1.2 kV to 46 kV Class
Dry-Type Medium Voltage
Distribution (Power) Transformers
500 kVA To 34 MVA
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Dry-Type Distribution (POWER) Transformers Catalog


The HPS HPWR Dry-Type Medium Voltage Distribution (Power) Transformers catalog contains
updated product, technical, installation and service information which enables HPS to continue to be your
first choice for quality and reliable dry-type medium voltage distribution (power) transformers.

The catalog is designed to make certain every decision you make is an informed decision. Unlike
other manufacturers, our catalog details everything you need to know about all aspects of our dry-type
medium voltage distribution (power) transformer product. Whether from materials to construction or from
installation to servicing, the HPWR catalog has it all.

Thank you for choosing Hammond Power Solutions as your transformer supplier and if you have any
questions about this catalog please feel free to contact us at the numbers listed on the back cover.

Selecting & Ordering your HPS Transformer


In addition to the quality and reliability that is built into every HPS transformer you purchase, we also
know that the ease at which you can find the correct product to match your needs and have it delivered is
equally important. HPS has more ways to accomplish this than any other transformer manufacturer in the
market today.

Additional Product Information


The HPS HPWR catalog, as well as any other product literature, is available in print form as well as
electronically on-line from www.hammondpowersolutions.com/product/product_literature. Download your
free copies anytime.

Quotation and Pricing


To authorized1 customers, we offer access to the industry’s most powerful on-line specification and
quotations program. HPS “E-Quotes” program allows anyone to specify, price or quote almost any
standard or custom HPS product. Each quote provides detailed product specifications and pricing as well
as current stock and availability information. To request access, just go to (www.hammondpowersolutions.
com) and click on the “LOGIN” button on the top right corner.

1
Available upon request to any Partner Distributors and authorized customers only. Contact Hammond Power Solutions for details.
-2-
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

INDEX
Section 1 About Hammond Power Solutions Inc. ................... Page 4
Transformer Terminology ...................
Page
6

Section 2 Compliance With Engineering Standards ................... Page 8


Transformer Test Standards - Type Tests ................... Page 9
- Production Tests
...................
Page
12
- Short Circuit Experience .............
Page
13

Section 3 Manufacturing Processes ...................


Page
14
Vacuum Impregnation ...................
Page
19

Section 4 Dry-Type Transformers vs. Liquid Filled .................. Page 20

Section 5 Medium Voltage Distribution Transformers


Energy Efficiency Guidelines ...................
Page
26
Standard Weight & Dimension Specifications ................... Page 28
Table 1 - Aluminum Energy Efficient Spec Table ................... Page 29
Table 2 - Copper Energy Efficient Spec Table ................... Page 29
Table 3 - Aluminum Non-Energy Efficient Spec Table ................... Page 30
Table 4 - Copper Non-Energy Efficient Spec Table ................... Page 31
Optional Terminal Locations ...................
Page
32

Section 6 Options and Accessories ................... Page 33
Standard Enclosure Specifications ...................
Page
34

Literature Order Form ...................


Page
38

Other HPS Products ...................


Page
39

-3-
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

THE COMPANY
SECTION 1

Established in 1917, Hammond Power Solutions Inc., formerly Hammond


Manufacturing - Transformer Group, is an industry leader in Magnetic
Transformer design and development. With 7 plants located throughout North
America and Mexico, we have expanded our manufacturing and product base to
offer you the broadest ranges of both standard and special dry-type transformers
available anywhere.
Our engineering experience and capability has resulted in a computer data
base of over one million transformer designs. We offer the most cost effective,
highest quality transformers necessary to satisfy your requirements.

MANUFACTURING FACILITIES
Hammond Power Solutions Inc., with its headquarters in Guelph,
Ontario, Canada, operates out of:
Guelph, Ontario Walkerton, Ontario Granby, Quebec
Monterrey, Mexico Baraboo, Wisconsin Compton, California
Our objective is to supply the best value in dry-type transformers in
North America. We are guided by our focus on quality, customer service
and value to our customers, as well as the strength of our employees.

HPS DRY-TYPE MEDIUM VOLTAGE


TRANSFORMERS
Our dry-type medium voltage distribution (power) transformers are
regarded for their high level of quality and service reliability that has
become synonymous with HPS transformer products. With three phase ratings up to 34 MVA, 46 kV,
250 kV BIL and single phase to 5 MVA, we feature the newest technology and manufacturing pro-
cesses.

APPLICATIONS
With the continued development in the technology of materials, designs and
manufacturing methods, the use of dry-type medium voltage transformers is
growing rapidly throughout North America.
HPS Transformers are suitable for any commercial, industrial, manufacturing
or production process application. Distribution (Power) transformers, unit substation
transformers, drive & rectifier duty and distribution transformers can be offered for a
variety of environmental conditions and built to meet the most onerous duty.
In addition to conventional indoor applications, our dry units are located
outdoors, on drilling platforms, in network vaults and in every location where
airborne contaminants pose a risk to electrical equipment.

-4-
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

CUSTOMER SERVICE

SECTION 1
Our customer service personnel are available to answer your questions immediately.
Our teams are technically trained and are able to answer questions on the phone. Stock
checks, expediting, quotations or technical information are always readily available. Our
commitment to customer service means you will be an informed, relaxed and satisfied
customer as quickly as possible.

DESIGN CAPABILITIES
HPS engineering services are located throughout our manufacturing facilities. Our
history and experience in transformer magnetics places us at the top in the industry. Our
extensive testing program - including all qualification tests and short circuit testing, plus
an exemplary field service record, ensures that our products not only meet all the
standards necessary, but more importantly, fulfill your expectations and requirements.
Our designs are cost effective and our transformers are built with modern
manufacturing techniques. We particularly emphasize our Value Added Engineering
whereby our design staff will interface with your team to produce the optimum
transformer. Our fully computerized design, CAD and 3-D modeling capabilities permits
quick and effective communication when time is vital.

A RELIABLE SOURCE
For over 90 years, HPS has continued to grow from a small family business to an industry
leader of electrical transformers. Our customers have come to rely on our products and
services and continue to depend on us for support at the most critical stages of their need. Our
stability and integrity as a supplier are paramount particularly in an industry environment where
demands must be resolved quickly and effectively.

TECHNICAL SUPPORT
HPS has an experienced technical team available to help you with your application or
design questions. Call our regional offices for assistance.

QUALITY ASSURANCE
HPS has been regarded for its quality since its very inception. With our commitment to
‘Excellence’ and ‘Continuous Improvement’, we build value and reliability into every HPS product. All
facilities have implemented quality management systems based on ISO 9001:2008 with the Guelph
facility having certification to that quality standard. Our distribution (power) transformer products are
designed to meet ANSI, CSA, UL , IEC and NEMA standards.

-5-
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

TRANSFORMER TERMINOLOGY
SECTION 1

Applied Potential (Hi-pot) Test winding when a lightning induced voltage surge reaches
This dielectric test verifies the integrity of the insulation the transformer.
of each winding to all other windings and ground.
Efficiency
Coil Hot-Spot Temperature Efficiency is the ratio of useful power output to the total
The coil hot-spot temperature is the absolute maximum power input.
temperature present in the transformer. This number is
equal to the sum of the following: Exciting Current (No-Load Current)
T Hot Spot = T ambient + T average winding rise + T Exciting current is current drawn by the transformer
hot spot rise adder or rise above average. under no load conditions. It is usually expressed in
percent of the rated current of the winding in which it is
Continuous Rating measured.
Continuous rating is the continuous power (kVA) the
transformer delivers to the load without exceeding its Frequency
specified temperature rise. In AC circuits, currents & voltages follow a cyclic
pattern. Frequency designates the number of such
Delta Connection ( ) cycles repeated every second. The unit of measure is
The delta connection is a standard three phase hertz.
connection with the ends of each phase winding
connected in series to form a closed loop. Sometimes Induced Potential Test
referred to as three wire. The phase relationship will This dielectric test verifies the integrity of insulation
form a Delta. within a transformer winding and between phases.

Wye Connection ( Y ) Insulating Materials


A wye connection is a standard 3-phase transformer These materials are used to electrically insulate the
connection with similar ends of each of the phase coils transformer. That includes windings - turn to turn and
connected. This common point forms the electrical layer to layer, and other assemblies in the transformer
neutral point and may be grounded. When the neutral such as the core and bus work.
is brought out it makes a 4 wire system.
kVA or Volt-Ampere Output Rating
Dielectric Tests The kVA or volt-ampere rating designates the output
These tests consist of the application of a voltage higher which a transformer can deliver for a specified time at
than the rated voltage for a specified time, for the rated secondary voltage and rated frequency, without
purpose of determining the adequacy of insulation exceeding the specified temperature rise. (1 kVA =
strength and electrical clearances. 1000 VA)

Impedance Natural Convection Cooling


Is the impeding element against current flow. Natural convection is the cooling class in which the
transformer is cooled by the natural circulation of air.
Basic Impulse Level Tests (BIL)
Impulse tests are dielectric tests consisting of the Load
application of a voltage waveform with a very steep rise The load of a transformer is the apparent power
voltage applied to a winding. The test simulates a delivered by the transformer in MVA, kVA, VA.
voltage and current surge through the transformer

-6-
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Transformer Terminology continued

SECTION 1
No-load Losses (Excitation Losses)
When a transformer is energized under no-load, Scott ‘T’ Connection
some power is drawn from the supply, predominately This is the connection for three phase using two special
to feed transformer core losses, but to a smaller single phase transformers. It is most frequently used
extent feed losses in the winding due to excitation to change from two phase to three phase or three phase
current. These losses are termed “no-load losses”. to two phase.

Load Losses Secondary Voltage Rating


Load losses are incident to load carrying. Load losses This rating designates the no-load load-circuit voltage
include I2R losses in the windings due to load current, for which the secondary winding is designed.
eddy current losses in the winding conductors, stray
loss due to stray fluxes in the winding, core clamps, Secondary Winding
etc. and due to circulating currents in parallel The secondary winding is the winding on the energy
windings. output side.

