Você está na página 1de 8

TPMJH-201001 1

Cable Ladder Bonding with Earth Wire,


Is it Necessary?
Michael J Hamilton, Member IEAust.

practice of using bonding wires across joined sections of cable


Abstract — In Western Australian mining sites there is a ladder for providing a continuous earth path, and the merit of
practice of bonding cable ladder sections with an earth wire, providing earth wires as an improvement to reducing the
instead of relying totally on the splice plates for earthing. A resistance across a splice plate section of the cable ladder
common requirement today is the provision of earthing
conductors linking cold formed cable ladder sections. There is a
system. The risk will also be investigated where an earth
lack of information relating as to the relevance of this bonding wire is not used to form part of the earthing system.
requirement or where this practice has originated. This paper
reports on testing carried out on actual cable ladder, and II. BACKGROUND
examines the effect of adding an earthing conductor to achieve a
continuous low resistance earth path between the cable ladder
sections. From an examination of the results, assessment is made The current practice as seen from experience of many cable
of the effectiveness of the bonding conductor, followed by ladder installations is the prolific use of bonding wires. Figure
discussion of the risks involved with and without earth wires, and 1, shows an example of such a typical installation in a mining
the merits of discontinuing or continuing the practice. environment that has earth bonding wires between all cable
ladder sections. Figure 2 showing a close up of the cable
Index Terms — Bonding, Earth Wire, Jumper, Cable Ladder, ladder. Generally only one earth bonding wire is installed to
Cable Tray, Earthing.
the ladder, which is to the outside face of the ladder system as
the inside rail would not easily be visible or accessible.
I. INTRODUCTION

F OR the majority of installations, especially in process and


crushing plants in mining industries, there is a large
quantity of cable ladder installed, where it is used primarily for
supporting electric cables. The cable ladder generally used is
metal, and as such is considered a wiring enclosure which may
become live, requiring grounding. Earthing of the cable ladder
is important and is also a requirement of The Wiring Rules,
AS 3000. Electrical grounding is essential for both personnel
safety and to ensure protection systems operate correctly to
remove power from a faulted cable. However the wiring
standards do not stipulate that cable ladder sections be bonded
by earthing wires across each joint, merely that the ladder
itself be bonded to the main earthing system.
Fig. 1. Typical photograph of installed cable ladder showing separate earth
There appears to be mixed opinions and engineering bonding cables.
knowledge as to the practice of installing bonding wires, or to
its relevance in the installation of cable ladder systems. In an effort to find out where this practice may have
developed from, questions that have been asked of electrical
This paper investigates the effectiveness of the current personnel on various sites offered no resolution. Some people,
a minority, believe the earth bonding wire is not required,
Manuscript received April 1, 2010. (Current version published April 1, whereas the vast majority believe it is required. Commonly
2010.) This work was supported in part by Kounis Metal Industries Perth
WA. Paper no. TPMJH201001.
electrical supervisors on site would not approve the installation
and would not allow power to be applied until all cable ladder
Michael J Hamilton is with Langkilde Engineering Services, Perth WA; bonding wires had been installed to all splice joints of cable
138 Burswood Road Burswood WA 6100, PO Box 932 Victoria Park WA
ladder.
6979, Tel: 08 6104 1300, Mob: 0418 277 177, e-mail: michaelh@les-
engineering.com.au.
File Number: TPMJH-201001.
TPMJH-201001 2

metre lengths of cable are given as:

• 16mm2 Copper Cable – 1.15 x 10-3 Ω


• 25mm2 Copper Cable – 7.27 x 10-4 Ω
• Ladder Rail (1.6mm x 130mm) – 0.357 x 10-4 Ω
• Ladder Rail (2.0mm x 130mm) – 0.285 x 10-4 Ω

The change from using 1.6mm ladder to 2.0mm ladder gives


a reduction in resistance by 20%. Similarly a change from
using 16mm2 bonding wire to 25mm2 gives a reduction in
resistance by 37%. For the analysis only 1.6mm type ladder is
considered as this would represent the most commonly used
type of cable ladder, and also give the least improved results.
For simplicity the galvanised coating of the steel has been
ignored.

