CT Series

DIN W48×H48mm, W72×H36mm, W72×H72mm counter/timer


Upgraded functions Upgrade

● Available to set 6 digits(0.00001 to 999999) prescale value


(4digit : 0.001 to 9999)
● Built-in Modbus communication function(Communication model)
● Available to set the One-Shot output time in 10ms.
(0.01sec. to 99.99sec.)
● Increase contact capacity to 5A(CTS, CTM Series)
● Available to set Count Start Point.(Initial value)
● Improved to select memory protection function in the indicator
● Added BATCH counter function(CTM Series)
● Added Counter Up-1 / Up-2 / Down-1 / Down-2 input modes
● Added Counter TOTAL / HOLD operation modes in the indicator
● Added Timer TOTAL / HOLD / On Time Display operation
modes in the indicator
● Added Timer INT2 / NFD / NFD.1 / INTG output modes
● Added Timer range 999.999s / 9999m59 / 99999.9h
Please read “Caution for your safety” in operation
manual before using.

DAQMaster(integrated device management program)


● DAQMaster is a integrated device management program for convenient
management of parameters and multiple device data monitoring.
< DAQMaster screen >
● Visit our website (www.autonics.com) to download user manual and
integrated device management program.
Item Minimum requirements
IBM PC compatible computer with Intel Pentium
System
Ⅲ or above
Operating system Microsoft Windows 98/NT/XP/Vista/7
Memory 256MB or more
Hard disk More than 1GB of free hard disk space
VGA 1024×768 or higher resolution display
Others RS-232 serial port(9-pin), USB port

Ordering information
CT 6 M - 2P 4 T

※A shaded ( ) part is upgraded or added function.


Communication No mark None
출력 회로의 수
T RS 485
Power supply 4 100-240VAC 50/60㎐
2 24VAC 50/60㎐ / 24-48VDC
2P Dual preset
Output
1P Single preset
I Indicator
S DIN W48×H48mm
Size
Y DIN W72×H36mm
M DIN W72×H72mm
Digit 4 9999(4digit) ※4digit type does not exist
6 999999(6digit) in the indicator type.
Item
CT Counter/Timer

J-8
Programmable Counter/Timer

Specifications (A)
Photo
electric
Series CTS CTY CTM sensor
Digit 4 6 6 6
(B)
Dual Preset CT4S-2P CT6S-2P CT6Y-2P CT6M-2P Fiber
Model Single Preset CT4S-1P CT6S-1P CT6Y-1P CT6M-1P optic
sensor
Single Preset - CT6S-1 CT6Y-1 CT6M-1
Digit Single Preset 11mm 10mm 10mm 13mm (C)
Size Single Preset 8mm 7mm 7mm 9mm Door/Area
sensor
Power Single Preset 100-240VAC 50/60Hz
Supply Single Preset 24VAC 50/60Hz / 24-48VDC (D)
Allowable voltage range 90 to 110% of rated voltage(AC Power type) Proximity
sensor
Power Single Preset Max. 12VA
consumption Single Preset AC: Max. 10VA / DC: Max. 8W
(E)
INA/INB Max. counting speed Selectable 1cps / 30cps / 1kcps / 5kcps / 10kcps Pressure
sensor
Counter Reset signal : Selectable 1ms, 20ms
Min. input
signal width Timer INA, INB RESET : Selectable 1ms, 20ms INA, INH, RESET, INHIBIT, BATCH
RESET : Selectable 1ms, 20ms (F)
Rotary
Selectable voltage input or No-voltage input encoder
Input [Voltage input] Input impedance is 5.4kΩ, 'H' level : 5-30VDC, 'L' level : 0-2VDC
[No-voltage input] Short-circuit impedance : Max. 1kΩ, Residual voltage : Max. 2VDC
(G)
One-shot output Count, timer : Selectable 0.01s to 99.99s Connector/
Socket
Contact Dual preset : SPST(1a) 2EA Dual preset : SPST(1a) 1EA, SPDT(1c) 1EA
With- output Single preset : SPDT(1c) 1EA Single preset : SPDT(1c) 1EA
out (H)
com. Solid state Dual preset : 1NPN open collector Dual preset:3NPN open collector Temp.
output Single preset : 1NPN open collector Single preset:2NPN open collector controller
Contact Dual preset : SPST(1a)2EA Dual preset: SPST(1a), SPDT(1c)
Control With- output Single preset : SPDT(1c)1EA Single preset: SPDT(1c) (I)
output out SSR/
com. Solid state - Dual preset: - Dual preset:2NPN open collector Power
output Single preset:1NPN open collector Single preset:2NPN open collector controller

Contact 250VAC 5A resistive load 250VAC 3A resistive load 250VAC 5A resistive load
With- output (J)
out Counter
com. Solid state 30VDC Max. 100mA Max.
output
External sensor power 12VDC ±10%, 100mA Max. (K)
Memory retention 10years(When using non-volatile semiconductor memory type) Timer

Repeat error
SET error Power ON Start : Max. ±0.01% ±0.05 sec (L)
Timer Signal Start : Max. ±0.01% ±0.03 sec Panel
Voltage error meter
Temperature error
Insulation resistance Min. 100MΩ(500VDC Megger) (M)
Tacho/
Dielectric strength 2,000VAC 50/60Hz for 1minute Speed/ Pulse
Noise strength (AC Power) ±2kV the square wave noise(pulse width:1㎲) by the noise simulator meter

Mechanical 0.75mm amplitude at frequency of 10 to 55(for 1 min.)Hz in each of X, Y, Z directions for 1 hour
Vibration (N)
Malfunction 0.5mm amplitude at frequency of 10 to 55Hz(for 1 min.) in each of X, Y, Z directions for 10 minutes Display
unit
Mechanical 300m/s²(approx. 30G) in each of X, Y, Z directions for 3 times
Shock
Malfunction 100m/s²(approx. 10G) in each of X, Y, Z directions for 3 times
(O)
Relay Mechanical Min. 10,000,000 operations Sensor
Life cycle Electrical Min. 100,000 operations controller

Protection IP65(Front panel only)


(P)
Ambient Switching
-10 to 55℃, storage : -25 to 65℃
temperature mode power
Environment supply
Ambient
35 to 85%RH, storage : 35 to 85%RH (Q)
humidity Stepper
motor&
Approval Driver&Controller
Unit weight Approx. 159g Approx. 149g Approx. 253g
(R)
※Environment resistance is rated at no freezing or condensation. Graphic/
Logic
panel

Communication specification (S)


Field
Protocol Modbus RTU(16bit CRC) network
device
Connection method RS485
Application standard Compliance with EIA RS485
(T)
Number of connections 31, it is available to set address 1 to 127 Software
Communication method Half Duplex
Synchronous method Asynchronous
(U)
Communication distance within max. 800meter Other
Communication speed 2,400/4,800/9,600/19,200/38,400bps(Factory default : 9,600bps)
Response waiting time 5 to 99ms(Factory default : 20ms)
Start bit 1bit(Fixed)
Data bit 8bits(Fixed)
Parity bit None, Even, Odd(Factory default : None)
Stop bit 1, 2bit(Factory default : 2bit)

J-9
CT Series

Connections Be careful that connections are different


between communication model and
non-communication model when wiring.
CT S-2P CT S-2P T
12VDC 100mA 12VDC 100mA
INB / INH RESET INB / INH RESET
INA 0VDC INA 0VDC

OUT2 A(+) RS485 B(-)


30VDC
100mA

OUT1 OUT2 OUT1 OUT2


- + - +
250VAC 5A 250VAC 5A 250VAC 5A 250VAC 5A
RESISTIVE RESISTIVE ※1 RESISTIVE RESISTIVE ※1

CT S-1P CT S-1P T
12VDC 100mA 12VDC 100mA
INB / INH RESET INB / INH RESET
INA 0VDC INA 0VDC

OUT A(+) RS485 B(-)


OUT 30VDC OUT
100mA

NO COM NC - + NO COM NC - +
250VAC 5A ※1 250VAC 5A ※1
RESISTIVE LOAD RESISTIVE LOAD

CT6S-I CT6S-I T
12VDC 100mA 12VDC 100mA
INB / INH RESET INB / INH RESET
INA 0VDC INA 0VDC

A(+) RS485 B(-)

- + - +

※1 ※1

CT6Y-2P CT6Y-2P T
SOLID
250VAC 3A 250VAC 3A STATE OUT
RESISTIVE LOAD RESISTIVE LOAD 30VDC 250VAC 3A 250VAC 3A
NC COM NO OUT 100mA RESISTIVE RESISTIVE A(+) B(-)

RS485
OUT1 OUT2 OUT2 OUT1
OUT2

0VDC RESET 0VDC RESET


INA - + INA - +
INB / INH INB / INH
12VDC 100mA ※1 12VDC 100mA ※1

CT6Y-1P SOLID
CT6Y-1P T SOLID
250VAC 3A STATE OUT 250VAC 3A STATE OUT
RESISTIVE LOAD 30VDC RESISTIVE LOAD 30VDC
NC COM NO 100mA NC COM NO 100mA A(+) B(-)

RS485
OUT OUT
OUT OUT

INA 0VDC RESET - + INA 0VDC RESET - +


INB / INH INB / INH
12VDC 100mA ※1 ※1
12VDC 100mA

J-10
Programmable Counter/Timer
CT6Y-I CT6Y-I T A(+) B(-) (A)
Photo
electric
sensor

RS485 (B)
Fiber
optic
sensor

(C)
Door/Area
sensor
0VDC RESET - + 0VDC RESET - +
INA INA
INB / INH INB / INH
12VDC 100mA ※1 12VDC 100mA ※1 (D)
Proximity
sensor

CT6M-2P CT6M-2P T (E)


※2 ※2 Pressure
12VDC 100mA INHIBIT 12VDC 100mA INHIBIT sensor
INB RESET BATCH RESET INB RESET BATCH RESET
INA 0VDC INA 0VDC (F)
Rotary
encoder
30VDC
SOLID STATE OUT RS485
100mA (G)
OUTPUT Connector/
COMMON OUT1 OUT2 BATCH Socket

A(+) B(-) OUT2 BATCH


(H)
Temp.
SOLID STATE OUT controller
OUT1 OUT2 OUT1 30VDC
OUT2
100mA (I)
SSR/
Power
controller

