Você está na página 1de 7

132 kV and 150 kV

Underground AC cable systems


EKS-0069

Document title EKS-0069 Rev 0 132 kV and 150 kV underground AC cable systems
Document no. 13/90592-213
Target group Electricity Transmission and external suppliers
Valid until 1 October 2019
Document Author Reviewer Approver
Revision
status Name Date Name Date Name Date
JNL, HSL,
0 Approved RAO 17.08.2017 SSV, JDV, 15.09.2017 JSC 19.09.2017
HRH, EOM,
PRA, MGB

Table of contents
1. Scope/introduction ...........................................................................................................2
1.1 Abbreviations and definitions ...........................................................................2
2. References and standards ................................................................................................2
2.1 General ...............................................................................................................2
2.2 Health and safety requirements .......................................................................4
2.3 Environmental requirements ............................................................................4
2.4 Quality requirements .........................................................................................4
3. Dependences and conditions ...........................................................................................5
4. Performance requirements ..............................................................................................5
5. Technical requirements ....................................................................................................5
6. Design requirements ........................................................................................................5
6.1 Cable system design ..........................................................................................5
7. Cable system installation ..................................................................................................5
Concept
7.1 Installation in rural areas ...................................................................................5
7.2 Installation in urban areas .................................................................................5
8. Cable system testing .........................................................................................................6
9. Monitoring package for cable systems ............................................................................6
10. Operation of cable systems ..............................................................................................6
11. Maintenance of cable systems.........................................................................................6
12. Decommissioning ..............................................................................................................6
13. Documentation .................................................................................................................7
14. Appendices ........................................................................................................................7

Doc. 13/90592-213 – EKS-0069 Klassificering: Til arbejdsbrug/Restricted 1/7


132 kV and 150 kV underground AC cable systems

1. Scope/introduction
This concept standard specifies Energinet's requirements for development, construction,
commissioning, maintenance, operation and decommissioning of High-Voltage (HV) cable
systems with voltage ratings of 132 and 150 kV.

The standard is intended to be used during development of cable projects, tendering for
new cables, tendering for installation of cables, tendering for test of cable systems, etc.

The standard ensures a unified approach to system design and ensures that all relevant
parts of Energinet agree on the requirements.

1.1 Abbreviations and definitions


AMD Amendment
DAS Distributed Acoustic Sensing
DTS Distributed Temperature Sensing
DVS Distributed Vibration Sensing
EDS Energinet design and configuration standard
EGS Energinet guideline
EHV Extra High Voltage
EKS Energinet concept standard
ETS Energinet technical standard
HV High Voltage
IEC International Electrotechnical Commission
OEFL Online Electrical Fault Localisation
PD Partial Discharge
PTS Point Temperature Sensing
TB Technical Brochure

2. References and standards


2.1 General
The design of the equipment must in general be based on the most recent version of the
applicable DS/EN and IEC standards and Cigré recommendations, including (but not limited
to):

 DS/EN 60228:2006 Conductors of insulated cables


 IEC 60287-1-1:2006 Electric cables – Calculation of the current rating – Part 1-1:
Current rating equations (100 % load factor) and calculation of losses – General
 IEC 60287-1-1:2006/AMD1:2014 Amendment 1 – Electric cables – Calculation of
the current rating – Part 1-1: Current rating equations (100 % load factor) and cal-
culation of losses – General
 IEC 60287-1-2:1993 Electric cables – Calculation of the current rating – Part 1:
Current rating equations (100 % load factor) and calculations of losses – Section 2:
Sheath eddy current loss factors for two circuits in flat formation
 DS/IEC 60287-1-3:2002 Electric cables – Calculation of the current rating – Part 1-
3: Current rating equations (100 % load factor) and calculation of losses – Current