Fig. 2. Close up of installed cable ladder showing earth bonding cables. Figure 3 shows the splice plate arrangement of two typical
joined cable ladder sections in detail. There are slotted holes
One manufacturer of cable ladder systems in Western
in the splice plate which allow for expansion of the ladder.
Australia, through requests from users and installers of such
Generally expansion is allowed for by leaving a 20mm space
cable ladder, also supplies bonding wires, firstly only with from each end of the cable ladder sections, and with all the
16mm2 cable and later more so with 25mm2 cable, and a
splice plate bolts tightened the ladder will still provide
special bonding wire bolt hole for such bonding wires.
movement during expansion and contraction.
Previously bonding wires had commonly been bolted to one of
the splice plate bolts prior to these specific bonding wire bolt
holes being available.

Generally the final inspection and sign off on an installation


is in the hands of the site electrical supervisor, whom will
often call for bonding wires to be installed to cable ladder
splice sections at all joints. When asked as to their reasoning
behind such an instruction the answer is often because it is
specified, or because it provides a sense of security. No
reference to sound engineering theory or practice was cited.

This paper investigates some theoretical analysis and


various tests on the cable ladder circuit to review the effect on Fig. 3. Picture of cable ladder sections joined with spice plate showing the
resistance with and without the use of bonding wires. earth bonding wire connected.
Assessment is also carried out on the risks that may present,
such as failure of bolts or failure to tighten splice plate bolts The equivalent circuit of the splice section between the
during construction, if there is no bonding earth wire present. joining of two sections of cable ladder is shown in figure 4.
This circuit model is used to determine the Thevenin
III. THEORETICAL ANALYSIS equivalent resistance between the points A and B, which is at
the locations where the bonding wire connects to the ladder.
A. System Components / Component Values
The following naming representation is used:
For the theoretical analysis, the following assumptions are
used for calculations. To determine the resistance of the • R.wire – the bonding wire resistance.
ladder, the steel has been taken as iron with a resistivity of • R.rung – the resistance of the rung section
9.71 x 10-8 Ω⋅m, compared with copper that has a resistivity of between the two side rails.
1.72 x 10-8 Ω⋅m, copper being 5.65 times better than iron. • R.rail – the resistance of the side rail sections.
Note that the area offered by the ladder rail is 272mm2 for • R.sp – the resistance of the splice plate
1.6mm and 340mm2 for 2.0mm, where the 1.6mm rail offers sections.
more than 10 times the area compared with 25mm2 copper • R.gap – the resistance across the 20mm gap
cables. between the two ladder sections,
The resistance values of 1 meter lengths of ladder and 1 relying on the splice plate only.
TPMJH-201001 3

A − B 100
% Improvemen t = × [% ] (1)
A 1

The percentage improvement, taken as the decrease in


resistance across the points for the addition of each cable size
is then:
• With 16mm2 cable – 11.3%, and
• With 25mm2 cable – 16.8%.

Fig. 4. Equivalent circuit of two joined cable ladder sections. A summary of the theoretical values for various widths of
cable ladder are given in Table I.
The resistor ‘R.wire’ between points A and B is the
resistance of a connected bonding wire, whose length is TABLE I
THEORETICAL RESISTANCE VALUES FOR VARIOUS SIZES OF CABLE LADDER
typically 600mm to reach between the two bonding points on WITH AND WITHOUT BONDING WIRE.
each section of ladder. Figure 5 shows the resultant circuit. Resistance b/w
Resistance b/w PERCENT
Ladder Points A and B With
Points A and B IMPROVEMENT
Width Earth Bonding Wire
(µΩ) (%)
(µΩ)
With 16mm2 bonding wire
600 88 78 11.33
300 85 76 11.01
150 81 72 10.51
With 25mm2 bonding wire
600 88 73 16.82
300 85 71 16.36
Fig. 5. Resultant circuit of cable ladder and bonding wire. 150 81 68 15.69

