Você está na página 1de 9

International Journal of Heat and Mass Transfer 53 (2010) 5355–5363

Contents lists available at ScienceDirect

International Journal of Heat and Mass Transfer


journal homepage: www.elsevier.com/locate/ijhmt

Reliability of material data measurements for hygroscopic buffering


Staf Roels a,*, Prabal Talukdar b, Chris James c, Carey J. Simonson d
a
Laboratory of Building Physics, Katholieke Universiteit Leuven, Kasteelpark Arenberg 40, B-3001 Leuven, Belgium
b
Department of Mechanical Engineering, Indian Institute of Technology Delhi, New Delhi 110016, India
c
Saskatchewan Research Council, 125 – 15 Innovation Blvd., Saskatoon, SK, Canada S7N 2X8
d
Department of Mechanical Engineering, University of Saskatchewan, 57 Campus Drive, Saskatoon, SK, Canada S7N 5A9

a r t i c l e i n f o a b s t r a c t

Article history: Numerical models of heat, air and moisture (HAM) transport in building components continue to
Received 25 September 2009 advance, but the reliability of the measured material properties, which serve as input for the HAM-mod-
Received in revised form 7 June 2010 els, remains very uncertain. In the framework of IEA/ECBCS Annex 41 a round robin experiment on the
Accepted 7 July 2010
determination of the hygric properties of porous building materials was performed to generate a dataset
Available online 11 August 2010
for benchmarking numerical models. In the round robin experiment, 14 laboratories measured the
vapour permeability and sorption isotherm of coated and uncoated gypsum board. Apart from a zero
Keywords:
off-set due to different conditions during oven-drying, the measured sorption isotherms showed accept-
Sorption isotherm
Vapour permeability
able agreement. But for the vapour transmission tests, though performed according to an international
Round robin testing standard, a wide spread in the measured data was found. The differences are most pronounced for vapour
Gypsum board tight specimen. The large number of participants in the round robin experiment, allowed to investigate
Moisture buffering possible causes for the observed deviations. To show the importance of correct material data, the conse-
quences of using this kind of contradictive results was investigated by calculating the impact on the
moisture penetration depth and equivalent moisture capacity.
Ó 2010 Elsevier Ltd. All rights reserved.

1. Introduction experiments in the literature are conducted on non-hygroscopic


materials, where a majority of the moisture accumulation is due
As computing power increases and numerical models for whole to condensation and frosting near a cold surface. Furthermore, in
building heat, air and moisture (HAM) transfer advance, there many cases the thermal transients dominate the problem. To
remains a general need for more experimental data that quantify benchmark models that intend to consider moisture buffering of
HAM transport in porous building materials. For example, recent hygroscopic materials in contact with indoor air, experimental
benchmark data for validating 1-D HAM simulation models pro- data are needed where the air humidity is changed in a transient
duced in a large international project [1] rely solely on numerical manner as presented in this study.
and analytical data because well-documented and accurate 1-D Within Subtask 2 of IEA/ECBCS Annex 41 [15,16] experimental
data are scarce. In IEA/ECBCS Annex 41 [2] numerical models have and numerical data for 1-D heat and moisture transfer in a bed
been used to simulate heat and moisture transfer between indoor of gypsum board were compared. Comparing the numerical and
air and hygroscopic materials during transient changes in indoor experimental data serves a dual purpose of validating the numer-
humidity because previous studies have shown that moisture buf- ical models as well as confirming the experimental data. However,
fering may improve comfort, air quality and energy consumption as previous research e.g. [17–19] showed that apart from the lack
in buildings [3–8]. To validate models that simulate moisture buf- of good benchmark cases, also attaining uniformity in measuring
fering of hygroscopic materials, new experimental data are needed material properties remains difficult, it was decided to perform
that accurately quantify heat and moisture transfer between first an inter-laboratory comparison of the measurement of the
humid air and hygroscopic materials during transient changes in hygric properties of porous materials by means of a round robin
the air humidity. Experimental data are available in the literature, test. Not all material properties have been measured, but the round
but most data are not well suited to benchmark detailed numerical robin focussed on those properties relevant for indoor moisture
models because carefully planned laboratory experiments are best buffering: the water vapour transmission properties and the sorp-
suited for model validation [4,6,9–14]. In addition many of the tion isotherm. Both material properties are based on common
measuring techniques, even described in international standards,
* Corresponding author. Tel.: +32 16 321349; fax: +32 16 321980.
but nevertheless an unacceptable spread in results was found. In
E-mail address: staf.roels@bwk.kuleuven.be (S. Roels). total 14 laboratories participated in the round robin test. The paper

0017-9310/$ - see front matter Ó 2010 Elsevier Ltd. All rights reserved.
doi:10.1016/j.ijheatmasstransfer.2010.07.020
5356 S. Roels et al. / International Journal of Heat and Mass Transfer 53 (2010) 5355–5363