Phase Tap
Unlike DC, AC power can be vectorially displaced. A tap is a connection brought out of a winding at some
Various vectorially displaced windings can be connected point between its extremities, usually to permit changing
to make an AC system. Each displaced winding is a the voltage ratio.
phase. In 3 phase transformers there are 3 vectorially
displaced windings. Temperature Class
Temperature class is a rating system for maximum
Power Factor temperature for the insulation in a transformer, i.e.
Power factor in a circuit is the relation of watts to volt Insulation Rating
amps. Class 105
Class 150 or 130
Polarity Tests Class 180
This standard test on transformers determines the Class 200
instantaneous direction of the voltages between the Class 220
windings. It determines if the winding connections are
correct. Temperature Rise
The average increase in temperature of a winding over
Primary Voltage Rating ambient (determined by change in resistance) is known
This rating designates the input voltage for which the as the Temperature Rise of a winding.
input winding is designed.

Primary Winding Transformer


The primary winding is the winding on the energy input A transformer is an electrical device without moving
(supply) side. parts which, by electromagnetic induction, transforms
power between circuits at the same frequency, usually
Ratio Test with changed values of voltage and current.
A ratio test is a standard test applied to transformers
and used to determine the ratio of turns between the
windings.

-7-
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

COMPLIANCE WITH ENGINEERING STANDARDS


All HPS dry-type distribution (power) transformers are CSA certified and meet the following
additional standards:
SECTION 2

 CSA-C22.2 No. 47: Air-Cooled (Dry-Type) Transformers

 CSA-C9: Dry-Type Transformers

UL approved transformers are available upon request and will meet the following additional
standards:

 UL 1561: Dry-Type General Purpose and Power Transformers

 UL 1562: Transformers, Distribution, Dry-Type over 600 volts.

HPS dry-type distribution (power) transformers can be built to comply with the following
engineering standards:

 IEEE-C57.12.01: General Requirements for Dry-Type Distribution and Power Transformers.

 ANSI-C57.12.51: Requirements for Ventilated Dry-Type

 ANSI-C57.12.70: Terminal Markings & Connections for Distribution & Power Transformers.

 ANSI-C57.12.91: Test Code for Dry-Type Distribution and Power Transformers.

 ANSI-C57.12.91: Guide for Short Circuit Testing of Distribution and Power Transformers.

 NEMA 250, UL 50 & UL 50E: Enclosures for Electrical Equipment.

 NEMA TR 1-1993 (R2000): Transformers, Regulators and Reactors.

 CSA C802.2 and DOE 10 CFR Part 431: Energy Efficiency Standards

-8-
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

TRANSFORMER TEST STANDARDS


All distribution (power) transformers are tested at HPS prior to shipment. Transformers must meet a
very exacting criteria to be certified acceptable for release. Tests are categorized as ‘Production Tests’
and ‘Type Tests’. Production Tests are applied to every transformer. Type Tests are required either to
qualify a new product or to further certify a production product. Type tests are optional and are available
at an additional cost.

SECTION 2
Type Tests
The following are descriptions of type tests performed (upon request) on HPS power transformers.

Temperature Rise Test Sound Level Test


The temperature rise test determines the The sound level test determines the sound
thermal performance of a transformer for which it emitted by a transformer.
was designed. Most standards require the test to record a
The temperature rise test is conducted at weighted sound pressure level which is the
rated current and/or voltage as per the procedures weighted average of sounds of different
defined in all relevant standards (e.g. CSA C-9, frequencies as defined in the standards. The
ANSI C57.12-91 etc.). sound pressure level is measured in dB with the
transformer energized at rated voltage with no
load (ANSI C57.12.91).

-9-
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Transformer Test Standards continued

Partial Discharge Test


Partial discharge is defined as an electric
discharge which only partially bridges the
insulation between conductors, and which may or
may not occur adjacent to a conductor.
SECTION 2

Partial discharges occur when the local


electric field intensity exceeds the dielectric
strength of the dielectric involved, resulting in local
ionization and breakdown. Depending on intensity,
partial discharges are often accompanied by
emission of light, heat, sound and radio influence
voltage (with a wide frequency range).
The relative intensity of partial discharge can Basic Impulse Level Test (BIL Test)
be observed at the transformer terminals by The BIL test determines the adequacy of the
measurement of the apparent charge. However, insulation structure to withstand a lightning
the apparent charge (terminal charge) should not induced voltage surge.
be confused with the actual charge transferred The test comprises of the application of an
across the discharging element in the dielectric impulse voltage of a specific wave shape to the
which in most cases cannot be ascertained. winding terminal under consideration, with all other
terminals and metal parts grounded.

The standard impulse levels for stand alone


dry-type transformers are:

Voltage Class BIL Full & Chopped Wave


5 kV 30 kV
15 kV 60 kV
18 kV 95 kV
25 kV 110* kV
34.5 kV 150 kV
46 kV 200 kV
*110 kV - IEEE C57.12.01,
125 kV - CSA C9.02

Impulse levels are also important for the


selection of lightning arresters. For special
applications or where the hazard of lightning strikes
is high, higher than standard BIL can be supplied.
Please contact our offices.

- 10 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Transformer Test Standards continued

Short-Circuit Test
CSA & ANSI Standards requires that dry-type
transformers be capable of withstanding a short
circuit, with rated voltage applied, provided that the
magnitude of the R.M.S. symmetrical current does

SECTION 2
not exceed 25 times the rated current and the
duration of the short circuit is limited to 2 seconds.
The RMS symmetrical short circuit current is a
direct inverse function of total impedance
(transformer impedance + system impedance as
applicable as per standard) and is calculated as
follows:

When a lightning or surge arrester is applied 100


Rated Current X
at the transformer terminals, the voltage stress at Z in percent

the terminals is limited by the arrester.
That is 5.0% Z gives 20 X normal, 6.0%
If there is any possibility the transformer
gives 16.6 X normal, etc.
terminals will be subjected to transient
over-voltages exceeding 80% of their BIL, it is
ANSI standard C57.12.91 “Test Code For
recommended that they be protected with the
Dry-Type Distribution and Power Transformers”
appropriate surge arresters.
defines a procedure by which the mechanical
capability to withstand a short circuit may be
demonstrated. The prescribed tests are not
designed to verify thermal performance; confor-
mance to short circuit thermal requirements is by
calculation. Most standards specify a method of
heat calculation and formulae to be utilized.

Additional information on HPS experience on short


circuits is described on page 13.

EMF (Electric & Magnetic Field) Test


Electric and Magnetic Fields are produced by
the distribution of electricity through current
carrying devices. New techniques have been
developed by HPS that allow for a reduction of the
radiated EMF levels produced on a particular side
of a transformer. HPS offers lab testing and
certification for transformer EMF levels.

- 11 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Transformer Test Standards continued

Production Tests Polarity and Phase-Relation Test


The following production tests are performed Polarity and phase-relation tests are made to
on every HPS transformer above 500 kVA. determine angular displacement and relative
phase sequence as required by customer
D.C. Resistance Measurement specifications.
SECTION 2

Measures the DC resistance of a coil using a


DC resistance bridge.

No-Load and Excitation Current Test


Rated Voltage is applied to one winding and
the current and losses are measured.
Voltage Ratio (turns ratio)
To confirm the voltage ratio conforms to the
nameplate voltage rating (within limits of Impedance Voltage and Load Loss Test
acceptable error as defined in the standards). One winding is shorted and a voltage is
applied to the other winding to force rated current
in the transformer windings. The losses, voltages
and currents are measured.

- 12 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Transformer Test Standards continued

Dielectric Tests
Short Circuit Experience
The purpose of dielectric tests is to
Critical to life expectancy of transformers is
demonstrate that the transformer has been their ability to withstand system short circuits.
designed and constructed to withstand the Standards typically call for a distribution (power)
overvoltages required by standards. transformer to survive the mechanical and thermal

SECTION 2
stresses of a short circuit across any winding, while
all other windings operate at rated voltage. The
magnitude of the rms symmetrical current can be
as much as 25 times normal rated current in that
winding, and can last for as long as 2 seconds.
Obviously, the qualities of a transformer to retain its
integrity in this environment is critical to its
survival.
At HPS, we recognize the importance of this
in our standard construction as there is little in the
way of recovery or resolution after an incident in the
field.
To date, 15 HPS distribution (power)
transformers have been short circuit tested, 4 in a
controlled laboratory test and 11 in field qualification
tests prior to energizing. All units passed with flying
colors.
The most onerous test of these was a test of
a 4400 kVA, 15 kV class power rectifier transformer
that was installed as part of a transit subway. To
prove its capability, the test duplicated the procedures
required for a cast coil transformer. The test consists
of an initial 4 second continuous short circuit on the
Applied Voltage Test highest current tap position followed by a ½ second
A power frequency such as 60 Hz, is applied burst on all the remaining voltage positions. In total,
to the winding voltage under test at a voltage this transformer accumulated 9 ½ seconds of short
corresponding to the voltage class of the winding, circuit and passed the test flawlessly. Verified by test
in accordance with table (5) in ANSI C57-12-01 or results, the impedance of this unit did not change
tables 9 or 10 of CSA C9. The voltage is applied to even considering the measuring instrument was a 3
the winding under test for 1 minute with all other decimal digital device.
windings and the core grounded. Make no assumptions about the ability of your
distribution (power) transformer to withstand short
Induced Voltage Test circuits. Ask your supplier to show you the record.
A voltage at 2 times the rated voltage is Here is ours, for the record.
applied for 7200 cycles between terminals of a As part of our development program to enhance
the quality of our transformers from time to time,
winding with terminals of all other windings open.
HPS will complete short circuit testing of some units
to determine optimum design and construction.