‘R.ladder’ represents the Thevenin equivalent resistance of


the series parallel combinations of the cable ladder and splice From Table I it is seen that the percentage increase is only a
plates. The simplified circuit however does not fully show the small value, which is not providing for much of an
parallel effects of the remaining lengths of ladder. improvement. The decrease in resistance with 16mm2 cable is
only 10 µΩ. Note though that the analysis is performed at
Due to the splice plate having a similar construction to the close proximity to the splice plate section where the effect is
ladder side rail the resistance of the end sections is effectively greatest with regards to the improvement in reducing the splice
halved by the paralleling of both the rail and splice plate. section resistance. Another important point to consider is the
Providing a good low resistance connection is made between end-to-end resistance of the cable ladder system in determining
the splice plate and rail section, the bonding wire in effect is the net benefit of adding a bonding wire, discussed further in
trying to improve on the resistance offered by the splice joint section V.
gap.
However these figures for the ladder are based on assumed
values of the resistivity of the cable ladder and that all joints
B. Theoretical Findings are perfect with no additional resistances, hence to obtain more
meaningful results it is required for actual test data to be
From figure 5 the equivalent resistance across the points A explored and analysed.
and B, R.ladder is determined by calculation to be 88 µΩ.
After adding a bonding wire across the points the effective IV. TESTING OF CABLE LADDER
resistance becomes:
• With 16mm2 cable – 78 µΩ, and
A. General
• With 25mm2 cable – 73 µΩ.

To determine the improvement of adding the bonding wires There are various types of cable ladder in use which are
formula (1) is used to calculate this, where A represents the generally constructed of steel and hot dip galvanised. For the
resistance without bonding wire and B the resistance with a Kounis cable ladder the galvanising is a coating of zinc at 390
bonding wire attached. gm/m2, approximately a thickness of 55µm. These cable
ladder types include:
TPMJH-201001 4

3/50 (NEMA 16A), 1.6mm thickness, 100mm high rails only 2 meters long. The effect this will have on the results will
4/70L (NEMA 20B), 1.6mm thickness, 130mm high rails be to raise the resistance values slightly as paralleling effects
4/70 (NEMA 20B), 2.0mm thickness, 130mm high rails of the ladder are reduced due to the remaining 4 meters of
5/112 (NEMA 20C), 2.0mm thickness, 146mmm high rails ladder not being present.

The most common cable ladder used in mining sites is the


C. Test Results
heavy duty type NEMA 20B. The NEMA 20B to Australian
rated ladder represents the Kounis 4/70L using 1.6mm steel
thickness and 4/70 uses 2mm steel thickness, where the 2mm Tables II and III give the test results from the series of tests
type ladder is being used predominantly in cyclone prone carried out on 600mm wide cable ladder, and Tables IV and V
areas. For the tests the 1.6mm steel ladder 4/70L will be used for 300mm wide ladder. Where tests include an earth bonding
for determining the effect of the bonding wire, as this will be wire, the size of the cable is 16mm2.
more common than with the 2mm ladder construction. Also
the 2mm ladder will give improved results over the 1.6mm
TABLE II
ladder tests. RESISTANCE TEST RESULTS FOR 600MM WIDE LADDER
WITH FINGER TIGHT BOLTS.
The purpose of the testing is to determine the reduction in Bolts Resistance Without Resistance With Percentage
resistance across the splice joint with the addition of the earth Finger Earth Bonding Wire Earth Bonding Improvement
Tight (µΩ) Wire (µΩ)
bonding wire, and to determine if the bonding wire provides an
Bolts In Splice Plate - 1 Side Only
advantage in various scenarios. 4 601.2 532.6 11.41%
3 598.1 534.5 10.63%
B. Method of Testing 2 606.1 536.7 11.45%
1 515.7 540.7 -4.85%
Bolts In Splice Plate – 2 Sides
The measurement points for the tests have been taken at 1 4 573.3 537.7 6.21%
meter distance from each end of the ladder sections with a gap 3 606.9 552.7 8.93%
between the two ladder sections of 20mm as would be 2 630.5 560.7 11.07%
maintained in an installation to allow for expansion. The 1 662.7 603.9 8.87%
measurement points therefore are 2.02m apart.

