Você está na página 1de 66

SETUP AND OPERATING

INSTRUCTIONS

Mark II
High Voltage Fire Pump Controllers

NS2000-30 (07-15-08)

IMPORTANT - DO NOT DISCARD

Network Power
Table of Contents

SECTION ONE
Introduction ........................................................................................................................... 1

Mounting Controller .............................................................................................................. 1


Floor Mount ..................................................................................................................1

Making Electrical Connections ............................................................................................. 2

General Pre-Start Up Operation ........................................................................................... 2

General Start Up Operation .................................................................................................. 3


Voltage Check .............................................................................................................. 3
Phase Rotation ............................................................................................................. 3
Motor Rotation .............................................................................................................. 4

Initial Start Up Operation ...................................................................................................4-5

Abbreviated Starting Sequence ............................................................................................ 5

SECTION TWO
Mark II Setup Notes .............................................................................................................. 6

Mark II Menu Structure - Overview ....................................................................................... 7


Mark II Menu Structure - Meter Menu .......................................................................... 8
Event Log Menu .................................................................... 9
Data Log Menu .................................................................... 10
Pressure Settings Menu ...................................................... 11
Timers Menu........................................................................ 12
Alarm Limits Menu ............................................................... 13
Clock Set Menu ................................................................... 14
Diagnostics Menu ................................................................ 15
System Setup Menu ............................................................ 16

i
Table of Contents
Detailed Instructions
Meter Function ......................................................................................................... 17

Event Log................................................................................................................. 18

Data Log .................................................................................................................. 19

Pressure Settings
Start Pressure ............................................................................................... 20
Stop Pressure ............................................................................................... 21
Pressure Recording ...................................................................................... 22
Manual Stop Only ......................................................................................... 23
Pressure Units .............................................................................................. 24
Low Suction & Level ..................................................................................... 25
Pressure Calibration ..................................................................................... 26

Timers
On Delay Time .............................................................................................. 27
Minimum Run Time ....................................................................................... 28
Off Delay Time .............................................................................................. 29
Weekly Test Time .......................................................................................... 30

Alarm Limits
Under Voltage ............................................................................................... 31
Over Voltage ................................................................................................. 32
Voltage Imbalance ........................................................................................ 33
Frequency ..................................................................................................... 34
Motor Overload ............................................................................................. 35
Reverse Phases............................................................................................ 36

Clock Set ................................................................................................................. 37


Daylight Savings Time .................................................................................. 38

Diagnostics
Software Version ........................................................................................... 39
Lamp Test ..................................................................................................... 40
120VAC Inputs (1-16) ................................................................................... 41

ii
Table of Contents
Diagnostics (cont..)
120VAC Inputs (17-24) ................................................................................. 42
120VAC Outputs ........................................................................................... 43
Keypad Test .................................................................................................. 44
Serial Loopback Test..................................................................................... 45
Flash Memory Test........................................................................................ 46
USB Loopback Test ...................................................................................... 47
USB Drive Test.............................................................................................. 48

System Setup
Model Configuration ...................................................................................... 49
Option Configuration ..................................................................................... 50
System Language ......................................................................................... 51
System Voltage ............................................................................................. 52
System Frequency ........................................................................................ 53
Motor FLA ..................................................................................................... 54
CT Ratio ........................................................................................................ 55
Serial Number ............................................................................................... 56
Flash Disk Autosave ..................................................................................... 57
Single Phase Mode ....................................................................................... 58
Clear Event Log ............................................................................................ 59
Clear Data Log .............................................................................................. 60
Change Passwords ....................................................................................... 61

iii
WARNING
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE
IT IS ENERGIZED! DEATH, PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAM-
AGE MAY RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY
THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING, AND ALWAYS FOLLOW GEN-
ERALLY ACCEPTED SAFETY PROCEDURES. CONTROLLER “ON-OFF” SWITCH MUST
BE IN THE EXTREME “OFF” POSITION TO OPEN THE ENCLOSURE DOOR. FIRETROL
CANNOT BE LIABLE FOR ANY MISAPPLICATION OR INCORRECT INSTALLATION OF
ITS PRODUCTS.

