Você está na página 1de 27

mP20

DX - DX/S - ES - TC - CW
MICROPROCESSOR CONTROL FOR DIRECT EXPANSION
AND CHILLED WATER UNITS

INSTRUCTION MANUAL

GB

© COPYRIGHT UNIFLAIR 1999

Version: 1.4 - 06/09/1999


Pag. 27 Cod. 05MP112A1A
1. CONTENTS
1. CONTENTS 2 fier and off-set sensors
2 8.6. Setting delay times 12
2. IMPORTANT 8.7. Remote control, supervision and stand-by manage- 13
3. INTRODUCTION 3 ment
4. CHARACTERISTICS 3 8.8. Changing the password 13
4.1. Basic circuit 3 8.9. Clearing the memory and restoring factory-set defaults 14
4.2. Eprom Memory 3 9. CALIBRATION AND SETTINGS 14
4.3. Optional circuits 4 9.1. Room setting alarms 15
4.4. User terminal 4 9.2. Setting the run hour counter alarm threshold 16
5. REMOTE CONTROLS 5 9.3. Setting second level alarms 16
6 10. CLOCK-CALENDAR - TIME BANDS 17
6. SPECIAL FUNCTIONS
6.1. Automatic inversion of strand-by unit 6 11. MANUAL CONTROLS 18
6.2. Setback function 7 12. MANUAL OVERRIDE OF START-UP/STOP 19
6.3. Automatic time-band operation 7
12.1. Manual override procedure 19
6.4. Emergency function 7
12.2. Exiting manual override 19
7. SWITCHING ON AND PROGRAMMING 7
13. ALARMS 19
7.1. Connecting the user terminal and power supply 7 13.1 Historical sequence of alarms 20
7.2. Display information with unit off 8 13.2 Description of alarm events 20
7.3. Switching the unit on and off 8 22
7.4. The STATUS screen 8
14. TROUBLESHOOTING
7.5. STATUS LOOP: visualisation of operational parame- 9 15. FACTORY PRE-SETS/CALIBRATION FIELDS 23
ters 15.1 Restoring factory pre-sets 23
7.6. Keypad 9
7.7. Consultation and programming menus 9
7.8. Interaction levels 9
8. CONFIGURATION OF THE CONTROL 10
8.1. Direct expansion circuits settings 11 DIAGRAM IN APPENDIX
8.2. Energy saving circuits settings 11
8.3. Setting of the twin-cool circuits 11 LAY-OUT OF BASIC CIRCUIT - STANDARD VERSION
8.4. Dehumidification and high temp. alarm settings 11 SCREEN FLOW CHART
8.5. Setting of hot gas re-heat, external devices, humidi- 12

2. IMPORTANT
Electronic components are sensitive to static discharges emitted by the human body. Touch an
earth connection before handling any electronic component.

Take out the components (basic circuit, user terminal, EPROM) from their containers only when
ready to assemble and avoid touching the electronic components.

Before undertaking any operation (connection, disconnection, external linking), always disconnect
the unit from the power supply.

2
3. INTRODUCTION
The control system consists of a Basic Circuit containing the micro- • setting up a network link of the circuits and the terminal which
processor , a read-only memory (EPROM) which contains the regula- can exchange data with the pre-selected circuit.
tion programme, a read/write memory (RAM) for operational vari- Once programmed, the basic circuit can function automatically follow-
ables, a permanent read/write memory (EEPROM) for the mainte- ing the pre-set data contained in the EEPROM memory.
nance of the most important data and the pre-set parameters even in The basic circuit can therefore be used on its own: this solution, how-
the case of power failure; the circuit also contains the terminals for ever - which does not provide any means of interface with the user for
electronic input and output connections and power supply. the setting of parameters and the display of data and events - is sug-
gested for units for which the programming of the functions and/or the
The User Terminal is used for programming the control parameters functional parameters are expected to be modified very rarely - or
(set points, differentials, alarm thresholds etc.) and the display of data never - as for example in unmanned installations.
and events (reading the set points and the controlled values, function
events and/or alarms etc.). This is also controlled by a microproces- To see the date and the time and to use the subroutines linked to
sor equipped with an LCD display, a keypad, LEDs and alarm time (time bands, memorising the time of alarm events) the basic
buzzer). circuit can be supplied with a clock circuit.
A single user terminal can be used to programme and display the
parameters of more than one basic circuit; this can be done: The control can be linked to a centralised supervision system; an op-
• by linking where necessary the terminal to the appropriate unit, tional serial board is available to this end , which makes possible the
through the six-way telephone cable link with an easily removable optoisolated interface to a RS422 network for data transmission.
connector

4. CHARACTERISTICS
4.1. BASIC CIRCUIT
The basic circuit (see lay-out of the basic circuit in the appendix) in
the electrical panel of the unit is connected to the user terminal with a DIGITAL RELAY OUTPUTS
two-wire half-duplex asynchronous cable with a six-way telephone DO1 Fan relay
connector; the maximum cable length for remote fitting of the user DO2 Compressor 1 relay / Chiller calling for dehumidification (CW
terminal is 50 metres. For longer distances a T-junction must be used units)
with 6-pole shielded cable (AWG24-type with twisted pair shielding DO3 Compressor 2 relay
and wires and resistance <80ohm/M) with maximum length DO4 Re-heat relay 1 / hot gas coil
200m.The inputs and outputs of the unit are summarised below: DO5 Re-heat relay 2
DO6 Humidifier relay / external humidifier call-on
OPTOISOLATED DIGITAL INPUTS DO7 Humidifier feed valve relay
DO8 Humidifier drain valve relay
DI1 Remote switch-on/switch-off inlet
DO9 Switch-over contact for control of dehumidification/coil part set
DI2 Flow switch pressostat
(in dehumidification/CW)
DI3 Clogged filter pressostat
DO10 Switch-over contact for 2nd level alarm signal (addressable)
DI4 Circuit 1. low pressure-stat / phase sequence control relay /
DO11 Switch-over contact for generic alarm signal
CW units: water flow switches
DI5 Circuit 1. high pressure-stat
DI6 Circuit 2. low pressure-stat ANALOGUE OUTPUTS - SIGNAL 0÷10V=
DI7 Circuit 2. high pressure-stat AO1 (DO12) Cold water valve
DI8 Electrical resistance safety thermostat AO2 (DO13) Hot water valve / external radiator control
DI9 Humidifier interface module (high level)
DI10 Flooding detector
DI11 Smoke-fire detector 4.2. EPROM MEMORY
DI12 T+H room limit sensors
The regulatory programme of the control system is contained in the
EPROM memory on the basic circuit and identified by an alphanu-
ANALOGUE INPUTS - NTC SENSORS meric code.
AI1 Room air temperature sensor
AI2 Delivery air temperature sensor mP20 v. 5.1 EN
AI3 Recirculating water / CW temperature sensor (NTC) Microprocessor Control
AI4 External air temperature sensor (NTC) Software Version
Language
25/06/99 SB n.1
ANALOGUE INPUTS - ACTIVE SENSORS -1÷1Vcc
Update
AI5 Room relative humidity sensor SB = Base circuit
AI6 Hot water temperature sensor SE = Expansion circuit
AI7 Humidifier interface module B7 LAN Address
AI8 Humidifier interface module B8 n. 1-5 for Base circuit
n. 6-7 for Expansion circuit

3
If the EPROM is replaced, observe the following procedures:
• disconnect the system from the power supply (turning off mains REFERENCE MARK
power at the electrical panel) making sure that the yellow LED
power indicator is off;
• remove the EPROM from its socket using a suitable extractor,
making sure that it is removed in a uniform manner, and taking
special care not to touch the components mounted in the
Fig. 1
socket on the circuit;
• insert the new EPROM in the correct way putting the semicircular
reference mark in the position indicated in the diagram of the cir-
cuit board: make sure that all the feet are aligned in their respec- Electronic components are sensitive to static discharges emit-
tive slots before pushing the EPROM gently into the socket as ted by the human body.
shown in fig.1. Touch an earth connection before handling any electronic component
and/or the basic circuit.
If an EPROM is replaced by one with a more recent version of the Remove the EPROM from its container only when ready to assem-
control program, this automatically clears the memory. If the new ble: do not touch the metal feet.
EPROM has the same version of the program, then clearing the
memory is not necessary. In this way the set points for each parame-
ter are maintained.

4.3. OPTIONAL CIRCUITS


1 2 3 4 5

4.3.a RS422 SERIAL CIRCUIT FOR CONNECTION TO SUPERVI-


SOTY/MAINTENANCE SYSTEMS
Network transmission of data is possible through the RS422 serial
circuit (see fig 2.a.) which is inserted on the main circuit board. The 6 7 8 9 pin 1: GND
serial board has a connection socket with 9 pins. pin 2: TX+
pin 3: TX-
pin 4: RX+
pin 5: RX-
4.3.b. CLOCK CIRCUIT
This allows the user to see the date and time and is indispensable for
operating programmes linked to time (time bands and memorising of RS422 SERIAL CIRCUIT
the time and date of the alarm event). Fig. 2a
The clock circuit (see fig 2b) is equipped with a rechargeable battery
which can run for more than one month without recharging.

4.3.c. LAN ADDRESS CIRCUIT


The LAN address circuit enables the microprocessor to be connected
to a Local Area Network (see special LAN manual).

4.3.d. CLOCK CIRCUIT/LOCAL NETWORK


There is only one connector on the mP20 circuit for either the clock
board or the LAN board. If both functions are needed then a single
CLOCK+LAN board must be fitted. CLOCK CIRCUIT LAN ADDRESS CIRCUIT
Fig. 2b Fig. 2c

4.3.e. RS485 SERIAL CIRCUIT FOR SUPERVISION AND REMOTE


CONTROL
Fig. 2.e. shows the RS485 serial board which enables opto-isolated pin 1: GND
interfacing with an RS485 data transmission network This optional M1 pin 2: RX+ / TX+
board is inserted in its own connector on the main circuit board (see pin 3: RX- / TX-
circuit layout diagram attached). Connection to the RS483 network is 1 2 3
via the extractable terminals on the board.