NO COM NO COM NC - + NO COM NO COM NC - +


(J)
250VAC 5A 250VAC 5A 250VAC 5A 250VAC 5A Counter
RESISTIVE RESISTIVE ※1 RESISTIVE RESISTIVE ※1
LOAD LOAD LOAD LOAD

CT6M-1P ※2 CT6M-1P T ※2
(K)
Timer
12VDC 100mA INHIBIT 12VDC 100mA INHIBIT
BATCH RESET BATCH RESET
INB RESET INB RESET
INA 0VDC INA 0VDC (L)
Panel
meter

SOLID STATE OUT 30VDC (M)


100mA RS485 Tacho/
OUTPUT Speed/ Pulse
COMMON OUT BATCH meter

A(+) B(-) OUT BATCH (N)


Display
SOLID STATE OUT unit

OUT OUT 30VDC


100mA (O)
Sensor
controller

(P)
NO COM NO - + NO COM NO - + Switching
250VAC 5A 250VAC 5A mode power
RESISTIVE supply
※1 RESISTIVE ※1
LOAD LOAD
(Q)
CT6M-I CT6M-I T Stepper
motor&
※2 ※2 Driver&Controller
12VDC 100mA INHIBIT 12VDC 100mA INHIBIT
INB RESET INB RESET (R)
INA INA Graphic/
0VDC 0VDC Logic
panel

(S)
Field
RS485 network
device

(T)
Software
A(+) B(-)

(U)
Other

- + - +
※1 ※1
※1: Source ※2: INHIBIT Signal
- AC Power: 100-240VAC 50/60Hz - Counter operation: If INHIBIT signal is applied,
- AC/DC Power: 24-48VDC, 24VAC 50/60Hz count input will be prohibited.
- Timer operation: If INHIBIT signal is applied, time
progressing will stop.(HOLD)
J-11
CT Series

Dimensions (unit:mm)
CTS Series
● Bracket 48 10 90 ● Panel cut-out
Min. 55

45.5 +0.5
0
60

45
Min. 62
45.5 +0.5
0

CTY Series 85 ● Panel cut-out


72 6 77 Min. 91

31.5 +0.6
0
Min. 40
36

30
68 +0.7
0

CTM Series 86 ● Panel cut-out


72 10 85
Min. 91

68 +0.7
0
Min. 91
67
68 +0.7
0

Parts description
CTS Series CTY Series CTM Series
1 8
1 7 10
4 1
6 2 5
5 9
3 3 6
7 2
4 6 2 13
8 3 5
9 10 7 4
8 12
1. Count indicator(Red LED) Model Changed Notice
CT6Y-1P
- Run mode
CT6S-1P PS2→PS There are no 11 9 10
: Count mode-Indicates count value. PS1, OUT1
CT4S-1P OUT2→OUT LEDs.
9. Mode key
Timer mode-Indicates time progressing. CT6M-1P - By pressing MD key for 3sec (parameter setting)/ 5sec (communication)
- Function setting mode CT6Y-I There are no in RUN mode, it moves to function setting mode.
: Indicates function setting mode. CT6S-I PS2→PS PS1, OUT1 - By pressing MD key in function setting mode, select function setting
CT6M-I OUT2 LEDs. mode. By pressing MD key over 3 sec., it moves to Run mode.
2. Preset value indicator (Yellow-Green LED)
※The indicator type does not exist - By pressing MD key over 1 sec. in function setting checking mode, it
- Run mode: Indicates preset value. in CT4S model.
- Function setting mode: Indicates setting value1. moves to Run mode.
3. Key Lock : Lights when setting key lock. 10. Set key
≪ : To enter into setting value(PS1, PS2) change status and shift digit
4. The operation of counter indicator
of setting value(PS1, PS2).
5. The operation of timer indicator
: To decrease setting value in setting value change mode, change

TMR LED flashes when the timer is operating. setting value in function setting mode, move down checked
TMR LED lights when the operating time stops. value in function setting check mode.
6. Check preset value and display change of it : To increase setting value in setting value change mode, change

PS1 LED lights when checking or changing the setting value1. setting value in function setting mode, move up checked value in
PS2 LED lights when checking or changing the setting value2. function setting check mode. By pressing MD key over 1 sec.
7. Output(OUT1, OUT2) indicator in Run mode, enters into function setting check mode.
OUT1 lights when output1 is on. 11. BATCH key
OUT2 lights when output2 is on. By pressing BA key in run mode to enter into BATCH counter
8. Reset key indication mode.
By pressing RST key in Run mode, the count value is initialized and 12. BATCH output indicator(red LED)
output is returned. 13. BATCH setting value checking and changing indicator
By pressing RST key in BATCH counter mode,BATCH count value (yellow-green LED)
resets. Lights when checking and changing BATCH setting value.

J-12
Programmable Counter/Timer

Input connections (A)


Photo
electric
sensor
No-voltage input(NPN)
(B)
● Solid-state input(Standard sensor : NPN output type sensor) ● Contact input Fiber
optic
sensor
Counter/Timer Counter/Timer Counter/Timer
Sensor CT Series Sensor CT Series CT Series (C)
Brown Brown Door/Area
+12V +12V +12V sensor

5.4Ω 5.4Ω 5.4Ω (D)


Black ※1 Black ※1 ※2 Proximity
Inner circuit Inner circuit Inner circuit sensor
of input part of input part of input part
(E)
Blue Blue Pressure
0V 0V 0V sensor

(NPN output) (NPN open collector output) (F)


Rotary
encoder
※1: INA, INB/INH, RESET, INHIBIT, BATCH RESET input part
※2: Counting speed: 1 or 30cps setting(Counter) (G)
Connector/
Socket

Voltage input(PNP)
(H)
● Solid-state input(Standard sensor : PNP output type sensor) ● Contact input Temp.
controller
Counter/Timer Counter/Timer Counter/Timer
Sensor CT Series Sensor CT Series CT Series (I)
SSR/
Brown Brown ※2 Power
+12V +12V +12V controller

(J)
Black ※1 Inner circuit Black※1 Inner circuit Inner circuit Counter
of input part of input part of input part
5.4㏀ 5.4㏀ 5.4Ω (K)
Blue Blue Timer
0V 0V 0V

(PNP output) (PNP open collector output) (L)


Panel
meter

※1: INA, INB/INH, RESET, INHIBIT, BATCH RESET input part


(M)
※2: Counting speed: 1 or 30cps setting(Counter) Tacho/
Speed/ Pulse
meter

(N)
Display

Input logic Selection[No-voltage input(NPN)/Voltage input(PNP)]


unit

(O)
1. The power must be cut off. 3. Select input logic by using input logic switch(SW1) Sensor
controller
2. Detach the case from the body. inside Counter/Timer.
(CTS, CTY Series) (P)
● Select No-voltage ● Select voltage Switching

input(NPN) input(PNP) mode power


supply

(Q)
Stepper
motor&
① NPN PNP NPN PNP Driver&Controller

(Factory default) (R)


② Graphic/
Logic
panel

(S)
Field
network
device

① (T)
Software

<CTS Series> <CTY Series> <CTM Series>


* Case detachment (U)
Squeeze toward ① and pull toward ② as shown Other
in picture.
4. Push a case in the opposite direction of 2-②.
Please check if the power is cut off. 5. Then apply the power to Counter/Timer.

J-13
CT Series

Output connections
Contact output Solid-state output
Counter/Timer Counter/Timer
CT Series ※1
CT Series

Load (+) Power


(Power of load) for load
Load (-) (DC)

※Use proper load and power for load not to excess ON/OFF
※Use proper load not to exceed the capacity.
capacity(30VDC Max. 100mA max.) of solid state output.
※Be sure not to apply reverse polarity of power.
※1: When use inductive load(Relay etc), surge absorber
(Diode, varistor etc) must be connected between both
sides of the load.

Factory default
Parameter Factory default
Input mode (ㅑIN) UP/Down-C (UD-C)
Output mode (OUtM) F (F)
CPS (CPS) 30cps (30)
Indication mode (indicator type)(DSpM) TOTAL (TOTAL)
OUT2 output time (OUt2) Hold (HOLD)
OUT1 output time (OUt1) 100ms (0)10)
Decimal point (DP)
Counter

------
Min. reset time (RST) 20ms (20)
Input logic (SIG) NPN (NPN)
Prescale decimal point (ScDP) 6digit type : -.-----, 4digit type : -.---­
Prescale value (SCL) 6digit type : 1.00000,4digit type : 1.000
Start Point setting (STRT) 000000
Counting memory (DATA) Clear (SLR)
Lock key (LOCK) Lock off (lOFF)
Preset value 1 (PS1) 1000 (1000)
Preset value 2 (PS2) 5000 (5000)
Time range (HOUR/MIN/SEC) 6Digit type: 0.001s-999.999s, 4Digit type: 0.001s-9.999s
Up/Down mode (U-D) UP (UP)
Indication mode(Indicator type)(DSpM) TOTAL (TOTAL)
Memory protection(Indicator type) (DATA) CLEAR (SLR)
Output mode (OUtM) OND (OND)
Timer

OUT2 output time (OUT2) Hold (HOLD)


OUT1 output time (OUT1) 100ms (0)10)
Input logic (SIG) NPN (NPN)
Input signal time (ImT) 20ms (20)
Lock key (LOCK) Lock off (lOFF)
Preset value 1 (PS1) 1000 (1000)
Preset value 2 (PS2) 5000 (5000)
Communication address (ADDR) 01 (001)
Communication

Communication speed (BPS) 9600bps (96)


Communication parity (PRTY) NONE (NONE)
Communication stop bit (STP) 2 (2)
Response waiting time (RSWT) 20ms (20)
Communication writing (COmY) Enable (ENA)

Error display
Error display Errors Output status How to return

EEP Failed in data loading


for exsiting setting OFF Power on again
values
PS1○
PS2○ FAIL
J-14
Programmable Counter/Timer

Operations and functions ※1


(A)
Photo
electric
RESET Change of sensor
BATCH RESET preset
(B)
Fiber
optic
sensor

BATCH counter RUN 1sec. Function setting


(C)
indication mode 1sec. check mode
※1 mode Door/Area
sensor
※BATCH counter is
Change of BATCH available for (D)
setting value. CT6M-1P/2P only. Proximity
3sec. 5sec. sensor
3sec.
※1. If no key is touched for 60 sec., the counter will (E)
Function 3sec.: Enters into parameter 1 group
return to RUN mode without being restored. Pressure
setting mode 5sec.: Enters into parameter 2 group sensor

(F)
Change of preset(Counter/Timer) Rotary
encoder

●Even if changing the preset value, input operation and output control will continue. In addition, the preset value could
be set to 0 and 0 preset value turns ON. According to output mode, preset value could not be set to 0. (When setting to 0, (G)
Connector/
preset value "0" will flash 3 times.) Socket