The removal of bolts is performed by removing the outer TABLE III


bolts and working in a clockwise direction on the left side and RESISTANCE TEST RESULTS FOR 600MM WIDE LADDER
an anticlockwise direction on the right side. Bolts are WITH TIGHTENED BOLTS.

removed from the front and rear splice plate. Where ‘a bolt is Resistance Without Resistance With Percentage
Bolts
Earth Bonding Wire Earth Bonding Improvement
removed’, it refers to one front and one rear bolt being Tight
(µΩ) Wire (µΩ)
removed. Where ‘bolts are removed from one side’ this refers Bolts In Splice Plate - 1 Side Only
to the right side section only, both from the front and back. 4 481.0 472.8 1.70%
3 483.2 474.8 1.74%
The various tests are performed with finger tight and torque 2 489.9 480.8 1.86%
tight bolts. The torque for tight bolts is maintained at 28Nm, 1 496.4 485.5 2.20%
the nominal torque value for 10mm bolts. For the finger tight Bolts In Splice Plate - 2 Sides
bolts, the bolts were screwed to a point where the nut and 4 482.0 472.3 2.01%
washer made contact with the ladder, just nipped up by the 3 485.5 475.5 2.06%
unassisted fingers of one hand. 2 497.4 485.7 2.35%
1 515.8 500.9 2.89%

Each set of the tests were performed without a bonding wire


attached, and then with the bonding wire attached. Where the Table VI shows the results of tests conducted with the full
bonding wire is attached, the bolts securing the bonding wire set of bolts in the splice plates and comparing the use of
are always tightened with a toque wrench. 16mm2 bonding wire with 25mm2.

The tests have been carried out using a Megger digital low Table VII gives results to further tests on independent
resistance meter (Ductor tester) with the measuring current set sections of ladder and earth bonding wire. Due to the
at 10Amps, giving a range of 1.999mΩ and an accuracy of complexity, theoretical values for 1 and 2 meter sections of
±0.2%, ±0.2µΩ. ladder have not been determined.

The tests have been carried out on short lengths of ladder,


TPMJH-201001 5

TABLE IV TABLE VII


RESISTANCE TEST RESULTS FOR 300MM WIDE LADDER COMPARISONS BETWEEN THEORETICAL AND MEASURED RESISTANCE VALUES
WITH FINGER TIGHT BOLTS. FOR SECTIONS OF 600MM WIDE LADDER AND EARTH WIRE.
Bolts Resistance Without Resistance With Percentage Theoretical Measured Percentage
Finger Earth Bonding Wire Earth Bonding Improvement Test Error
Resistance (µΩ) Resistance (µΩ)
Tight (µΩ) Wire (µΩ)
Splice Plate 230.6 216.8 5.98%
Bolts In Splice Plate - 1 Side Only
600W Ladder Not Determined 354.4
4 534.1 510.4 4.44%
(1m)
3 537.8 511.1 4.96%
600W Ladder Not Determined 629.0
2 544.6 515.3 5.38%
(2m)
1 543.1 511.9 5.74%
300W Ladder Not Determined 323.5
Bolts In Splice Plate - 2 Sides
(1m)
4 530.0 504.2 4.87%
300W Ladder Not Determined 580.7
3 549.6 512.1 6.82%
(2m)
2 582.3 525.0 9.84%
16mm2 Earth 736.0 699.5 4.96%
1 610.1 542.8 11.03% Wire
25mm2 Earth 461.6 476.0 3.12%
Wire