JS2

RS485 SERIAL CIRCUIT


Fig. 2e

4
4.4. USER TERMINAL

LCD ALPHANUMERIC DISPLAY

PANEL OPENING CATCH

PROGRAMMING PANEL

ALARM LED

UNIT ON LED

Fig. 3

The user terminal is equipped with: The seven membrane keys, which are accessible only when the pro-
• LCD display with 4 lines, 20 alphanumeric characters for consul- tective door is opened using the catch, have the following functions:
tation and programming of the system;
• LED displays showing power on (green) and alarm (red); scrolling key for subsequent screens and vertical
• Alarm buzzer, which can be switched off with the appropriate key movement of the cursor
and if necessary disconnected completely with software;
• Command and programming keys. key to access the selected screens and horizontal
movement of the cursor
The three buttons on the front of the panel have the following func-
tions: key to increase setting values

Turns the system on and off. key to decrease setting values


The setting is memorised in order to allow automatic intelli-
gent resetting. If programmed (see CONTROL CONFIGU- key to modify and accept values (Enter)
RATION: SETTING OF AUTO RESTART) the machine as-
sumes the same state (ON/OFF) that it had before the inter- escape key: return to original screen of the current
ruption of the power supply. read/write routine

Full escape key: return to STATUS screen


Switches the buzzer off and resetting the alarms.
If pressed once the alarm buzzer stops; if pressed twice the
alarm memory is reset and the alarm event display is can-
celled.
A continuing alarm state causes the signal to continue even
after the button has been pressed.
The sequence of the last 30 alarms is maintained in the
memory and can be accessed with the appropriate routine.

Reads parameters and events.


This displays unit status and the alarm sequence memory.

5
4.4.1. REMOTE TERMINAL
An optional wall mounting kit is available for remote installation of the
user terminal, including a metal housing for the terminal.
The terminal is linked to the basic circuit via the cable equipped with
connectors at both ends: insert the connector into socket A which is
accessible from the back of the container (see fig 4).
A

Fig. 5

Wall mounting is possible by using the appropriate support box to


which the user terminal is fixed (see fig 6).
The complete support of the user terminal is in turn attached to the
plate and fixed to the wall with screws B (see fig 7); finally, the sup-
port must be attached to the plate with the lower fixing screws C.

Fig. 4

Fig. 7a
6 Fig. 7b
7
c
b

Wall plate code PAKT070X3A can be used for the remote fixing of the user terminal with a coonecting cable with plugs at both ends. (See sec-
tion on Basic Circuit). The terminal is connected by inserting the plug in socket A on the back of the casing (see fig. 5).
Important: the wall fixing kit for the terminal is suitable for indoor installations only. For outdoor installations a housing with an adequate IP level
of protection must be used - please contact the nearest service centre for further information.

5. REMOTE CONTROLS

The unit can be turned off and on with an external remote control SUPERVISION SYSTEM: a supervision system exchanges data
system. The unit ‘s resources are, however, controlled by the mi- via a serial cable with the basic circuit which has remote monitor-
croprocessor. ing and control. For further details, see relevant report.
The types of remote control provided for are the following:

REMOTE CONTROL: The unit is turned on by closing a potential-


free remote N.O. contact linked to the base circuit (see electronic
diagram of the circuit and lay-out of the base circuit).

6
6. SPECIAL FUNCTIONS

6.1. AUTOMATIC INVERSION OF THE STAND-BY UNIT


The microprocessor is programmed to run two units automatically, of
which one operates normally (the basic unit) and the other operates button for 5 seconds. The cycle re-set is confirmed by a
in reserve (the stand-by unit), without the need for external systems. double beep.
To enable this function it is bnecessaru to connect terminals 960-964 • AUTOMATIC CALL OF THE STAND-BY UNIT if the current unit
(2nd level addressable alarm relay) on the first unit to terminals 20-50 malfunctions, including if the power fails, signalled by the general
(remote control) on the second unit and vice versa. The terminals for alarm (see configuration of the controls: setting the alarms).
the interconnection of two units are shown on the electrical diagrams
The stand-by unit can be set to switch on instead of the normal unit
supplied with the units. The operation of more than two units re-
or in addition to it (see CONFIGURATION OF THE CONTROLS:
quires connection to the local network: see the relevant technical
MANAGEMENT OF THE STAND-BY UNIT).
guide.
The additional function is useful, for example, when the high room
The management of the stand-by unit includes:
temperature alarm is activated, caused by overheating. However, if
• AUTOMATIC TIMED INVERSION which, at programmed inter- the electrical power supply is only sufficient for one unit, it is possible
vals, switches between the stand-by unit and the operating unit; to programme the stand-by unit to operate instead of the normal unit.
The time interval can be set in the “Cycle Duration”. To re-set the
run hour counter which controls stand-by operation, press the

6.2. SETBACK FUNCTION


The setback function, which can be activated or de-activated using activation is not therefore conditioned by signals from any remote
the keypad, consists of the automatic starting of the unit which is off, control systems, over which it takes priority.
but powered, when the following room limits are exceeded: It is possible to programme the recycled air fan to operate during the
• minimum temperature setback function in order better to regulate the room temperature
• maximum temperature (see CONFIGURATION OF THE CONTROL, VARIOUS CONTROL
• minimum relative humidity PARAMETERS).
• maximum relative humidity The intervention of the unit caused by the setback mode is not con-
sidered to be an alarm condition.
The task of the safety cycle is to control the room conditions - al-
though in a wider field - even when the unit is switched off; its

6.3. AUTOMATIC TIME BAND OPERATION


This feature - which can only be activated if the controls are equipped • a weekly cycle distinct from the daily cycles, divided into week-
with a clock circuit - allows automatic activation or deactivation of the days, pre-holidays (automatic for Saturdays), holidays (automatic
units to be set on a time basis (time band operation). for Sundays)
The following can be memorised (see CLOCK CALENDAR -TIME It is possible to override the timer programme for seven successive
BANDS): days to programme days of the week as pre-holidays or holidays or
• up to three on-off cycles daily, each one with a start and end time; vice versa (e.g. Christmas or other special holidays).

6.4. EMERGENCY FUNCTION (special version)


A special version is available for emergency management.
The microprocessor control can receive an external electrical signal
to indicate power loss (instead of the remote ON/OFF control).

The control then stops electrical resistance function until power is


restored. This situation can be overridden manually with the user
terminal.

7
7. SWITCHING ON AND PROGRAMMING
The programming of the microprocessor and Once the functional parameters have been In the absence of programming, the basic
the INTERACTION (WRITING/READING of set, the basic circuit can function independ- unit operates with the factory default settings.
the functional parameters) is only possible ently without the user terminal, which can There follows a description of the use of the
through the user terminal equipped with a then be removed or used for the program- terminal for programming and reading the
LCD display linked directly to the basic unit ming of other units and connected only in operating parameters of the basic unit (see
connected to the local network through a case of necessity (for the reading of events or factory settings - calibration fields).
transmission line (see relevant technical to change the parameters).
guide).

7.1. CONNECTING THE USER TERMINAL AND POWER SUPPLY


Correctly insert the cable link (connectors) the power supply LED on the base circuit
(see FEATURES - USER TERMINAL) with- comes on (see LAY-OUT OF THE BASIC
out forcing the connection and turn on the UNIT); INITIALISATION
power supply. The control is activated as fol- • it emits a short acoustic signal; PLEASE WAIT....
lows: • the display shows the following message
for 10 seconds, before returning to unit off
status (see paragraph below).

8
7.2. DISPLAY INFORMATION WITH UNIT OFF
When the unit is connected to the power If the unit is programmed in the SETBACK
A supply but not on, 3 fields are active on the MODE (see SPECIAL FUNCTIONS: SET-
display (see fig. D-1): BACK MODE), the following message ap-
B
A. Current time and date (only if unit is fitted pears at regular intervals in field C:
C with clock circuit);
B. Room temperature and (with free-cooling) ATTENTION: UNIT
outside temperature; IN SETBACK MODE
C. Indication of unit switched off by:
TO START THE UNIT 1
1. ON/OFF switch;
PRESS THE ON BUTTON EXAMPLE 1: message shown on the display
2. SUPERVISION system (see REMOTE
CONTROLS: SUPERVISION SYS- in the unit equipped with a clock circuit and
WARNING: SWITCHED OFF 2 TEM); free-cooling cycle turned off by the remote
BY REMOTE CONTROL! 3. Automatic unit inversion cycle (see control.
SPECIAL FUNCTIONS: AUTOMATIC
16:45 12/10/97
WARNING: SWITCHED OFF 3 INVERSION OF CURRENT/STAND-
IN : 2 3 ° C EXT: 1 5 °C
BY SUPERVISOR! BY UNITS);
WARNING: STOPPED BY
4. Timer programme - in units fitted with a
REMOTE CONTROL!
SWITCHED OFF BY PROGRAMME 4 clock circuit - with display of the next
RESTART. AT 13:15 LU start time (see SPECIAL FUNCTIONS:
AUTOMATIC TIME BAND OPERA- EXAMPLE 2: message on display on unit
TION); without clock circuit, programmed for manual
WARNING: UNIT 5
STOPPED IN STAND-BY! 5. Manual override switch off (see MAN- on/off switching.
UAL OVERRIDE FOR SWITCHING
UNIT OVERRIDE OFF 6 ON / OFF) .
TEMPERATURE: 2 3 ° C
PRESS THE ON BUTTON
TO START THE UNIT,
D-1 PRESS 'ON'

7.3. SWITCHING THE UNIT ON AND OFF


According to the pre-set configuration, (see unit returns to the state it had before power MATIC INVERSION OF BASE/STAND-
CONFIGURATION OF THE CONTROL: was cut and restarts if it was operating. BY UNITS).
SETTING AUTOMATIC RESTART), the con- AUTOMATICALLY: the control is configured If programmed in the SETBACK MODE (see
trol of the unit can be programmed: to enable switching the machine off and on to SPECIAL FUNCTIONS: SETBACK MODE),
occur automatically with: the unit starts up automatically even if the
LOCALLY: the unit is operated with the 1. a remote control command; pre-set thermohygrometric limits have been
button; one touch switches the unit on, two 2. a SUPERVISION system (only in units exceeded
touches switches it off. with serial circuit);
In order to avoid the unit switching on and off 3. programmed automatic timer (possible NB. during automatic operation, the
too often, there is a delay between pressing only in units with clock circuit); button is inactive, except when manual over-
the on/off button and compressor start-up. the automatic inversion cycle of the base ride is activated (see SWITCHING ON/OFF
The status of the system is memorised: if unit (see SPECIAL FUNCTIONS: AUTO- MANUALLY).
programmed, when power is restored, the