1. 2. 3. (H)
Temp.
controller

(I)
SSR/
Power
controller

(J)
Counter

(K)
In Run mode, it enters into the The preset value is set to ' ' The preset value is set to '200' Timer
preset value setting mode using , and keys, then using , and keys, then
using key. 'PS1' LED lights press key to enter into the press key to complete PS2 (L)
and first digit of preset value PS2 setting mode. setting and return to Run mode. Panel
flashes. meter

※Press key to save set value after changing the setting value. Then, it moves to next parameter or returns (M)
Tacho/
to RUN mode. However, if no key is touched for 60 sec., it will return to RUN mode without being saved. Speed/ Pulse
meter

Function setting check mode (N)


● Setting value of function setting mode can be confirmed using the and keys. Display
unit

Switching display function in preset indicator (O)


●Setting value 1(PS1) and setting value 2(PS2) are displayed each time pressing key in dual preset model. Sensor
controller
(In timer, it is available for output mode.)
(P)
Reset Switching
mode power
supply
● In Run mode or function setting mode, if key or applying the signal to the RESET terminal on the back side,
present value will be initialized and output will maintain off status. When selecting voltage input(PNP), short no. 10 (Q)
Stepper
and no. 12 terminals, or when selecting no-voltage input(NPN), short no. 11 and no. 12 terminals to reset. motor&
Driver&Controller

(R)

BATCH Counter(For CT6M-1P /CT6M-2P model only)


Graphic/
Logic
panel
In BATCH counter indication mode, 'BATCH counter value' is displayed in count indicator and 'BATCH counter (S)
setting value' is displayed in preset indicator. Field
network
device
Change of BATCH setting value
If pressing key in Run mode, it will enter into BATCH counter indication mode. (T)
Software
1. 2.
(U)
It enters into BATCH value is set to '200' Other

settingvalue change using , and keys,


mode using key. then press key to complete
(BA.S lights, first digit BATCH setting value and
of setting value flashes.) move to BATCH counter
indication mode.

J-15
CT Series
BATCH counter operation
Power ON
OFF
Preset output

Batch Reset

999999
Batch setting value

0
BA.O LED ON
OFF
Batch ON
output OFF

BATCH counting operation


● BATCH counting value is increasing until BATCH reset signal applied. BATCH counting value will be circulated when it is
over 999999.
1) BATCH counting operation in Counter : Counts the number of reaching setting value of CT6M-1P or reaching dual
setting value of CT6M-2P
2) BATCH counting operation in Timer: Counts the number of reaching setting time.
(In case of "FLK" output mode, count the number of reaching T.off setting time
and T.on setting time.)
BATCH output
● If input signal is applied while changing BATCH setting value, counting operation and output control will be performed.
● If BATCH count value equals to BATCH setting value, BATCH output will be ON and maintain ON status until BATCH reset
signal is applied.
● When the power is cut off then resupplied in status of BATCH output is ON, BATCH output maintains ON status until
BATCH reset signal is applied.

BATCH reset input


● If pressing reset button or applying the signal to BATCH reset terminal on the back side panel, BATCH counting value will
be reset. When selecting voltage input(PNP), short no. 10 and no. 14 terminals, or when selecting no-voltage input(NPN),
short no. 11 and no. 14 terminals to reset.
● When BATCH reset is applied, BATCH counting value maintains at 0 and BATCH output maintains in the OFF status.

Application of BATCH counter function


● Counter ● Timer
In case, put 5 products in a box then pack the boxes when Fills milk into the bottle for 3sec.(setting time) When 500
they reaches to 200. bottles are filled, BATCH counting finish lamp is turned on.
- Counter preset setting value="5", BATCH setting (Setting time : 3sec., BATCH setting value : 500)
value="200"
- When the count value of counter reaches to the preset
value "5", the control output(OUT) will be on, and at
this time the count value of the BATCH counter will be BATCH output Productivity :
increased by "1". The control box which is received the Operation valve Control 500bottels
(Open valve output Lamp on when
control output (OUT) repeatedly controls conveyor to for 3sec.) it is completed.
CT6M-
move the full box and to place the next empty box for 1P4 BATCH counting
finish lamp
standby. When the BATCH count value reaches to "200", Control the
BATCH output will be ON. Then the control box stops operation valve
Control
conveyor and provides a control signal for packing. Bottle sensing box
sensor

Count input BATCH output BATCH output


lamp
Control
output Control signal
(OUT) for packing
Control signal
CT6M-1P4 Control box
for conveyor
Preset value = 5

Third Second First


box box box
Current BATCH count value = 3

J-16
Programmable Counter/Timer

Flow chart for function setting mode (A)


Photo
electric
sensor
Run mode
(B)
Fiber
optic
3sec. 3sec. 5sec. 3sec. sensor

(C)
Parameter group1 ,
Parameter group2 Door/Area
sensor
(GRp1) (GRp2)
※3
Counter Timer (D)
(COUN) Counter/Timer (T1ME) Proximity
sensor
(C-T) Communication
※3 ※3 (E)
Input mode Time range Com. address Pressure
sensor
(IN) (HOUR/MIN/SEC) (ADDR)
※3 ※2 ※3 (F)
Rotary
Output mode Up/Down mode Com. speed encoder

(ㅐㅕㅆOUtM) (U-D) (BPS)


Indication mode ※1 ※3
(G)
Connector/
(DSpM) Socket
※1 Indication mode Com. parity
※3 (DSpM) (PRTY) (H)
Max. counting speed Temp.
controller
(CPS)
Memorize Com. stop bit
※2 ※3 counting value (STP) (I)
SSR/
(DATA) Power
OUT2 output time ※3 controller
(OUT2)
Function setting mode

Output mode Response


※3 (OUtM) waiting time (J)
Counter
OUT1 output time (RSwT)
※3
(OUT1)
OUT2 output time (K)
※3 (OUT2) Com. writing Timer

Decimal point ※3
(COmW)
(DP) (L)
OUT1 output time Panel
meter
(OUT1) ※1: Indicator
Min. reset time ※2: Output type (M)
(RST) ※3: If changing the setting Tacho/
Input logic Speed/ Pulse
(SIG) value of function, OUT1, meter

Input logic OUT2 will turn OFF and


(SIG) return to Run mode, then (N)
Display
Input signal time present value resets. unit
※3 (InT)
Prescale decimal (O)
point Sensor
controller
(ScDP) Lock key
(LOCK)
※3 (P)
Switching
mode power
Prescale value supply
(RST) ※Counter
※3 - Single preset model has no "OUT1 output setting time" setting function (Q)
Stepper
mode and OUtT is displayed in "OUT2 output time" setting function mode. motor&
Start Point value - In case of DN, DN-1, DN-2 input mode, there is no "Start Point value" setting Driver&Controller

(STRT) function mode. (R)


- In case of F or N output mode, there is no "OUT2 output time" setting function Graphic/
Logic
mode.(Fixed to HOLD) panel
Memorize counting value - In case of S, T or D output mode, there is no "OUT2 output time" setting
(DATA) function mode. (S)
Field
※Timer network
device
- In case of FLk1, FLk2 or INtG output mode and OND, OND1, OND2 output
Lock key mode of single preset model, OUtT is displayed in "OUT2 output time" function
(LOCK) setting mode and there is no "OUT1 output time" function setting mode. (T)
Software
- The output modes except for OND, ONd1, ONd2 and INt2 output mode there is no
"OUT1 output time" function setting mode.
(U)
※If changing setting value of parameter group1, display value and output will be initialize. Other

※Press key over 3sec./5sec. in RUN mode to enter into parameter 1 group/ parameter 2 group.
Press key over 3 sec. in function setting mode to return RUN mode.
※Input operation and output control can be set in function setting mode.
※If changing set value of ※3 marked parameters in function setting mode, OUT1 and OUT2 output will be turned OFF and
then the current value is reset.
※Parameter 2 group is not available to non-communication models.

J-17
CT Series

Parameter setting(Counter)
( key: To select setting mode, or key: To change setting value)
Setting mode How to set
Counter/Timer ※CONE: COUNTER
ㅊㅊC-T COUN TIME TIME: TIMER

Input mode UD-C UP UP-1 UP-2 DN DN-1 DN-2 UD-A UD-B


IN

● UP, UP-1, UP-2 or DN, DN-1, DN-2 input mode


F N C R K P Q A
Output mode
※In case that output mode is F, N there is no "OUT2 output time" setting mode. (Fixed to HOLD)
OUtM ※If output mode is set to D when max. counting
● UD-A, UD-B, UD-C input mode
F N C R K P Q A S T D speed is set to 5Kcps, 10Kcps, max. counting
speed is automatically set to 30cps. (Factory
Indication mode default setting)
DSpM ● In case of the indicator
HOLD TOTAL ※In case of the indicator, indicate mode selection (DSpM)is displayed.
※It is added that the function which can set the preset value when selecting
HOLD.(Refer to J-22 page 'Counter operation of the indicator'.)

※Counting speed is that of one by one(1:1) duty ratio of INA or INB input signal,
Max. counting speed
30 1K SY 10K 1 and it is applied in INA and INB at thesame time.
CPS ※In case of setting D in output mode, you can choose 1cps, 30cps, 1Kcps.

: To shift flashing digit position of OUT2 ※Set OUT2 one-shot output time.
OUT2 output time
output time value. ※Setting range: 0.01 to 99.99 sec.
OUT2
: To change OUT2 output time value. ※It does not appear if F, N output mode is selected.
: To shift flashing digit position of OUT1 ※Set OUT1 one-shot setting time
OUT1 output time ※Time range: 0.01 to 99.99 sec., Hold
output time value.
OUT1 ※HOLD is displayed by pressing key 4 times.
: To change OUT1 output time value.
● 6digit type
------ -----.- ----.-- ---.--- --.---- -.-----
※1
Decimal point
● 4digit type ※Setting the decimal point is applied same to counting
DP ---- ---.- --.-- -.--- value and setting value.

Min. reset time


1 20 unit: ms ※Set the min. external RESET signal width.
RST

Input logic NPN: No-Voltage input


※Check input logic value(PNP, NPN).
SIG PNP: Voltage input

● 6digit type
※1
Prescale
decimal point ● 4digit type ※Prescale decimal point position is not set below the decimal
ScDP point setting digits (DP).