INTRODUCTION
Firetrol® combined automatic and manual fire pump controllers are intended for starting
electric motor driven fire pumps.
Firetrol fire pump controllers are listed, approved or certified by the following approving
authorities: Underwriters’ Laboratories, Inc., Underwriters’ Laboratories of Canada, Canadian
Standards Association, City of New York Department of Buildings and Factory Mutual. They
are built to meet or exceed the requirements of the approving authorities listed above as well
as NEMA and the latest editions of NFPA 20 and NFPA 70.
These instructions are intended to assist in the understanding of the installation and opera-
tion of these controllers. Read the instructions thoroughly prior to connecting the controller.
If there are any unanswered questions, please contact the local Firetrol representative or
factory service department.

MOUNTING CONTROLLER
NOTE—Consult the appropriate job plans to determine the controller mounting location. Tools
and materials (all mounting) required:
1. Assortment of common hand tools of the type used to service electromechanical equip-
ment.
2. Drill for drilling floor anchor holes.
3. Hand level.
4. Tape measure.
5. Eight anchors, bolts and washers, per enclosure.

FLOOR MOUNT
NOTE—Consult the appropriate job plans to determine the controller mounting location. Refer
to the controller dimension print for necessary mounting dimensions.
The controller is floor mounted by using the two pre-drilled holes in each leg. The holes
are dimensionally on the same line for ease of mounting.
1. Using either the dimension print or by measuring the distance between the center lines
of the holes on one leg, transcribe these dimensions onto floor.
2. Drill two holes in the floor for anchoring the leg.
3. Mark the location of the holes for the opposite leg and drill two more holes.
4. Secure the controller to the floor with bolts and washers and tighten.
5. Check to be sure the enclosure door opens freely and that the enclosure is level.

1
MAKING ELECTRICAL CONNECTIONS
Important Precautions—
Prior to making any field connections:
1. Verity that the following information is compatible with other related equipment on the
project:
•Firetrol catalog number
•Motor horsepower, voltage, phase and frequency
•System pressure
2. The project electrical contractor must supply all necessary wiring for field connections in
accordance with the National Electrical Code, local electrical code and any other authority
having jurisdiction.
3. Open the enclosure doors and inspect the internal components and wiring for any
signs of frayed or loose wires or other visible damage.
4. Refer to the appropriate field connection drawing in the manual for all wiring information.
Procedure—
All field connections, remote alarm functions and AC wiring are brought into the enclosure
through the top, bottom, or side conduit entrances as indicated on the dimension drawing.
Refer to the National Electrical Code, the local electrical code or any other authority having
jurisdiction for proper conduit entrance location.
1. Use a hole punch, not a torch nor a drill, and punch a hole in the enclosure for the size
conduit being used.
2. Install necessary conduit.
3. Pull all wires necessary for field connections, remote alarm functions, AC power and all
other optional features. Allow enough excess wire inside the enclosure to make up connec-
tions to the appropriate line, load and control terminal block points. Be sure to consult
the appropriate field connection diagram included with the manual. For proper wire
sizing, refer to the National Electrical Code, NFPA 70.
4. Make all field connections to the remote alarm functions and any other optional features.
Do not connect AC power.
5. Verify AC line voltage, phase and frequency with the controller data plate on the enclosure
door prior to connecting AC power.
6. Connect the AC power.
7. Check to see that all connections are both correctly wired (in accordance with the field
connection diagram) and tight.
8. Close the enclosure doors.

GENERAL PRE-START UP OPERATION


1. Check the controller for bolts, nuts and electrical connections which may have loosened
during shipment.
2. If a remote start push-button is used, connect the wires to terminals 6 and 7.
3. If a deluge valve is used, remove the jumper from terminals 1 and 8. Connect wires from
the normally closed contact on the deluge valve to terminals 1 and 8.
4. If a FTA200 remote alarm panel is used, connect like numbered terminals in the remote
alarm panel to terminals 17, 18, 19 and 20 in the fire pump controller. Terminals H and N
must be connected if a FTA200 alarm panel is used.
5. If a FTA200 remote alarm panel is used, connect a reliable, separate, supervisory 120
volt power supply to terminals L1 and L2 in the alarm panel.
2
GENERAL START UP OPERATION
General operating procedures are indicated on the data plate fastened to the front of the
controller enclosure door. The following information is merely in greater detail:
Close and secure Power and Transformer Compartment doors.
Voltage Check—
1. Energize the incoming power feeder.
2. Close the Isolating Disconnect Switch by moving the handle to the “ON”
position.
3. Place the “Normal-OFF-Test” selector switch in the Normal position.
4. Press the METER push-button on the Mark II interface panel. The 3 phase
voltage will be displayed. Confirm that the measured voltage matches the voltage
stamped on the data plate.