7.4. THE STATUS SCREEN


When the unit is in operation, the STATUS •


D. Indication of the slave status of the unit
screen appears on the display, and has five which may be:
active fields (see fig D-2): A
• “REMOTE”: to a remote control (see
A. The time (only in the units equipped with a B REMOTE CONTROLS);
clock circuit), room temperature, room • “SUPERV.”: to a supervision system
humidity (only with humidity sensors); C D E (see REMOTE CONTROLS);
B. Current operation: according to the work- • “CYCLE”: to an automatic inversion cy-
ing conditions, the following indications cle (see SPECIAL FUNCTIONS:
are provided: AUTOMATIC INVERSION OF STAND-
• COOLING MAN REMOTE ALARM BY UNIT);
• HEATING • “TIME”: to a timer programme (see
• DEHUMIDIFICATION FORCE SUPERV. SERV. SPECIAL FUNCTIONS: AUTOMATIC
• RE-HEATING TIME BAND FUNCTION).
WATCH CYCLE
C. Manual override with regard to the auto-
matic cycle: TIME E. Indication of fault, which may be:
D -2
• “MAN“ in the operating mode with • “ALARM” if there is an alarm;
manual commands (see MANUAL • “SERV.” if the run hours counter
COMMANDS); threshold is exceeded (see SERVICE
• “FORCE” if the machine is turned on by ALARM).
manual override (see SWITCHING
ON/OFF MANUAL OVERRIDE);
• “WATCH” when the unit enters the
SETBACK MODE to maintain the
THERMOHYGROMETRIC parameters
within the established limits (see SPE-
CIAL FUNCTIONS: SETBACK MODE);
• EMERG” if the emergency function is
activated (see SPECIAL FUNCTIONS:

EMERGENCY FUNCTION)

9
7.5. STATUS LOOP: VISUALISATION OF OPERATING PARAMETERS
The unit’s function parameters can be read in to the pre-selected configuration is shown.
Pressing the button, accessed by opening
Hour and date are only shown if the clock
sequence by pressing the button on the the terminal cover, returns to the STATUS
circuit is fitted.
front panel. At the end of the reading cycle display immediately.
the STATUS display returns The information shown on the display is illus-
trated under the STATUS panel in the
SCREEN flow chart. Only information related

7.6. KEYPAD
The keypad, described in the section on the B. Internal buttons, accessed by opening the menu screen structure. A cursor shows the
User Terminal, is divided into two parts: protective cover, used for interacting with active screen.
A. External buttons used for current opera- the system memory.
tions (switching on/off, reading parame- During consultation, calibration and setting,
ters, silencing alarm buzzer, etc.); the display guides the user through the

7.7. CONSULTATION AND PROGRAMMING MENU


(cf. Screen flow chart appendix)
Access to consultation and programming of pressing the page down button; The se- rameter (whether numerical or yes/no) with
control parameters is arranged in menus and quence is circular and leads back to the first the and buttons (numerical values
is obtained from any of the visualisation loops screen. can be altered only within the limits of the
for the function parameters by pressing the The write subroutines allow the variation of pre-set calibration);
horizontal scrolling button found under memorised data and require a password for • press the button to enter new values.
the cover of the user terminal. access. The password is in a sealed enve-
lope attached to this manual, addressed to Pressing the button moves the cursor to
the service manager. the next parameter, leaving any unmodified
ACCESS TO MENUS AND SUBROUTINES data unchanged in the memory.
Each of the three areas of the menu which
VARIATION OF PARAMETERS IMPORTANT:
give access to the reading / calibration sub-
routines is composed of several options (one Calibration and/or configuration parameters in • pressing the button takes the screen
per line). To continue, move the cursor verti- a subroutine are modified as follows: back to the start of the subroutine.
cally using the button and then access the • choose the screen (using the button) • pressing the button returns to the
option by pressing the button. which contains the required parameter. STATUS screen.
The flashing cursor appears in the top left
corner of the screen;
SUBROUTINE OPERATIONS
press the button to move the cursor to
The sequential passage between screens
the parameter; change the value of the pa-
within each subroutine is performed by

7.8. INTERACTION LEVELS


Attached is the screen flow chart for reading 2. OPERATIONAL PARAMETER SETTING 4. CONFIGURATION LEVEL in which the
and programming the control. LEVEL which allows the modification of following are possible:
The appearance of the screen in the opera- the setting values of: • the adapting of software to the re-
tional sequence depends on the pre-selected • set points of function parameters; quested functions;
configuration. (e.g. the screen for the electri- • thresholds of programmable alarms; • operations on the microprocessor
cal resistance does not appear if the machine • thresholds of cumulative function hours memory.
is not fitted with it). of individual components to indicate re- This level is only accessible with the
The interaction of the user with the control is quests for maintenance. CONFIGURATION / MANUAL COM-
on 4 levels: This level is accessed with the SETTING MAND password contained in the sealed
password. envelope attached to this manual and ad-
1. READING which, as well as the visualisa- dressed to the Service manager.. In this
tion of parameters, consists of the reading 3. MANUAL COMMAND LEVEL which al- level it is also possible to modify the
of the following: lows the manual starting of the various SETTING and CONFIGURATION / MAN-
• current date and time (if clock circuit components of the unit, independently of UAL COMMAND passwords (see CON-
fitted) room conditions. FIGURATION OF CONTROL: CHANG-
• room conditions This level is accessed with the CON- ING PASSWORDS).
• values measured by sensors con- FIGURATION / MANUAL COMMAND
nected to the system password.
• set point s of function parameters
• alarm events and memories (with time
and date of event if clock circuit fitted);

This level, freely accessible, also permits


access to the setting of the clock and to
the programming of time bands

10
8. CONFIGURATION OF THE CONTROL

The microprocessor control must be configured, i.e. adapted There is a specific part of the programme which accesses the
to the unit in which it is to be installed. CONFIGURATION subroutine and to the other operations
This operation is normally performed when the control is in- which are normally performed by service technicians.
stalled in the unit, i.e. in the factory. To access the CONFIGURATION subroutine follow the se-
It may however happen that modifications need to be carried quence below until screen 75 which requests the SERVICE
out because of changes to the unit or to the system. password.

_ Alarm Display Alarm Display Access to Software


Set Point Display Set Point Display Configuration Menu Configuration
Settings Settings Enter Password: Remote Control
Service _ Service 00000 Operat on Memory

(screen 11) (screen 11) (screen 75) (screen 76)

Hardware Unit Type DX Closed circuit Setup Closed circuit Setup


_ Configuration Compressor No. 1 Temp. E.S. °C 08.0
Delay Setting Electric Reheat 3 Set Point. °C 28.0 Summer Temp. °C 28.0
Manual Control Hot Water Reheat N Rad-Cooler On-Off Rad-Cooler On-Off

(screen 76a) (screen 84a) (screen 85a - DX, DX-S e TC) (screen 85b - ES)

Closed circuit Setup

Chilled Water Activ.


Set Point °C 07.0

(maschera 86 - TC)

Screen 84 enables configuration of the unit type: direct expansion, energy saving with free cooling, twin-cool, chiller water.
Depending on the configuration, one of the screens from 85 to 87 is shown for the settings of:
- outside air temperature set point for free cooling activation;
- water temperature set point for changeover to chilled water function;
- temperature set points for the chilled water circuit.

Chilled Water setup Hot Gas Coil N Humidifier Mod. : --- Offset Adj.
Dehum. Cycle Start External Dehumid. N V: --- Ph. - TAM: --- (sonda interessata)
Set Point °C 07.0 External Humidif. N Steam Cap. kg/h: -- Read value °C 22.7
High Temo. °C 15.0 Nom. Curr. A: 00.00 Adjustament °C 0.0

(screen 87- CW) (screen 88) screen 89) (screen from 90 a 93)

11
DX 8.1. DIRECT EXPANSION CIRCUIT SETTINGS
Enables the setting of the closed circuit water temperature
Closed Circuit Setup set point necessary for condensation.
Radiator control can be either On-Off or modulating.
Set Point °C 28.0
Rad-Cooler On-Off
85a

ES 8.2. ENERGY SAVING CIRCUIT SETTINGS

Closed Circuit Setup This appears only with Energy Saving versions and enables
Temp. E.S. °C 08.0 the settings necessary for the maintaining of water tempera-
Summer Temp. °C 28.0 ture in the closed circuit at two levels:
Rad-Cooler On-Off/Modul. • at minimum value (ES temperature) during the energy re-
covery phase;
85b
• at a value sufficient for condensation (Summer Temp.) dur-
ing the mechanical cooling phase (only when compressors
are working).
The control of the radiator connected (Rad-Cooler) can be On-
off or Modulating.

TC 8.3. SETTING OF THE TWIN-COOL CIRCUIT

Closed Circuit Setup This screen enables the settings necessary for the maintain-
ing of water temperature in the closed circuit at two levels: at
Set Point °C 28.0 minimum value (ES temperature) during the energy recovery
Rad-Cooler On-Off/Modul phase and at a value sufficient for condensation (Summer
Temp.) during the mechanical cooling phase (only when
85a compressors are working).
The control of the radiator (Rad-Cooler) can be On-off or
Modulating.
Close Circuit Setup

Chiller Water Activ. Appears only with Twin-Cool versions enables the settings
Set Point °C 07.0 necessary for activating the transition to chilled water func-
tion.
86

CW 8.4. DEHUMIDIFICATION AND ALARM SETTINGS


A special control is activated in these units during dehumidifi-
cation which functions as follows:
Chilled Water setup
Dehum. Cycle Start - when dehumidification is requested the corresponding digi-
Set Point °C 07.0 tal output is immediately activated (which sends a message
High Temp. °C 15.0 to the chilled water production group to produce water at a
lower temperature for dehumidification)
87 - The temperature sensor at the chilled water intake is read;
- When the reading value reaches the set-point (see screen
87) the valve is overridden to max. opening;
When the water temperature sensor is installed it is automati-
cally possible to control the unit as “sensible heat only”, i.e. as - If the set-point is not reached after 15 minutes a fault condi-
an oversized unit which enables the use of chilled water at tion is indicated by an audible signal, an alarm status and a
temperatures higher than the normal 7/12°C. detailed message (see section on Alarms).
The need to have a sensor on the chilled water intake enables
the setting of a High Temp. limit alarm which signals any fault
in the chilled water production system (i.e. the water tempera-
ture is too high for cooling) (see section on Alarms).

12
8.5. SETTING THE HOT GAS RE-HEAT, EXTERNAL DEVICES,
HUMIDIFIER AND OFF-SET SENSORS
_ Alarm Display Alarm Display Access to Software
Set Point Display Set Point Display Configuration Menu Configuration
Settings Settings Enter Password: Remote Control
Service _ Service 00000 Operat on Memory
(screen 11) (screen 11) (screen 75) (screen 76)

Hardware Unit Type DX ....