※Setting range of prescale value


Prescale value : To shift the flashing digit. 6digit type: 0.00001 to 99999.9
SCL : To change the prescale value. 4digit type: 0.001 to 999.9
※Refer to the J-20 page ' Prescale function'.
※Setting range of Start Point value (Connected with decimal point setting)
Start Point Value : To shift the flashing digit. 6digit type: 0.00000 to 999999
STRT : To change the Start Point value. 4digit type: 0.000 to 9999
※Refer to the J-20 page ' Start Point function'.
Memory protection ※CLR: Initializes count value when power is off.
CLR REC
DATA ※REC : Memorizes count value at the moment of power off.

LOFF LOc1 ※LOFF:Cancellation of the lock mode.


Lock key LOc1: Locks key.
LOCK LOc2: Locks , , keys.
LOc3 LOc2 LOc3: Locks , , , keys.

※1. Explanation of decimal point and prescale decimal point setting


- Decimal point setting : Set decimal point of the display value on front indicator.
- Prescale decimal point setting : Set prescale decimal point of counting regardless of decimal point of display value
on front indicator.

J-18
Programmable Counter/Timer

Input operation mode(Counter) (A)


Photo
electric
sensor
Input mode Count chart Operation
(B)
Fiber
INA H No counting optic
L sensor

H ※If INA is counting input, INB is (C)


INB
UP L
No 7
inhibition input. Door/Area
sensor
(UP) counting 6 If INB is counting input, INA is
5
4 inhibition input. (D)
3 Proximity
2 sensor
Count 1
0
value 0
H (E)
INA Pressure
L sensor
Ⓐ Ⓐ
※Counts when INA input signal is up.
H
UP-1 INB L ( ) (F)
Rotary
No counting 5 ※INA: Counting input encoder
(Up-1) 4
3
※INB: Inhibition input
Count
2 (G)
value 1 Connector/
0 0
Socket

INA H (H)
L Temp.
Ⓐ Ⓐ controller
※Counts when INA input signal is
INB H
UP-2 L down. ( ) (I)

(Up-2) No counting 4 ※INA: Counting input SSR/


Power
3 ※INB: Inhibition input controller
2
Count 1
value 0 0 (J)
Counter

INA H No counting
L
Ⓐ Ⓐ Ⓐ Ⓐ (K)
Timer
INB H ※If INA is counting input, INB is
DN L
n
inhibition input.
(L)
(Down) n-1 If INB is counting input, INA is Panel
n-2 inhibition input. meter
n-3
n-4
Count n-5
n-6 (M)
value n-7 Tacho/
0 Speed/ Pulse
meter
INA H
L (N)
Ⓐ Ⓐ Display
※Count when INA input signal is up. unit
INB H
DN-1 L ( )
n ※INA: Counting input (O)
(Down-1) n-1 No counting Sensor
n-2 ※INB: Inhibition input controller
n-3
Count n-4
value n-5 (P)
Switching
0 mode power
H supply
INA
L (Q)
Ⓐ Ⓐ Stepper
※Counts when INA input signal is motor&
INB H Driver&Controller
DN-2 L
n No counting
down. ( )
(Down-2) n-1
※INA: Counting input (R)
Graphic/
n-2 ※INB: Inhibition input Logic
n-3 panel
Count n-4
value n-5 (S)
0 Field
network
device
H
INA L
Ⓐ Ⓐ ※INA: Counting input (T)
Software
H INB: Counting command input
UD-A INB
L
(Up/Down-A) 4 4 ※When INB is L, counting Up. (U)
3 3 3
Count 2 2 2 When INB is H, counting Down. Other
1 1
value 0
0

J-19
CT Series

Input operation mode(Counter)


Input mode Count chart Operation
INA H
L
※INA: Up counting input
INB H
INB: Down counting input
ㅕㅕUD-B L
4 4 ※When both INA and INB are applied
(Up/Down-B) 3 3 3 to L->H, it will remain previous
2 2 2
Count 1 counting value.
value 0
0

INA H
L
BBBB
※When use A,B phase of encoder
INB H
UD-C L with connecting to INA, INB, please
(Up/Down-C)
3 3 set counter input mode(IN) as
2 2 2 phase different input(UD-C).
Count 1 1
0
value 0

※ⓐ signal width should be over min. signal width and ⓑ signal width should be over a half min. signal width.
If not, ±1 will occur.
※Min. signal width by counting speed
※The meaning of "H" and "L"
Counting Min. signal INA High
Voltage input (NPN) No-Voltage input (PNP) speed width (INB) Low ON OFF ON OFF
1cps 500㎳
H 5-30VDC Short circuit Ton Toff
30cps 16.7㎳
1kcps 0.5㎳ T
L 0-2VDC Open
5kcps 0.1㎳
10kcps 0.05㎳ ※Ton, Toff : Min. signal width

Prescale function(Counter)
This function is to set and indicate calculated unit for actual length, liquid measure, position etc. It is called "Prescale value"
for measured length, measured liquid, measured position, etc per 1 pulse.
For example, P is the number of pulses per 1 revolution of a rotary encoder and L is the desired length to be measured.
Prescale value is [the desired length (L)]/[the number of pulses (P) per 1 revolution of the rotary encoder.].
It is the length per 1 pulse of a rotary encoder.
Ex) Control length by the counter and the rotary encoder
Roller
Cutter [In case of 22mm diameter(D) of roller connected
with the encoder of 1,000 pulse]

Rotary encoder
π × Diameter of the roller(D)
● Prescale value =
The number of pulses per
1 revolution of the encoder
Motor
3.1416 × 22
=
1000

Counter = 0.069mm/pulse
Motor controlling
system

To control conveyor position in 0.1mm, set the decimal point to tenth place(-----.-) in decimal point setting mode(DP) and
set the prescale decimal point to thousandth place(---.---) in prescale decimal point setting mode(ScDP)Then set prescale
value "0.069" in prescale setting mode (SCL).

Start point function(Counter)


This function is that start point value works as initial value when on counting mode.
● In case of DN, DN-1 or DN-2 in timer input mode, it is not available.
● When reset is applied, the present value is initialized to start point.
● After count up in C, R, P, Q After count up in

J-20
Programmable Counter/Timer

Output operation mode(Counter) One-shot output(0.01 to 99.99 sec.)


Retained output
One-shot output Retained output (A)
Photo
electric
sensor

Output Input mode (B)


Operation
mode Up, Up-1, 2 Down, Down-1, 2 Up/Down A, B, C Fiber
optic
sensor

RESET
(C)
999999 ※After count-up, counting display Door/Area
PRESET2 sensor
F PRESET1
value increases or decreases until
(F) 0 reset signal is applied and retained (D)
output is maintained. Proximity
OUT1 sensor
OUT2
(OUT)
(E)
Pressure
RESET sensor
999999
PRESET2 ※After count- up, counting display
N PRESET 1 value and retained output are main-
(F)
Rotary
encoder
(N) 0
tained until reset signal is applied.
OUT1
(G)
OUT2 Connector/
(OUT) Socket

RESET ※When count-up, counting display value


(H)
999999 will be reset and count simultaneously. Temp.
PRESET2 ※OUT1 retained output will be off after controller
C PRESET 1
OUT2 one- shot time.
0 (I)
(C) ※The one-shot output time of OUT1 SSR/
OUT1 Power
one-shot output time is operated controller
OUT2 gardless of OUT2 output.
(OUT)
(J)
RESET ※After OUT2 one-shot time, counting Counter

999999 display value will be reset and count


PRESET2 simultaneously.
R PRESET1 ※OUT1 retained output will be off after
(K)
Timer
(R) 0 OUT2 one-shot time.
OUT1 ※OUT1 one-shot output time is operated (L)
OUT2
regardless of OUT2 output. Panel
(OUT) meter

RESET ※After count-up, counting display (M)


999999 value increases or decreases until Tacho/
Speed/ Pulse
PRESET2 RESET input is applied.
K PRESET1 ※OUT1 retained output is off after
meter

(K) 0 OUT2 one-shot time. (N)


Display
OUT1 ※OUT1 one-shot output time is operated unit
OUT2
regardless of OUT2 output.
(OUT)
(O)
※After count-up, counting display value is Sensor
RESET maintained while OUT2 output is on. controller

999999 Counting value is internally reset and


PRESET2 counts simultaneously. (P)
※When OUT2 output is off, displays
P PRESET1 counting value while OUT2 is ON,
Switching
mode power
supply
(P) 0 and it increases or decreases.
※OUT1 retained output is off after (Q)
OUT1 OUT2 one-shot time. Stepper
OUT2 ※OUT1 one-shot output time is oper- motor&
Driver&Controller
(OUT) ated regardless of OUT2 output.
(R)
RESET ※After count-up, counting display Graphic/
Logic
999999 value increases or decreases during panel
PRESET2
OUT2 one-shot time.
Q PRESET1
0
※OUT1 retained output is off after (S)
Field
(Q) OUT1 OUT2 one-shot time. network
device
OUT2
※OUT1 one-shot output time is operated
(OUT) regardless of OUT2 output.
(T)
Software
RESET
999999 ※After count-up, counting display value
PRESET2 (U)
and OUT1 retained output are main-
A PRESET 1
tained until RESET input is applied.
Other

0
(A) ※OUT1 one-shot output time is oper-
OUT1
ated regardless of OUT2 output.
OUT2
(OUT)
※The single preset type output(OUT) is operated as OUT2 of dual preset type.
※OUT1 output could be set to 0 in all modes and 0 value output turns ON.
※OUT2 output could not set to 0 in C(C). R(R), P(P) or Q(Q) output mode.

J-21
CT Series

Output operation mode(Counter) Retained output Coincidence


output

Output mode Up/Down - A, B, C Operation

RESET
999999
PRESET2 ※OUT1 and OUT2 keeps ON status in
S PRESET1
0
following condition:
Counting display value ≧ PRESET1
(S) -99999
Counting display value ≧ PRESET2
OUT1
OUT2
(OUT)

RESET
999999 ※OUT1 output is off:
PRESET2
T PRESET1
0
Counting display value ≧ PRESET1
※OUT2 keeps ON status in following
(T) -99999 condition:
OUT1 Counting display value ≧ PRESET2
OUT2
(OUT)

RESET ※When counting display value is equal


999999 to setting value(PRESET1, PRESET2)
D PRESET2
PRESET1
0
only, OUT1 or OUT2 output keeps ON
status.
(D) ※When setting 1kcps for counting
-99999
speed, solid state contact output
OUT1
OUT2 should be used.
(OUT)
※The single preset type output(OUT) is operated as OUT2 of dual preset type.
※The dual preset model OUT1 output is operated as one-shot or retained output.(except S, T, D mode)
※OUT1 output could be set to 0 in all modes and 0 value output turns ON.
※OUT2 output could not set to 0 in C(C), R(R), P(P) or Q(Q) output mode.