Nomenclature

A surface area of finishing material (m2) V volume of the room (m3)


b width of the masked edge (m)
Cme correction factor for the masked edge () Greek symbols
d thickness of the specimen (m) d water vapour permeability (s)
db depth of humidity buffer layer (m) l water vapour resistance factor ()
gv (vapour) flux (kg/m2 s) q density (kg)
m weight of the specimen (kg) n moisture capacity with respect to relative humidity (kg/m3)
pv vapour pressure (Pa) U relative humidity ()
Rv gas constant of water vapour (462 J/kg/K)
S hydraulic diameter (m) Subscripts
sd equivalent air layer thickness (m) o dry (weight)
T temperature (K) sat saturated (vapour pressure)
tp period of humidity variations (s) v vapour
u moisture content mass per mass (kg/kg) w wet

starts with a description of the test materials and test series. Then 3. Water vapour transmission test
the results of the measured data are compared and discussed and
the consequences of using this kind of contradictive results when A water vapour transmission test is a standardised method
simulating hygroscopic buffering is elucidated. Finally, the most [21,22] to characterise a porous material with respect to water va-
reliable data is transformed into analytic expressions that can be pour diffusion. It is commonly referred to as cup-method, because
used in numerical HAM-models. Comparison of the numerical pre- the general measuring principle is sealing a vapour tight cup con-
dictions using this input data with the results of a dynamic hygric taining a desiccant or saturated salt solution, with the test mate-
loading experiment is presented in [20]. rial. The desiccant or saturated salt solution will realise a
constant relative humidity below the sample and when the cup
is then placed in a test chamber at constant temperature but at dif-
2. Test materials and test series ferent relative humidity (RH) than the one in the cup, a vapour
pressure gradient is realised across the specimen. Regular gravi-
The ECBCS Annex 41-project of the International Energy metric measurements of the cup are used to determine the weight
Agency focused on indoor hygric buffering. Therefore, a finishing gain (or loss) of the cup and hence the moisture flux gv (kg/m2 s)
material (gypsum board) was selected as test material and the through the specimen. Assuming that the whole process can be de-
material was measured both uncoated and finished with a prim- scribed by Fick’s law for vapour diffusion the water vapour perme-
ing coat and two kinds of finishing coats. As will be shown fur- ability d (s) of the material can be determined. In Europe the
ther, the applied coat will significantly change the material vapour permeability is usually replaced by the vapour resistance
properties, enlarging the relevance of the round robin experi- factor l () or equivalent air layer thickness sd (m) as typical va-
ment as similar results can be expected for all kind of porous pour transfer property of the building material:
building materials. Due to the large number of participants in dDpv da Dpv da Dpv
the project, no real round robin was performed, but samples of gv ¼ ¼ ¼ ð1Þ
d ld sd
the same batch were randomly distributed among the participat-
ing laboratories. The gypsum board and primer have been sup- with Dpv (Pa) the difference in vapour pressure at the opposite sides
plied by GYPROC BPB, Belgium. The gypsum board is from the of the specimen, da (s) the water vapour permeability of stagnant air
type ‘GYPROC A ABA-board’ with overall dimensions of and d (m) the thickness of the specimen. Note that in Eq. (1) the va-
1200  2400 mm2 and a thickness of 12.5 mm. For the finishing pour resistance of the stagnant air layers below and above the spec-
coats two types, labelled A and L, have been used. Both were imen are neglected.
supplied by BOSS Paints, nv Bossuyt, Belgium. Finishing coat A is
an acrylic paint (type Decomat, BOSS paints) and is coloured 3.1. Test method and test conditions
light blue. Finishing coat L is a latex paint (Bolatex, BOSS paints)
and is coloured light yellow. For the current round robin experiment, the water vapour
Three test series have been measured: (1) the uncoated gypsum transmission properties have been determined in accordance to
board; (2) the gypsum board covered with the priming coat and ac- EN ISO12572:2001 Hygrothermal performance of building materials
rylic finishing coat A; (3) the gypsum board covered with the prim- and products – determination of water vapour transmission proper-
ing coat and latex coat L. This series allows one to assess the ties. A complete description of the test method and procedure
reliability of the measurement of the vapour permeability of a can be found in [22]. All three test series (the uncoated gypsum
layer of paint. In total 20 plates of gypsum board (2400  1200 board, the gypsum board covered with primer and paint A and
 12.5 mm3) have been cut in different parts of 500  300 mm2. the gypsum board covered with primer and paint L) were mea-
All parts were labelled. To randomise the test samples as much sured at three test conditions as given in Table 1. Test condition
as possible, parts from different boards were sent to each partner. C1 and C2 of Table 1 correspond, respectively, to set A and set C
Each partner cut specimens from these parts in such a way that for in Chapter 7.1. of European standard [22]. Test condition C3 was
each material property, specimens of different boards are mea- included to allow an analytic fit to the measured data, which could
sured. For series 2 and 3, the priming coat and finishing coat were be used in the benchmark for the numerical models [20]. If CaCl2-
applied with a paint roller by the University of Leuven and the flocks were used as desiccant in test condition C1, it was asked to
painted gypsum board samples were distributed among all make sure to start from fully dried (at 200–250 °C) flocks as previ-
participants. ous studies showed that it is difficult to maintain 0% RH within the
S. Roels et al. / International Journal of Heat and Mass Transfer 53 (2010) 5355–5363 5357

Table 1
Test conditions for the determination of the water vapour transmission properties.

