Você está na página 1de 10

MHI BUSINESS CONFIDENTIAL

Mitsubishi HRSG
(Heat Recovery Steam Generator)

HRSG System Design

August 5, 2005 1
MHI BUSINESS CONFIDENTIAL

System Outline
To Condensate Water
#2HRSG

From
#2 HRSG

Preheater
Steam
Deaerator Economizer

Evaporator

Superheater Steam
Gas Turbine

Condenser
#1 Gas Turbine
#1 HRSG
(Heat Recovery Steam Generator)
August 5, 2005 2
MHI BUSINESS CONFIDENTIAL

HRSG Performance
Type Mitsubishi Heat Recovery Steam Generator
Triple Pressure Natural Circulation Reheat (Vertical
Gas Flow)
Design Condition Air Temp=30℃, NG Firing
Steam HP-SH Outlet 280.1 t/h
Flow IP-SH Outlet 37.5 t/h
LP-SH Outlet 40.7 t/h
RH Outlet 311.6 t/h
Steam HP-SH Outlet 130.8 kg/cm2a
Press. IP-SH Outlet 40.4 kg/cm2a
LP-SH Outlet 6.76 kg/cm2a
RH Outlet 37.6 kg/cm2a
Steam HP-SH Outlet 540 ℃
Temp. IP-SH Outlet 270.9 ℃
LP-SH Outlet 256.6 ℃
RH Outlet 568 ℃
August 5, 2005 3
MHI BUSINESS CONFIDENTIAL
HP System M

Air Vent
PT

N2 Supply HP DRUM LT
※2
※2 DCS
DCS
Cont. Blow M
EVA
Int. Blow
3ry ECO ※1

1ry SH DCS
2ry ECO
N2 Supply
1ry ECO
TE
2ry SH
Drain FT
※1
M

FT
August 5,To HP
2005 ST From HP BFP 4
MHI BUSINESS CONFIDENTIAL
IP System M

Air Vent PT

N2 Supply IP DRUM LT
※2
※2 DCDAS
DCS
Cont. Blow M
EVA
Int. Blow
2ry ECO ※1

SH 1ry ECO
Drain M N2 Supply

FT ※1 FT
RH DeSH Spray
To LTR
August 5, 2005 From IP BFP 5
MHI BUSINESS CONFIDENTIAL
LP System M

Air Vent
PT

N2 Supply LP DRUM LT
※2
※2 DCS
DCS
Cont. Blow M
EVA
Int. Blow
※1

ECO
SH
Drain M
N2 Supply

※1 FT
FT
To LP ST
August 5, 2005 From LP BFP 6
MHI BUSINESS CONFIDENTIAL
RH System

From IP SH

From HP ST
1ry RH

DCS

From IP BFP

TE
2ry RH
Drain M

To IP ST

August 5, 2005 7
MHI BUSINESS CONFIDENTIAL
Rreheater System
• N. Gas Firing Operation
DCS
Open Close
TE
M

From CP
PR-HTR

M
M

To Deaerator

Open

• Oil Firing Operation


Close Open
TE
M

From CP
PR-HTR

M
M

To Deaerator

Open
August 5, 2005 8
MHI BUSINESS CONFIDENTIAL

HRSG Operation Guideline


(HRSG Control)
• HRSG Outlet Steam Temperature
– HP-SH outlet steam temperature is kept under 540℃
by de-superheater spray.
– RH outlet steam temperature is kept under 568℃ by
de-superheater spray.

• Steam Drum Level


– Steam drum level is controlled by feed water control
valve.
– In case of level going up, the level is decreased by
intermittent blow down.

August 5, 2005 9
MHI BUSINESS CONFIDENTIAL

HRSG Operation Guideline


(HRSG Control)
• Preheater inlet feed water temperature
– During N.gas firing, in order to increase the preheater
inlet water temperature above the flue gas dew point,
the inlet water temperature is kept as follows.

・Preheater inlet temp. => 55℃

– Preheater inlet condensate water temperature is


controlled by re-circulating the preheater outlet water.

August 5, 2005 10

Você também pode gostar