Counter operation of the indicator(CT6S-I, CT6Y-I, CT6M-I)


Indicate Count chart
mode In case of input mode is Up In case of input mode is Down Operation
(DSpM) (Up, Up-1, Up-2) (Down, Down-1, Down-2)

RESET RESET Count value increases or decreases


until RESET input is applied.
TOTAL 999999 999999 When reaching max. count value or
(TOTAL)
0 min. count value, it will be reset and
0 count simultaneously.
-99999

RESET Count value increases or decreases


999999 999999
PRESET until RESET input is applied, count
HOLD PRESET
value indicator flashes when reaching
(HOLD)
preset value(Up count) or 0(Down
0 count).
0

● In case of the input mode is Command input (UD-A), Individual input(UD-B), Phase difference input(UD-C).

RESET
999999

※In case of UP/DOWN (UD-A, UD-B, UD-C) input mode, in-


0
dication mode (DSpM) of the configuration is not displayed.
-99999

J-22
Programmable Counter/Timer

Parameter setting(Timer) (A)


Photo
( key: To select setting mode or key: To change setting value) electric
sensor

Setting mode How to set (B)


Fiber
optic
Counter/Timer ※COUN: COUNTER sensor
C-T COUN TIME TIME: TIMER
(C)
Door/Area
6digit type sensor

SEC SEC SEC SEC M S M S


(D)
99(999 999(99 9999(9 999999 995(99 9995(9 Proximity
sensor
0.001s to 0.01s to 0.1s to 1s to 0.01s to 0.1s to
999.999s 9999.99s 99999.9s 999999s 99m59.99s 999m59.9s (E)
Pressure
sensor

HOUR H M H M 5 MIN MIN M 5


(F)
9999(9 999959 995959 999999 9999(9 999959 Rotary
encoder
0.1h to 1m to 1s to 1m to 0.1m to 1s to
99999.9h 9999h59m 99h59m59s 999999m 99999.9m 9999m59s
Timer range (G)
HOUR/MIN/SEC 4digit type Connector/
Socket

SEC SEC SEC SEC SEC


(H)
(999 9(99 99(9 9999 9959 Temp.
controller
0.001s to 0.01s to 0.1s to 1s to 1s to
9.999s 99.99s 999.9s 9999s 99m59s (I)
SSR/
Power
controller
HOUR H M MIN MIN
(J)
9999 9959 9999 99(9 Counter
1h to 1m to 1m to 0.1m to
9999h 99h59m 9999s 999.9m
(K)
Timer
UP/DOWN mode ※UP: Time proceeds from 0 to the setting value.
UP DN ※DN: Time proceeds from the setting value to 0.
U-D
(L)
※Used for the indicator only. Panel

Indication mode TOTAL HOLD ONtD ※ It is added that the feature which set the setting time when meter

DSpM selecting H OLD or ONtD (Refer to J-28 page ' Timer (M)
operation for the indicator'). Tacho/
Speed/ Pulse
※Used for the indicator only. meter
Memory protection ※치CLR : Initializes time value when power is off.
CLR REC (N)
DATA REC : Memorizes time value at the moment of power off. Display
unit

OND ONd1 ONd2 FLK FLk1 FLk2 INT (O)


Output mode Sensor
OUtM controller
INTG NFd1 NFD OFD INt2 INt1
(P)
Switching
mode power
key: To shift flashing digit position of OUT2 output time value. supply
key: To change OUT2 output time value.
OUT2 output time ※Set OUT2 one-shot output time. (Q)
OUT2 Stepper
※Setting range: 0.01 to 99.99sec. motor&
Driver&Controller
※HOLD is displayed by pressing key 4 times.
(R)
Graphic/
key: To shift flashing digit position of OUT1 output time value. Logic
panel
key: To change OUT1 output time value.
OUT1 output time ※Set OUT1 one-shot output time. (S)
OUT1 ※Setting range: 0.01 to 99.99sec., Hold Field
network
※HOLD is displayed by pressing key 4 times. device

Input logic ※NPN: No-Voltage input (T)

※PNP: Voltage input ※Check input logic value(PNP, NPN). Software


S1G

※CTS/CTY: Set min. external INA, INH, RESET signal width. (U)
Input signal time Other
1 20 [unit: ms] ※CTM: Set min. external INA, RESET, INHIBIT,
InT
BATCH RESET signal width.

LOFF LOc1 ※LOFF: Cancellation of the lock mode


Lock key LOc1: Locks key.
LOCK LOc2: Locks , , keys.
LOc3 LOc2 LOc3 : Locks , , , keys.

J-23
CT Series
One-shot output
One-shot output Retained output
Retained output
Output operation mode(Timer)
Output mode Input mode
Operation
Signal On Delay(Power Reset)
POWER 1) Time starts when INA signal turns on.
2) When INA signal turns off, time resets.
INA(START) 3) When INA signal is on:
INH(INHIBIT) Power ON Time Start is operated
Power OFF Time Start is operated
RESET
4) Control output operates as retained
Setting time2
OND UP Setting time1
or one-shot output.
(OND)
Display 0 INA
Setting time2 T1
Down
Setting time1 OUT1
0 T2
OUT2
OUT1 (OUT)
T1: Setting time1
OUT2 T2: Setting time2
Signal On Delay 1(Power Reset) 1) Time starts when INA signal turns on,
if INA signal is applied repeatedly,
POWER only initial signal is recognized.
2) When INA signal is on:
INA(START) Power ON Time Start is operated
INH(INHIBIT) Power OFF Time Start is operated
3) Control output operates as retained
RESET or one-shot output.
4) Only first INA input signal is valid in
ONd1 UP
Setting time2
case INA input signal is repeatedly
(OND.1) Setting time1 applied.
Display 0
INA
Setting time2
T1
Down Setting time1 OUT1
0 T2
OUT2
OUT1
(OUT) T1: Setting time1
OUT2 T2: Setting time2
Power On Delay(Power Hold) 1) Time starts when power turns on.
(There is no INA function.)
POWER
2) Time resets when reset turns on.
INA(START) Time starts when reset turns off.
INH(INHIBIT) 3) Control output operates as retained
RESET or one-shot output.
4) It memorizes display value at the
Setting time2 moment of power off.
ONd2 UP Setting time1 HOLD
(OND.2) Display 0
Setting time2 POWER T1
Down
Setting time1
0 OUT1 T2
OUT2
OUT1
(OUT) T1: Setting time1
OUT2 T2: Setting time2
t a t-a
Flicker(Power Reset) 1) Time starts when INA signal turns on.
2) When INA signal is on:
POWER Power ON Time Start is operated
INA(START) Power OFF Time Start is operated
3) Control output operates as retained
INH(INHIBIT) output, output turns off for the T.off
RESET time and turns off for the T.off time
T.off
and turns on for the T.on time repeat-
setting time edly.
FLK T.on
setting time
Ta+Tb = T.off setting time
4) The T.on time and T.off time must be
(FLK) UP set individually.
0 5) In case of using the contact output, min.
Display T.off setting time must be set over 100ms.
setting time
Down T.on POWER
setting time
INA
0 T.off T.on T.off
T.off T.on Ta Tb T.on T.off T.on T.off T.on T.off OUT2
OUT2(OUT) (OUT)

※Power Reset: There is no memory protection.(Initializes the display value when power is off)
Power Hold: There is memory protection.(Memorizes the display value at the moment of power off, indicates the memorized
display value when power is resupplied.)
J-24
Programmable Counter/Timer

Output operation mode(Timer) One-shot output One-shot output Retained output


Retained output
(A)
Photo
electric
sensor

Output mode Input mode (B)


Operation Fiber
Flicker 1(Power Reset) optic
sensor
Hold output 1) Time starts when INA signal turns on.
2) When INA signal is on: (C)
POWER
Power ON Time Start is operated Door/Area
Power OFF Time Start is operated sensor

INA(START) 3) Control output operates as retained


output. (D)
INH(INHIBIT) 4) In case of using the contact output, min. Proximity
sensor
setting time must be set over 00ms.
RESET
Setting time (E)
Pressure
Up sensor
0 POWER
Display INA
Setting time (F)
T T T Rotary
Down OUT2 encoder
0 (OUT)
T:Setting time
FLk1 OUT2(OUT) (G)
Connector/
(FLK.1) Socket
One-Shot output 1) Time starts when INA signal turns on.
2) When INA signal is on:
(H)
POWER Power ON Time Start is operated Temp.
Power OFF Time Start is operated controller
INA(START) 3) Control output operates as one-shot
INH(INHIBIT) output. (I)
4) In case of using the contact output, SSR/
Power
RESET min. setting time must be set over controller
Setting time 100ms.
(J)
0 POWER Counter
Up
Setting time INA
Display T T T
OUT2 (K)
0 Timer
Down t t t (OUT)
T:Setting time
OUT2(OUT)
(L)
Panel
Flicker 2(Power Hold) 1) Time starts when INA signal turns ON and meter
the display value at the moment when
Hold output power is off is memorized. (M)
2) When INA signal is on: Tacho/
Speed/ Pulse
POWER Power ON Time Start is operated meter
Power OFF Time Start is operated
INA(START) 3) Control output operates as retained output. (N)
INH(INHIBIT) 4) Control output will be reversed when it Display
reaches to setting time.(At the initial unit
RESET start, OUT2 control output is OFF).
Setting time 5) In case of using the contact output, min. (O)
Up setting time must be set over 100ms. Sensor
controller
0
Display POWER (P)
Setting time Switching
Down INA mode power
0 T T-c c T supply
OUT2
(Q)
(OUT)
FLk2 OUT2(OUT) Hold T:Setting time Stepper
motor&
Driver&Controller
(FLK.2)
One-Shot output 1) Time starts when INA signal turns ON and (R)
the display value at the moment when Graphic/

POWER power is off is memorized. Logic


panel
2) When INA signal is on:
INA(START) Power ON Time Start is operated (S)
Power OFF Time Start is operated Field
INH(INHIBIT)
3) Control output operates as one-shot network
device
RESET output.
Setting time 4) In case of using the contact output, min.
Up setting time must be set over 100ms. (T)
Software
0
Display POWER
Setting time
Down INA (U)
T T-c c T Other
0 OUT2
t t t a t-a t (OUT)
Hold T:Setting time
OUT2(OUT)

※Power Reset: There is no memory protection.(Initializes the display value when power is off)
Power Hold: There is memory protection.(Memorizes the display value at the moment of power off, indicates the memorized
display value when power is resupplied.)

