NUMBER:ELE-P68-M13-CE-
ELECTRICAL TEST CERTIFICATION 0019
TESTE DE CABOS DE BAIXA TENSÃO DATA:
LOW VOLTAGE CABLE TEST DATE:05/04/2017
CLIENTE: PROJETO: PAGINA:
CLIENT:TUPI/BV PROJECT:P68 PAGE:1 OF 1
TERMINAÇÕES EXTERNAS
APROVADO / APPROVED
EXTERNAL TERMINATIONS
TERMINAÇÕES INTERNAS APROVADO / APPROVED
INTERNAL TERMINATIONS
CONEXÕES
CONNECTIONS APROVADO / APPROVED
SUPORTES
APROVADO / APPROVED
SUPPORTS
CONTINUIDADE
APROVADO / APPROVED
CONTINUITY
ATERRAMENTO APROVADO / APPROVED
EARTHING
INSPEÇÃO ELÉTRICA / ELECTRICAL INSPECTION
RESISTÊNCIA DE ISOLAMENTO / ISOLATION RESISTANCE
PONTO / PERIOD RESISTÊNCIA (MΩ) / RESISTANCE (MΩ)
FASES A x B >2200
FASES B x C >2200
FASES C x A >2200
FASE A x TERRA >2200
FASE B x TERRA >2200
FASE C x TERRA >2200
TENSÃO APLICADA (KV) / APPLIED VOLTAGE (KV) TEMPO DE APLICAÇÃO(Min) / APPLIED TIME (Min)
1KV 1Min
TEMPERATURA °C / TEMPERATURE °C UR (%)
8°C 50%
OBSERVAÇÕES / OBSERVATIONS
APROVAÇÃO / APPROVAL
EXECUTANTE / REPRESENTATIVE VERIFICAÇÃO / VERIFICATION TUPI BV