Doc. 13/90592-213 – EKS-0069 Klassificering: Til arbejdsbrug/Restricted 2/7


132 kV and 150 kV underground AC cable systems

sharing between parallel single-core cables and calculation of circulating current


losses
 DS/IEC 60287-2-1:2015 Electric cables – Calculation of the current rating – Part 2-
1: Thermal resistance – Calculation of the thermal resistance
 IEC 60287-2-2:1995 Electric cables – Calculation of the current rating – Part 2:
Thermal resistance – Section 2: A method for calculating reduction factors for
groups of cables in free air, protected from solar radiation
 DS/IEC 60287-3-1:2017 Electric cables – Calculation of the current rating – Part 3-
1: Operating conditions – Site reference conditions
 IEC 60287-3-3:2007 Electric cables – Calculation of the current rating – Part 3-3:
Sections on operating conditions – Cables crossing external heat sources
 DS/IEC 60840:2012 Power cables with extruded insulation and their accessories
for rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) – Test
methods and requirements
 IEC 60853-1:1985 Calculation of the cyclic and emergency current rating of ca-
bles. Part 1: Cyclic rating factor for cables up to and including 18/30(36) kV
 IEC 60853-1:1985/AMD1:1994 Amendment No. 1
 IEC 60853-1:1985/AMD2:2008 Amendment 2 – Calculation of the cyclic and
emergency current rating of cables – Part 1: Cyclic rating factor for cables up to
and including 18/30 (36) kV
 IEC 60853-2:1989 Calculation of the cyclic and emergency current rating of ca-
bles. Part 2: Cyclic rating of cables greater than 18/30 (36) kV and emergency rat-
ings for cables of all voltages
 IEC 60853-2:1989/AMD1:2008 Amendment 1 – Calculation of the cyclic and
emergency current rating of cables – Part 2: Cyclic rating of cables greater than
18/30 (36) kV and emergency ratings for cables of all voltages
 DS/IEC 60853-3:2002 Calculation of the cyclic and emergency current rating of
cables – Part 3: Cyclic rating factor for cables of all voltages, with partial drying of
the soil
 DS/IEC 62067:2012 Power cables with extruded insulation and their accessories
for rated voltages above 150 kV (Um = 170 kV) up to 500 kV (Um =550 kV) – Test
methods and requirements
 Cigré TB 303:2006 Revision of qualification procedures for high voltage and extra
high voltage AC extruded underground cable systems
 Cigré TB 347:2008 Earth Potential Rises in specially bonded Screen Systems
 Cigré TB 446:2011 Advanced design of metal laminated coverings: recommenda-
tion for tests, guide to use, operational feed back
 Cigré TB 560:2013 Guideline to Maintaining the Integrity of XLPE Cable Accesso-
ries
 DIN VDE 0292:2007 System for cable designation

Doc. 13/90592-213 – EKS-0069 Klassificering: Til arbejdsbrug/Restricted 3/7


132 kV and 150 kV underground AC cable systems

Furthermore, at least the following Energinet standards should be taken into account:

 EKS-0070 220 kV and 400 kV underground AC cable systems

 EDS-0074 Installation of underground AC cables in urban areas


 EDS-0075 Installation of underground AC cables in rural areas
 EDS-0076 Design of performance and integrity monitoring systems for HV and EHV
cable systems
 EDS-0077 Design of underground AC cable systems

 ETS-0054 Bonding equipment and auxiliary equipment for underground AC cable


systems
 ETS-0066 Underground AC cables
 ETS-0067 Accessories for underground AC cables
 ETS-0068 Optical equipment for monitoring temperature and vibrations along HV
and EHV cable systems
 ETS-0079 Equipment for monitoring point temperatures along HV and EHV cable
systems
 ETS-0080 Equipment for online electrical fault localisation of HV and EHV cable
systems
 ETS-0081 Equipment for online partial discharge measurements on HV and EHV
cable systems
 ETS-0082 Testing of underground cables and accessories
 ETS-0108 Equipment for optical time domain reflectometry monitoring of fibres

 EGS-0084 Underground AC cables - cable data sheet


 EGS-0085 Underground AC cables - joint data sheet
 EGS-0086 Underground AC cables - termination data sheet

2.2 Health and safety requirements


HV cable systems must be designed, installed and commissioned in a way that takes health
and safety into consideration to the absolute highest possible level for everybody involved
in design, production, transport, installation, commissioning, operation, maintenance, and
decommissioning of the system.