- 13 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

MANUFACTURING PROCESSES
Hammond Power Solutions produces the most reliable, technologically superior medium voltage
distribution (power) transformers in the market today.
This is a result of continuing development in all phases of the design and manufacturing processes
in meeting the requirements of a broad range of customers and the most onerous applications. Our dry
type transformers are now the largest in kVA and impulse voltage level of any manufacturer.
Additionally, these transformers have demonstrated improved withstand ability to short circuits and
will provide a life expectancy considerably in excess of current industry standards.

Core Construction
HPS cores are manufactured from high
SECTION 3

grade non-aging, fully processed silicon steel


laminations. Cores are precision cut to close
tolerances using modern equipment, to eliminate
burrs and minimize losses. They feature core
construction that optimizes energy efficiency.
The core is resin sealed to prevent the
ingress of moisture.

Coil Construction
Coils are either layer (barrel) or disc wound
to suit the voltage class. Typically, disc wound
coils are utilized above 8.7 kV class. Available in
aluminium or copper, windings are designed with
wire or foil conductors for optimum performance
for the application.
Disc wound coils feature comb construction
to electrically balance voltage stresses over the full
length of the coil.
All internal connections are brazed or TIG or
MIG welded.

- 14 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Manufacturing Processes continued

Insulation
Typically HPS dry-type medium voltage distribution (power) transformers are manufactured with a
220°C insulation system. High temperature resistant materials are used including NOMEX® Aramid
papers, silicone coated fiberglass, NOMEX® sleeving, supersil duct sticks and pressure sensitive glass
tape. All materials meet or exceed UL standards for use on dry-type medium voltage distribution (power)
transformers.

SECTION 3
Core and Coil Assembly
As a completed assembly, the coils are held rigidly in place between insulators clamped to the upper
and lower core frames under high compression.

- 15 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Manufacturing Processes continued

Winding terminals can be secured firmly to


the transformer structure.
SECTION 3

The picture below shows how low voltage bus


bars are bolted to the upper or lower steel support
frame with insulators and quality hardware, all to
ensure the integrity of the core and coil assembly.
Other optional termination methods are available.

- 16 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Manufacturing Processes continued


Impregnation
It is critical that transformers maintain the integrity of the dielectric properties of the insulation
materials essential for long-term life expectancy. In order to meet designed life expectancies, transformers
must not be compromised during the impregnation process.

At HPS, transformer coils are impregnated with two complete vacuum-pressure impregnating cycles:

• Coils are placed in a sealed tank and a full vacuum is drawn.


• The impregnation resin is then introduced into the chamber and the coils, or assembly, are then
completely immersed in the impregnation resin.

SECTION 3

- 17 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Manufacturing Processes continued


Impregnation continued
• The tank is then pressurized to force the impregnation resin to thoroughly penetrate the windings.
• The coils or assembly are then removed from the chamber and oven cured.
• A complete second impregnating cycle follows to ensure thorough and complete impregnation.
SECTION 3

The result are transformer coils which exhibit virtually partial


discharge free performance, a superior resistance to environmental
conditions and a new standard of reliability even for the most
onerous industrial, utility or commercial applications.

- 18 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

VACUUM IMPREGNATION

Polyester Resin Impregnation


For most general purpose indoor transformer applications regardless of voltage class, our ‘HPSI’
resin impregnation system is preferred. This material is a blend of resins that exhibit much higher dielec-
tric strength and bonding properties than any varnishes previously used or other encapsulations including
oil modified epoxies. This resin system is ideal for transformers in meeting the following requirements:

 Low moisture absorption

 High dielectric strength

SECTION 3
 High bond strength

 Excellent mechanical properties

 Stability at high temperatures

 Excellent thermal shock properties

 Longevity of life at maximum transformer temperatures

 UL approved for 220°C insulation systems for any voltage class

 Fungus resistant reactive components makes it environmentally superior.

 Thixotropic epoxy encapsulation is available to customers considering additional protection.

- 19 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

DRY-TYPE TRANSFORMERS
The Better Alternative to Liquid Filled
Transformer technology, like many other technologies, has evolved of the last 50 years. During this
period of evolution advances are made and set backs occur. Sometimes what may seem as a
breakthrough one year becomes a risk years or decades later. Liquid filled (specifically PCB filled) trans-
formers is a great example of this. What was once thought as the best way to cool transformers became,
as we know decades later, a great environmental disaster. Much has been published on retrofit and
retrofit alternatives. It is important to look at the three main contenders for replacing PCB-filled
transformers; namely mineral oil, silicone and dry-type transformers. Transformers can be classified into
three major groups depending on the type of coolant used.
In liquid filled transformers, the cooling and dielectric media can be mineral oil, silicone fluids,
aliphatic hydrocarbon, esters or other similar fluids which remain in a liquid state during the operation of
the transformer.
In liquid vapor condensation transformers, core and coils are immersed in a low boiling point fluid
such as Tri-tetrachlorobenzene. This fluid evaporates, taking transformer heat away as its latent heat and
then returns in liquid form through condensation in the radiator tubes.
In dry-type transformers, air is used as the cooling and dielectric medium. In the last 25 years this
SECTION 4

transformer type has received much attention and considerable technological improvements have been
made. Today, dry-type transformers are available up to 35 MVA and 44 kV system voltages at 250 kV BIL.
Most are manufactured with vacuum pressure impregnation in polyester or silicone varnish. For tougher
environmental conditions, VPI epoxy sealed and cast resin transformers have also been developed.

Criteria for Selecting a Transformer

Fire Risks (see table 1 - page 23)


Due to the high cost of low voltage cable or bus, it has become a trend to bring high voltage lines
close to installed loads. For cost reasons, transformers are located in habitable areas such as buildings
where fire risk has to be minimized. Additionally, the fire risks in chemical and mining industries
necessitated non-flammable equipment. It was for these applications that liquids were first used.
To minimize the fire risk, the coolant should be non-flammable or exhibiting a high flash and fire
point, and have a low rate of fire propagation if on fire. Factory Mutual has under taken extensive studies
on conductive and radiant heat release rates when transformers are on fire. The heat release rate
determines how fast the surrounding materials will catch on fire. Obviously, the lowest possible rate is
preferred.

Health and Environmental Concerns


Health concerns have always been sensitive and now there is an increased awareness of envi-
ronmental issues as well. Since the early 1970s, PCBs have been linked with many health risks and their
use is banned in almost all environmentally aware countries.
It is essential that when selecting the best transformer solution, you ensure that the transformer
uses biodegradable and environmentally friendly materials. Although the health concerns of both mineral
oil and silicone fluids as a cooling medium in transformers currently are considered negligible, one cannot

- 20 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

The Better Alternative to Liquid Filled continued

ignore the environmental impact of such fluids during a failure and possible fire of a transformer using
these materials. Dry-Type transformers use air as a coolant, and hence health and environmental concern
disappear. Insulation and support structures are considered environmentally safe for all transformers.

Insulation (see table 2 - page 23)


Since higher temperature insulations are more expensive, it is a design practice to use insulation
temperature classes equal to or less than the coolant temperature class. Table 2 lists the insulation
temperature classes available for the various coolants.
The major insulation used in liquid cooled transformers is kraft paper. Both mineral oil and
silicone have good dielectric characteristics, with the dielectric constant close to kraft paper, which makes
them suitable for very high voltages, i.e. 765 kV systems.
Dry-type transformers, for those of 500 kVA and larger, are designed typically with 220°C
insulation systems where aramid paper, NOMEX®, is the major insulation. NOMEX® has a high dielectric
tensile and compression strength. Of further benefit, dry-type core and coils are protected against
moisture by vacuum pressure impregnation with polyester or epoxy varnishes. This tougher insulating
material together with the impregnation process improves the short circuit mechanical strength over liquid

SECTION 4
cooled transformers. The dielectric property of coolant air does restrict the use of dry type transformers to
44 kV systems, with 250 kV BIL.

Performance Comparison (see table 3 - page 23)


With increased energy costs and space limitations, transformer losses and size is vital.
Technological advances in dry-type transformer construction have made possible a substantial reduction
in overall dimensions. Even though dry-type core and coils are larger than the equivalent liquid cooled
transformer, overall dimensions of dry-type transformers are smaller. This is possible as dry-type
transformers do not require space for cooling radiators or transition cells.
The no-load losses of liquid cooled transformers tend to be slightly lower than dry-types. The real
difference appears in the load losses. Dry-type transformers operate at higher temperatures resulting in
higher thermal resistance and moderately higher load losses.
Since liquid acts as a sound absorbent, liquid cooled transformers have a slightly lower audible
sound level. However, lower loss levels and resultant lower sound levels are possible for each type of
transformer with some impact on the relative price and size.

Installation Costs (see table 4 - page 23)


As there are no radiator banks used in dry-type transformers, it is easy to terminate bus work in
any desired location. This makes coordination with switchgear extremely simple and provides an
aesthetically pleasing arrangement.
Disconnecting chambers are often required for liquid filled transformers resulting in additional
cost. This will facilitate either a space constraint or an unusual installation.
The relative first cost of a transformer is given in Table 3 (see page 23), but the total installation
cost is more important to the end user.
Liquid filled transformers require catch basins or curbs to contain the liquid in case of a leak in the

- 21 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

The Better Alternative to Liquid Filled continued

tank. Additionally, pressure release valves for hermetically sealed units, and in some instances
disconnecting chambers for bus coordination, all add significantly to the total installed cost. For some
installations, the heat release rate of the transformer liquid may require much more air space above and
surrounding the transformer. Moreover, depending on site location, many insurance companies charge
substantially higher premiums.
Table 4 (on page 23) lists some of the cost additions for different types of transformers. It should
be noted that not all cost additions are necessarily applied together. The first cost of a transformer tends
to favour liquid cooled transformers as the system voltage and BIL go up, particularly above 150 kV BIL.
In retrofitting difficult installations, particularly in locations with narrow passageways or where access is
limited, enclosures of dry-type transformers can be knocked down. Removable bus work is also an
effective option at the design stage.