TABLE V
RESISTANCE TEST RESULTS FOR 300MM WIDE LADDER
WITH TIGHTENED BOLTS.
D. Summary of Results
Resistance Without Resistance With Percentage
Bolts
Tight
Earth Bonding Wire Earth Bonding Improvement The results show that between 300mm ladder and 600mm
(µΩ) Wire (µΩ) wide ladder, the percentage improvements with the bonding
Bolts In Splice Plate - 1 Side Only
wire attached are similar and as such further comparisons will
4 453.4 446.0 1.63%
refer only to 600mm ladder as this is the most common type
3 456.1 447.6 1.86%
used. The 300mm wide ladder tests give better results due to
2 462.7 454.0 1.88%
1 469.4 458.5 2.32%
the reduction in rung resistance, and are provided only for
Bolts In Splice Plate - 2 Sides reference.
4 453.4 446.0 1.63%
3 457.4 449.8 1.66% From the results it can be seen that the measurements taken
2 470.5 461.8 1.85% are as expected, as bolts are removed the resistance across the
1 484.1 471.4 2.62% splice increases. The addition of the earth bonding wire in the
case for finger tight bolts provides a reasonably consistent
value as bolts are removed from the one side. As bolts are
TABLE VI removed from both sides of the splice plate the resistance
MISCELLANEOUS TESTS FOR SECTIONS OF LADDER. varies considerably, indicating that the splice plate is
Measured Measured Percentage providing the majority of conductivity.
Resistance with Resistance with Improvement
Test
16mm2 Bond wire 25mm2 Bond wire
(µΩ) (µΩ) Interestingly the finger tight tests provided a low resistance
600mm, 524.9 537.7 2.44% value without the bonding wire and with only a small
Finger improvement of around 10 to 11% with the bonding wire
Tight Bolts attached. The case of torque bolts shows that the splice plate
600mm, 472.8 469.6 0.67%
Tight Bolts
provides a very low resistance, and little improvement was
300mm, 448.3 445.2 0.69% measured with the addition of the bonding wire, around 1.74%
Tight Bolts with all tightened bolts. The use of a larger bonding wire
25mm2 also proved little advantage in reducing the effective
resistance, as the percentage improvement is only 0.7% against
using the 16mm2 wires.

Comparing the measurements between a straight 2m length


of ladder, at 629.0 µΩ to the tested joint section without a
bonding wire of 481.0 µΩ, shows that the tested splice section
has less resistance than a nominal section of ladder, this can be
attributed to the paralleling effect of the splice plate with the
ladder rail sections. Also comparing a length of ladder with
copper cable shows that a one meter length of cable ladder has
less resistance than a 600mm length of cable, 16mm2 or
TPMJH-201001 6

25mm2. In fact the resistance of ladder would be comparable [R splice ] [ ] (3)


+ (L ⋅ Rladder ) − Rsplice||wire + (L ⋅ Rladder )
to copper cable a little greater than 50mm2. If the resistance of %I =
the splice section under test is compared, we obtain a cable Rsplice + (L ⋅ Rladder )
that would be equivalent to almost 95mm2 copper cable.
From (3) it can be shown that as L is increased then the
V. DISCUSSION addition of Rsplice and Rsplice||wire is significantly reduced. If this
theory is applied to two infinite lengths of ladder joined
A. General together, then as the test points are taken to infinity, the
improvement by equation (3) would reduce to zero.
Theoretical results show that the bonding wire has a small
advantage, around 15% in reducing the resistance at the splice For the case where two 6m ladder sections are connected
section, however this result is only based on using an isolated with a splice plate and comparing the resistance from each
section of ladder, localised at the splice joint. This is only end, i.e. 12m apart with and without the earth bonding wire we
across a short distance of 540mm, not a complete ladder obtain the following resistances.
length.
With no bond wire – 3,705.8 µΩ
The findings presented from the testing shows that the With bonding wire – 3,697.6 µΩ
bonding wire provides almost no value in reducing the
resistance across the splice plate; however this testing is Then using (1) the improvement calculated by adding the
performed over an increased distance of 2 meters compared bonding wire is 0.22%, a very small improvement. Conversely
with the theoretical result. Further, the effectiveness should be if we look at conductance instead of resistance, taking the
calculated over complete lengths of ladder which are joined inverse of the above values and calculating the improvement
together to obtain a better representation. To determine how using (1) in terms of conductance we obtain;
the testing point locations affects the results a look at end to
end resistance is required. With no bonding wire – 3,705.8 µΩ ⇒ 269.847 Siemens
With bonding wire – 3,697.6 µΩ ⇒ 270.445 Siemens
B. End to End Resistance
The improvement by adding the bonding wire is 0.598
End-to-end resistance refers to the location of the measuring Siemens, the percentage improvement however remains the
points along the length of the ladder system and the effect that same at 0.22%, as the value of change remains proportional,
this has when the test points are moved further away from the the percentage improvement anyhow is basically zero.
splice plate location. Thus assuming a linear resistance value
per meter for the ladder section and another value for the C. Risk of Splice Joint Failure
splice section, located within a small bounded region, and then
comparing this with installing a bonding wire to further reduce To look at the risk associated with not having a bonding
the resistance of the splice region. wire attached the following assumption is made; the splice
joint provides no benefit, hence the reason for the bonding
The effect then of end-to-end resistance is the change in wires. The risk is that the cable ladder earthing system fails to
resistance as measured as the points are moved outwards from provide a continuous earth path.
the centre, and as a result the resistance increases due to the
linear addition of the ladder length the further the It appears reasonable to argue that a failure might be
measurement points are moved away, and as such the rendered by 3 possible events; corrosion induced – fracture
advantage (reduction in resistance) of the bonding wire and failure of a bolt or bolts – a bolt or bolts that have come
becomes less the further the measurement points are moved loose, any of which would then allow the splice plate and rail
out. This is further shown by formula (2). to open up, all 3 events then leading to a high resistance joint
and therefore reducing the conductivity of the ladder system.
R total = Rsplice + (L ⋅ Rladder ) (2)
Where; The probability of a failure of one bolt or bolts (be it a
L = length of ladder minus splice [m] bonding wire bolt or a splice plate bolt) is difficult to
Rladder is for a 1m section determine and a figure is not assumed, rather one method is
compared to another. If a system is relied on with a single
Combining (1) and (2) to obtain (3). bonding wire then if a single bolt fails, the complete earthing
system fails. However if two bonding wires are installed, one
on each of the side rails, then the probability would be halved,
assuming the events are independent, in other words, would be
TPMJH-201001 7