Set Conditions (°C–RH) Temperature (°C) Relative humidity


Climatic chamber Cup
C1 23–0/50 23 ± 0.5 Aqueous solution 53% Desiccant
Mg(NO3)2 CaCl2-flocks or Mg(ClO4)2
C2 23–50/93 23 ± 0.5 Aqueous solution 53% Aqueous solution 94%
Mg(NO3)2 KNO3
C3 23–86/93 23 ± 0.5 Aqueous solution 85% Aqueous solution 94%
KCl KNO3

cup [23,24]. Specific prescriptions for the preparation and more de- creases with increasing relative humidity. This feature is far more
tails on the applied test assemblies can be found in [15]. pronounced for the latex coat than for the acrylic coat. Compared
to the uncoated gypsum board where the wet cup value of the
3.2. Main results equivalent air layer thickness (test condition C3) is ±70% of the
dry cup value, a reduction with almost a factor three is found for
The results of the water vapour transmission tests are presented the acryl coat and a reduction with a factor seven for the latex coat.
as equivalent air layer thickness (sd-values in m). Fig. 1 shows the As can be seen in Fig. 1, when comparing the results of the dif-
mean values as measured by the different participating laborato- ferent laboratories, the data show remarkable high differences.
ries as a function of relative humidity for the three test series when Knowing that the measurements are carried out according to the
no corrections for the air layers or for the masked edge are per- prescriptions of an existing standard, unacceptable deviations are
formed (see Section 3.3). Fig. 2 shows the probability density func- found. Furthermore, the more vapour tight the specimen is (dry
tions of the same results with error bars, indicating the maximum cup values of gypsum board covered with latex coat), the more
and minimum values measured by each lab. The uncoated gypsum pronounced the differences become.
board is found to be very vapour open. In fact, only the dry cup va- Remarkably is that, when comparing the individual results of
lue (test condition C1) exceeds an equivalent air layer thickness of each of the laboratories (see horizontal minimum–maximum bars
0.1 m, the criterion used in the standard as minimum value to in Fig. 2), the deviations are most of the time much smaller than
make cup tests applicable due to the increasing uncertainty on the deviations between the laboratories. This suggests that there
the measurement results for more vapour open materials. Applying could be systematic differences between the participating labora-
a primer and finishing coat on the gypsum board changes the va- tories. However, when plotting the data of the three test series ver-
pour permeability considerably, but the type of coat seems to be sus one another, no indication for systematic differences between
very important. Applying an acryl finishing coat triples the equiv- the participating laboratories could be found. This can be seen in
alent air layer thickness (mean value of all laboratories for test con- Fig. 3, which plots as an example, the sd-value measured for the
dition C1), while the latex coat multiplies the equivalent air layer dry cup conditions on the latex coated gypsum board as a function
thickness with almost a factor 30! But, the dependency of the va- of the value measured by the same laboratory on the acrylic coated
pour permeability on relative humidity is far more pronounced for gypsum board.
the coated gypsum board than for the uncoated gypsum board. Put
otherwise, the vapour resistance of the finishing coat strongly de- 3.3. Discussion

The results presented in Figs. 1–3 correspond to uncorrected


10 data. Depending on the test set-up assembly two types of correc-
tions are required. According to Annex G of the European standard
latex coated
[22] a correction for the vapour resistance of the layer of air in and
equivalent air layer thickness (m)

above the cup has to be applied for very permeable materials. Paz-
era and Salonvaara [23] also stress this issue when dealing with va-
1 pour open materials. In the European standard, very permeable
acrylic coated materials are defined as materials with an equivalent air layer
thickness less than 0.2 m. This is the case for the uncoated gypsum
board and for the gypsum board with acrylic finishing coat under
test condition C2 and C3. (Note that for uncoated gypsum board
uncoated only test condition C1 is within the scope of the standard.)
0.1
For the air layer in the test cup, the measured permeance has
to be corrected with the permeance of the stagnant air layer in
the cup. Since most of the laboratories followed the prescriptions
very well, which stated that the air space between the desiccant
or aqueous solution and the specimen had to be within the range
0.01 of 15 ± 5 mm, all correction are in the same order of magnitude.
0 20 40 60 80 100 In this way applying a correction for the air layer in the cup just
relative humidity (%) reduces the calculated equivalent air layer thickness (mean value
after correction 0.107 m instead of 0.128 m), but has hardly any
Fig. 1. Mean values of the equivalent air layer thickness as determined by the difference on the spread in the results. To ensure that the resis-
participating laboratories for uncoated, acrylic coated and latex coated gypsum
board. The continuous lines correspond to the analytic expression used for the
tance of the air layer above the cup is negligible, [22] requests
numerical simulations (see Section 5). Note that, the equivalent air layer thickness that the air in the test chamber is well mixed and to ensure an
is plotted on a logarithmic scale. air velocity above each specimen of at least 2 m/s. Furthermore,
5358 S. Roels et al. / International Journal of Heat and Mass Transfer 53 (2010) 5355–5363

0.75

probability (-) 0.5

test condition C1: 0/50 % RH


0.25 test condition C2: 50/93 % RH
test condition C3: 86/93 % RH
UNCOATED GYPSUM BOARD
0
0.00 0.05 0.10 0.15 0.20 0.25 0.30
1

0.75
probability (-)

0.5

test condition C1: 0/50 % RH


0.25 test condition C2: 50/93 % RH
test condition C3: 86/93 % RH
GYPSUM BOARD with ACRYLIC COAT
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70
1

0.75
probability (-)