Maintenance Considerations
Transformers in general require a low degree of maintenance. Dry-type transformers require an
annual inspection and cleaning of dust.
Periodic inspection for leaks and rust is required for liquid cooled transformers. Liquid coolants
SECTION 4

need monitoring and have to be reconditioned when necessary. Gauges and fan operation have to be
examined annually.
Transformers are inherently reliable pieces of equipment. However, in case of difficulty, dry-types
can be easily inspected and minor repairs concluded on site.
In the case of liquid cooled transformers, the core and coil have to be removed from the tank for
inspection. This can be both messy and costly, and repairs on site are often not practical.
The core and coil assembly in a liquid filled transformer is isolated from atmospheric
contamination when the tank is hermetically sealed, or air is brought in through a silica-gel breather in a
free breathing transformer. The cost is only slightly above that of an indoor liquid transformer, and hence
liquid filled transformers are popular for outdoor applications.
Dry-type transformers are also available for outdoor applications in EEMAC or NEMA type 3R or
4 enclosures. Both are at a higher premium over an indoor transformer.

Conclusion
For current applications, over 250 kV BIL and for units over 35 MVA, liquid cooled transformers
are for now the only solution.
For higher voltage applications in fire risk areas, silicone transformers are a normal choice, but
again environmental concerns should be considered.
For indoor or outdoor applications, up to 250 kV BIL and up to 35 MVA (45 MVA with additional
fan cooling), dry-type transformers offer the most cost effective solution with many design advantages
and minimizes the environmental and health risks.

- 22 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Table 1: Flammability Characteristics


Description Mineral Oil Silicone Fluid Dry-Type
(insulation class 220°C)

Coolant Flash Point 155°C 310°C -


Insulation Flash Point - - Above 500°C
Heat Release Rate above 1000 kw/m 2
less than 1000 kw/m 2
Negligible
Burning Mass (% of Total Mass) Up to 50% Up to 55% Less than 5%

Table 2: Transformer Winding Insulation System


Temp. Avg. Winding Rise Hot Spot Max.
Class (measured by rise Winding Winding Mineral Silicone Dry-Type
°C of resistance) Rise Temp.

Class 105 55 65 105 X X X


Class 150 80 110 150 - X X
Class 180 115 140 180 - - X
Class 220 150 180 220 - - X

SECTION 4
Maximum permissible temperature rise based on average ambient of 30°C during any 24 hour period with a maximum ambient of 40°C.

Table 3: Comparison of a 15kV, 2000 kVA Transformer


Description Liquid Cooled Dry-Types
Mineral Oil Silicone Epoxy Varnish
Winding Temp. Rise 65°C 65°C 115°C 80°C 115°C 150°C

Relative Price % 100 130 125 125 110 95


Relative Size % 100 105 100 105 100 95
Relative No Load Losses % 100 100 103 105 102 100
Relative Load Losses % 100 100 115 100 115 130
Audible Sound % 100 100 105 110 110 110

Table 4: Installation Cost Comparison for 15 kV Class Indoor Transformer


Description Dry-Types Liquid Cooled
Varnish Epoxy Mineral Oil Silicone Fluid
Temp. Rise 150°C 80°C 115°C 80°C 65°C 65°C

Transformer $23K $30K $30K $46K $24K $31K


Accessories ≤$1.8K ≤$1.8K ≤$1.8K ≤$1.8K ≤$2.3K ≤$2.3K
Catch Basin - - - - ≤$2.3K ≤$2.3K
Curbs - - - - ≤$1.2K ≤$1.2K
Insurance* - - - - $1.2K $1.2K
Installation $575 $575 $575 $575 ≤$2.3K ≤$2.3K

Total Costs $25.4K $32.4K $32.4K $48.4K $33.3K $40.3K


*Additional premium over standard premium.

- 23 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

VPI vs. Cast Coil


The selection of HPS VPI transformers introduces a number of significant benefits versus cast
coil transformers for most applications. Cast coil transformers have found a level of acceptance in North
America and Europe but have fallen from favour due to the very high number of field incidences involving
this type of construction.

Winding Technology

The HPS VPI transformer for 60 BIL and higher utilizes disc wound high voltage windings. This
type of winding results in a very balanced electrical and mechanical winding without the potential of
severe voltage stresses between layers. The total voltage of the winding is more evenly distributed along
the full length of the winding. Essentially, the high voltage winding conductors are divided into twenty or
more sections where the voltage difference between the sections is substantially reduced. Typically, the
difference in potential between consecutive sections is between 500 and 1000 volts.
Cast coil transformers use layer or barrel type windings which do not result in as balanced a
design for voltage over the full length of the coil. The total winding conductors, in a layer winding, are
divided over only three or four consecutive layers. This results in a type of construction that has much
SECTION 4

higher voltage stresses between turns. The potential difference can be 4000 to 10000 volts between the
start and finish position of consecutive layers. This is much more susceptible to surge or impulse damage.

VPI Encapsulation vs. Cast

The massive amount of cast resin necessary for a cast coil high voltage and/or low voltage
winding is actually detrimental to the life expectancy of the unit. The co-efficient of expansion of the VPI
material is substantially less than that of the copper or aluminum conductors in the winding and cannot
keep up with particularly cyclical loads that quickly heat and subsequently cool the coils.

In the example of industrial loads where the transformer experiences periods of load followed by
no load, the cast resin is expanding and contracting at quite a different rate than the transformer coils.
Eventually, and that period would appear to be from five to seven years, the cast resin fatigues, cracks
appear and sections of will in fact fall away from the winding. This has been experienced and docu-
mented from field installations of cast coil transformers. The VPI transformer with its encapsulation of the
coils, is far better able to accommodate cyclical loads without fatigue to the resin. VPI transformers have
been in service since their inception over 40 years ago.

- 24 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

VPI vs. Cast Coil continued

Temperature Rise

Epoxy cast transformers are limited to a temperature of 100°C. The maximum hot spot shifts in a
cast coil transformer to the center of the coil near the core, and the lower temperature rise becomes
necessary to keep the cast resin from deteriorating.

VPI transformers maintain the traditional maximum hot spot at the top of the coil, near the core,
resulting in a far more efficient cooling process.

Impulse Characteristics

VPI transformers are designed with creep distances and clearances to meet the actual voltage
class and impulse dimensional requirements.

Cast coil transformers are slightly more compact, but necessitate the cast resin, and its integrity,

SECTION 4
to meet the impulse requirements. Any cracks or voids in the cast resin will result in creep distances less
than standard that will lead to unit failure.

VPI transformers meet impulse and creep distances even without the encapsulation.

Short Circuit Withstand

The short circuit withstand ability of HPS VPI transformers is paramount.

A recent test transformer was subjected to a 4 second continuous asymmetrical short circuit,
equivalent to the test for a cast coil transformer, plus a complete series of short circuit to meet the ANSI
test requirements.

In all, the VPI units accumulated 9 1/2 seconds of short circuit. The unit passed the test
flawlessly. The impedance of the transformer did not change at all, even though the test instrument was a
3 decimal digital measuring device.

HPS takes very strong exception to any position that cast coil transformers are superior in any
way to VPI transformers. We believe and have proven quite the contrary that VPI transformers are not
only equivalent but superior to cast coil transformers for almost any application.

- 25 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

MEDIUM VOLTAGE Distribution transformer


ENERGY EFFICIENCY GUIDELINES
In the past several years, there has been an accelerated rate of change to introduce energy
efficiency standards for transformers in North America. In addition to the benefits to the environment,
energy efficient transformers realize substantial savings in operating costs, thereby having a direct impact
on the initial investment evaluated over a period of time.

United States - Energy Efficiency Regulations


In the U.S. all medium voltage dry-type distribution transformers (as defined below) manufactured
after January 1st, 2010, must meet the minimum energy efficiency standards outlined in DOE 10 CFR
Part 431. The range of product covered by these standards are:

Primary (high) Voltage 601V to 34.5 kV


Secondary (low) Voltage 600V and below
Dry-Type Single Phase 15-833 kVA

Rating Three Phase 15-2500 kVA


Frequency 60 Hz only
For transformers exempted from the DOE efficiency regulations please refer to the following DOE link:
http://www.access.gpo.gov/nara/cfr/waisidx_09/10cfr431_09.html

US Department of Energy
DOE 10 CFR Part 431 Efficiency Levels
SECTION 5

Dry-Type Distribution Transformers - Medium Voltage

Single Phase Three Phase

> 96 kV BIL 20 -45 kV BIL > 96 kV BIL


20 - 45 kV BIL 46 - 95 kV BIL 46 - 95 kV BIL
kVA Efficiency kVA Efficiency Efficiency
Efficiency (%) Efficiency (%) Efficiency (%)
(%) (%) (%)

15 98.10 97.86 - 15 97.50 97.18 -


25 98.33 98.12 - 30 97.90 97.63 -
37.5 98.49 98.30 - 45 98.10 97.86 -
50 98.60 98.42 - 75 98.33 98.12 -
75 98.73 98.57 98.53 112.5 98.49 98.30 -
100 98.82 98.67 98.63 150 98.60 98.42 -
167 98.96 98.83 98.80 225 98.73 98.57 98.53
250 99.07 98.95 98.91 300 98.82 98.67 98.63
333 99.14 99.03 98.99 500 98.96 98.83 98.80
500 99.22 99.12 99.09 750 99.07 98.95 98.91
667 99.27 99.18 99.15 1000 99.14 99.03 98.99
833 99.31 99.23 99.20 1500 99.22 99.12 99.09
2000 99.27 99.18 99.15
2500 99.31 99.23 99.20
All efficiency values are at 50% of nameplate-rated load, 75˚C.