J-25
CT Series

Output operation mode(Timer) One-shot output One-shot output Retained output


Retained output

Output mode Input mode


Operation
Interval (Power Reset)
1) Control output turns ON and time starts
when INA signal turns ON.
POWER
2) When INA signal is on:
INA(START) Power ON Time Start is operated
Power OFF Time Start is operated
INH(INHIBIT) 3) When it reaches setting time, indication
RESET value and control output are reset
ㅑㅜINT Setting time
automatically.
(INT) 4) Control output is ON when time is
Up progressing.
0
Display POWER
Setting time
Down INA
T T
0 OUT2
(OUT)
OUT2(OUT) T:Setting time

Interval 1(Power Reset) 1) Control output turns ON and time starts


when INA signal turns ON.
2) When INA signal is on:
POWER
Power ON Time Start is operated
Power OFF Time Start is operated
INA(START) 3) When it reaches setting time, indication
value and control output are reset
INH(INHIBIT) automatically.
4) Control output is ON when time is
INt1 RESET progressing.
(INT.1) Setting time 5) INA input is ignored while time is
Up progressing.
0
Display POWER
Setting time
INA
Down T
0 OUT2
(OUT)
OUT2(OUT) T:Setting time

Interval 2(Power Reset) 1) Time starts when INA input is ON and


resets when INA input is OFF.
2) INA input is ON, OUT1 output is ON during
T1 or t1.
POWER 3) When it reaches setting time1, display
INA(START) value resets and OUT2 output is ON
during T2 or t2 output time.
INH(INHIBIT) ※ Output turns OFF when reaching the
setting time even if one-shot time
RESET is longer than setting time.
INt2 Setting time1
Setting time2
(INT.2) Up
0
Display INA
T1 T1: Setting time1
Setting time2
Down OUT1 T2: Setting time2
Setting time1 T2 t1: One-shot1
t1
OUT2 t2: One-shot2
0
t2
OUT1
(Single preset model has no INT.2 mode)
OUT2

※Power Reset: There is no memory protection.(Initializes the display value when power is off)
Power Hold: There is memory protection.(Memorizes the display value at the moment of power off, indicates the memorized
display value when power is resupplied.)

J-26
Programmable Counter/Timer

Output operation mode(Timer) One-shot output One-shot output Retained output


Retained output
(A)
Photo
electric
sensor

Output mode Input mode (B)


Operation Fiber
Signal Off Delay1(Power Reset) optic
sensor
1) If INA is ON, control output remains
POWER ON. (except when power is off and (C)

INA(START) reset is on) Door/Area


sensor
2) When INA signal is OFF, time pro-
INH(INHIBIT)
cesses.
(D)
RESET 3) When it reaches setting time, indi-
OFD Setting time cation value and control output are
Proximity
sensor

(OFD) Up reset automatically.


(E)
0
Display POWER
Pressure
Setting time sensor

Down INA
T
0 (F)
Rotary
OUT2 encoder
OUT2(OUT) (OUT) T: Setting time

On-Off Delay (Power Reset) 1) When INA input is ON, output is (G)
Connector/
ON and time is progressing, then Socket
POWER output is OFF after On_Delay time.
2) When INA input is OFF, output is (H)
INA(START) ON and time is progressing, then Temp.
controller
INH(INHIBIT) output is OFF after Off_Delay time.
3) If INA input is OFF within On_Delay (I)
RESET
time, step 2 starts again. SSR/

NFD
Power
On_Delay 4) If INA input is ON within Off_Delay controller
Off_Delay time, step 1 starts again.
(NFD) Up
(J)
0 INA Counter
Display T1 T2
On_Delay
OUT2
Down
Off_Delay (OUT) T1: On_Delay (K)
Timer
0 T2: Off_Delay

OUT2(OUT) (L)
Panel
meter
On-Off Delay1 (Power Hold) 1) When INA input turns ON, time
progresses and output turns ON (M)
POWER after On_Delay time. Tacho/
Speed/ Pulse
2) When INA input turns OFF, time meter
INA(START) progresses and output turns OFF
after Off_Delay time. (N)
INH(INHIBIT) Display
3) If INA input turns OFF within On_ unit
RESET Delay time, output will turn ON and
NFd1 Up
On_Delay
step2 operate.
4) If INA input turns ON within Off_
(O)
Sensor
(NFD.1) Display Off_Delay Delay time, output will turn OFF controller
Up
Down 0 and step1 operate. (P)
Display Switching
On_Delay mode power
INA supply
Down T1 T2
Off_Delay
(Q)
0 OUT2 Stepper
(OUT) T1: On_Delay motor&
Driver&Controller
OUT2(OUT) T2: Off_Delay
(R)
Integration Time(Power Reset) Graphic/
Logic
panel
POWER
(S)
INA(START) Field
network
INH(INHIBIT) 1) Time is progressing while INA input device

RESET is ON.
INTG Setting time 2) Time progress stops while INA input is (T)
(INTG) OFF. Software
Up
0
3) When it reaches the setting time,
Display output is ON.
(U)
Setting time Other
Down
0
OUT2(OUT)

※Power Reset: There is no memory protection.(Initializes the display value and the output status when re-supplying the power.)
Power Hold: There is memory protection.(It memorizes the status of power off. When re-supplying the power, it returns
the memorized display value and the output status.)

J-27
CT Series

Timer operation of the indicator(CT6S-I, CT6Y-I, CT6M-I)


When memory protection setting is OFF

POWER
INA(START)
1) Time starts when INA input is ON.
INH(INHIBIT)
2) Setting value is initialized when Reset input
RESET is ON.
Max.
3) Time progress stops when INHIBIT input is
time range
Up ON.
0 4) Resets when power is OFF.
Display Max.
time range
Down
TOTAL 0
(TOTAL) When memory protection setting is ON
POWER
INA(START) 1) Time starts when INA input is ON.
INH(INHIBIT) 2) Setting value is initialized when Reset input
RESET is ON.
Max. 3) Time progress stops while INHIBIT input
Up
time range is ON.
0 4) Display value at the moment of power OFF
Display
Max. is memorized.
Down time range
0
When memory protection setting is OFF
POWER
INA(START) 1) Time progresses when INA input is ON.
INH(INHIBIT) 2) Time progress stops while INA input is OFF.
RESET
3) When time reaches setting time, display
value will stop and flash.
Setting time
Up 4) When reset input is applied, display value
0 is initialized.
Display 5) Resets when power is OFF.
Setting time
Down
HOLD 0
When memory protection setting is ON
(HOLD)
POWER
1) Time progresses when INA input is ON.
INA(START)
2) Time progress stops while INA input is OFF.
INH(INHIBIT) 3) When time reaches setting time, display
RESET value will stop and flash.
Setting time 4) When reset input is applied, display value
Up is initialized.
0 5) Display value the moment when power is
Display
Setting time OFF is memorized.
Down
0
When memory protection setting is OFF
※ON time indicate mode of INA input
POWER
1) Time reset start operates when INA input
INA(START)
turns ON.
INH(INHIBIT) 2) Time progress stops while INA input is OFF.
RESET 3) When time progress stops and power is
Setting time off, the display value is initialized.
Up 4) If progress time is greater than setting
0 time when INA input turns off, display
Display
Setting time value flashes and operation stops until
Down reset signal is applied.
ONtD 0
When memory protection setting is ON
(On Time
Display) POWER ※ON time indicate mode of INA input
INA(START) 1) Time reset start operates when INA input
INH(INHIBIT) turns ON.
RESET 2) Time progress stops while INA input is OFF.
3) When time progress stops and power is
Setting time
off, the display value is memorized.
Up 4) If progress time is greater than setting
0 time when INA input turns off, display
Display
Setting time value flashes and operation stops until
Down reset signal is applied.
0

J-28
Programmable Counter/Timer

Timer '0' time setting (A)


Photo
Available output operation mode to set '0' time setting electric
sensor

OND, ONd1, ONd2, NFD, NFd1 (B)

Operation according to output mode(at 0 time setting)


Fiber
optic
sensor
1) OND(Signal ON Delay) mode [OND]
● Setting time1 is set to 0 ● Setting time2 is set to 0 (C)
Door/Area
UP mode DOWN mode sensor

INA(START)
INA(START) (D)
Setting time 2 Proximity
Setting time2 sensor

0 0
(E)
Pressure
OUT1 OUT1 sensor

OUT2 OUT2
(F)
2) OND.1(Signal ON Delay 1) mode [ONd1] ● Setting time2 is set to 0 Rotary
encoder
● Setting time1 is set to 0
UP mode DOWN mode (G)
INA(START) Connector/
INA(START) RESET
Socket

RESET Setting time1


(H)
Setting time2 Temp.
controller
0
0
OUT1 (I)
SSR/
OUT1 Power
OUT2 controller
OUT2
3) OND.2(Power ON Delay2) mode [ONd2] ● Setting time2 is set to 0 (J)
Counter
● Setting time1 is set to 0
UP mode DOWN mode UP mode
(K)
POWER POWER Timer

RESET RESET
Setting time 1 Setting time1 (L)
Panel
meter
0 0
(M)
OUT1 OUT1 Tacho/
Speed/ Pulse
OUT2 OUT2 meter

4) NFD(ON-OFF Delay) mode [NFD] ● ON_Delay setting time is set to 0 (N)


Display
● OFF_Delay setting time is set to 0 unit

INA(START)
INA(START) (O)
RESET Sensor
RESET controller
Off_Delay
On_Delay Up 0 (P)
Up 0 Switching
Display Off_Delay mode power
supply
Display On_Delay 0
Down
Down 0 (Q)
OUT2 Stepper
OUT2 (OUT) motor&
Driver&Controller
(OUT)
5) NFD.1(ON-OFF Delay1) mode [NFd1] ● ON_Delay setting time is set to 0 (R)
Graphic/
● OFF_Delay setting time is set to 0 Logic
INA(START) panel

INA(START)
RESET (S)
Field
RESET network
Off_Delay device
On_Delay Up 0
Up 0 Display Off_Delay (T)
Software
Display On_Delay 0
Down
Down 0 OUT2
OUT2 (OUT) (U)
Other
(OUT)
Setting value1(PS1) is higher than Setting value2(PS2)
OND(OND), OND.1(ONd1)or OND.2(ONd2)output mode
● UP mode: When the timer setting value1 is greater than the setting value 2, OUT1 output does not turn ON.
● DOWN mode: When the timer setting value1 is greater than the setting value 2, OUT1 output does not turn ON.
If the setting value 1 is same as the setting value2 and START signal is applied, OUT1 output turns ON
immediately.
J-29
CT Series

Communication mode
Parameter setting ( key: To select setting mode, or key: To change setting value)

Setting mode How to set


※Setting range of com. address: 1 to 127
Com. address : To shift flashing digits of Com. address.
※If the same address is applied during multicom.,
(ADDR) : To change the flashing digits.
it will not work correctly.