0.5

test condition C1: 0/50 % RH


0.25 test condition C2: 50/93 % RH
test condition C3: 86/93 % RH
GYPSUM BOARD with LATEX COAT
0
0.00 1.00 2.00 3.00 4.00 5.00
equivalent air layer thickness (m)

Fig. 2. Cumulative distribution function of the mean values of the equivalent air layer thickness as determined by the participating laboratories for uncoated (top), acrylic
coated (middle) and latex coated (bottom) gypsum board. The error bars indicate the minimum and maximum value measured by the laboratory.

it is advised to use cups without a high rim. For most laboratories Some participants use cup types with ‘masked edges’, which
the air velocity in the test chamber is much lower than 2 m/s means that the edge of the specimen overlaps the edge of the
[15]. Moreover, different types of cups have been used, some with cup. This overlap zone is a possible route for two dimensional va-
and others without a rim. To investigate the possible influence of pour transfer, leading to an overestimate of the vapour permeance,
the air velocity in the test chamber, the measured equivalent air since the total flow through the specimen in the test assembly is
layer thickness as measured by the participating laboratories is greater than that through the exposed area of the specimen. Annex
plotted as a function of air velocity above the cups. Fig. 4 shows F of EN ISO12572:2001 proposes a correction if a masked edge is
the data for test condition C1 (dry cup) for uncoated gypsum present. This is done by dividing the measured vapour flow with
board and for gypsum board coated with an acrylic paint. No sig- a correction factor Cme:
nificant correlation can be found. Also, concerning the type of  
4d 2
cups, no correlation could be found between the measured values C me ¼ 1 þ ln ð2Þ
and the presence of a rim.
pS 1 þ expð2pb=dÞ
S. Roels et al. / International Journal of Heat and Mass Transfer 53 (2010) 5355–5363 5359

5.0 tor of 10 (between 0.4 and 4.3 m)! Since this is the most vapour
tight material, a possible explanation could be leakage through
the seal. To investigate this, Fig. 5 replots the probability function
4.0 of the measured mean values, with the type of seal indicated. Ex-
latex coated gypsum board

cept for two outliers, cups with a wax seal seem to perform much
2
better than all other kinds of seals. The lowest value of the two out-
R = 0.2538 liers corresponds to a special way of sealing where the wax is
3.0
poured into a collar. The second outlier, with a value of 2.2 m cor-
responds to a mean value of two measurements around 3.4 m and
three measurements around 1.4 m. So, there it seems that the seal
2.0 is imperfect for three of the five cases.

1.0 4. Sorption isotherm

In addition to the water vapour permeability, the sorption iso-


therm of the gypsum board was measured as part of the round ro-
0.0
bin experiment. The sorption isotherm, or hygroscopic curve,
0.2 0.3 0.4 0.5 0.6 describes the relation between moisture content and relative
acrylic coated gypsum board humidity for open porous materials. If these materials – starting
from dry state – are exposed to moist air, moisture is adsorbed
Fig. 3. Equivalent air layer thickness (m) measured for the dry cup conditions on
at the inner surface of the pores, resulting in an increase of the
the latex coated gypsum board plotted as a function of the value measured by the
same laboratory on the acrylic coated gypsum board. weight of the material. This sorption process can be identified by
two phenomena: molecular mono- and multilayer surface adsorp-
tion in the lower relative humidity range, and capillary condensa-
0.6 tion in the relative humidity range above approximately 40%. Both
phenomena combined are described by the sorption isotherm. The
uncoated gypsum board
measured sd-values dry cup (m)

general principle for the determination of the sorption isotherm is


0.5 gypsum board with acrylic coat conditioning specimen at different relative humidity and gravimet-
rically determining the equilibrium moisture content at each rela-
0.4 tive humidity. Due to hysteresis effects ad- and desorption
measurements result in different sorption isotherms.

0.3
4.1. Test method and test conditions

0.2 Since the hygroscopic behaviour of the finishing paint is in the


precision range of most weighing devices, it was decided to deter-
0.1 mine the sorption isotherm only on the uncoated gypsum board.
For the determination of the isothermal adsorption curve initially
oven dried samples had to be conditioned at different relative
0.0 humidities and at constant temperature until a static sorption
0 0.5 1 1.5 2 equilibrium was attained between the relative humidity of the
air velocity above cup (m/s) environment and the moisture content of the specimen. Equilib-
rium between moisture content and relative humidity is defined,
Fig. 4. Influence of the air velocity above the cups on the measured equivalent air in this paper, when repeated weighing, at intervals of at least
layer thickness of uncoated gypsum board and gypsum board with an acrylic one week, show a difference in mass of 0.1% or less. The equilib-
finishing coat for test condition C1 (dry cup).
rium moisture content mass by mass u (kg/kg) of the specimens
is calculated as