considered twice as unlikely to fail compared with the single For rigid splice plate connections of materials and finishes
wire bonding method. other than aluminium or galvanised steel, bonding jumpers
may be required. For example, stainless steel splice plates may
For the case where splice plates are deemed suitable and no require bonding jumpers depending UL Classification.”
bonding wires exist then there are 8 bolts in each splice plate,
thus for a ladder splice there are 16 bolts in total making an Section 4.8 – Bonding to steel and earth;
earth connection. If for the worst case bolts failed only on one “Metallic cable trays shall be bonded to building steel and
side, 8 bolts for a total failure then the probability of this earth as supplemental grounding for ground fault protection
system failing would be 8 times less likely to fail than for the and signal grounding (noise prevention). The tray shall be
first case relying on a single bonding wire. The splice method bonded to building steel and earth, at least every 18m (60 ft).
is therefore offering very good odds against a failure of the This is only required when cable tray system is not inherently
earthing system. bonded (connected) to building steel and earth metallic
support systems”.
For the case where cable ladder is purposely broken, then if
two bonding wires are installed, one to each side rail, the NFPA 70 Article 392.7 (B) states;
probability of a complete failure is less likely by a factor of “Steel or aluminium cable tray systems shall be permitted to
two. Thus this would be a preferred method for bonding and be used as equipment grounding conductors, provided all the
earthing in this situation due to the reduced risk involved. following requirements are met:” Specifically part (4) states,
“Cable tray sections, fittings, and connected raceways are
It would be very unlikely that a bolt would fail under normal bonded in accordance with 250.96, using bolted mechanical
conditions, correctly tightened and with minimal vibration. connectors or bonding jumpers sized and installed in
However failure may be caused by the following; over-torqued accordance with 250.102.”
bolts at installation that later fail due to vibration; bolts that
had not been tightened (i.e. finger tight) during installation and Cable Tray Institute, Technical Bulletin Number 8, Titled
later falling out; corrosion or build up at the splice joint due to ‘Bonding Jumpers Not Required for Standard Cable Tray
chemicals or mineralised water if the cable ladder has been Splice Plates’ states;
installed in severe environments. “It is not necessary to install bonding jumpers in parallel
with the standard rigid aluminium or steel one-piece metallic
The risk of a bolt failure is significantly small under normal bolted side rail splice plates that are the connections between
conditions, and can be reduced, by proper tightening and the tray sections. Here, the use of bonding jumpers does not
verification, routine inspection and maintenance which would make a safety contribution to a properly installed cable tray
also affect any bonding wires being used. system, and wastes both materials and labour.”