_ Configuration Compressor No. 1 (screen 85a - DX,DX-S)
Delay Setting Electric Reheat 3 (screen 85a, 86 - TC)
Manual Control Hot Water Reheat N (screen 55b - ES)
(screen 87 - CW)
(screen 76a) (screen 84)

Closed circuit Setup Chilled Water setup Hot Gas Coil N Humidifier Mod.: --
Dehum. Cycle Start External Dehumid. N V: --- Ph. - TAM: ---
Chilled Water Activ. Set Point °C 07.0 External Humidif. N Steam Cap. kg/h: --
Set Point °C 07.0 High Temp. °C 15.0 Nom. Curr. A: 00.00

(screen 86 - TC) (screen 87 - CW) (screen 88) (screen 89)

Offset Adj. Cl. Filter P-stat N


(sensor) Flood detector N
Read Value °C 22.7 Smoke/Fire-stat N
Adjustament °C 00.0 T+H Instruments N

(screen: 90 - 93) (screen: 93b)

Screen 88 is used to set: Screens 90,91,92 and 93 can be used for adjusting the read values
• the presence of a hot gas re-heat coil; of the temperature sensors via the display of the read values on a
• the use of an external dehumidifier piloted by the DO9 output, measurement instrument..
which substitutes the dehumidification by the resources of the The adjustment can be made at intervals of 0.1 °C and the maxi-
unit. mum adjustment possible is from -9.9°C to +9.9 °C.
• The use of an external on/off humidifier piloted by the D06 relay
output in place of the unit’s dehumidification system (see section When the unit is configured in the factory, the microprocessor con-
on Base Circuit). trol analyses the analogue and digital inputs to detect automatically
the sensors which are connected to the terminal board. If optional
Screen 89 is used to set the model of built-in humidifier, the nomi-
sensors (clogged filter, flooding, smoke/fire or temperature & hu-
nal voltage, the number of phases, the model of amperometric
midity) are connected to the board after the unit is delivered, these
transformer (TAM) and the steam production capacity (Steam
Cap.). The nominal current absorption is also shown (Nom. Curr.A). must be specified in screen 93b.
NOTE: the electrical diagram supplied with the unit gives details of
analogue and digital inputs for the connection of optional sensors..

8.6. SETTING DELAY TIMES


_ Alarm Display Alarm Display Access to Software
Set Point Display Set Point Display Configuration Menu Configuration
Settings Settings Enter Password: Remote Control
Service _ Service 00000 Operat on Memory
(screen 11) (screen 11) (screen 75) (screen 76)

Harware Power On Delay s 000 Anti-Hunting Time


Configurations LP-Stat Delay s 180 Constant of Room
_..Delay Settings Start Trans. s 60 Temp. Control min 01
....Manual Control T+H Al. Delay min 15
(screen 76a) (screen 94) (screen 94b)

The first screen (n° 94) is used to set: • the delay after the start-up of the unit before the signalling of room
• the unit re-start delay after power loss (Power On Delay); condition alarms (T+H Al. Delay)
• the initial period after compressor start-up during which the low The next screen (n° 94b) sets the room temperature control anti
pressure pressostat reading is ignored (LP-Stat Delay);
hunting constant for avoiding excessive thermal swings. This value
• the delay between the start-up of the unit and the start of regulation. must increase with the thermal inertia of the air conditioned room.
(Start Trans.);
.

13
8.7. REMOTE CONTROL, SUPERVISION AND STAND-BY MANAGEMENT
_ Alarm Display Alarm Display Access to Software
Set Point Display Set Point Display Configuration Menu Configuration
Settings Settings Enter Password: Remote Control
Service _ Service 00000 Operat on Memory

(screen 11) (screen 11) (screen 75) (screen 76)


I/O via Contact N Autom. Switch-Over Autom. Switch-Over Usage of T+H values
I/O via Serial N Base / Std-by Pair Base / Std-by Pair Mode: Mean
Id# 01 Speed 1200 Cycle Time h 175 Cycle Time h 175 Aut.Changeover
Units Switch-Over N 1 Unit On Limit N No. of Unit (2-5) 2 Mean/Loc.Diff.°C 2.0
(screen 77) (screen 78) (screen 79 LAN) (screen 79a LAN)

Software
Configuration Screen 79 is only shown when:
_Renote Control a. “Unit switch-over - YES” is selected in screen 77;
Operat on Memory b. The unit is in a local network.
This screen enables the setting of:
(screen 76) • the rotation time of the stand-by unit (Cycle Time)
• the number of units connected in the local network (No. of Units (2-
Screen 77 sets: 5) and in the rotation group.
• remote control via potential-free contact (I/O via Contact)
• remote control by supervision system via RS422 or RS485 serial If the stand-by management of units in a LAN is NOT required:
line - (I/O via Serial) • select ‘Unit Switch-Over’ - YES in screen 77
• the serial address of the unit if connected to a serial supervision • set the number of units in the LAN in screen 79
network • go to screen 77 in the Remote Control subroutine again and select
• the serial transmission speed (Speed) -1200, 2400, 4800 (and for “Unit Switch-Over - NO” in screen 77.
RS485) 9600 and 19200.
• The group configuration with one unit in stand-by (Unit Switch-Over). Screen 79.a (only shown with LAN configuration) enables the selec-
tion of unit function with mean temperature and humidity values or
As described in the section on special functions, it is possible to man- with local values.
age two units with stand-by functions. - Mode: Local: unit control uses temperature and humidity values read
by local sensors.
Screen 78 (which does not appear if the unit is in a local network) - Mode: Mean: unit control uses average temperature a d humidity
sets: readings from sensors on all the units in the LAN In this mode there is
• the rotation time of the stand-by unit (Cycle Time) a settable differential value (default 2°C) which automatically switches
• the possibility to have only one unit functioning (1 Unit On Limit), in between mean and local values.
order to avoid overloading power supply line which is insufficient for
both units. (e.g. UPS)

8.8. CHANGING THE PASSWORD


_ Alarm Display Alarm Display Access to Software
Set Point Display Set Point Display Configuration Menu Configuration
Settings Settings Enter Password: Remote Control
Service _ Service 00000 Operat on Memory

(screen 11) (screen 11) (screen 75 ) (screen 76)

Software _ Password Settings Set-up of Passwords


Configuration Memory Clear-up for Accessing to:
Remote Control Factory Pre-set Settings 00000
_ Operat. on Memory Service 00000

(screen 76) (screen 80) (screen 81)

Screen 81 enables the Settings and Service menu access passwords


to be changed.
Since access to the CONFIGURATION subroutine is possible only
with the relative password, make a note of the new password before
changing the old one.

14
8.9. CLEARING THE MEMORY AND RESTORING FACTORY-SET DEFAULTS

_ Alarm Display Alarm Display Access to Software


Set Point Display Set Point Display Configuration Menu Configuration
Settings Settings Enter Password: Remote Control
Service _ Service 00000 Operat on Memory
(screen 11) (screen 11) (screen 75) (screen 76)

Software Password Settings The Memory Clear-up The Set Point Reset
Configuration _ Memory Clear-up Involves the Loss of Involves the Loss of
Remote Control Factory Pre-set all Recorded Data all Recorded Data
_ Operat. on Memory Confirm? _NO YES Confirm? _NO YES
(screen 76) (screen 80) (screen 82) (screen 83)

Screen 82 interacts with the data in the microprocessor EEPROM. Set Point Reset automatically restores the factory defaults (see FAC-
TORY DEFAULTS-SETTING FIELDS) when the memory has been
Clearing the memory (“memory clear-up”) is necessary if the EPROM
cleared or when it is necessary to restore all parameters to default
is changed (for example to up-date the program) or if the data (set-
values with a single command.
points, configuration choices, etc.) is disrupted.
After this operation it is necessary to re-configure the control and re-
After clearing the memory it is necessary to re-set the factory de-
adjust the set-points if the desired settings are different from the de-
faults, re-configure the control and re-set parameters which were dif-
faults.
ferent from the defaults. (See FACTORY DEFAULTS-SETTING
FIELDS).

9. CALIBRATION AND SETTINGS


All variables are pre-set in the factory to enable the control to function The setting variables in the memory can be checked and modified in
correctly and guaranteeing the maintenance of standard conditions in the SETTINGS subroutine by following the sequence below and then
the room (see FACTORY DEFAULTS-SETTING FIELDS).
pressing the button to read the data in sequence.
By choosing the SET POINT DISPLAY mode, the password is not
requested and settings can be read but not modified.

.....Alarm Display Access _ Room Cond. Setting Cool. Set P. °C 23.0


Set Point Display to Settings Humidifier Setting Sensitivity °C 1.5
_...Settings Enter Password Alarm Setting Time constant s 0600
.... Service 00000 Clock Facility Del. Temp.Limit °C 14
(screen 11) (screen 67) (screen 41) (screen 42)

Cool. Set P. °C 23.0 _ Relative Humidity _ Humidification Setback mode N


Heat. Set P. °C 23.0 Dehumid. Control: N Humid.Set P. rH% 45 Min. Temp. °C 16
Sensitivity °C 1.5 Dehum.Set P. rH% 55 Hum.Prop.Band rH%0.5 Max. Temp °C 28
Deh.Prop.Band rH% 05
(screen 43) (screen 44) (screen 45) (screen 46)

If dehumidification control is activated, the set points relating to humidity are also shown :

Relative Humidity Relative Humidity Humidifier Setting _ Set Backmode NO


Dehumid. Control: NO Dehumid. Control: YES Set Humidif. %rH 45 Min. Temp. °C 16.0
Set Dehumid. %rH 55 Humidif.prop.band 05 Max Temp. °C 28.0
Dehum.prod.band. 05

(screen 44) (screen 44) (screen 45) (screen 46)

If setback mode is activated the set points relating to humidity are also shown:

_ Set Backmode NO Set Backmode YES Set Backmode


Min. Temp. °C 16.0 Min. Temp. °C 16.0 Min. Rel Hum. rH% 35
Max Temp. °C 28.0 Max Temp. °C 28.0 Max Rel.Hum. rH% 75

(screen 46) (screen 46) (screen 47)

If the humidifier is configured using screen 89, the humidifier settings can be accessed:
.....Alarm Display Access Room Cond. Setting _ Humidifier Setting
Set Point Display to Settings _ Humidifier Setting Maximum Steam
_...Settings Enter Password Alarm Setting Production kg/h 02.0
.... Service 00000 Clock Facility (30-100% Nom. Cap.)