Com. speed
24 48 96 192 384 ※2400/4800/9600/19200/38400bps
(BPS)

Com. parity NONE EVEN ODD ※NONE: None EVEN : Even number ODD: Odd number
(PRTY)

Com. stop bit


1 2
(STP)

※Setting range according to com. speed.


: To shift flashing digits position of com. 2400bps 16ms to 99ms
esponse
response waiting time. 4800bps 8ms to 99ms
waiting time
: To change the flashing digits position 9600bps 5ms to 99ms
(RSwT)
value. 19200bps 5ms to 99ms
38400bps 5ms to 99ms

Com. write ※ENA : Permits com. write(Enable)


ENA DISA
(COmW) DISA : Prohibits com. write(Disable)

Application of system organization


GND
V(12-24VDC)
RS232C RS485 Terminating
B(-) resistance B(1)
RxD - RxD CT Series
TxD - TxD A(+)
GND - GND A(+) #31

RS232C Cable A(+) B(-) A(+) B(-) A(+) B(-)


B(-)
Computer CT Series CT Series CT Series
ON OFF #01 #02 #30
A(+)
※It is recommended to use communication converter, RS485 to Serial converter(SCM-38I, sold separately), USB to
RS485 converter(SCM-US48I, sold separately). Please use a proper twist pair for RS485 communication.
Communication control ordering
1. The communication method is Modbus RTU(PI-MBUS-300-REV.J).
2. After 1sec. of power supply into the high order system, it starts to communicate.
3. Initial communication will be started by the high order system. When a command comes out from the high order system,
CT Series will respond.
Address code

Address code
Command

Command
CRC16

CRC16
Data

Data

Upper system
Address code
Command

CRC16
Data

CT Series

A B C

※A → Min. 1sec. after applying power


B → 38400bps: Approx. 1ms.
19200bps: Approx. 2ms.
9600bps: Approx. 4ms.
4800bps: Approx. 8ms.
2400bps: Approx. 16ms.
C → Min. 20ms
J-30
Programmable Counter/Timer
Communication command and block (A)
Photo
The format of query and response electric
sensor
1) Read Coil Status(Func 01 H), 5) Preset Multiple Registers(Func 10 H) (B)
Read Input Status(Func 02 H Fiber
optic
● Query(Master) sensor
● Query(Master)
Error
Starting Error Check Starting No. of (C)
No. of Points Data Data Check Door/Area
Slave Address (CRC 16) Slave Address Register Byte
Address Function Function (CRC 16) sensor
Address Count
High Low High Low Low High
High Low High Low High Low High Low Low High
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte (D)
Proximity
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte sensor
CRC 16
● Response(Slave) CRC 16 (E)
Pressure

● Response(Slave)
sensor
Error Check
Slave Byte (CRC 16)
Address Function Count Data Data Data
Starting Address No. of Register
Error Check
(F)
Low High Slave (CRC 16)
Function Rotary
Address encoder
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte High Low High Low Low High

1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte


CRC 16 (G)
Connector/
Socket
2) Read Holding Registers(Func 03 H), CRC 16
Read Input Registers(Func 04 H)
6) Application (H)
● Query(Master) Read Coil Status(Func 01 H)
Temp.
controller
Starting Error Check Master reads OUT2 00002(0001H) to 00003(0002H),
Slave No. of Points
Address (CRC 16) (I)
Address Function OUT1 output status(ON : 1, OFF : 0) from the SSR/
High Low High Low Low High Power
Slave(Address 01). controller
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte
● Query(Master)
(J)
CRC 16 Starting Address No. of Points
Error Check Counter
Slave (CRC 16)
Function
● Response(Slave) Address
High Low High Low Low High
Error Check 01 H 01 H 00 H 01 H 00 H 02 H EC H 0B H (K)
Slave Function Byte Data Data Data
(CRC 16)
Timer
Address Count On slave side OUT2 00003(0002H) : OFF,
High Low High Low High Low Low High
OUT1 00002(0001H) : ON (L)
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte Panel
● Response(Slave) meter

CRC 16 Data Error Check


Slave (M)
Function Byte Count (00003 to (CRC 16) Tacho/
3) Force Single Coil(Func 05 H) Address
00001) Low High Speed/ Pulse
meter
● Query(Master) 01 H 01 H 01 H 02 H D0 H 49 H

Error Check Read Input Register (Func 04 H)Master reads preset value (N)
Display
Slave Coil Address Force Data
Address Function
(CRC 16) 21004(03EBH) to 21005(03ECH) of counter/timer, Slave unit

High Low High Low Low High (Address 15).


(O)
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte Sensor
controller
● Query(Master)
CRC 16 Error Check (P)
Starting Address No. of Points
● Response(Slave) Slave
Address
Function (CRC 16) Switching
mode power
High Low High Low Low High supply
Error Check
Slave Coil Address Force Data 0F H 04 H 03 H EB H 00 H 02 H 00 H 95 H
Function (CRC 16) (Q)
Address Stepper
High Low High Low Low High In case that the present value is 123456(0001 E240 H) in motor&
Driver&Controller
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte slave side, 31004(03EBH): E240 H, 31005(03ECH): 0001H
(R)
Graphic/
CRC 16 Logic
● Response(Slave) panel
4) Preset Single Register(Func 06 H) Error Check (S)
● Query(Master) Slave
Function
Byte Data Data
(CRC 16) Field
network
Address Count
Register Error Check High Low High Low Low High device
Slave Preset Data
Address (CRC 16)
Address Function 0F H 04 H 04 H E2 H 40 H 00 H 01 H E2 H 28 H
High Low High Low Low High (T)
Software
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte

CRC 16 (U)
Other
● Response(Slave)
Register Error Check
Slave Preset Data
Address (CRC 16)
Address Function
High Low High Low Low High
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte

CRC 16

J-31
CT Series
Modbus Mapping Table
1) Reset/Output 4) Monitoring data
No(Address) Func Explanation Setting range Notice No(Address) Func Explanation Setting range Notice
00001(0000) 01/05 Reset 0:OFF 1:ON BA.O LED 0:OFF 1:ON Bit 5
00002(0001) 01 OUT2 output 0:OFF 1:ON display status
00003(0002) 01 OUT1 output 0:OFF 1:ON OUT2 LED 0:OFF 1:ON Bit 6
display status
For BATCH OUT1 LED
00004(0003) 01 BATCH output 0:OFF 1:ON 0:OFF 1:ON Bit 7
output model display status
For BATCH BA.S LED
00005(0004) 01/05 BATCH resets 0:OFF 1:ON 0:OFF 1:ON Bit 10
output model display status
31001 LOCK LED
04 display status 0:OFF 1:ON Bit 11
2) Terminal input status (03E8)
PS2 LED
No(Address) Func Explanation Setting range Notice 0:OFF 1:ON Bit 12
display status
Terminal input PS1 LED
10001(0000) 02 INA input status 0:OFF 1:ON 0:OFF 1:ON Bit 13
status display status
Terminal input TMR LED
10002(0001) 02 INB input status 0:OFF 1:ON 0:OFF 1:ON Bit 14
display status
status
CNT LED
Terminal input 0:OFF 1:ON Bit 15
10003(0002) 02 INHIBIT input status 0:OFF 1:ON display status
status 31002(03E9) Present value For BATCH
Terminal input 04 of BATCH 0 to 999999 output
10004(0003) 02 RESET input status 0:OFF 1:ON 31003(03EA) counter model
status
BATCH RESET Terminal input 31004(03EB)
10005(0004) 02 0:OFF 1:ON Counter
input status status
Present value 6digit type: 999999
-99999 to Use counter
3) Product Information 04 of and timer
4digit type: -999 to 9999
31005(03EC) counter/timer Timer: Within time setting in common
No(Address) Func Explanation Notice
range
30001~30100 04 Reserved -
30101(0064) 04 Product number H Counter:
Model ID Counter: decimal point 40058 Data
30102(0065) 04 Product number L 31006(03ED) 04 Display unit of display value Timer:
30103(0066) 04 Hardware version - Timer: Time range 40102 Data
30104(0067) 04 Software version -
31007(03EE) Counter
30105(0068) 04 Model no. 1 "CT" 6digit type: -99999 to
30106(0069) 04 Model no. 2 "6M" Use counter
PS(2) 999999
04 setting value 4digit type: -999 to 9999 and timer
30107(006A) 04 Model no. 3 "-2"
30108(006B) 04 Model no. 4 "PT"
31008(03EF) Timer: Within time setting in common
range
30109(006C) 04 Reserved -
30110(006D) 04 Reserved - Counter
31009(03F0) 6digit type: -99999 to
30111(006E) 04 Reserved - Use counter
PS1 999999
04 setting value 4digit type: -999 to 9999 and
30112(006F) 04 Reserved - timer
30113(0070) 04 Reserved -
31010(03F1) Timer: Within time setting in common
30114(0071) 04 Reserved - range
31011(03F2) Setting value Use counter
30115(0072) 04 Reserved - 04 of BATCH 0 to 999999 and timer
30116(0073) 04 Reserved - 31012(03F3) counter in common
30117(0074) 04 Reserved - Checking the 0: NPN, 1 : PNP
31013(03F4) 04 input logic
Coil Status
30118(0075) 04 0000
Start Address
Coil Status
30119(0076) 04 Quantity - ● Date format of 31001(03E8) address bit
Input Status Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit4 Bit 3 Bit 2 Bit 1 Bit 0
30120(0077) 04 0000
Start Address
CNT TMR PS1 PS2 LOCK BA.S - - OUT1 OUT2 BA.O - - - - -
30121(0078) 04 Input Status Quantity - 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 0 0 or 1 0 or 1 0 or 1 0 0 0 0 0
Holding Register
30122(0079) 04 Start Address 0000 ※2 Words data format: Upper data has high number address.
Holding Register Ex)31004 : Present Value(Low Word),
30123(007A) 04 -
Quantity 31005 : Present Value(High Word)
Input Register
30124(007B) 04 0064
Start Address
5) Preset value setting group
30125(007C) 04 Input Register Quantity -
No(Address) Func Explanation Setting range Notice
40001(0000) 03 PS2 setting value Counter Use counter
06 and timer
40002(0001) 16 PS setting value 6digit type: 0 to in common
999999
40003(0002) 03 4digit type: 0 to 9999 Use counter
PS1 setting Timer: Within time
06 and timer
40004(0002) 16 value setting range in common
40005(0004) 03 BATCH coun- Use counter
06 ter 0 to 999999 and timer
40006(0005) 16 setting value in common