- 26 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Canada - Energy Efficiency Regulations


In Canada, all medium voltage dry-type distribution transformers (as defined below) manufactured
after January 1st, 2005, must meet the minimum energy efficiency guidelines as per CSA C802.2.
NRCan has recently evaluated the U.S. DOE 10 CFR Part 431 efficiency levels and determined they are
more cost effective than thus, suitable for use in Canada. As a result, in 2010 the Canadian Energy
Efficiency Act - Energy Efficiency Regulations (SOR/94-651) will be updated and the regulation will
harmonize the minimum efficiency levels with those established in the U.S. DOE 10 CFR Part 431. At the
time of printing of this catalog, these harmonized efficiency levels were proposed only; but HPS believes
these efficiency standards will be added to the Canadian Efficiency Regulations in the near future.
The range of product covered by these standards are:
Primary (high) Voltage Over 1.2 kV
Secondary (low) Voltage Less than 4000 Amps
Dry-Type Single Phase 15-833 kVA

Rating Three Phase 15-7500 kVA


Frequency 60 Hz only
For transformers exempted from the Canadian Efficiency Regulations please refer to the following NRCan link:
http://laws.justice.gc.ca/eng/sor-94-651/page-1.html

Canadian Energy Efficiency Act - Energy Efficiency Regulations


Efficiency Levels
Dry-Type Distribution Transformers - Medium Voltage

Single Phase Three Phase

> 96 kV BIL 20 -45 kV BIL > 96 kV BIL

SECTION 5
20 - 45 kV BIL 46 - 95 kV BIL 46 - 95 kV BIL
kVA Efficiency kVA Efficiency Efficiency
Efficiency (%) Efficiency (%) Efficiency (%)
(%) (%) (%)

15 98.10 97.86 97.80 15 97.50 97.18 97.11


25 98.33 98.12 98.07 30 97.90 97.63 97.57
37.5 98.49 98.30 98.25 45 98.10 97.86 97.80
50 98.60 98.42 98.37 75 98.33 98.12 98.07
75 98.73 98.57 98.53 112.5 98.49 98.30 98.25
100 98.82 98.67 98.63 150 98.60 98.42 98.37
167 98.96 98.83 98.80 225 98.73 98.57 98.53
250 99.07 98.95 98.91 300 98.82 98.67 98.63
333 99.14 99.03 98.99 500 98.96 98.83 98.80
500 99.22 99.12 99.09 750 99.07 98.95 98.91
667 99.27 99.18 99.15 1000 99.14 99.03 98.99
833 99.31 99.23 99.20 1500 99.22 99.12 99.09
2000 99.27 99.18 99.15
2500 99.31 99.23 99.20
3000 99.34 99.26 99.24
3750 99.38 99.30 99.28
5000 99.42 99.35 99.33
7500 99.48 99.41 99.39
All efficiency values are at 50% of nameplate-rated load, 75˚C.

- 27 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

STANDARD WEIGHT AND DIMENSIONAL SPECIFICATIONS


The tables on pages 29, 30 and 31 list three phase general purpose distribution (power) transformers
specifications for 150°C temperature rise units.
Table 1 and Table 2 list Energy Efficient (CSA C802.2 and DOE 10 CFR Part 431) copper and
aluminum respectively, for units 500 kVA to 7500 kVA in voltage classes from 1.2 kV to 15 kV.
Table 3 and Table 4 list non-energy efficient copper and aluminum respectively, for units 500 kVA to
15000 kVA in voltage classes from 1.2 kV to 46 kV.

For specifications on other sizes and ratings or specialty transformers such as: dual HV windings,
dual LV windings, rectifier transformers, traction duty transformers or cycloconverter transformers, please
consult our quotations department.

TYPICAL SPECIFICATIONS
To download a current copy of the HPS Dry-Type Medium Voltage (Power) Transformer Typical
Specifications (CSI Format) document, please go to:
http://www.hammondpowersolutions.com/products/locate_by_product/drytype_power_transformers
SECTION 5

Special Applications
The HPS line of distribution (power) transformers
offers unparalleled reliability and performance for the
most difficult applications including mining,
excavation, transit, marine, pulp and paper and utility.
Any applications where harmonics, short circuits, Impulse Levels
high intermittent loads or exposed environmental
hazards are prevalent, or reduced electromagnetic Hammond Power Solutions offers voltage
emissions or energy efficiencies are required, classes up to 46 kV and 250 kV BIL. The
Hammond Distribution (power) transformers should unique design parameters utilizing disc
be the one of choice. wound technology readily adapt to these
higher voltage classes. Our designs have
been subjected to all type tests per ANSI
and CSA specifications and have proven
their capability and reliability.

- 28 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS
Table 1 - Energy Efficient, Aluminum, 150°C Rise, Standard Configurations
Core & Coil Stubs Up (Fig. 1) Stubs Up Bus Arrgt. (Fig. 2 or 3) Straight Bus to End (Fig. 4)
Class Minimum
kVA W H D Weight Encl. W H D Weight Encl. W H D Weight
(kV) LV (Volts)
(IN) (IN) (IN) (LB) No. (IN) (IN) (IN) (LB) No. (IN) (IN) (IN) (LB)
1.2 208Y/120 45 40 32 2400 NJ2 48.5 59 34 2800 P3 66 72 54 3100
500 2.5 & 5 208Y/120 49 52 35 3100 NJ6 64 71 40 3700 P3 66 72 54 3800
15 208Y/120 66 62 35 5600 P12 78 91.5 60 6700 P13 90 91.5 60 6900
1.2 208Y/120 46 49 32 3600 NJ3 51.5 66 39 4000 P3 66 72 54 4300
750 2.5 & 5 208Y/120 49 53 36 4100 NJ7 64 75 47 4700 P3 66 72 54 4800
15 208Y/120 66 63 37 6400 P12 78 91.5 60 7500 P13 90 91.5 60 7700
1.2 208Y/120 57 56 35 3900 NJ6 64 71 40 4500 P6 78 72 60 5000
1000 2.5 & 5 208Y/120 59 60 36 4700 NJ7 64 75 47 5300 P12 78 91.5 60 5900
15 208Y/120 70 67 38 7400 P12 78 91.5 60 8500 P13 90 91.5 60 8700
1.2 416Y/240 63 58 38 4900 P6 78 72 60 5900 P6 78 72 60 6000
1250 2.5 & 5 416Y/240 63 59 38 5600 P12 78 91.5 60 6700 P12 78 91.5 60 6800
15 416Y/240 72 67 41 7500 P13 90 91.5 60 8700 P13 90 91.5 60 8800
1.2 416Y/240 64 56 38 5300 P6 78 72 60 6300 P6 78 72 60 6400
1500 2.5 & 5 416Y/240 65 60 38 6300 P12 78 91.5 60 7400 P12 78 91.5 60 7500
15 416Y/240 73 69 41 9600 P13 90 91.5 60 10800 P13 90 91.5 60 11000
1.2 416Y/240 68 59 41 7200 P6 78 72 60 8200 P13 90 91.5 60 8600
2000 2.5 & 5 416Y/240 69 61 41 7800 P12 78 91.5 60 8900 P13 90 91.5 60 9200
15 416Y/240 75 74 44 10800 P20 114 110 72 12600 P20 114 110 72 12800
2.5 & 5 416Y/240 74 66 44 8300 P13 90 91.5 60 9500 P13 90 91.5 60 9700
2500
15 416Y/240 79 79 44 11500 P20 114 110 72 13300 P20 114 110 72 13500
2.5 & 5 416Y/240 78 64 44 10000 P13 90 91.5 60 11200 P15 102 91.5 60 11500
3000
15 416Y/240 84 84 44 12800 P20 114 110 72 14600 P20 114 110 72 14800
2.5 & 5 600Y/346 88 78 46 15400 P20 114 110 72 17200 P20 114 110 72 17400
4000
15 600Y/346 91 84 50 16300 P20 114 110 72 18100 P20 114 110 72 18300
2.5 & 5 600Y/346 92 79 52 17900 P20 114 110 72 19700 P20 114 110 72 19900
5000
15 600Y/346 96 85 55 18400 P20 114 110 72 20200 P20 114 110 72 20400
7500 15 2400Y/1385 100 102 59 22800 Consult Factory Consult Factory
Note: All dimensions above are estimates only. For exact dimensional information please refer only to a certified “Approval
Drawing” that must be requested at the time of order/quote. Please refer to page 32 for termination configuration details.