15
To change the setting variables and adjust the performance of the unit • Heat. Set P.: heating set point (°C)
it is necessary to enter the SETTINGS subroutine and follow the se- • Sensitivity: . proportional heating band (°C)
quence below up to screen 67 which requests the Setting password.
SCREEN 44
Enter the password which is found in the envelope enclosed with this For dehumidification control:
• Dehumid. Control: dehumidification function enabled/disabled
manual and press the button to enter the subroutine. • Dehum. Set P.: dehumidification set point (rH%)
If the password is not correct access to the subroutine is denied. • Deh. Prop. Band.: hysteresis of dehumidification (rH%)
If an incorrect password is entered three times, an alarm status is ac-
SCREEN 45
tivated and memorised.
For humidification control (only with an internal or external humidifier)
IMPORTANT: at any time it is possible to: • Humid. Set P.: humidification set point (rH%)
• return to the previous menu with; • Hum. Prop. Band.: proportional humidification function band (rH%)

• return to the STATUS screen with: SCREEN 46


For setback mode control:
• Setback mode: setback mode function enabled/disabled
The number and the content of the screens are related to the maxi- • Min. Temp.: re-heat temperature set point during setback mode
mum configuration. In the subroutines only information relating to the (°C)
actual configuration appears. • Max. Temp.: cooling temperature set point during setback mode:
Values can only be changed in the enabled setting fields. (°C)
N.B.: default values are shown in the screens in this manual (see
FACTORY DEFAULTS-SETTING FIELDS). SCREEN 47
For setback mode control.
SCREEN 42
• Min. Rel Hum.: humidification start set point during setback mode
• Cool. Set P.: cooling set point (°C) (rH%)
Important: to lower the cooling set point it may be necessary to lower
• Max. Rel Hum.: dehumidification start set point during setback
the heating set point as well, in order to prevent the cooling proportio-
mode (rH%)
nal band overlapping the heating band.
• Sensitivity: .proportional cooling band (°C) SCREEN 48
• Time Constant: integration time of P+I (s), only for close control For setting the steam production capacity of the built-in humidifier.
mode. • Maximum Steam Production: max. steam production limit in kg/h
• Del. Temp. Limit:: discharge air minimum temperature limit (°C), N.B. by reducing the steam production capacity to the level required
(only with optional temperature sensor. by the room, it is possible to optimise humidification function and ex-
tend the life of the steam cylinder.
SCREEN 43
• Cool. Set P.: cooling set point (°C) (read only)

9.1. ROOM SETTING ALARMS


.....Alarm Display Access Room Cond. Setting _ Temperature Alarms.
Set Point Display to Settings Humidifier Setting Humidity Alarms
_...Settings Enter Password _ Alarm Setting Run Hour
.... Service 00000 Clock Facility 2nd Level Alarms

(screen 11) (screen 67) (screen 41) (screen 49)

Cool. Set P. °C 23.0 Temperature Alarms. Dehum. Set P. rH% 55


Room High T. °C 30 _ Humidity Alarms High Rel.Hum. rH% 80
Heat. Set P. °C 23.0 Run Hour Hum. Set P. rH% 45
Room Low T. °C 10 2nd Level Alarms Low Rel.Hum. rH% 30

(screen 50) (screen 49) (screen 51)

For setting the minimum and maximum room temperature and


SCREEN 51
relative humidity limits; when the limit is reached the specific alarm
is signalled by the internal sensor. • Dehum. Set P dehumidification set point (rH%) (read only)
• High Rel.Hum: high room relative humidity alarm threshold
SCREEN 50 (rH%)
• Cool. Set P.: cooling set point(°C) (read only) • Hum. Set P: humidification set point (rH%) (read only)
• Room High T: high room temperature alarm threshold (°C) • Low Rel.Hum: low room relative humidity alarm threshold(rH%)
• Heat. Set P: heating set point (°C) (read only)
N.B. the display of the lines depends on the unit resources avail-
• Room Low T. low room temperature alarm threshold(°C)
able.
N.B. the last two lines only appear if there is at least one heating
device present.

16
9.2. SETTING THE RUN HOUR COUNTER ALARM THRESHOLD

.....Alarm Display Access Room Cond. Setting Temperature Alarms.


Set Point Display to Settings Humidifier Setting Humidity Alarms
_...Settings Enter Password _ Alarm Setting _ Run Hour
.... Service 00000 Clock Facility 2nd Level Alarms

(screen 11) (screen 67) (screen 41) (screen 49)

Air Filter (Risorsa specifica)


Tot.Run Hours 00000 Tot.Run Hours 00000
Alarm Limit H 01000 Alarm Limit H 00000
Reset -- Reset --

(screen 52) (screens 53 to 60)

This part of the programme enables the setting of the service in- Use the key to scroll down the devices present in the unit.:
tervals of the unit’s components by fixing a run hour limit. 1. Dirty filters
When the component concerned reaches the limit the control sig- 2. Compressor 1 (or 1.1 in a unit with 4 compressors)
nals the service request, activating an alarm condition and display- 3. Compressor 1.2 (in a unit with 4 compressors)
ing “SERV” on the first screen. 4. Compressor 2 (or 2.1 in a unit with 4 compressors)
5. Compressor 2.2 (in a unit with 4 compressors)
6. Electric re-heat 1
7. Electric re-heat 2
8. Humidifier
9. Complete unit

9.3. SETTING SECOND LEVEL ALARMS


Alarm Display Access Room Cond. Setting Temperature Alarms.
Set Point Display to Settings Humidifier Setting Humidity Alarms
_ Settings Enter Password _ Alarm Setting Run Hour
Service 00000 Clock Facility _ 2nd Level Alarms

(screen 11) (screen 67) (screen 41 ) (screen 49)

2nd Level Alarms 2nd Level Alarms 2nd Level Alarms 2nd Level Alarms
Air Flow/Fans Y Air filters N High RoomTemp Y Flooding N
Compressors Y Humidifier Y Low Room Temp Y Smoke/fire N
El.Heaters Y LowRoomR.Hum Y High RoomR.Hum Y Ext.RoomSensor N

(screen 61) (screen 62) (screen 63) (screen 64)

2nd Level Alarms 2nd Level Alarms 2nd Level Alarms


Main Sensor Y Wrong Password N Compr.Run Hours N
Auxil. Sensor N Unit Run Hours N Reheat.Run Hours N
Local Network N Filter Run Hours N Humidifier Run H. N

(screen 65) (screen 66) (screen 67)

This part of the programme enables the choosing of which alarms


de-energise the adressable alarm relay (2nd level).

When one or more units are connected of which one is in stand-


by, the selected alarms activate the changeover of the functioning
unit and the switching on of the stand-by unit.

17
10. CLOCK-CALENDAR - TIME BANDS
Microprocessors fitted with the optional clock circuit, as well as • alarm events.
displaying the current time and date, enable the associating of the The programming of the current time and date and the program-
following with time: ming of the time bands is done using the CLOCK FUNCTION sub-
• the starting and stopping of the unit according to a time sched- routine which is accessed as follows:
ule (see. SPECIAL FUNCTION: AUTOMATIC TIME BAND
FUNCTION);

Alarm Display Access Room Cond. Setting Clock - Calendar


Set Point Display to Settings Humidifier Setting Hours/Minutes 00:00
_ Settings Enter Password Alarm Setting DD/MM/YY 00/00/00
Service 00000 _ Clock Facility Weekday
(screen 11) (screen 67) (screen 41) (screen 68)

Unit On-off Cycle Regular Day Saturday/Pre-Holiday Sunday and Holiday


(Max 3 On-off Daily Cy- On 00:00 Off 00:00 On 00:00 Off 00:00 On 00:00 Off 00:00
cles) On 00:00 Off 00:00 On 00:00 Off 00:00 On 00:00 Off 00:00
Enable: N On 00:00 Off 00:00 On 00:00 Off 00:00 On 00:00 Off 00:00

(screen 70) (screen 71) (screen 72) (screen 73)

If the ‘unit on-off cycle’ function is enabled:

Unit On-off Cycle Unit On-off Cycle Programmed Cycle: N PROGRAM. 00/00/00
(Max 3 On-off Daily Cy- (Max 3 On-off Daily Cy- Regular day MO TU WE TH FR SA SU
cles) cles) To Change _N N N N N P F
Enable: _NO Enable: YES Press Key >>

(screen 70) (screen 70) (screen 69) (screen 74)

PROGRAM. 00/00/00
MO TU WE TH FR SA SU
≥P N N N N P F

(screen 74)

• a weekly cycle which divides the daily cycles into weekdays


Screen 68 sets: (Monday to Friday), pre-holidays (default for Saturday) and holi-
• the time of day (hours, minutes); days (default for Sundays).
• the date (day, month, year). If YES is selected in screen 70, the time band function is acti-
This enables the setting of the automatic start and stop of the unit vated. Screens 71-72 and 73 set the on and off cycles of the unit
on a time basis (time bands) with: for weekdays, pre-holidays and holidays. It is possible to change
• up to three daily on/off cycles, each with a start time and a stop the default settings for classification of days of the week. The
time; symbol >P in screen 74 indicates that, for example, a weekday
has been manually changed into a pre-holiday.

18
11. MANUAL CONTROLS
All unit components are normally in automatic function. The programmed function mode can be read by entering the
MANUAL CONTROL read-only subroutine, following the sequence
To facilitate service and regulation operations or in an emergency
it is possible to override the regulation process and manually start: below and then pressing the key to read all the settings in se-
• recirculation fans quence.
• the compressor Entering the subroutine in this way does not allow changing of the
• the electrical re-heat parameters.
• the hot gas re-heat
• the external air intake damper To change the function mode of a component, move the cursor to
• the condenser fans.
the relevant line, press the or key to change between
Obviously all safety devices are active during manual override.
AUTO and MAN and then confirm with .