At this time, it is necessary to prepare the controller for


normal operation. See section 2 for setup instructions
for the Mark II. After the Mark II has been configured,
return to this section.

Phase Rotation
The Mark II is designed to indicate phase loss and/or phase reversal. Separate LED’s
indicate POWER ON and PHASE REVERSAL. If external alarms are wired, these failures
will also be indicated at the remote alarm location. The Mark II is factory programmed for the
standard ABC phase relationship. If voltage is available on all three phases and the PHASE
REVERSAL LED comes on, see Section 2 - Alarm Limits-Reverse Phases.

To simulate a phase reversal for testing purposes, push and


hold the phase reversal push-button located on the right hand
side of the Mark II with the door open (see photo on right). The
phases will be reversed internal to the Mark II and a phase
reversal alarm will be initiated. The alarm will clear when the
button is released.

3
MOTOR ROTATION
Confirm direction of motor rotation as follows:
1. Close and secure enclosure doors.
2. Press and hold the STOP push-button. Close the Isolating Disconnect Switch, by moving
handle to the “ON “ position then release the STOP push-button.
3. The pump motor should rotate immediately if system pressure is low. If system pressure
is not low, press the manual START push-button and immediately press the manual STOP
push-button.
4. Observe direction of motor rotation.
5. If rotation is incorrect, confirm that the isolating switch/circuit breaker is in the OFF position,
open enclosure door and reverse any two of the motor leads (T1, T2, T3) on the load side
of contactor M. For example, T1 and T2, T1 and T3 or T2 and T3.
6. Retest for proper rotation following steps 1 through 4.
INITIAL START-UP OPERATION
1. Press and hold the STOP push-button. Place disconnect switch in ON position then
release the STOP push-button. The pump may start immediately if system pressure is
low. The PUMP RUNNING and LOW PRESSURE LED’s will be lit.
2. If the Mark II is configured for automatic shutdown (MANUAL STOP disabled), the pump
motor will continue to run for the period of time set in the MIN RUN (or OFF DELAY) screen
and then stop automatically, providing the STOP pressure setting has been reached.
Both the system pressure and MIN RUN (or OFF DELAY) time remaining will be shown
on the display. Depressing the STOP push-button during the running period will stop the
motor as long as the button is held in. However, the motor will restart when the button is
released if system pressure is below the stop setting.
3. If the controller is configured for manual shutdown (MANUAL STOP enabled), the pump
will continue to run until the STOP push-button is depressed.
4. To stop the motor otherwise, press and hold the STOP push-button or move the “Normal-Off-
Test” selector switch to “Off” position and place the DISCONNECTING MEANS handle
in the OFF position.

FOR MANUAL START


1. Follow the initial start-up instructions. The isolating switch should be closed, the POWER
AVAILABLE LED should be illuminated and system pressure normal, i.e. higher than the
programmed START PRESSURE setting.
2. Press the START push-button. The pump motor should start and continue to run. It will
not stop automatically. The running period timer and pressure switch have no control over
this manual operation.
3. To stop, press the STOP push-button.
4. Starting from a remote START push-button (if used) functions in the same way as the local
START push-button.
5. If the pump motor restarts, system pressure is below the START PRESSURE setting.

4
Emergency Run Mechanism
This Device is used to mechanically close the motor contactor M in the event of coil burnout
or other electrical problems which would prevent normal starting of the pump motor.
If control circuit power is not available, the Emergency Run Mechanism mechanically closes
contractor M starting the motor.

To START move the emergency run handle counter-clockwise (left) until it is latched “ON”
the motor will start and continue to run.

-Warning- This is an EMERGENCY device and should be used only in an emergency run
situation. Casual or Careless use of this mechanism may result in damage to the controller
electrical components. It is not intended for, nor should be used as a testing device.

To STOP the pump motor when the emergency run handle is in the “ON” position, move the
handle to “OFF” and place the isolating switch handle in the “OFF” position.

ABBREVIATED STARTING SEQUENCE


FTA2000 HIGH VOLTAGE CONTROLLER
1. Follow all of the initial start-up instructions.
2. The motor will start and run at full line voltage.

5
SECTION 2

Mark II Set Up
Set Up Notes:

These instructions often refer to pressing the “right arrow” - key; earlier versions of the
Mark II interface panel had an “ACK” key instead. Pressing the “ACK” key will have the same
results as the key when following these instructions.

