Aquastat Controllers ®
Installation 3
INSERTION
Operation
1 ELEMENT
For proper selection of settings, follow the boiler manu-
facturer recommendations.
High limit controller—shuts off burner when water tem-
1 WITH VERTICAL MOUNTING OF IMMERSION WELL,
ELEMENT IS ATTACHED TO BOTTOM OF THE CASE.
perature exceeds high limit setting. Burner restarts
when temperature drops to high limit setting, less
2 SELECT MODELS HAVE SCREW TERMINAL, NOT TAB
TERMINAL. M8806 differential.
Low limit controller—maintains minimum boiler tem-
perature for domestic hot water. Turns on burner at
INSTALLING DIRECT IMMERSION MODELS temperature setting, minus differential.
(L6006B) Circulator controller—prevents circulation of water that
Install fitting in boiler tapping as follows: is not hot enough. Breaks circulator circuit at tempera-
1. Be sure sealing washer is in place as shown in Fig. 3. ture setting minus differential; remakes the circuit
Make sure that spud of capsule compression fitting is screwed when the temperature setting is reached.
in tightly enough to prevent leaking.
2. Insert immersion bulb (sensing element) through cap- Switching action is as follows:
sule compression fitting. Adjust the adapter clamp so that it Upon a drop in boiler water temperature (to dial setting,
fits over the groove at the opening of the capsule compres- less differential), makes R to B burner contact; breaks R to W
sion fitting. contact, preventing circulator operation. Upon a rise in boiler
3. Tighten adapter clamp screws so the Aquastat® Con- water temperature (to dial setting), breaks R to B burner
troller is firmly attached to the capsule compression fitting. contact, makes R to W circulator contact.
95-5973—3 2
Adjustment Fig. 4—Mounting L6006C on pipe or tank.
ADAPTER
CLAMP
AQUASTAT®
SPLIT SLEEVE CONTROLLER
CASE
M8771
ADAPTER CLAMPS
FIT OVER
GROOVE
1
BULB COMPRESSION
FITTING
2 L6006 OR L6007
M8774
IGNITION CIRCULATOR
SENSING BULB AND LOW
4 LIMIT CONTROL
SWITCHING RELAY
3 W
T R
T B 2 3
L1
CIRCULATOR (HOT)
BURNER
L2
MOTOR
LINE VOLTAGE 1
LOW VOLTAGE
3 95-5973—3
Fig.6—Typical wiring hookup using L6006 and Checkout
L6007 with L8148A.
SERIES 80
THERMOSTAT Check to make certain that the Aquastat® Controller is
L1 L2 installed and adjusted properly. Put the system into operation
(HOT)
L6006, L6007
1 and observe the action of the device through several cycles to
CIRCULATOR AND make certain that it provides proper low and/or ligh limit and
LOW LIMIT
CONTROL R
circulator control.
L1 L2 T T
2 W 3
B B
L8148A
R
2
C1 C2 B1 B2
1 2
CIRCULATOR
1 2 1 2
Home and Building Control Home and Building Control Helping You Control Your World
Honeywell Inc. Honeywell Limited—Honeywell Limitée
1985 Douglas Drive North 740 Ellesmere Road
Golden Valley, MN 55422 Scarborough, Ontario
M1P 2V9 QUALITY IS KEY
95-5973—3
Printed in U.S.A. 4