_ Alarm Display Alarm Display Access to Software


Set Point Display Set Point Display Configuration Menu Configuration
Settings Settings Enter Password: Remote Control
Service _ Service 00000 Operat on Memory
(screen 11) (screen 11) (screen 75) (screen 76)

Hardware Manual Override Manual Override Manual Override


Configurations Unit start-Up N Unit start-Up N Dehumidification N
Delay Setting Compressor 1 N Y0 Ramp % N Reheating 1 N
_ Manual control Compressor 2 N Y1 Ramp % N Reheating 2 N

(screen 76a) (screen 95) DX (screen 96) CW (screen 97)

Manual Override Manual Override


Humidifier Y0 Ramp % 000
Drain Valve N Y1 Ramp % 000

(screen 98) (screen 99)

SCREEN 95 (not for CW units) • Reheating 2: switching on of second stage of electric re-heat
• Unit start-Up: switching on the fan
• Compressor 1: switching on compressor 1 SCREEN 98
• Compressor 2 switching on compressor 2 • Humidifier Drain Valve: overrides the drain function of the hu-
midifier
SCREEN 96 (only for CW units)
• Unit start-Up: switching on the fan SCREEN 99
• Y0 Ramp %: override of analogue output 0. • Y0 Ramp: overrides analogue output 0 in direct expansion units
• Y1 Ramp %: override of analogue output 1 • Y1 Ramp: overrides analogue output 1 in direct expansion units

SCREEN 97
• Dehumidification: override of dehumidification function
• Reheating 1: switching on of first stage of electric re-heat

19
12. MANUAL OVERRIDE OF START-UP/STOP

This subroutine is necessary to stop or start SWITCH ON/OFF


If the key is pressed on a unit con- MANUAL OVERRIDE
the unit manually when it been started or
trolled by one of the above devices, the dis- PLEASE TYPE IN
stopped by one of the automatic function de-
play automatically goes to screen 201 which PASSWORD: 00000
vices (shown in field D of the STATUS
shows any manual function overrides. (screen 201)
SCREEN: (see START-UP AND STOPPING;
To enter the subroutine, type the SETTINGS
THE STATUS SCREEN):
password, found in the envelope attached to If an incorrect password is entered three
• Remote control;
times an alarm condition is activated and
• Supervision system; the manual, and press the key (see
memorised.
• Automatic inversion of the stand-by unit; SWITCHING ON AND PROGRAMMING:
• Automatic time band function. CONSULTATION AND PROGRAMMING IMPORTANT: at any time it is possible to:
MENU).
• return to the start of the subroutine with:
• return to the STATUS screen with:

12.1. MANUAL OVERRIDE PROCEDURE


If the unit is controlled by one of the auto- To force the unit to turn on or off, press the _UNIT SWITCHED-ON BY
matic devices, screen 202 is shown. (∗)
If the unit has been stopped by one of the key again; TO MANUALLY STOP
automatic devices, screen 203 is shown. PRESS ON/OFF KEY
• if the unit has been forced to turn off, in
field C of the display appears the message: (screen 202)
The line with the asterisk contains the de-
scription of the device controlling the unit: “UNIT FORCED OFF - PRESS THE ON
• REMOTE CONTROL (also for CDC exter- KEY” (see . SWITCHING ON AND PRO- _UNIT SWITCHED-OFF BY
nal control system); GRAMMING: DISPLAY INFORMATION (∗)
WHEN THE UNIT IS OFF); TO MANUALLY START
• SUPERVISOR;
• if the unit has been forced to turn on, in PRESS ON/OFF KEY
• BASE/STAND-BY CYCLE;
field C of the STATUS screen appears the (screen 203)
• TIME PROGRAMME.
message “FORCE” (see SWITCHING ON
AND PROGRAMMING: THE STATUS
SCREEN). _UNIT MANUALLY OFF
TO GO BACK TO
12.2. EXITING MANUAL OVERRIDE (∗)
PRESS ON/OFF KEY
To exit manual override , shown in field C of If the unit is forced on, screen 205 will ap- (screen 204)
the STATUS screen with the message pear.
“FORCE”, (see SWITCHING ON AND PRO- The line on the screen with the asterisk (∗)
GRAMMING: THE STATUS SCREEN), press _UNIT MANUALLY ON
gives the description of the device controlling
TO GO BACK TO
the unit. (∗)
the key and type the SETTING Pass-
word. After exiting manual override the word PRESS ON/OFF KEY
If the unit is forced off, screen 204 will ap- “FORCE” no longer appears in field C of the (screen 205)
pear. STATUS screen.

13. ALARMS
All alarm conditions are signalled: • NO7-C7, with a dirty filter alarm LOOP (see STATUS LOOP: DISPLAYING
1. acoustically, by the buzzer in the user (optional) FUNCTION PARAMETERS).
terminal;
Only if programmed (see SETTING THE 2nd The message ALARM is displayed until the
2. visually, by the red LED on the front and by
LEVEL ALARMS), the alarm condition of the cause of the alarm has been eliminated.
one of the messages below in field E of the
display: specified components activates:
If the cause of the last alarm is no longer
• ALARM, if there is a fault; • the exchange of the general alarm signal
SERV., if one of the programmed com- contact C10-NO10-NC10,; the automatic present, keeping the button pressed
ponent service thresholds has been calling of the stand-by unit (see REMOTE eliminates that alarm message. If the cause
passed (see RUN HOUR COUNTER CONTROL, SUPERVISION AND STAND- of the alarm is still present, the buzzer will
OPERATIONS). BY MANAGEMENT continue to sound.
3. By the closing of the potential-free NO
contacts (see LAYOUT OF THE BASE Press the key to silence the buzzer (if The message SERV. Is displayed until the
CIRCUIT): active) and the alarm description. run hour counter is re-set (see RUN HOUR
• NO8-C8, with a recirculation fan alarm; COUNTER OPERATIONS).
Press the to read any other alarm
• NO6-C6, with a compressor alarm;
events in sequence and to enter the STATUS
• NO11-C11, with an electric re-heat
alarm;

20
13.1. HISTORICAL ALARM SEQUENCE
In order to reconstruct the historical alarm SERV events (when the run hour counter Pressing the key returns to the
sequence the microprocessor keeps the last threshold is passed) are not memorised and STATUS screen from any alarm reading
30 alarm events in the memory. are therefore not read. screen.
All memorised alarms can be read in series In the sequence, the first alarm read is the
AL12
starting from any screen in the STATUS most recent event..
AIR FILTER BLOCKED
LOOP and following the sequence shown
All descriptions of alarm conditions include a
here and then pressing the key. number from 01 to 30 next to the letters AL in
the top right corner of the display. This num-
ber indicates the time order of the event. Af-
_ ALARM DISPLAY
ter the 30th event is passed, the numbers 12:44 12 / 10 / 97 AL12
SET POINT DISPLAY AIR FILTER BLOCKED
SETTINGS
start again from 01.
SERVICE Microprocessors with the optional clock cir-
(screen 11) cuit associate the time and date with the
alarm event.

13.2. DESCRIPTION OF ALARM EVENTS


All possible alarm messages which can be shown on the user To find the solution to any problems, please refer to the Trouble-
terminal display are listed below. shooting section in this manual and to the instruction manual for
the unit controlled by the microprocessor.
It should be noted that some of these refer to specific unit For alarms in progress (i.e. not alarms in the historical sequence),
configurations and will not appear unless the unit in question the last two lines of the screen give general indications for the so-
has the relevant feature. lution of the problem.

Alarm LAN 1 Indicates EEPROM write error - it Alarm LAN 1 Detected by dirty filter differential
EEPROM Failure: must be replaced. Clogged Filters pressostat. Causes an alarm signal
Replace Control Board Clean or Replace only - does not influence unit function.
Filter Element
Alarm LAN 1 Access alarm
Attempt to Access Alarm LAN 1 For CW units only. Detected by
With Wrong(Min. 3 Oc- Flood Alarm flooding sensor. Causes the unit to
currences) Password Check Water switch off only if included among sec-
Connections ond level alarms.
Alarm LAN 1 Compressor alarm: on DX, ES, TC
Compr.1 Low Pressure units only. Alarm LAN 1 Detected by smoke/flame sensor.
Check refrig. Circuit Causes circuit 1 compressors to stop. Presence of Causes the unit to switch off only if
/Refrigerant Charge See Note 1. SMOKE/FIRE included among second level alarms.

Alarm LAN 1 Compressor alarm: on DX, ES, TC Alarm Only on TC units. Causes function to
Compr.1 High Press. units only. CW Valve Failure or change from chilled water to direct
Check Refrig. Circuit Causes circuit 1 compressors to stop Water Flow too Low expansion.
and/or Condenser Also displayed when the room tem-
perature sensor detects the exceeding
Alarm LAN 1 Compressor alarm: only on DX, ES of the set limit for the first time.
Compr.2 Low Pressure and TC units.
Check Refrig. Circuit Causes circuit 2 compressors to Alarm LAN 1 Signal only.
/Refrigerant Charge switch off. See note 1. Room Limit Exceeded
(by Ext. Sensors)
Alarm LAN 1 Compressor alarm: only on DX, ES,
Compr.1 High Press TC units. Alarm LAN 1 Signal only.
Check Refrig. Circuit Causes circuit 2 compressors to turn Room Temperature
and/or Condenser off. Above Max. Limit

Alarm LAN 1 Fan alarm: detected by airflow differ- Alarm LAN 1 Signal only.
Loss of Air Flow ential pressostat. Causes compres- Room Temperature
Check Fan/Switch sors, electric re-heat and humidifier to Below Min. Limit
turn off, leaving only fans operating.
Alarm LAN 1 Signal only.
WARNING! LAN 1 Causes the unit to turn off. Room Rel. Humidity
Wrong Power Phases See NOTE 1. Above Max. Limit
Sequence: Please
Change-Over 2 Phases Alarm LAN 1 Signal only.
Room Rel. Humidity
Alarm LAN 1 Alarm detected by safety thermostat, Below Min. Limit
Heaters Overheating Causes the electric re-heat to turn off..
Check Air Flow
and/or Safety Switch

21
Alarm LAN 1 Humidifier alarm; disables humidifica- Service Alarm LAN 1 Signal only. Displayed only if time
Humidifier: High Current: tion function El. Heater 1 threshold is not zero.
Check Cylinder / Draining Exceeded 00000 Run
Hours
Alarm LAN 1 Humidifier alarm; disables humidifica-
Humidifier: Loss of tion function. Service Alarm LAN 1 Signal only. Displayed only if time
Water: Check El. Heater 2 threshold is not zero.
Water Supply Exceeded 00000 Run
Hours
Alarm LAN 1 Humidifier alarm; disables humidifica-
Humidifier: Loss of tion function. Service Alarm LAN 1 Signal only. Displayed only if time
Power: Check Humidifier threshold is not zero.
Electrical Circuit Exceeded 00000 Run
Hours
Alarm LAN 1 Causes compressors, electric re-heat
Room Rel. Hum. and humidifier to turn off, leaving only Alarm LAN 1 CW units only. Detected by tem-
Sensor fans operating Water too Warm to perature sensor when chilled water
Failed/Disconnected get Dehumidification temperature does not reach the
Check Chiller Group value set on the terminal within 15
Alarm LAN 1 Causes compressors, electric re-heat minutes of the call for dehumidifica-
Room Temp. and humidifier to turn off, leaving only tion.
Sensor fans operating
Failed/Disconnected Alarm LAN 1 CW units only (Signal only).
High Chilled Water
Alarm LAN 1 Disables the function of the unit linked Temperature:
Water In Temp. to sensor measurement (dry cooler Check Chiller Group
Sensor control)
Failed/Disconnected Alarm LAN 1 Signal only.
Local Area Network
Alarm LAN 1 Disables the function of the unit linked Interrupted
Outdoor Temp. to sensor measurement (free-cooling Check Wiring
Sensor control).
Failed/Disconnected LAN 1
No alarm
Alarm LAN 1 Disables the function of the unit linked
Deliv. Temp. to sensor measurement.
Sensor
Failed/Disconnected