The correction factor depends on two ratios: the width of the u ¼ ðmw  mo Þ=mo ð3Þ
masked edge b (m) divided by the thickness of the specimen d
(m) and the thickness of the specimen d divided by the hydraulic with mw (kg) the mass of the moist specimen and mo (kg) the mass
diameter S (m) of the specimen. Since the gypsum board is only of the specimen in dry state. To control the relative humidity of the
12.5 mm thick, the effect of the masked edge is limited. For the environment, the samples were placed in desiccators that contain
cup assemblies with the most extreme masked edge (a square different aqueous solutions. To control the temperature, the desic-
cup with a masked edge of 21% of the exposed area and a circular cators were stored in temperature controlled climatic chambers at
cup with a masked edge of 24% of the exposed area) the correction 23 ± 1 °C. The measurements were performed at four relative
factor is 1.089 and 1.106, respectively. Though this influences the humidities: 33%, 53%, 79.5% and 94%. For the adsorption curve, dif-
obtained equivalent air layer thickness by approximately 10%, it ferent specimen could be used for the different relative humidities.
hardly influences the variation of the results and cannot explain So, specimen were not necessarily taken stepwise from low to high
the deviations found between the different laboratories. relative humidity, but to save time all the adsorption isotherm data
Most striking when comparing the data and looking at the points could be determined simultaneously using different speci-
cumulative distribution function of the measured mean values, is men. When equilibrium was achieved all specimen had to be taken
the wide spread found in the dry cup data (test condition C1) of stepwise from high to low relative humidity to study the desorption
the gypsum board finished with the latex coat (see Fig. 2, bottom). behaviour starting at different points. So both the specimen at 53%,
The measured mean equivalent air layer thickness varies by a fac- 79.5% and 94% RH were stepwise taken from high to low relative
5360 S. Roels et al. / International Journal of Heat and Mass Transfer 53 (2010) 5355–5363

0.75

probability (-) 0.5

wax seal
0.25 rubber seal
epoxy seal
other
0
0.00 1.00 2.00 3.00 4.00 5.00
equivalent air layer thickness (m)
Fig. 5. Influence of the type of seal on the measured equivalent air layer thickness of gypsum board with a latex finishing coat for test condition C1 (dry cup).

humidity. In this way, some of the intermediate scanning curves be-


tween the ad- and desorption isotherm were measured.
To allow a statistic analysis, each participant had to prepare
0.015
from the delivered boards five test specimen for each relative
humidity, each of them with a surface area of 60  60 mm2. All moisture content (kg/kg)
specimens had to be dried beforehand at a temperature of 50 °C
until the weight loss between two successive measurements, with
0.01
a time interval of at least 24 h, remained less than 0.1%. Drying at a
higher temperature was found not recommendable since also
chemically bounded water may be removed. Some preparatory
measurements indicated that drying at 50 °C in a vented oven
0.005
was not dehydrating the gypsum but was also not removing all
the hygroscopically bounded water. This means that the starting
point of the sorption isotherm (the intended dry weight) does
not correspond to the origin of the sorption isotherm graph. The
0
shape of the curve, though, will not be influenced and since the
main focus is the dynamic hygric behaviour of the material, the 0 20 40 60 80 100
measured slope of the sorption isotherm is of main interest. More relative humidity (%)
details on the prescriptions of preparation and measurements of
Fig. 7. Adsorption (solid line) and desorption curve (dashed line) as measured by
the specimen can be found in [15]. one of the participants.

4.2. Results
example of the measured desorption and intermediate scanning
Fig. 6 shows the adsorption curves (mean of five specimen) as curves starting from the different positions on the adsorption iso-
measured by the participating laboratories. Fig. 7 shows a typical therm. As could be expected, a significant difference in absolute

0.03
1
moisture content (kg/kg)

0.75
probability (-)

0.02

0.5

0.01 0.25 RH: 33-53%


RH: 53-79.5%
RH: 79.5-94%

0
0.0000 0.0005 0.0010 0.0015
0
capacity [(kg/kg)/%RH]
0 20 40 60 80 100
relative humidity (%) Fig. 8. Cumulative distribution function of the mean values of the piecewise
capacity determined for the adsorption curve by the participating laboratories. The
Fig. 6. Sorption isotherm of uncoated gypsum board as measured by the partic- error bars indicate the minimum and maximum values determined by each
ipation laboratories for the adsorption curve. laboratory.
S. Roels et al. / International Journal of Heat and Mass Transfer 53 (2010) 5355–5363 5361