2.3 Environmental requirements


HV cable systems must be designed in a way that takes environmental aspects into consid-
eration to the absolute highest possible level. This means that systems must be designed to
minimise the environmental impact on the entire lifecycle of the cable, including design,
production, transport, installation, commissioning, operation, maintenance, and decom-
missioning of the system.

2.4 Quality requirements


In addition to the standard ISO certificates, etc., Energinet expects HV cable systems to be
produced in a way that makes it possible to trace the quality of all subcomponents (cables,

Doc. 13/90592-213 – EKS-0069 Klassificering: Til arbejdsbrug/Restricted 4/7


132 kV and 150 kV underground AC cable systems

monitoring equipment, etc.) to the greatest possible extent. This will enable a better and
more accurate root cause analysis in case of future failures.

3. Dependences and conditions


Section intentionally left blank; dependences and conditions pecified elsewhere.

4. Performance requirements
Section intentionally left blank; performance requirements specified elsewhere.

5. Technical requirements
Section intentionally left blank; technical requirements specified elsewhere.

6. Design requirements
6.1 Cable system design
Cable systems must be designed according to:

 EDS-0077 Design of underground AC cable systems


 ETS-0054 Bonding equipment and auxiliary equipment for underground AC cable
systems
 ETS-0066 Underground AC cables
 ETS-0067 Accessories for underground AC cables

Power cables and accessories may come from different suppliers. In that case it must be
specified that the requirements of ETS-0082 must be respected.

7. Cable system installation


7.1 Installation in rural areas
In rural areas, i.e. where:

 It is possible to have long open trenches


 Limited inconvenience is caused for traffic
 Limited amount of parallel and crossing power cables, gas line, district heating
pipes, water pipes, etc. is foreseen

The installation must be performed according to EDS-0075.

7.2 Installation in urban areas


In urban areas, where it is not possible to have long open trenches, etc., the installation
must be performed according to EDS-0074.

Doc. 13/90592-213 – EKS-0069 Klassificering: Til arbejdsbrug/Restricted 5/7


132 kV and 150 kV underground AC cable systems

8. Cable system testing


Cable systems must be tested according to ETS-0082.

As standard, 132 kV and 150 kV cable systems must not have PD monitored joints during
commissioning testing, only in case the cable system is considered vital for the transmission
system.

9. Monitoring package for cable systems


As standard on all new cable systems, Energinet installs DTS, DVS/DAS, and PTS systems in
order to monitor the cable system behaviour. All three monitoring systems (DTS, DVS/DAS,
and PTS) must be delivered by the same supplier in order to ensure limited requirements
for communication and simple interfaces for Energinet.

Under special circumstances, Energinet will install an OEFL system instead of a DVS/DAS
system. This may especially be the case for cable systems where optical fibres are not in-
stalled along the cables.

For the moment, Energinet does not consider the need for online monitoring of PD in cable
systems, and a PD monitoring system must therefore not be permanently installed.

Monitoring system must be in accordance with EDS-0076, ETS-0079, ETS-0080, ETS-0081,


and ETS-0108

10. Operation of cable systems


Cable systems must be operated to the limits defined in EDS-0077, ETS-0054, ETS-0066,
ETS-0067, EGS-0084, EGS-0085, and EGS-0086.

The cable operating voltage must never exceed the maximum voltage defined in the above
specifications, and the cable operating temperature must never exceed the maximum tem-
perature defined in the above specifications.

11. Maintenance of cable systems


Cable systems must be tested and maintained according to ETS-0082.

The cable system must be maintained according to the maintenance plans supplied by
cable manufacturers and accessory manufacturers.

12. Decommissioning
Cable systems must be decommissioned according to the Danish laws and regulations.
Energinet will to the greatest possible extent excavate, pull up and dispose power cables,

Doc. 13/90592-213 – EKS-0069 Klassificering: Til arbejdsbrug/Restricted 6/7


132 kV and 150 kV underground AC cable systems

accessories, and auxiliary equipment in order to leave the cable route as if the cable system
had never been installed.

The cable system should to the greatest possible extent be disposed of for recycling.

13. Documentation
Section intentionally left blank; documentation specified elsewhere.

14. Appendices
No appendices.

Doc. 13/90592-213 – EKS-0069 Klassificering: Til arbejdsbrug/Restricted 7/7

Você também pode gostar