Alarm LAN 1 Disables the function of the unit linked


Hot Water Temp. to sensor measurement. NOTES:
Sensor
Failed/Disconnected 1. If the Phase Sequence Error alarm is shown, check the electrical
connections and also whether the LP pressostat has intervened. It
Service Alarm LAN 1 Signal only. Displayed only if time could be that the refrigerant charge needs to be increased (see unit
Air Filter threshold is not zero. instruction manual).
Exceeded 00000 Run In the same way, if there is a Low Pressure Circuit xx alarm, the
Hours cause of this alarm must be investigated (intervention of LP pres-
sostat or phase sequence relay).
Service Alarm LAN 1 Signal only. Displayed only if time
Unit threshold is not zero.
2. If a unit is in a local network, the LAN address of the unit is di-
Exceeded 00000 Run
splayed in addition to alarm or service messages.
Hours

Service Alarm LAN 1 Signal only. Displayed only if time


Compressor 1 threshold is not zero. Not available on
Exceeded 00000 Run CW units.
Hours

Service Alarm LAN 1 Signal only. Displayed only if time


Compressor 2 threshold is not zero. Not available on
Exceeded 00000 Run CW units.
Hours

Service Alarm LAN 1 Signal only. Displayed only if time


Compressor 2 threshold is not zero. Not available on
Exceeded 00000 Run CW units.
Hours

Service Alarm LAN 1 Signal only. Displayed only if time


Compressor 2 threshold is not zero. Not available on
Exceeded 00000 Run CW units.
Hours

22
14. TROUBLESHOOTING
Many problems can be caused by loose header connections. In the In any case it is advisable to contact the nearest authorised
event of an alarm, check that all wires are securely attached to the Service Centre, with at least a general indication of the nature
header. of the problem.
To facilitate diagnosis of the problem it is helpful to have an electrical
diagram of the unit in which the control is fitted.

PROBLEM POSSIBLE CAUSE CHECK / CORRECTIVE ACTION


THE UNIT DOES NOT SWITCH ON A) The unit’s on-board electrical panel Check mains power. Check that the power switch on the
(Mains LED on base circuit is off, is not powered electrical panel is closed.
display is off, other LEDs are off) B) The base circuit of the control is not 1) Check that auxiliary power switch is primed;
powered. 2) Check mains power at headers G and G0 on the base
circuit;
3) Check that the protection fuse for the base circuit is
intact;
4) Check the electrical connections (see unit electrical
diagram).
AFTER SWITCHING ON, THE CON- A) The EPROM is nor positioned cor- Disconnect the power supply, position the EPROM cor-
TROL IS NOT IN NORMAL CONDI- rectly rectly (see CHARACTERISTICS) and re-connect the
TION (alarm LED on; no LCD display power supply. N.B.: read the IMPORTANT WARNINGS
or random display; buzzer active) on page 2 CAREFULLY
B) Some of the EPROM pins were See above
bent during installation.
C) The microprocessor chip has been The control must be replaced: contact the authorised
incorrectly handled service centre
THE USER TERMINAL DOES NOT D) The user terminal is not connected. Disconnect the power supply, connect the terminal and re-
RESPOND TO THE BUTTONS BE- connect the power supply. N.B.: read the IMPORTANT
ING PRESSED WARNINGS on page 2 CAREFULLY
E) The EPROM is nor positioned cor- Disconnect the power supply, position the EPROM cor-
rectly rectly (see CHARACTERISTICS) and re-connect the
power supply. N.B.: read the IMPORTANT WARNINGS
on page 2 CAREFULLY
A NON-EXISTENT ALARM CONDI- F) The contact connected to the digital Switch the contact over (see LAYOUT OF BASE CIR-
TION APPEARS REPEATEDLY input is normally open instead of CUIT)
normally closed
G) Defective contact on the relative Check the closure of the contact on the base circuit head-
digital input connections ers.
H) Fault on the digital input circuit The control must be replaced. Contact the Service Centre
ON THE DISPLAY APPEARS THE The memory chip is damaged Contact the Service Centre; change the base circuit
MESSAGE: EEPROM DAMAGED -
CHANGE CONTROL CIRCUIT

23
15.1. FACTORY PRE-SETS - CALIBRATION FIELDS
The microprocessor function parameters are These values can be adapted to the de- For convenience, next to the parameter is
pre-set in the factory at the most common mands of the environment, within the mini- given the number of the screen in which that
function values (DEFAULT values). mum and maximum limits given in the table parameter can be modified.
below.
CONFIGURATION STATUS PARAMETER NUMBERS

Screen PARAMETER DEFAULT Screen SETTING VALUE PRE-SET MIN MAX.

Humidity control: 42 Cooling set point °C 23,0 18,0 32,0


44 Dehumidification NO 42 Cooling sensitivity °C 1,5 0,5 9,9
89 Humidification NO 42 Time constant sec 0600
46 Setback mode NO 42 Delivery Temp. limit °C 14 10 25
50 High room temp. alarm threshold °C 30 20 45
Addressing for 2° level alarm: 43 Heating set point °C 23,0 5,0 25,0
61 Airflow / fan YES 43 Heating sensitivity °C 1,5 0,5 9,0
61 Compressors YES 50 Low room temp. alarm threshold. °C 10 25 25
61 Electrical Heaters YES
62 Air filter NO 44 Dehum. set point rH% 55 40 90
62 Humidifier YES 44 Dehum. prop. band. rH% 05 03 15
62 Low Room R.Hum. YES 51 High room rH alarm threshold rH% 80 40 99
63 High Room Temp.. YES 45 Hum. set point rH% 45 20 80
63 Low Room Temp. YES 45 Hum. prop. band. rH% 05 03 20
63 High Room R.Hum. YES 51 Low room rH alarm threshold rH% 30 05 65
64 Flooding NO
64 Smoke/fire NO Setback mode control
64 External Room sensor NO 46 Min. Temp. °C 16 5,0 24,0
65 Main sensor YES 46 Max. Temp. °C 28 20,0 35,0
65 Auxiliary Sensor NO 47 Min. Rel. Hum. rH% 35 20 60
65 Local Network NO 47 Max. Rel. Hum. rH% 75 50 90
66 Wrong password NO
66 Unit Run Hours NO 78 Cycle Time h 168 1 999
66 Filter Run Hours NO 79 No. of Unit 2 2 5
67 Compr.Run Hours NO Changing the password
67 Reheat.Run Hours NO 81 Password for settings 00000 00000 32000
67 Humidifier Run Hours NO 81 Password for service * 00000 32000
∗ Passwords contained in sealed en-
velope attached to this manual
84 Compressor number 1 1 4
Remote control, supervision and stand-by management 84 Electrical Reheat 3 0 3
77 I/O via Contact NO
77 I/O via Serial NO Counter threshold
77 Id# 01 Speed 1200 Filter counter threshold h 1000 0 32000
77 Units Switch-Over NO Humidifier h 500 0 32000
78 1 Unit On Limit NO All other devices h 0 0 32000
84 Hot water re-heat NO
88 Hot gas coil NO Energy Saving circuit settings
88 External Dehumidifier NO 85 Temp. E.S. °C 8,0 5 24
88 External Humidifier NO 85 Summer Temp. °C 28,0 15 40
Manual override - DX Twin-cool circuit settings
95 Unit start-up NO 86 Chilled Water Activ. - set point °C 7,0 7 25
95 Compressor n.1 NO Dehumidification and alarm settings
95 Compressor n.2 NO 87 Chill. water set-up - Dehum. cycle °C 7,0 5 20
start
Manual override - CW 87 Chilled Water set-up - High Temp. °C 15,0 5 20
96 Unit start-up NO
96 Y0 Ramp % NO 90÷93 Offset sensors - Adjustment °C 0 -9,9 +9,9
96 Y1 Ramp % NO Setting delay times
97 Dehumidification NO 94 Power On Delay sec 0 0 300
97 Reheating n.1 NO 94 Low pressure delay sec 180 0 300
97 Reheating n.2 NO 94 Start Transitory sec 60 0 99
98 Humidifier - drain valve NO 94 T+H Alarm Delay min 15 0 99
99 Y0 Ramp % 000 94b Anti-Hunting time constant of room min 1 0 30
99 Y1 Ramp % 000

15.1. RESTORING FACTORY PRE-SETS


The instruction RESTORE DEFAULT PRE- This may be useful if the control needs to be After this operation the control must be re-
SETS (see CONFIGURATION OF THE reconfigured or to return with a simple com- configured and any set points different from
CONTROL: CLEARING THE MEMORY) can mand to the default settings after a trial cycle the default must be adjusted.
be used to restore automatically the factory of the unit.
pre-sets.