values can be observed in Fig. 6 when comparing the measured Hence, the reliability of both the equivalent moisture penetra-
adsorption isotherms. This can be attributed to the different tion depth model as well as the equivalent moisture capacity mod-
oven-drying conditions and corresponding correction for the dry el mainly relies on the measured moisture capacity and vapour
weight. When comparing the slopes of the curves (see Fig. 8) a permeability. To show the impact of the spread in data measured
much better agreement is found. Between 30% and 80% RH the for these properties, Table 2 summarises the minimum, mean
slope of the adsorption curve is – ignoring one outlier – for all insti- and maximum values of the calculated moisture penetration depth
tutes in the same order of magnitude. For the higher RH’s (above that can be obtained from the round robin data for the uncoated
80%) a larger spread is obtained. For the desorption curves – data and coated gypsum board, when submitted to daily indoor humid-
not included, but presented in [15] – it was observed that, apart ity variations (tp = 24 h, Ti = 293 K). As can be seen for most condi-
from the first desorption step, the slope of the adsorption, desorp- tions the maximum values are two to three times larger than the
tion and scanning curves is almost the same. This can also be seen minimum values. For the latex coated gypsum board at 30% RH
in Fig. 7. So, it seems that hysteresis on the hygric capacity plays the calculated penetration depth may even vary with a factor up
mainly a role in the first part, in the current case when the switch to nine!
is made from loading to unloading. To investigate the impact on the assumed hygric buffering
capacity of the gypsum board the multiplication factor M as used
5. Consequences for hygroscopic buffering models in the equivalent moisture capacity model is calculated for a small
(one person) room of 27 m3 with 36 m2 of gypsum board as finish-
The previous sections showed that, though determined accord- ing material. Applying the data of Table 2, the moisture capacity of
ing common measuring techniques, a wide spread in the measured the indoor air is assumed to increase with a factor 24–87 for the
data was found. Therefore it is interesting to investigate the impact uncoated gypsum board (30% RH) and with a factor varying be-
of using this kind of contradictive results when simulating hygro- tween 8 and 72 when the room is finished with the latex coated
scopic buffering of indoor enclosures. The measured data are typi- gypsum board. Similar results are obtained at other RH-conditions.
cally used as input data in numerical HAM-models or to calculate Hence, it can be concluded that reliable simulations of moisture
derived properties as the moisture penetration depth or the equiv- buffering can be obtained only if the uncertainty on measurement
alent moisture capacity. The sensitivity of numerical models to data of sorption isotherm and vapour permeability can be solved
variations in vapour permeability and sorption isotherm has been first.
extensively studied in [20] who compared numerical results with
experimental data of hygroscopic buffering measured in a bed of 6. Analytic expressions for the material properties
gypsum boards. Here, the impact on the derived equivalent mate-
rial properties will be shown. The gypsum board that was characterised in the current round
The equivalent moisture penetration depth model and the robin experiment has also been used in a numerical bench mark
equivalent moisture capacity model are simplified lumped ap-
proaches, frequently used in building energy simulation models,
to simulate hygroscopic buffering by finishing materials when in- Table 2
Calculated moisture penetration depth for the different gypsum boards under three
door humidity variations occur [2,25]. In the equivalent moisture relative humidity conditions.
penetration depth model it is assumed that only a thin surface
layer of the material interacts with the indoor air (the so-called Penetration depth (m)

humidity buffer). The depth of the humidity buffer db is related Minimum Mean Maximum
to the period of the typical humidity variations in the indoor air Uncoated gypsum board 30% 0.049 0.113 0.191
[26]: 73% 0.092 0.133 0.200
sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi 90% 0.031 0.055 0.094
tp  d  pv ;sat Acrylic coated 30% 0.031 0.068 0.114
db ¼ ð4Þ 73% 0.064 0.091 0.134
pn
90% 0.024 0.046 0.096

where tp (s) is the period, d (s) and n (kg/m3) are the water vapour Latex coated 30% 0.010 0.026 0.094
permeability and moisture capacity of the buffering layer and pv,sat 73% 0.030 0.051 0.083
90% 0.016 0.029 0.055
(Pa) the saturated vapour pressure. Moisture storage and transport
in this buffer layer are then described with a single control volume
equation.
The second model, the equivalent moisture capacity model, is
more simplified. Here, it is presumed that the humidity in the buf- Table 3
Parameters of the analytic expressions of the equivalent air layer thickness sd(U) and
fer layer of the finishing materials is at all times in equilibrium
sorption isotherm u(U).
with the room air humidity. The moisture buffering capacity of
the finishing materials can then easily be taken into account by Gypsum board Acryl coat Latex coat
increasing the room air moisture capacity with a multiplication Equivalent air layer thickness sd(U)
factor M. The correction factor M is calculated from the surface a 7.080 3.125 0.270
b 0.240 0.127 0.003
area, moisture capacity and moisture penetration depth of the
c 3.800 5.450 8.250
interior finishing:
!, Sorption isotherm u(U)
 usat 0.077 0.066 0.056
V A  q  n  db V
M¼ þ ð5Þ s 1 2 2
Rv T i pv ;sat Rv T i l1 1.00 0.19 0.32
a1 215.23 0.27 0.68
with V/(RvTi) (m3 kg/J) the moisture capacity of the zone air, A (m2) n1 1.628 1.525 1.55
the total surface area and q (kg/m3) the density of the finishing l2 0.81 0.68
a2 14.89 93.40
material, Rv (462 J/kg/K) the gas constant of water vapour and Ti
n2 2.200 1.46
(K) the interior air temperature.
5362 S. Roels et al. / International Journal of Heat and Mass Transfer 53 (2010) 5355–5363