J-32
Programmable Counter/Timer
6) Function setting mode (Counter group) (A)
Photo
No(Address) Func Explanation Setting range Notice electric
sensor
40051(0032) 03/06/16 Counter/Timer(C-T) 1: COUN 1: TIME Use counter and timer in common
(B)
0: UP 5: DN-2 Fiber
optic
1: UP-1 6: UD-A sensor
40052(0033) 03/06/16 Input mode(IN) 2: UP-2 7: UD-B -
3: DN 8: UD-C (C)
Door/Area
4: DN-1 sensor

40053(0034) 03/06/16 Indication mode(DISM) 0: TOTAL 1: HOLD For the indicator


0: F 3: R 6: Q 9: T (D)
Proximity
40054(0035) 03/06/16 Output mode(OUTM) 1: N 4: K 7: A 10: D - sensor

2: C 5: P 8: S
Maximum counting 0: 1 2: 1K 4: 10K (E)
40055(0036) 03/06/16 - Pressure
speed(CPS) 1: 30 3: 5K sensor
40056(0037) 03/06/16 OUT2(OUT) output time 0001~ 9999 unit: ×10㎳
40057(0038) 03/06/16 OUT1 Output time 0001~ 9999 unit: ×10㎳ (F)
Rotary
0: ------ 2: ----.-- 4: --.---- 4digit type 0: ---- encoder
40058(0039) 03/06/16 Decimal point(DP)
1: -----.- 3: ---.--- 5: -.----- 1: ---.- 2: --.-- 3: -.---
40059(003A) 03/06/16 Min. reset time(RST) 0: 1 1: 20 unit: ms (G)
Connector/
Prescale decimal 0: -----.- 3: ---.--- 5: -.----- 4digit type Socket
40060(003B) 03/06/16
point position(SClD) 2: ----.-- 4: --.---- 1: ---.- 2: --.-- 3: -.---
40061(003C) 6digit type: )00001 to 999999 Connected with prescale (H)
03/06/16 Prescale value(SCL) Temp.
40062(003D) 4digit type: )001 to 9999 decimal point position controller
40063(003E) 6digit type: 000000to 999999 Connected with decimal
03/06/16 Start value(STRT)
40064(003F) 4digit type: 0000to 9999 point position of display value (I)
SSR/
40065(0040) 03/06/16 Memory protection(DATA) 0: CLR 1: REC Use counter and timer Power
controller
40066(0041) 03/06/16 Lock key(LOCK) 0: lOFF 1: LOc1 2: LOc2 3: LOc3 in common
(J)
7) Function setting mode (Timer group) Counter

No(Address) Func Explanation Setting range Notice


Use counter and timer (K)
40101(0064) 03/06/16 Counter/Timer(C-T) 0: COUN 1: TIME Timer
in common
4digit type
(L)
0: 0.001s to 9.999s 5: 0.1m to 999.9m Panel
meter
1: 0.01s to 99.99s 6: 1m to 9999m
2: 0.1s to 999.9s 7: 1m to 99h59m (M)
3: 1s to 9999s 8: 1h to 9999h Tacho/
Speed/ Pulse
4: 1s to 99m59s meter
Time range
40102(0065) 03/06/16 6digit type -
(HOUR/MIN/SEC) (N)
0: 0.001s to 999.999s 6: 1s to 9999m59s Display
unit
1: 0.01s to 9999.99s 7: 1m to 99999.9m
2: 0.1s to 99999.9s 8: 1m to 999999m
(O)
3: 1s to 999999s 9: 1s to 99h59m59s Sensor
controller
4: 0.01s to 99m59.99s 10: 1m to 9999h59m
5: 0.1s to 999m59.9s 11: 0.1h to 99999.9h (P)
Switching
UP/Down mode
40103(0066) 03/06/16 0: UP 1: DN - mode power
(U-D) supply

0: OND 3: FLK 7: INt1 10: NFD (Q)


Output mode
40104(0067) 03/06/16 1: ONd1 4: FLk1 8: INt2 11: NFd1 - Stepper
motor&
(OUTM)
2: ONd2 5: FLk2 9: OFD 12: INtG Driver&Controller

OUT2(OUT) Output time (R)


40105(0068) 03/06/16 0000 to 9999(0: Hold) unit: ×10ms Graphic/
(OUT2) Logic
OUT1 Output time panel
40106(0069) 03/06/16 0000 to 9999(0 : Hold) unit: ×10,ms
(OUT1) (S)
Field
40107(006A) 03/06/16 Input signal time(INT) 0: 1 1: 20 unit: ms network
device
40108(006B) 03/06/16 Memory protection(DATA) 0: CLR 1: REC Use counter and timer in common
40109(006C) 03/06/16 Lock key(LOCK) 0: lOFF 1: LOc1 2: LOc2 3: LOc3 Use counter and timer in common
(T)
40110(006D) 03/06/16 ndication mode(DSpM) 0: TOTAL 1: HOLD 2: ONtD For the indicator Software

(U)
Other

J-33
CT Series
8) Function setting mode (Communication group)
No(Address) Func Explanation Setting range Notice
40151(0096) 03/06/16 Com. address (ADDR) 1 to 127 -
40152(0097) 03/06/16 Com. speed (BPS) 0: 24 1: 48 2: 96 3: 192 4: 384 unit: ×100bps
40153(0098) 03/06/16 Com. parity (PRTY) 0: NONE 1: EVEN 2: ODD -
40154(0099) 03/06/16 Stop bit (STP) 0: 1 1: 2 -
40155(009A) 03/06/16 Response waiting time (RSwT) 05 to 99 unit: ms
40156(009B) 03/06/16 Com. writing (COmW) 0: ENA 1: DISA -

Exception processing
When communication error occurs, the highest bit of received function is set
to 1, then sends response command and transmits exception code.
Error Check(CRC16)
Slave Address Function+80H Exception Code
Low High
1Byte 1Byte 1Byte 1Byte 1Byte
● Illeegal Function(Exception Code: 01H): Not supporting command
● Illegal Data Address(Exception Code: 02H): Mismatch between the number of asked data and the number of transmit-
table data.
● Illegal Data Value(Exception Code: 03H): Mismatch between asked the number of data and transmittable the number of
data in device
● Slave Device Failure(Exception Code: 04H): Command is processed incorrectly.

Example)
Master reads output status (ON:1, OFF:0) of non existing coil 01001 (03E8 H) from Slave (Address17).

● Query(Master)
Starting Address No. of Points Error Check(CRC16)
Slave Address Function
High Low High Low Low High
11H 01H 03H E8H 00H 01H ##H ##H

● Response(Slave)
Error Check(CRC16)
Slave Address Function + 80H Exception Code
Low High
11H 81H 02H ##H ##H

Read and write of parameter value using communication


Read of the parameter area
00002(OUT2), 00003(OUT1), 00004(BA, 0), 10001 to 10005(Terminal input), 30101 to 30125(Product information),
31001 to 31013(Monitoring data)
Read and write of the parameter area
00001(Reset starts), 00005(BATCH Reset starts), 40001 to 40006(Setting value saving group),
40051 to 40066(Counter setting group), 40101 to 40110(Timer setting group),
40151 to 40156(Communication setting group)
Read of communication
Read parameter value using communication.(Function : 01H, 02H, 03H, 04H)
It is able to read communication regardless of permitting/prohibiting communication writing.
Communication write
Change parameter value using communication.(Function: 05H, 06H, 10H)
● When change the parameter setting value of ' Function setting mode Counter group' or ' Function setting mode
Timer group' using communication, reset indication will flash in 3 sec. and display value will be reset.(Counting display
value and progress time before changing parameter setting value are not saved.)
● When change the parameter setting value of ' Preset value setting group' or ' Function setting mode Communica-
tion group' using communication, counting display value or progress time will not be reset.
● In prohibit writing communication setting ( = 1: ), a write command does not process.
● If set value beyond the setting range, this setting value is substituted for the value within the setting range and then
memorized.

J-34
Programmable Counter/Timer

Proper usage (A)


Photo
electric
The power ON/OFF sensor

(B)
Fiber
Power ON optic
sensor
OFF
100㎳ 500㎳
The unstable time (C)
against the input signal. Door/Area
sensor

Power voltage rises for 100ms after power on and falls for (D)
500ms after power off. Therefore be sure to apply input Proximity
sensor
signal after 100ms and power turns on again after 500ms
when power turns off. (E)
Pressure
● Be sure to use insulated and resistive voltage /current or sensor
Class2 supply power device to input 24VAC/24-48VDC
power supply model. (F)
Rotary
encoder
Input signal line
● Use as short a cable from the sensor to this unit as possible. (G)
Connector/
● Use shielded cable for long input line. Socket

● Wire as separating input line from the power line.


(H)
Temp.
controller

When selecting input logic (I)


SSR/
Be sure that supply power is off when selecting input logic, Power
controller
then select logic input according to input logic changing
method. (J)
Counter

Contact count input (When it is used as Counter)


If apply contact input at high speed mode(1k, 5k, 10k), it (K)
Timer
may cause miscount by chattering.
Therefore set low speed mode(1cps or 30cps) at contact input. (L)
Panel
meter
When test dielectric voltage and insula-
tion resistance of the control panel with this (M)
Tacho/
Speed/ Pulse
unit installed. meter

● Please isolate this unit from the circuit of control panel. (N)
● Please make all terminals of this unit short-circuited. Display
unit

Do not use below places. (O)


Sensor
● Place where there are severe vibration or impact. controller

● Place where strong alkalis or acids are used. (P)


● Place where there are direct ray of the sun. Switching
mode power
● Place where strong magnetic field or electric noise are supply

generated. (Q)
Stepper
motor&
Installation environment Driver&Controller

● It shall be used indoor. (R)


Graphic/
● Altitude Max. 2000m Logic
panel
● Pollution Degree 2
● Installation Category II (S)
Field
network
device

(T)
Software

(U)
Other

J-35