24
LAY-OUT OF BASIC CIRCUIT - mP20 DX-DX/S-ES-TC-CW
(without hot gas reheat)
FUSE (250 V ∼ - 2A RIT) EPROM WITH APPLICATION
PROGRAM

POWER SUPPLY CONNECTOR G RS422/RS485 BOARD (OPTIONAL) FOR CONNECTION TO


24V∼ - 50/60Hz -15VA G0 SUPERVISORY/TELEMAINTENANCE SYSTEMS

JUMPER TO SELECT THE LOCAL J9 J8


NETWORK COMMUNICATION MODE
LOCAL NETWORK 1
MICROPROCESSOR GND 2
RX/TX - B8 HUMIDIFIER INTERFACE 3
RX/TX+ +24Vcc
POWER LED MODULE JUMPER TO SELECT ANALOGUE INPUT
B7
B5 (J14) - B6 (J15) IN 0÷1V OR 4÷20 mA
TELEPHONE-TYPE CONNECTOR FOR CONNECTION TO 1-2 = 4÷20 mA 2-3 = 0÷1V
THE USER TERMINAL UNIT OR TO LOCAL NETWORK
+24V
ANALOGUE INPUTS
REAL TIME CLOCK BOARD (OPTIONAL)
or NETWORK CIRCUIT (OPTIONAL) J15 B6 HOT WATER TEMPERATURE SENSOR
AVSS ROOM RELATIVE HUMIDITY SENSOR
J14 B5
ANALOGUE OUTPUTS B4 EXTERNAL AIR TEMPERATURE SENSOR
AVSS
VG0 B3 RECIRCULATING WATER / CW TEMP. SENSOR
VG1 B2 DELIVERY AIR TEMPERATURE SENSOR
COLD WATER VALVE Y1 AVSS
HOT WATER VALVE / EXTERNAL RADIATOR CONTROL Y0 B1 ROOM AIR TEMPERATURE SENSOR
DIGITAL INPUTS ID11-220V∼ DIGITAL INPUTS
24V~ IDCM2 0
ID11-24V∼ ID10 FLOODING DETECTOR
0 ID11-Com ID9 HUMIDIFIER INTERFACE MODULE (high level)
-------- ID8 24V∼ ELECTRICAL RESISTANCE SAFETY THERMOSTAT
24V~ ID12-220V∼ ID7 CIRCUIT 2. HIGH PRESSURE-STAT
ID12-24V∼ ID6 CIRCUIT 2. LOW PRESSURE-STAT
0 ID12-Com
DIGITAL OUTPUTS IDCM1 0
NO11 ID5 CIRCUIT 1. HIGH PRESSURE-STAT
C11 ID4 LOW PRESSURE-STAT & PHASE SEQUENCE CONTROL RELAY
NC11 ID3 24V∼ CLOGGED FILTER PRESSOSTAT (OPZ)
-------- ID2 FLOW SWITCH PRESSOSTAT
N.O. NO10 ID1 REMOTE SWITCH-ON AND SWITCH-OFF INLET
COM C10
N.C. DIGITAL OUTPUTS
NC10 C1
-------- NO1
N.O. NO9 --------
COM C9 C1
N.C. NC9 NO1

NO8 NO3
C8 C3
-------- --------
NO7 NO4
C7 C4
-------- --------
NO6 NO5
C6 C5 mP20
-------- -------- DX-DX/S-ES-TC-CW
NO13 NO12
C13 C12
Version 1.4
STATUS mP20 Screen Flow Chart MENU 3 Subroutine Alarms
hh:mm XX.X °C XX% rH MENU- screen 1 DX, DX-S, ES, TC, CW (version 1.4.)
Deumidification Software
Re-heat ALARMS DISPLAY Configurations
Man/Force Cycle/Time SETTING DISPLAY Remote Control
SETTINGS Operat. on Memory hh:mm gg/mm/aa AL --
01 Subroutine Setting Room (T, UR) Alarm Description
SERVICE
76
11 MENU 2 Subroutine Setting Humidifier
(hh:mm XX DD/MM/YY)*
Room Temp. °C XX.X ROOM SETTING Hardware 20
Alarm display subroutine (read only) Subroutine Setting Alarms
Delivery Temp. °C XX.X Read only HUMIDIF. SETTING. Configurations
Room Humid. rh% XX Setting display subroutine (MENU 2) ALARMS SETTING Delay Settings 17:12 05/07/98 AL07
02 CLOCK FUNCTIONS Subroutine Setting Clock And Time Bands Manual Control Outdoor sensor limits passed
Read and write
Setting subroutine (MENU 2) 41 76a
(SEQUENTIAL DISPLAY OF
Service (MENU 3) 21
ALARMS IN PROGRESS)

Subroutine Clock Facility DISPLAY OF HISTORICAL


SEQUENCE OF
Service Subroutine MEMORISED ALARM
CONDITIONS
Compressor 1.1 ON
Compressor 1.2 ON Clock/calendar setting
Compressor 2.1 ON Hour/Minutes XX:XX
Compressor 2.2 ON DD/MM/YY XX/XX/XX
Unit Type: DX, DX-S, ES, TC Unit Type: CW Weekday XX
03 Compressors No. X 68
Electric Reheat X Electric Reheat X
Hot Water Reheat No/Yes Hot Water Reheat No/ Yes Settings display subroutine
Electric re-heat 1 ON
Electric re-heat 2 -- 84a 84b UNIT ON-OFF CYCLE
Hot Water Valve (Max 3 On-Off cycles daily)
Open XXX % Enabled: No/yes
Chilled Water Setup
04 Dehum. Cycle Start Cool Set P. °C XX.X
70
Set Point °C XX Sensitivity °C X.X
High Temp. °C XX Time constant s XXXX
Energy Saving -- No Yes
87 Del. Temp. Limit °C XX
Cold Water Valve 42
Open XXX % Programmed cycle: N
DX, DX-S TC ES Weekday Cool Set P. °C XX.X
05 ES CW To change
Closed Circuit Setup Closed Circuit Setup Heat. Set P. °C XX.X
press >> Sensitivity °C X.X
Temp. E.S. °C XX
Set Point °C XX Summer Temp. °C XX 69
Rad-Cooler On-Off / Modul. Rad-Cooler On-Off / Modul. 43
Chilled Water Valve 85b
85a
Open XXX % PROGRAM. XX dd/mm/yy
06 TC e CW MO TU WE TH FR SA SU
Closed Circuit Setup N N N N N P F Relative Humidity Relative Humidity
Chilled Water Activ. Dehumid. Control: No Dehumid. Control: Yes
Humidifier -- 74
Set Point °C XX Dehumid Set. RH% XX
Valve Intake --
Dehum.prop.band. RH% XX
Valve Sintake --
86 44 44b
Prod. Vap. kg/h XX.X
07
Weekdays
Humidification
On 00:00 Off 00:00
Hot Gas Coil No/Yes Humid. Set P. rH% XX
Outside air °C XX.X On 00:00 Off 00:00
External Dehumid. No/Yes External Dehumid. No/Yes Hum. Prop. Band. rH% XX
Closed circuit °C XX.X On 00:00 Off 00:00
External Humidif. No/Yes External Humidif. No/Yes
Hot Water °C XX.X 71
45
88 88b
08a ES
Saturday and pre-holidays
Humidifier Mod.: XXX
On 00:00 Off 00:00
Outside air °C XX.X V:230/400 Ph. 1/3 TAM: XXX Setback mode No/Yes Setback mode Yes
On 00:00 Off 00:00
Cold Water °C XX.X Steam Cap. kg/h: XX Min Temp. °C XX.X Min Temp °C XX.X
On 00:00 Off 00:00
Hot Water °C XX.X Nom. Curr. A: XX.XX Max Temp. °C XX.X Max Temp °C XX.X
72
89
08b TC and CW
46 46b
Offset Adj. Sunday and holidays
Programme Version (*) SENSOR On 00:00 Off 00:00 Setback mode
Read value °C XX On 00:00 Off 00:00 Min Rel Hum. rH% XX
mP20 3.5 18.06.98 Adjustment °C 0.0 On 00:00 Off 00:00 Max Rel Hum. rH% XX
90-93 73
09
47
Subroutine Remote Control mP20 Screen Flow Chart
DX, DX-S, ES, TC, CW (page 2) (version 1.4.) Subroutine Tarature Alarms
Temperature Alarms screen 50
I/O via Contact N MENU 4 Humidity alarms screen 51
MENU 3 I/O via Serial N
Run hour screen 52
Id# 01 Speed 1200
Software 2nd Level Alarms screen 61
Units Switch-Over N/Y
Configurations Subroutine Delay Settings 49
Remote Control 77
Operat. on Memory
76
Power on Delay s XXX Cool. Set P. °C XX.X
77 - Units Switch-Over LP-Start Delay s XXX Room High T. °C XX
Hardware 2nd Level Alarms
Start Trans. s XX Heat Set P. °C XX.X
Configurations NO YES Airflow/fan NO/YES
T+H Al. Delay min XX Room Low T. °C XX
Delay Settings Compressors NO/YES
Manual Control Autom. Switch-Over Autom. Swich-Over 94 50 Electric heater NO/YES
Base / Std-by Pair Base / Std-by Pair 61
76a Cycle Time h XXX Cycle Time h XXX Anti-Hunting Time
1 Unit On Limit N No. of Unit (2-5) X Constant of Room 2nd Level Alarms
79 Temp. Control min XX Air filters NO/YES
78 Dehum. Set P. rh% XX
High Rel. Hum. rh% XX Humidifier NO/YES
LAN 94b Hum. Set P. rh% XX Low Room R.Hum. NO/YES
Low Rel. Hum. rh% XX 62
51
Usage of T+H values
Mode: Local / Mean 2nd Level Alarms
Aut.Changeover High Room Temp. NO/YES
Mean/Loc.Diff.°C 2.0 Low Room Temp. NO/YES
High Room Humid. NO/YES
63

Subroutine Manual Control 2nd Level Alarms


(SPECIFIC RESOURCE)
Subroutine Operate on Memory Tot. Run hours XXXXX Flooding NO/YES
Alarm Limit h. XXXXX Smoke/Fire NO/YES
Ext.Room sensor NO/YES
Manual Override Reset --
52 64
Unit star-up NO/YES
Password Settings screen 81 Compressor 1 NO/YES
Memory Clear-up screen 82 Compressor 2 NO/YES 2nd Level Alarms
Factory Pre-set
screen 82 95 DX, ES, TC SEQUENTIAL DISPLAY OF Main sensor NO/YES
RUN HOUR LIMITS OF ALL Auxil. sensor NO/YES
80
Manual Override COMPONENTS Local network NO/YES
Unit start-up NO/YES 65
Y0 Ramp % XXX 53-60
Y1 Ramp % XXX
96 2nd Level Alarms
Set-up Passwords CW
Wrong Password NO/YES
for Accessing to: Unit Run Hours NO/YES
Settings 00000 Manual Override Filter Run Hours NO/YES
Service 00000 Dehumidification NO/YES 66
81 Reheating 1 NO/YES
Reheating 2 NO/YES
97 2nd Level Alarms
The Memory Clear-up
Compr. Run Hours NO/YES
Involves The Loss of
Reheat Run Hour NO/YES
all Recorded Data Manual Override Humidifier Run H. NO/YES
Confirm? _NO YES Humidifier 67
82 Drain Valve N

98
The Set Point Reset Humidif Setting Subroutine
Involves The Loss of
all Recorded Data Manual Override Humidifier setting
Confirm? _NO YES Y0 Ramp % XXX Max steam production setting
83 Y1 Ramp % XXX kg/h XX.X
(30-100 % nomal P.)
99 DX

Você também pode gostar