case in which the dynamic behaviour of a bed of gypsum boards sealed with wax. It can be concluded that for experiments carried
was simulated. James et al. [20] describes the dynamic experiment out according to an existing ISO standard, the obtained results
and the result of the numerical simulations. To perform the numer- show unacceptable differences. This is in agreement with previous
ical simulations, initial conditions, boundary conditions and mate- round robin testing and stresses the need for further research on
rial properties were given to the different participants. The given the reliability of cup tests to come to an adequate revision of the
material properties were deduced from the results of the presented existing standards.
round robin experiment. The previous sections showed that both Both the sorption isotherm, desorption isotherm and some
the equivalent air layer thickness and the moisture capacity are intermediate scanning curves have been determined on uncoated
strongly nonlinear functions of relative humidity. To exclude inter- gypsum board. Due to differences in the determined dry weight,
polation differences in the numerical simulations analytic expres- the absolute curves deviate significantly, the measured slopes of
sions were fit through the measured data. The equivalent air the sorption isotherm correspond much better. Therefore, compar-
layer thickness of the acrylic and latex coat was determined by ison of the results was based on the piecewise capacity of the sorp-
subtracting the value measured on the uncoated gypsum board tion isotherm. Based on the mean values as measured by each of
from the one measured on the coated board. Equivalent air layer the participating laboratories it can be concluded that a rather
thickness sd as a function of relative humidity for both uncoated good agreement is found in the adsorption curve as long as the rel-
gypsum board and the two finishing layers were described by an ative humidity remains below 80%. At higher values of humidity,
exponential expression of the form the differences between the laboratories increases. Both for the
main desorption curve as well as for the intermediate scanning
sd ðUÞ ¼ a þ b  ecU ð6Þ
curves hysteresis were mainly found to play a role in the first
with U () the relative humidity and a, b and c fitting parameters. desorption step. For the following desorption steps the piecewise
To determine the parameters the measured mean values were used, capacity was nearly the same as determined from the adsorption
except for the latex coat, for which the fit was based only on the lab- curve.
oratories sealing the cups with wax. The obtained expressions are The consequences of using this kind of contradictive measure-
compared with the mean measured data in Fig. 1. ment data for simulating hygroscopic buffering, was investigated
The sorption isotherms u(U) are described with an analytical by calculating the equivalent moisture penetration depth and
function of the form moisture capacity. Due to the spread in results on the basic prop-
  erties, it was found that the equivalent moisture properties, which
X
s
ni
1ni
ni are commonly used in building energy simulation models, cannot
uðUÞ ¼ usat li ð1 þ ða: lnðUÞÞ Þ ð7Þ
i
be predicted with an acceptable level of reliability. For the current
case, the calculated moisture penetration depth may vary with a
with s the number of subsystems, li a weighing factor and ai, ni and factor two to nine, and similar results are found when calculating
also usat are used as parameters. The data for the uncoated gypsum the multiplication factor used to increase the indoor air capacity
board is based on the mean values of the round robin experiments. in the equivalent capacity model. So, it can be concluded that the
The data of the two finishing coats was determined out of the round current uncertainty on measurement data of sorption isotherm
robin experiment [27]. and vapour permeability hamper reliable simulations of hygro-
The parameters of both analytic expressions for the uncoated scopic buffering. The same conclusion most probably holds for all
gypsum board, the acrylic coat and the latex coat are summarised kind of simulations in which vapour transport through the material
in Table 3. plays an important role.

7. Conclusions Acknowledgments

Within IEA/ECBCS Annex 41 Subtask 2 a numerical and experi- The authors would like to gratefully thank all the participants of
mental analysis of moisture buffering was performed. It was the round robin experiment within IEA/ECBCS Annex 41 for their
decided to investigate whether it is possible to determine the nec- joint effort.
essary moisture properties with an acceptable level of precision
and repeatability. Therefore, a round robin test was set-up. In total
14 laboratories measured the vapour permeability and sorption References
isotherm of gypsum board. The vapour transmission properties
[1] C.E. Hagentoft, A.S. Kalagasidis, B. Adl-Zarrabi, S. Roels, J. Carmeliet, H. Hens, J.
have been measured on three test series: uncoated gypsum board, Grunewald, M. Funk, R. Becker, D. Shamir, O. Adan, H. Brocken, K. Kumaran, R.
gypsum board covered with a priming coat and acrylic finishing Djebbar, Assessment method of numerical prediction models for combined
coat and gypsum board covered with a priming coat and latex fin- heat, air and moisture transfer in building components: benchmarks for one-
dimensional cases, J. Therm. Envelope Build. Sci. 27 (4) (2004) 327–352.
ishing coat. The tests were carried out in accordance to EN [2] M. Woloszyn, C. Rode, IEA Annex 41 Whole Building Heat, Air, Moisture
ISO12572:2001. Three test conditions (0%/50%, 50%/93% and 86%/ Response. Modeling Principles and Common Exercises, K.U.LEUVEN, Belgium,
93% RH) were considered. Comparing the results, it was found that 2008.
[3] C. Rode, N. Mendes, K. Grau, Evaluation of moisture buffer effects by
the obtained vapour resistance data show surprisingly high differ- performing whole building simulations, ASHRAE Trans. 110 (2) (2004) 783–
ences. The differences are most pronounced for vapour tight spec- 794.
imen. The highest measured mean dry cup value of gypsum board [4] A. Holm, H. Kunzel, K. Sedlbauer, Predicting indoor temperature and humidity
conditions including hygrothermal interactions with the building envelope,
finished with latex coat is more than 10 times larger than the low- ASHRAE Trans. 110 (2) (2004) 820–826.
est measured mean value. Although the deviations within the re- [5] C.J. Simonson, M. Salonvaara, T. Ojanen, Heat and mass transfer between
sults of each laboratory are much smaller than the deviations indoor air and a permeable and hygroscopic building envelope : Part 1 – Field
measurements, J. Therm. Envelope Build. Sci. 28 (1) (2004) 63–101.
between the laboratories, no systematic differences could be found
[6] C.J. Simonson, M. Salonvaara, T. Ojanen, Heat and mass transfer between
between the participating laboratories. Neither could the type of indoor air and a permeable and hygroscopic building envelope : Part 2 –
desiccant in the dry cup, the masked edge or the vapour resistance Verification and numerical studies, J. Therm. Envelope Build. Sci. 28 (2) (2004)
of the air layers in and above the cups explain the observed differ- 161–185.
[7] O.F. Osanyintola, C.J. Simonson, Moisture buffering capacity of hygroscopic
ences. Yet, when analysing the type of seal, it was found that the building materials: experimental facilities and energy impact, Energy Build. 38
highest equivalent air layer thicknesses were measured on cups (2004) 1270–1282.
S. Roels et al. / International Journal of Heat and Mass Transfer 53 (2010) 5355–5363 5363