Table 2 - Energy Efficient, Copper, 150°C Rise, Standard Configurations

SECTION 5
Core & Coil Stubs Up (Fig. 1) Stubs Up Bus Arrgt. (Fig. 2 or 3) Straight Bus to End (Fig. 4)
Class Minimum
kVA W H D Weight Encl. W H D Weight Encl. W H D Weight
(kV) LV (Volts)
(IN) (IN) (IN) (LB) No. (IN) (IN) (IN) (LB) No. (IN) (IN) (IN) (LB)
1.2 208Y/120 40 40 29 2800 NJ2 48.5 59 34 3200 P3 66 72 54 3400
500 2.5 & 5 208Y/120 46 47 35 3200 NJ6 64 71 40 3900 P3 66 72 54 4000
15 208Y/120 65 62 35 5800 P12 78 91.5 60 6900 P13 90 91.5 60 7200
1.2 208Y/120 48 41 32 3700 NJ3 51.5 66 39 4200 P3 66 72 54 4300
750 2.5 & 5 208Y/120 48 52 36 4200 NJ7 64 75 47 4800 P3 66 72 54 4900
15 208Y/120 61 66 37 6500 P12 78 91.5 60 7600 P12 78 91.5 60 7800
1.2 208Y/120 57 54 34 4400 NJ6 64 71 40 4900 P6 78 72 60 5500
1000 2.5 & 5 208Y/120 61 57 36 5200 P3 66 72 54 6100 P6 78 72 60 6300
15 208Y/120 68 66 38 8000 P12 78 91.5 60 9100 P13 90 91.5 60 9400
1.2 416Y/240 63 59 37 6300 P6 78 72 60 7300 P6 78 72 60 7400
1250 2.5 & 5 416Y/240 67 60 37 6700 P12 78 91.5 60 7800 P13 90 91.5 60 8100
15 416Y/240 70 71 37 7700 P12 78 91.5 60 8800 P13 90 91.5 60 9100
1.2 416Y/240 66 52 38 6400 P6 78 72 60 7400 P6 78 72 60 7600
1500 2.5 & 5 416Y/240 69 57 38 7200 P6 78 72 60 8200 P13 90 91.5 60 8600
15 416Y/240 69 74 38 9400 P20 114 110 72 11200 P20 114 110 72 11500
1.2 416Y/240 68 55 41 8100 P6 78 72 60 9100 P13 90 91.5 60 9500
2000 2.5 & 5 416Y/240 73 59 41 8500 P12 78 91.5 60 9600 P13 90 91.5 60 9900
15 416Y/240 79 70 41 11800 P13 90 91.5 60 13000 P15 102 91.5 60 13400
2.5 & 5 416Y/240 72 64 44 9500 P12 78 91.5 60 10600 P13 90 91.5 60 11000
2500
15 416Y/240 75 75 44 12500 P20 114 110 72 14300 P20 114 110 72 14600
2.5 & 5 416Y/240 72 64 44 10900 P12 78 91.5 60 12000 P13 90 91.5 60 12400
3000
15 416Y/240 76 72 44 13200 P20 114 110 72 15000 P20 114 110 72 15300
2.5 & 5 600Y/346 84 72 46 15800 P13 90 91.5 60 17000 P15 102 91.5 60 17400
4000
15 600Y/346 86 78 50 16600 P20 114 110 72 18400 P20 114 110 72 18800
2.5 & 5 600Y/346 84 80 52 18400 P20 114 110 72 20200 P20 114 110 72 20600
5000
15 600Y/346 88 90 55 19100 P23 114 122 72 21200 P23 114 122 72 21600
7500 15 2400Y/1385 96 90 59 24900 P23 114 122 72 27000 P23 114 122 72 27400
Note: All dimensions above are estimates only. For exact dimensional information please refer only to a certified “Approval
Drawing” that must be requested at the time of order/quote. Please refer to page 32 for termination configuration details.

- 29 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS
Table 3 - Non-Energy Efficient, Aluminum, 150°C Rise, Standard Configurations
Core & Coil Stubs Up (Fig. 1) Stubs Up Bus Arrgt. (Fig. 2 or 3) Straight Bus to End (Fig. 4)
Class Minimum
kVA W H D Weight Encl. W H D Weight Encl. W H D Weight
(kV) LV (Volts)
(IN) (IN) (IN) (LB) No. (IN) (IN) (IN) (LB) No. (IN) (IN) (IN) (LB)
1.2 208Y/120 42 43 29 2300 NJ2 48.5 59 34 2700 P3 66 72 54 2800
2.5 & 5 208Y/120 47 47 32 2600 NJ6 64 71 40 3100 P3 66 72 54 3200
15 208Y/120 63 52 32 4000 P6 78 72 60 5000 P13 90 91.5 60 5300
500
25 208Y/120 69 64 38 4700 P13 90 91.5 60 5900 P13 90 91.5 60 6000
34.5 208Y/120 73 69 39 5600 P13 90 91.5 60 6800 P15 102 91.5 60 7000
46 208Y/120 81 77 40 5900 P20 114 110 72 7700 P20 114 110 72 7800
1.2 208Y/120 48 53 30 2700 NJ3 51.5 66 39 3200 P3 66 72 54 3300
2.5 & 5 208Y/120 47 49 33 3600 NJ6 64 71 40 4100 P3 66 72 54 4200
15 208Y/120 63 54 34 4700 P6 78 72 60 5700 P13 90 91.5 60 6000
750
25 208Y/120 69 65 34 5700 P13 90 91.5 60 6900 P13 90 91.5 60 7000
34.5 208Y/120 73 70 39 6500 P13 90 91.5 60 7700 P15 102 91.5 60 7900
46 208Y/120 81 78 40 7600 P20 114 110 72 9400 P20 114 110 72 9500
1.2 208Y/120 55 54 32 4000 NJ6 64 71 40 4500 P6 78 72 60 5100
2.5 & 5 208Y/120 57 56 33 4400 NJ6 64 71 40 4900 P6 78 72 60 5500
15 208Y/120 67 59 35 5700 P12 78 91.5 60 6800 P13 90 91.5 60 7000
1000
25 208Y/120 69 70 35 6600 P13 90 91.5 60 7800 P13 90 91.5 60 7900
34.5 208Y/120 75 75 39 7400 P20 114 110 72 9200 P20 114 110 72 9400
46 208Y/120 81 82 42 9200 P20 114 110 72 11000 P20 114 110 72 11200
1.2 416Y/240 61 56 35 4500 P3 66 72 54 5400 P6 78 72 60 5600
2.5 & 5 416Y/240 61 56 35 5100 P3 66 72 54 6000 P6 78 72 60 6200
15 416Y/240 69 60 37 6700 P12 78 91.5 60 7800 P13 90 91.5 60 8000
1250
25 416Y/240 73 70 37 7600 P13 90 91.5 60 8800 P15 102 91.5 60 9000
34.5 416Y/240 77 77 39 8700 P20 114 110 72 10500 P20 114 110 72 10700
46 416Y/240 85 84 42 10700 P20 114 110 72 12500 P20 114 110 72 12700
1.2 416Y/240 63 54 35 5400 P6 78 72 60 6400 P6 78 72 60 6500
2.5 & 5 416Y/240 63 57 35 6000 P6 78 72 60 7000 P6 78 72 60 7100
15 416Y/240 71 62 37 7700 P13 90 91.5 60 8900 P13 90 91.5 60 9100
1500
25 416Y/240 77 72 38 8900 P20 114 110 72 10700 P20 114 110 72 10900
34.5 416Y/240 81 78 39 10100 P20 114 110 72 11900 P20 114 110 72 12100
46 416Y/240 87 84 42 12100 P20 114 110 72 13900 P20 114 110 72 14100
1.2 416Y/240 67 57 37 7400 P6 78 72 60 8400 P13 90 91.5 60 8800
2.5 & 5 416Y/240 67 58 37 7900 P6 78 72 60 8900 P13 90 91.5 60 9300
15 416Y/240 73 68 40 9300 P13 90 91.5 60 10500 P13 90 91.5 60 10700
2000
25 416Y/240 79 72 40 10800 P20 114 110 72 12600 P20 114 110 72 12800
SECTION 5