VI. PROBING FURTHER From the above excerpts it is clear that other standards do
not require cable ladder to have additional bonding using earth
Investigating other practices from standards of other wires, and in the case of NFPA and NEC actually allows the
organisations gives the following: use of cable ladder as an earthing conductor to earth
equipment back to the main earth.
NEMA standard VE 2 Section 4.7.1 Cable tray used as an
Equipment Ground Conductor (EGC) states the following; VII. CONCLUSION
“The use of aluminium and steel cable trays is permitted as
an Equipment Grounding Conductor per NEC Article 392 For the tested galvanised steel cable ladder, it is concluded
when labelled and marked with the available cross sectional that bonding wires are not required to bond across the standard
area. (See Table 4-4.) If the cable tray is to be used as an EGC, splice plates, as the benefit of such a practice is negligible and
bonding jumpers must be installed on both side rails at the provides no addition safety merits.
locations illustrated in figures 4.57 through 4.60, unless the
splice plates meet the electrical continuity requirements of As for not installing bonding wires, the risk is very low due
NEMA VE 1. See table 4-5 for minimum sizes of grounding to the large number of bolts being used in the splice plates.
conductors.
If the connectors are UL Classified bonding jumpers or a The most important bonding connection is the connection of
continuous ground are not required. the cable ladder system to the main earth. Splice plate
It is not necessary to install bonding jumpers at standard bonding wires need only be installed where gaps have been left
rigid aluminium or galvanised steel splice plate connectors or in the cable ladder to reinstate a continuous earthed ladder
offset reducing splice plate connectors or any UL Classified system.
connectors.
TPMJH-201001 8

VIII. PROPOSED INSTALLATION PRACTICE

In light of the findings from the results of cable ladder


testing, discussions and further information, the following
points are put forward as proposed installation guidelines for
installing cable ladder.

• Cable ladder shall be earthed back to the main earthing


system via two main earth conductors, or via one earth
conductor with a loop installed to each side rail.
Fig. 7. Cable tray sections, horizontal adjustable splice plate showing
• Bonding between cable ladder sections is provided with bonding wires.
the slice plates and no additional earth wire conductors
are required. ACKNOWLEDGMENT
• Where cable ladder sections are separated and are not
joined via splice plates, two off earth conductors shall The author thanks Kounis Metal Industries and David
be provided to maintain a continuous earth. Kounis, Sheet Metal Manager for providing cable ladder,
• Where expansion gaps or sliding expansion joints are premises, materials and test equipment for performing the tests
used a bonding earth wire shall be installed to maintain required for the paper.
a continuous earth.
• Where adjustable splice plates are used, these shall REFERENCES
include an earth bonding cable unless the plates meet
continuity requirements, (as per NEMA Standard VE [1] AS3000-2009 - The wiring Rules.
1). [2] NEMA Standard VE 2-2006 – Cable Tray Installation Guidelines.
• Develop/use a testing or inspection procedure to ensure [3] NEC NFPA 70-2008 (Article 392)
[4] Olex Cable Handbook.
that spice plate bolts have been tightened correctly after [5] Web – Cable Tray Institute – Cable Tray Installation.
installation has been completed. [6] Cable Tray Institute, Rosslyn, Virginia USA, Technical Bulletin
Number 8.
The figures 6 and 7 show earth bonding requirements for the [7] Cooper B-Line Cable Tray Manual.

types of ladder splice plates; adjustable vertical plates, and


horizontal adjustable plates. These require bonding wires as Michael J. Hamilton (M’98) received the bachelor of engineering degree
they would not offer good conductivity due to the hinged with honours in electrical engineering from Curtin University of Technology
of Perth WA, Australia, in 2000.
joints, and use of only one bolt. He is currently Senior Electrical/Controls Engineer for Langkilde
Engineering Services an engineering company located in Burswood, Perth,
Western Australia. His previous work experience includes Electrical
Engineer positions at EPCM companies and site positions in engineering and
maintenance departments within the mining industry at BHP Billiton Iron Ore
Port Operations, Western Mining (WMC) Nickel Smelter Operation and
Goldfields Australia, St Ives Gold Operation.
Mr. Hamilton is member of IEEE and a committee member of the
Goldfields Electrical Industry Group situated in Kalgoorlie. He was a
recipient of the Best Student Paper Award from the IEEE Power Engineering
Society in 1999.

Fig. 6. Cable tray sections, vertical adjustable splice plate showing bonding
wires.

Você também pode gostar