[8] J. Kurnitski, T. Kalamees, J. Palonen, L. Eskola, O. Seppänen, Potential effects of [18] B. Time, S. Uvslokk, Intercomparison on measurement of water vapour
permeable and hygroscopic lightweight structures on thermal comfort and permeance, Nordtest-project agreement 1529-01, Prosjektrapport 339,
perceived IAQ in a cold climate, Indoor Air 17 (2007) 37–49. Norges byggforskningsinstitutt, Oslo, 2003.
[9] F. Tariku, K. Kumaran, Hygrothermal modeling of aerated concrete wall and [19] S. Roels, J. Carmeliet, H. Hens, O. Adan, H. Brocken, R. Cerny, Z. Pavlik, C. Hall, K.
comparison with field experiment, in: P. Fazio et al. (Eds.), Research in Building Kumaran, L. Pel, R. Plagge, Interlaboratory comparison of hygric properties of
Physics and Building Engineering, Taylor and Francis Group, London, 2007, pp. porous building materials, J. Therm. Envelope Build. Sci. 27 (4) (2004) 307–
321–328. 325.
[10] K. Svennberg, K. Lengsfeld, L.E. Harderup, A. Holm, Previous experimental [20] C. James, C.J. Simonson, P. Talukdar, S. Roels, Numerical and experimental data
studies and field measurements on moisture buffering by indoor surface set for benchmarking hygroscopic buffering models, Int. J. Heat Mass Transfer
materials, J. Build. Phys. 30 (2007) 261–274. 53 (2010) 3638–3654.
[11] T. Kalamees, J. Vinha, Indoor humidity loads and moisture production in [21] ASTM, ASTM E 96-05, Standard Test Method for Water Vapour Transmission of
lightweight timber-frame detached houses, J. Build. Phys. 29 (3) (2006) 219– Materials, American Society for Testing and Materials, vol. 14.06, 2005.
245. [22] EN ISO 12572:2001, Hygrothermal performance of building materials and
[12] M. Qin, R. Belarbi, A. Ait-Mokhtar, A. Seigneurin, An analytical method to products – determination of water vapour transmission properties, European
calculate the coupled heat and moisture transfer in building materials, Int. Committee for Standardization, Brussels, Belgium, 2001.
Commun. Heat Mass Transfer 33 (1) (2005) 39–48. [23] M. Pazera, M. Salonvaara, Examination of stability of boundary conditions in
[13] P. Talukdar, S.O. Olutimayin, O.F. Osanyintola, C.J. Simonson, An experimental water vapour transmission tests, J. Build. Phys. 33 (1) (2009) 45–64.
data set for benchmarking 1-D, transient heat and moisture transfer models of [24] S. Roels, How reliable are standard cup tests for the determination of the
hygroscopic building materials, Part I: experimental facility and material vapour permeability of building materials? in: N.T. Bayazit et al. (Eds.),
property data, Int. J. Heat Mass Transfer 50 (2007) 4527–4539. Proceedings of the Fourth International Building Physics Conference: Energy
[14] P. Talukdar, O.F. Osanyintola, S.O. Olutimayin, C.J. Simonson, An experimental Efficiency and New Approaches, 15–18 June 2009, Istanbul, Istanbul Technical
data set for benchmarking 1-D, transient heat and moisture transfer models of University, 2009, pp. 1001–1006.
hygroscopic building materials, Part II: experimental, numerical and analytical [25] H. Janssen, S. Roels, Qualitative and quantitative assessment of interior
data, Int. J. Heat Mass Transfer 50 (2007) 4915–4926. moisture buffering by enclosures, Energy Build. 41 (2009) 382–394.
[15] S. Roels, IEA Annex 41 Whole Building Heat, Air, Moisture Response. [26] M.J. Cunningham, The building volume with hygroscopic materials – an
Experimental Analysis of Moisture Buffering, K.U.LEUVEN, Belgium, 2008. analytic study of a classical building physics problem, Build. Environ. 38
[16] S. Roels, C. James, P. Talukdar, C.J. Simonson, Reliability of transient heat and (2003) 329–337.
moisture modeling for hygroscopic buffering, ASHRAE Trans. 115 (2) (2009). [27] S. Roels, J. Carmeliet, Water vapour permeability and sorption isotherm of
[17] BCR, Eur 14800 – The BCR Programme on Applied Metrology and Chemical coated gypsum board, in: Proceedings of the 7th Symposium on Building
Analysis, Projects and Results 1988–1992, Office for official publications of the Physics in the Nordic Countries, The Icelandic Building Research Institute,
European Communities, Luxembourg, 1992. Reykjavik Iceland 2005, pp. 609–616.

Você também pode gostar