User Passwords:

Adjusting the settings of the Mark II can severely effect the operation of the fire pump controller.
Any adjustments should be done by qualified personnel. This manual will refer to an “opera-
tor” level password and an “supervisor” level password. The “operator” level password allows
changes that might normally be made by maintenance personnel. The “supervisor” password
allows changes that may more seriously affect the operation of the fire pump controller. A
“supervisor” level password might be required by well-trained maintenance personnel, pump
distributors or manufacturers representatives.

The “operator” level password is shown below. This password is also on a label affixed to
the back of the Mark II on the inside of the controller door. Although this password may be
changed, it is not recommended. Cost to the owner may be incurred if the factory password
is changed, then forgotten.

When prompted for the Operator Level password enter the following key sequence:

METER-MENU-METER-MENU-PRINT-ENTER

The Supervisor Level password will be supplied as necessary or will already be known by the
person performing the changes to the controller.

Interlock Jumper
NOTICE: The controller is shipped with an interlock jumper in place to prevent motor
starting during the setup procedure. The Mark II display will have the INTERLOCK ON
LED turned on and the ALARM LED will blink. This will not interfere with the setup
procedure. This interlock jumper must be removed for the controller to operate au-
tomatically. Remove the jumper wire connected between field terminals #1 and #10
when setup is complete.

6
MARK II MENU STRUCTURE
MAIN DISPLAY HOME

VOLTAGES & CURRENTS


METER FREQUENCY & PHASE
MINIMUM MOTOR START VOLTAGES
-DETAIL- MAXIMUM MOTOR START CURRENTS
SEE FIGURE A
PAGE 8

UNDER VOLTAGE
OVER VOLTAGE
EVENT ALARM VOLTAGE IMBALANCE
MENU 3000 EVENTS MENU
LOG LIMITS FREQUENCY
-DETAIL- -DETAIL- MOTOR OVERLOAD
SEE FIGURE B SEE FIGURE F REVERSE PHASES
PAGE 9 PAGE 13

CALLS/STARTS
TOTAL MOTOR RUN TIME CLOCK SET DATE/TIME
LAST MOTOR RUN TIME MENU
SET DAYLIGHT SAVINGS TIME
LAST MOTOR START
MAXIMUM RUN CURRENTS -DETAIL-
LAST PHASE FAILURE SEE FIGURE G
LAST PHASE REVERSAL PAGE 14
DATA
MENU LAST LOCKED ROTOR TRIP
LOG SOFTWARE VERSION
LAST LOCKED ROTOR TRIP CURRENTS
-DETAIL- LAMP TEST
MINIMUM VOLTAGES
SEE FIGURE C 120VAC INPUTS 1-16
MAXIMUM VOLTAGES
PAGE 10 120VAC INPUTS 17-24
TOTAL UNIT RUN TIME
120VAC OUTPUTS
MIN/MAX FREQUENCY MENU DIAGNOSTICS KEYPAD TEST
MIN/MAX PRESSURE
SERIAL LOOPBACK TEST
-DETAIL- FLASH MEMORY TEST
SEE FIGURE H USB LOOPBACK TEST
PAGE 15 USB DRIVE TEST
STOP PRESSURE
START PRESSURE MODEL CONFIGURATION
PRESSURE EVENT RECORDING OPTION CONFIGURATION
PRESSURE MANUAL STOP ONLY SYSTEM LANGUAGE
MENU
SETTINGS PRESSURE UNITS SYSTEM VOLTAGE
-DETAIL- LOW SUCTION/LEVEL SYSTEM FREQUENCY
SEE FIGURE D ZERO CALIBRATION MOTOR FLA
PAGE 11 SPAN CALIBRATION SYSTEM CT RATIO
MENU SERIAL NUMBER
SETUP
FLASH DRIVE AUTOSAVE
-DETAIL-
SEE FIGURE I SINGLE PHASE
PAGE 16 CLEAR EVENT LOG
ON-DELAY
CLEAR DATA LOG
MINIMUM RUN
CHANGE PASSWORDS
MENU TIMERS OFF DELAY
ACCELERATION/BYPASS
-DETAIL- WEEKLY TEST
SEE FIGURE E
PAGE 12
NOTE:
THE MENU STRUCTURE SHOWN HERE AND THE
CORRESPONDING DETAIL FIGURE DRAWINGS ARE SUPPLIED
AS A VISUAL REFERENCE ONLY. FOR DETAILED
PROGRAMMING INSTRUCTIONS PLEASE REFER TO THE
PROGRAMMING SECTION OF THIS MANUAL.
THIS MANUAL COVERS MANY MODELS OF CONTROLLERS,
THEREFORE SOME MENU ITEMS SHOWN MAY NOT BE
AVAILBLE FOR ALL CONTROLLER TYPES.