34.5 416Y/240 87 80 42 12000 P20 114 110 72 13800 P20 114 110 72 14000
46 416Y/240 93 88 45 14800 P23 114 122 72 16900 P24 120 122 72 17200
2.5 & 5 416Y/240 73 64 40 8500 P12 78 91.5 60 9600 P13 90 91.5 60 9900
15 416Y/240 77 74 40 10400 P20 114 110 72 12200 P20 114 110 72 12400
2500 25 416Y/240 85 82 40 12200 P20 114 110 72 14000 P20 114 110 72 14200
34.5 416Y/240 93 90 42 13700 P23 114 122 72 15800 P24 120 122 72 16100
46 416Y/240 101 98 44 17500 P24 120 122 72 19800 P26 130 122 72 20100
2.5 & 5 416Y/240 77 62 40 10200 P13 90 91.5 60 11400 P13 90 91.5 60 11600
15 416Y/240 83 79 40 12200 P20 114 110 72 14000 P20 114 110 72 14200
3000 25 416Y/240 91 78 40 14400 P20 114 110 72 16200 P20 114 110 72 16400
34.5 416Y/240 97 87 42 15900 P23 114 122 72 18000 P24 120 122 72 18300
46 416Y/240 105 95 45 20000 P26 130 122 72 22400 P28 145 122 72 22900
2.5 & 5 600Y/346 87 76 42 15700 P15 102 91.5 60 17000 P15 102 91.5 60 17200
15 600Y/346 90 80 46 16300 P20 114 110 72 18100 P20 114 110 72 18300
4000 25 600Y/346 93 81 48 18000 P20 114 110 72 19800 P20 114 110 72 20000
34.5 600Y/346 101 88 48 19700 P24 120 122 72 22000 P26 130 122 72 22300
46 600Y/346 109 96 50 24900 P26 130 122 72 27300 P28 145 122 72 27800
2.5 & 5 600Y/346 91 77 48 18300 P15 102 91.5 60 19600 P20 114 110 72 20300
15 600Y/346 95 81 50 18800 P20 114 110 72 20600 P20 114 110 72 20800
5000 25 600Y/346 93 88 50 20200 P20 114 110 72 22000 P20 114 110 72 22200
34.5 2400Y/1385 101 96 52 21900 P24 120 122 72 24200 P26 130 122 72 24500
46 2400Y/1385 109 102 56 29700 Consult Factory Consult Factory
15 2400Y/1385 99 98 54 23200 P23 114 122 72 25300 P24 120 122 72 25700
25 2400Y/1385 101 92 54 26100 P23 114 122 72 28200 P24 120 122 72 28600
7500
34.5 2400Y/1385 109 98 60 29600 P26 130 122 72 32000 P28 145 122 72 32500
46 2400Y/1385 117 102 63 39900 Consult Factory Consult Factory
15 2400Y/1385 115 94 60 26000 P26 130 122 72 28400 P26 130 122 72 28700
25 2400Y/1385 124 100 62 29000 P28 145 122 72 31700 P28 145 122 72 31900
10000
34.5 2400Y/1385 138 110 62 36000 P30 163 122 72 38900 P30 163 122 72 39200
46 2400Y/1385 146 113 64 43800 Consult Factory Consult Factory
15 2400Y/1385 118 110 60 27000 P26 130 122 72 29400 P26 130 122 72 29700
25 2400Y/1385 126 110 60 29300 P28 145 122 72 32000 P28 145 122 72 32100
15000
34.5 2400Y/1385 140 112 64 36000 P30 163 122 72 38900 P30 163 122 72 39300
46 2400Y/1385 148 118 68 45000 Consult Factory Consult Factory
Note: All dimensions above are estimates only. For exact dimensional information please refer only to a certified “Approval
Drawing” that must be requested at the time of order/quote. Please refer to page 32 for termination configuration details.
- 30 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS
Table 4 - Non-Energy Efficient, Copper, 150°C Rise, Standard Configurations
Core & Coil Stubs Up (Fig. 1) Stubs Up Bus Arrgt. (Fig. 2 or 3) Straight Bus to End (Fig. 4)
Class Minimum
kVA W H D Weight Encl. W H D Weight Encl. W H D Weight
(kV) LV (Volts)
(IN) (IN) (IN) (LB) No. (IN) (IN) (IN) (LB) No. (IN) (IN) (IN) (LB)
1.2 208Y/120 45 39 27 2500 NJ2 48.5 59 34 2900 P3 66 72 54 3100
2.5 & 5 208Y/120 44 42 32 2700 NJ3 51.5 66 39 3100 P3 66 72 54 3300
15 208Y/120 62 52 32 4100 P6 78 72 60 5100 P6 78 72 60 5200
500
25 208Y/120 62 63 37 4700 P12 78 91.5 60 5800 P13 90 91.5 60 6100
34.5 208Y/120 67 68 39 5100 P13 90 91.5 60 6300 P13 90 91.5 60 6500
46 208Y/120 73 74 42 5400 P20 114 110 72 7300 P20 114 110 72 7400
1.2 208Y/120 46 40 30 3025 NJ3 51.5 66 39 3500 P3 66 72 54 3600
2.5 & 5 208Y/120 46 48 33 3400 NJ3 51.5 66 39 3800 P3 66 72 54 4000
15 208Y/120 58 57 34 4800 P9 66 91.5 54 5800 P12 78 91.5 60 6000
750 25 208Y/120 64 65 34 5700 P12 78 91.5 60 6800 P13 90 91.5 60 7100
34.5 208Y/120 69 70 39 6400 P13 90 91.5 60 7600 P15 102 91.5 60 7900
46 208Y/120 75 72 40 6800 P20 114 110 72 8700 P20 114 110 72 8800
1.2 208Y/120 55 52 31 4400 NJ6 64 71 40 4900 P6 78 72 60 5500
2.5 & 5 208Y/120 59 53 33 4800 NJ6 64 71 40 5300 P6 78 72 60 5900
15 208Y/120 65 58 35 6200 P12 78 91.5 60 7300 P13 90 91.5 60 7600
1000 25 208Y/120 69 67 35 6700 P13 90 91.5 60 7900 P13 90 91.5 60 8100
34.5 208Y/120 74 72 39 7700 P20 114 110 72 9600 P20 114 110 72 9700
46 208Y/121 79 76 41 8400 P20 114 110 72 10300 P20 114 110 72 10400
1.2 416Y/240 61 57 34 5600 P3 66 72 54 6500 P6 78 72 60 6700
2.5 & 5 416Y/240 65 57 34 5900 P6 78 72 60 6900 P6 78 72 60 7000
15 416Y/240 67 64 34 7000 P12 78 91.5 60 8100 P13 90 91.5 60 8400
1250 25 416Y/240 73 67 34 8100 P13 90 91.5 60 9300 P15 102 91.5 60 9600
34.5 416Y/240 79 72 36 9000 P20 114 110 72 10900 P20 114 110 72 11000
46 416Y/240 85 80 38 9800 P20 114 110 72 11700 P20 114 110 72 11800
1.2 416Y/240 65 50 35 6500 P6 78 72 60 7500 P6 78 72 60 7700
2.5 & 5 416Y/240 67 54 35 6900 P6 78 72 60 7900 P13 90 91.5 60 8400
15 416Y/240 67 67 35 7600 P12 78 91.5 60 8700 P13 90 91.5 60 9100
1500 25 416Y/240 77 69 35 9200 P13 90 91.5 60 10400 P15 102 91.5 60 10800
34.5 416Y/240 83 74 38 10200 P20 114 110 72 12100 P20 114 110 72 12300
46 416Y/240 89 82 42 10900 P20 114 110 72 12800 P24 120 122 72 13400
1.2 416Y/240 67 53 37 8200 P6 78 72 60 9200 P13 90 91.5 60 9600
2.5 & 5 416Y/240 71 56 37 8700 P6 78 72 60 9700 P13 90 91.5 60 10100
15 416Y/240 77 64 37 10200 P13 90 91.5 60 11400 P15 102 91.5 60 11800
2000 25 416Y/240 79 72 37 11400 P20 114 110 72 13300 P20 114 110 72 13500

SECTION 5
34.5 416Y/240 85 78 40 12500 P20 114 110 72 14400 P20 114 110 72 14600
46 416Y/240 93 84 44 13600 P20 114 110 72 15500 P24 120 122 72 16100
2.5 & 5 416Y/240 71 62 40 9700 P12 78 91.5 60 10800 P13 90 91.5 60 11200
15 416Y/240 73 70 40 11400 P20 114 110 72 13300 P20 114 110 72 13500
25 416Y/240 79 74 40 12500 P20 114 110 72 14400 P20 114 110 72 14600
2500
34.5 416Y/240 85 80 42 13700 P20 114 110 72 15600 P20 114 110 72 15800
46 416Y/240 91 86 44 15900 P20 114 110 72 17800 P24 120 122 72 18400
2.5 & 5 416Y/240 71 62 40 11100 P12 78 91.5 60 12200 P13 90 91.5 60 12600
15 416Y/240 75 67 40 12500 P13 90 91.5 60 13700 P15 102 91.5 60 14100
25 416Y/240 84 75 40 14600 P20 114 110 72 16500 P20 114 110 72 16700
3000
34.5 416Y/240 91 81 42 15800 P20 114 110 72 17700 P20 114 110 72 17900
46 416Y/240 97 88 45 18100 P24 120 122 72 20400 P26 130 122 72 20800
2.5 & 5 600Y/346 83 70 42 16100 P13 90 91.5 60 17300 P15 102 91.5 60 17700
15 600Y/346 85 74 46 16600 P20 114 110 72 18500 P20 114 110 72 18700
4000
25 600Y/346 89 78 48 19100 P20 114 110 72 21000 P20 114 110 72 21200
34.5 600Y/346 95 84 48 20500 P20 114 110 72 22400 P24 120 122 72 23100
46 600Y/346 103 92 50 22400 P25 121 122 72 24700 P26 130 122 72 25100
2.5 & 5 600Y/346 83 78 48 18800 P20 114 110 72 20700 P20 114 110 72 20900
15 600Y/346 87 86 50 19500 P20 114 110 72 21400 P20 114 110 72 21600
25 600Y/346 91 86 50 21300 P20 114 110 72 23200 P20 114 110 72 23400
5000
34.5 2400Y/1385 98 92 52 22700 P23 114 122 72 24800 P24 120 122 72 25300
46 2400Y/1385 105 100 56 26400 Consult Factory Consult Factory
15 2400Y/1385 95 86 54 25400 P20 114 110 72 27300 P20 114 110 72 27600
7500 25 2400Y/1385 101 90 54 29000 P23 114 122 72 31100 P24 120 122 72 31600
34.5 2400Y/1385 109 96 60 32200 P26 130 122 72 34600 P28 145 122 72 35300
46 2400Y/1385 115 102 63 37200 Consult Factory Consult Factory
15 2400Y/1385 120 94 60 30000 P27 139 122 72 32000 P27 139 122 72 32300
25 2400Y/1385 126 100 62 35000 P28 145 122 72 37100 P28 145 122 72 37400
10000
34.5 2400Y/1385 132 110 62 38000 P29 154 122 72 40900 P29D 154 122 78 41200
46 2400Y/1385 140 113 64 41300 Consult Factory Consult Factory
15 2400Y/1385 122 110 60 42500 P27 139 122 72 44400 P27 139 122 72 44700
25 2400Y/1385 126 110 60 51000 P28 145 122 72 53100 P28 145 122 72 53400
15000
34.5 2400Y/1385 136 112 64 58000 P30 163 122 72 60300 P30 163 122 72 60600
46 2400Y/1385 145 118 68 69000 Consult Factory Consult Factory
Note: All dimensions above are estimates only. For exact dimensional information please refer only to a certified “Approval
Drawing” that must be requested at the time of order/quote. Please refer to page 32 for termination configuration details.
- 31 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

TERMINAL LOCATIONS
The following are some of the examples of terminal locations available on HPS Dry-Type Medium Voltage
Distribution (Power) Transformers.

LV
D+3
W D

HV
HV HV
PLAN VIEW
D
HV
HV LV
H

H LV

LV

W
FRONT VIEW RIGHT SIDE VIEW
FRONT VIEW RIGHT SIDE VIEW

STUBS UP (CORE & COIL ONLY) 'NJ' STYLE ENCLOSURE

Figure 1 Figure 2
SECTION 5

LV LV

HV HV
PLAN VIEW PLAN VIEW
D+2
D+2
W D
D

HV HV LV LV LV

H H HV

HV

W
FRONT VIEW RIGHT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW

STUBS UP IN 'P' STYLE ENCLOSURE STRAIGHT BUSS TO END IN 'P' STYLE ENCLOSURE

Figure 3 Figure 4

HPS Dry-Type Distribution (Power) Transformers Terminations


are also available in “Switchboard” designs.
- 32 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

OPTIONS AND ACCESSORIES


The following options/accessories are available on all HPS Distribution (Power) Transformers:

1) Neutral grounding resistors and monitors. 8) Fans: Fans with or without control circuit, or
• Commonly installed to meet regulatory codes provision only for fan rating.

2) Temperature monitoring devices.


• For customers requiring on-line monitoring on
transformer conditions. Option for digital and
dial type, with and without contacts.

3) Strip Heater
• Strip heaters are commonly used to maintain
the interior temperature of an installation in the
event of shutdown or cold weather conditions.

