carrier Transfer (Intertripping) Note the directional characteristic
• Carrier signal sent to other end to
bring about simultaneous tripping of
line-section
– After tripping, auto-reclosure relays
takes over
• Fault at F2 near RA
relay at far end (RB) operate with time t2
Non-simultaneous operation of CBs
relay at local end (RA) operate with time t1
• Relay nearer to fault (RA) send carrier signal to far end (RB) simultaneous
tripping of CBs at both ends
Carrier Assisted Distance Protection
Scheme for carrier transfer
Fault in section AB
• No signal is sent to block tripping A2 and B1
Carrier Assisted Distance Protection
• time delay provided A2 does not operate earlier than receiving blocking
signal
• Parallel tuned circuit comprising L and C, inserted between bus bar and
connection of coupling capacitor to line
Electronic Equipment
(i) Transmitter
(ii) Receiver
(iii) Relay
Transmitter unit
Block diagram of
transmitting unit
• Each band has certain band width (e.g. 150-300 kHz, 90-115kHz)
Carrier Current Protection
Receiving unit
Frequency spacing
• Different frequencies used in adjacent line sections
• Wavetraps ensure that carrier signals do not enter next line section
• Receiver filters filter-out other frequencies