4) Ground Fault Relay


• For use where customer requires on-going • Fans can be added after for additional cooling
monitoring of ground fault status. when desired.

5) Anti-vibration Mountings: 9) Seismic: Seismic snubbers, restraints or


anti-vibration pads, vibrations isolators. provision.

• When additional noise dampening is required, • Additional isolation protection for certain

SECTION 6
anti-vibration pads or noise isolators can be used Seismic environments
to reduce operating noise even further. Isolators
can also be used for meeting anti-sway
Other accessories available include:
requirements for elevated installations
 Power source For Fans/Thermometers
6) Lightning Arresters:  Secondary Circuit Breaker in Separate Component
station, intermediate, distribution class.
 Bushings: A) high voltage B) low voltage
• For extra protection against failure under
adverse electrical conditions caused by  Provisions for Cable Entry
lightning  Ground Bus (1/4” X 2” Copper)

7) Nameplate: aluminum or stainless steel  Mimic Bus


• In some environments, the customer may  Kirk Key Interlock
want nameplates with a longer lifespan for
visibility many years beyond normal.  Current and Potential Transformers
 Secondary metering: ammeter or voltmeter.
 Electrostatic Shield

- 33 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

HPS ENCLOSURES
An enclosure is a surrounding case constructed to provide a degree of protection to personnel
against access to hazardous parts and to provide a degree of protection to the enclosed equipment
against specified environmental conditions.

Applicable Engineering Standards


HPS Enclosures are designed in accordance with the following standards:

• CSA 22.2 No. 47 (General Purpose)


• CSA 22.2 No. 94 (Specialty Enclosures)
• NEMA 250
• UL 50 and UL 50E

Please ensure to reference all local and national electrical codes and applicable transformer
standards before selecting an enclosure for your application.

Definitions
Degree of protection: The extent of protection provided by an enclosure against access to
hazardous parts, against ingress of foreign solid objects and/or against
ingress of water and verified by approved standardized test methods.
Hazardous parts: A part that is hazardous to approach or to touch.
Indoor Locations: Areas which are protected from exposure to the weather.
Non-ventilated: Constructed so as to provide no intentional circulation of external air
through the enclosure.
Outdoor locations: Locations that are exposed to the weather.
Ventilated: Constructed so as to provide for the circulation of external air through the
enclosure to remove excess heat, fumes or vapors.
SECTION 6

Enclosure Selection
The selection of the appropriate enclosure is vital for the long term reliability of your HPS product.
The “degree of protection” an enclosure actually provides can only be determined by referencing
the appropriate test methods outlined in the above mentioned standards.

The list below is just some of the typical enclosure types available for HPS products, their
applications, and the environmental conditions they are designed to meet.

HPS Typical Enclosure Types


TYPE 1
This is a general purpose ventilated enclosure constructed for indoor use only to provide a degree of
protection to personnel against access to hazardous parts; to provide a degree of protection of the
equipment inside the enclosure against ingress of solid foreign objects (falling dirt).

- 34 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

TYPE 2
This is a general purpose ventilated enclosure constructed for indoor use only to provide a degree of
protection to personnel against access to hazardous parts; to provide a degree of protection of the
equipment inside the enclosure against the ingress of solid foreign objects (falling dirt); and to provide a
degree of protection with respect to harmful effects on the equipment due to the ingress of water (dripping
or light splashing).

TYPE 3RI
This is a general purpose ventilated enclosure constructed for indoor use only to provide a degree of
protection to personnel against access to hazardous parts; to provide a degree of protection of the
equipment inside the enclosure against the ingress of solid foreign objects (falling dirt); and to provide a
degree of protection with respect to harmful effects on the equipment due to the ingress of water
(sprinkler head spray, light splashing of liquids).

TYPE 3R
This is a general purpose ventilated enclosure constructed for either indoor or outdoor use to
provide a degree of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against the ingress of solid foreign objects (falling dirt);
and to provide a degree of protection with respect to harmful effects on the equipment due to the ingress
of water (rain, sleet, snow); and that will be undamaged by the external formation of ice on the enclosure.

TYPE 3RE
This is a general purpose ventilated enclosure constructed for either indoor or outdoor use to
provide a degree of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against the ingress of solid foreign objects (falling dirt
and blowing non-conductive dust ); and to provide a degree of protection with respect to harmful effects
on the equipment due to the ingress of water (rain, sleet, windblown snow); and that will be undamaged
by the external formation of ice on the enclosure.

TYPE 4

SECTION 6
This is a general purpose non-ventilated enclosure constructed for either indoor or outdoor use to
provide a degree of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against the ingress of solid foreign objects (falling dirt
and windblown dust); and to provide a degree of protection with respect to harmful effects on the
equipment due to the ingress of water (rain, sleet, snow, splashing water, and hose directed water); and
that will be undamaged by the external. (Note: not submersible)

TYPE 4X
This is a general purpose non-ventilated enclosure constructed for either indoor or outdoor use to
provide a degree of protection to personnel against access to hazardous parts; to provide a degree of
protection of the equipment inside the enclosure against the ingress of solid foreign objects (windblown
dust); and to provide a degree of protection with respect to harmful effects on the equipment due to the
ingress of water (rain, sleet, snow, splashing water, and hose directed water); that provides an additional
level of protection against corrosion; and that will be undamaged by the external formation of ice on the
enclosure. (Note: not submersible)

- 35 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

TYPE 12
This is a general purpose non-ventilated enclosure constructed (without knockouts) for indoor use
only to provide a degree of protection to personnel against access to hazardous parts; to provide a
degree of protection of the equipment inside the enclosure against the ingress of solid foreign objects
(falling dirt and circulating dust, lint, fibers, and flyings); and to provide a degree of protection with respect
to harmful effects on the equipment due to the ingress of water (dripping and light splashing). (Note: not
submersible)

CONVERSION OF NEMA ENCLOSURE TYPE RATINGS TO


IEC 60529 ENCLOSURE CLASSIFICATION DESIGNATIONS (IP)
(Cannot be Used to Convert IEC Classification Designations to NEMA Type Ratings)

IP IP
1st Character
NEMA Enclosure Type 2nd Character
3, 3X, 3R, 12,
1 2 4, 4X 5 6 6P
3S,3SX 3RX 12K, 13
IP0_ IP_0
IP1_ IP_1
IP2_ IP_2
IP3_ IP_3
IP4_ IP_4
IP5_ IP_5
IP6_ IP_6
IP_7
IP_8
A B A B A B A B A B A B A B A B A B

IP First Character = The A shaded block in the “A” column represents the first IP character. This indicates
that the NEMA Enclosure Type exceeds the requirements for the respective IEC 60529 IP First Character
SECTION 6

Designation. This IP First Character Designation is the protection against access to hazardous parts and
solid foreign objects.
IP Second Character = The B shaded block in the “B” column represents the second IP character. This
indicates that the NEMA Enclosure Type exceeds the requirements for the respective IEC 60529 IP
Second Character Designation. This IP First Character Designation is the protection against the ingress
of water.
Example: NEMA Type 3R = IP24
Note: Please refer to NEMA standards publication 250-2003 for exact details of the above table.

- 36 -
© Hammond Power Solutions Inc. Data subject to change without notice.
HPS DRY-TYPE DISTRIBUTION (POWER) TRANSFORMERS

Notes

SECTION 6

- 37 -
© Hammond Power Solutions Inc. Data subject to change without notice.
OTHER HPS CATALOGS

Yes, I am interested in receiving more information on


other HPS® Transformer Products.
If you are interested in other HPS Transformer Products, please visit www.hammondpowersolutions.com.
All of our literature and much more is also available to download free, 24 hours a day, 7 days a week through
the HPS web site at: www.hammondpowersolutions.com/products/product_literature

Canada: or United States:


Literature Services Literature Services
Hammond Power Solutions Inc. Hammond Power Solutions, Inc.
595 Southgate Drive 1100 Lake Street
Guelph, Ontario, Canada N1G 3W6 Baraboo, WI 53913-2866
Toll Free: 1-888-798-8882 Toll Free: 1-866-705-4684
Fax: 519-822-9688 Fax: 608-356-2452

E-MAIL: catalog@hammondpowersolutions.com
URL: www.hammondpowersolutions.com

If you would like to be contacted by your local HPS Sales Representative or Authorized HPS Distributor,
please fill in the information below, photocopy this page and fax or mail it to the above number or address.

My need for Transformer Products is: Immediate Future

Please send me the name of your local HPS Sales Representative


Please provide me with the name of the local Authorized HPS Distributor

Name: E-Mail Address:

Company:

Address:
Please check one:
City, State:
Electrical Distributor Electronic Distributor
Zip Code: Contractor Panel Builder
MRO OEM
Telephone:
Consultant Engineering Firm
Fax: Other:

Hammond Power Solutions Inc.


- Your First Source for Transformers

- 38 -
© Hammond Power Solutions Inc. Data subject to change without notice.
OTHER HPS TRANSFORMER PRODUCTS

Specialty/Custom Multi-Pulse Drive Transformers


Distribution Transformers

Rectifier Transformers Dry-Type Network Transformers

Specialty/Custom World’s Largest Dry-Type MV


Distribution (Power) Transformers Distribution (Power) Transformers

- 39 -
© Hammond Power Solutions Inc. Data subject to change without notice.
Canada
595 Southgate Drive
Guelph, Ontario
N1G 3W6
Tel (519) 822-2441
Fax (519) 822-9701
Granby, QC
USA
1100 Lake Street
Baraboo, Wisconsin
53913-2866
Baraboo, WI
Tel (608) 356-3921
Fax (608) 355-7623 Guelph, ON
Walkerton, ON

Toll free in Canada


1-888-798-8882

Toll free in United States Compton, CA


1-866-705-4684

sales@hammondpowersolutions.com
www.hammondpowersolutions.com Monterrey, MX

Distributed by:

© Hammond Power Solutions Inc.


Literature No.: HPWR
Issue Date: May 2010