77
MARK II MENU STRUCTURE

MAIN DISPLAY

METER HOME

VOLTAGES
&
CURRENTS

FREQUENCY
&
PHASE

MIN. START
VOLTAGES

MAX. START
CURRENTS

FIGURE A
DETAIL INFORMATION - SEE PAGE 17

8
MARK II MENU STRUCTURE

MAIN DISPLAY

MENU MENU

SEE FIGURE C HOME


EVENT
LOG
(3000 EVENTS)

ENTER
ANY
SCREEN

MOST RECENT
EVENT
(TIME-DATE)

NEXT MOST EVENT


RECENT ENTER
EVENT EVENT #
(x Search Mult) SEARCH MULT.

CHANGE
ENTER SEARCH MULT.
(x1 - x10 - x100)

NEXT MOST
RECENT
EVENT
(x Search Mult)

NEXT MOST
RECENT
ENTIRE EVENT
EVENT (x Search Mult)
LOG

NEXT MOST
RECENT
EVENT
(x Search Mult)

ENTIRE
EVENT FIGURE B
LOG

DETAIL INFORMATION - SEE PAGE 18


9
MARK II MENU STRUCTURE

MAIN DISPLAY

FROM FIGURE B MENU MENU

SEE FIGURE D HOME


DATA LOG

ANY
SCREEN

#CALLS/ MAXIMUM MINIMUM


RUN VOLTAGES
#STARTS CURRENTS

TOTAL LAST
MOTOR MAXIMUM
PHASE VOLTAGES
RUN TIME FAILURE

LAST LAST TOTAL


MOTOR PHASE UNIT RUN
RUN TIME REVERSAL TIME

LAST LAST LOCKED


MOTOR MIN/MAX
ROTOR FREQUENCY
START TRIP

LAST LOCKED MIN/MAX


ROTOR TRIP SYSTEM
PRESSURE
CURRENTS
FIGURE C
DETAIL INFORMATION - SEE PAGE 19
10
MARK II MENU STRUCTURE

MAIN DISPLAY

FROM FIGURE C
ANY
HOME
MENU MENU SCREEN

SEE FIGURE E
MANUAL DETAIL
PRESSURE
STOP INFORMATION
SETTINGS
ONLY SEE PAGE 23

DETAIL DETAIL
STOP PRESSURE
INFORMATION INFORMATION
PRESSURE UNITS
SEE PAGE 21 SEE PAGE 24

DETAIL LOW DETAIL


START
INFORMATION SUCT & INFORMATION
PRESSURE
SEE PAGE 20 LEVEL SEE PAGE 25

PRESSURE DETAIL DETAIL


INFORMATION PRESSURE
RECORDING INFORMATION
SEE PAGE 22 CALIBRATION
SEE PAGE 26

FIGURE D

11
MARK II MENU STRUCTURE

MAIN DISPLAY

FROM FIGURE D ANY


SCREEN HOME
MENU MENU

SEE FIGURE F
TIMER
SETTINGS

ON DETAIL WEEKLY DETAIL


DELAY INFORMATION TEST INFORMATION
TIME SEE PAGE 27 TIME SEE PAGE 30

MINIMUM DETAIL
RUN INFORMATION
TIME SEE PAGE 28

OFF DETAIL
DELAY INFORMATION
TIME SEE PAGE 29

FIGURE E

12
MARK II MENU STRUCTURE

MAIN DISPLAY

FROM FIGURE E ANY


SCREEN HOME
MENU MENU

SEE FIGURE G
ALARM
LIMITS

DETAIL DETAIL
UNDER MOTOR
INFORMATION INFORMATION
VOLTAGE OVERLOAD
SEE PAGE 31 SEE PAGE 35

DETAIL DETAIL
OVER REVERSE
INFORMATION INFORMATION
VOLTAGE PHASES
SEE PAGE 32 SEE PAGE 36

DETAIL
VOLTAGE
INFORMATION
IMBALANCE
SEE PAGE 33

DETAIL
FREQUENCY
INFORMATION
LIMITS
SEE PAGE 34

FIGURE F

13
MARK II MENU STRUCTURE

MAIN DISPLAY

FROM FIGURE F MENU MENU

SEE FIGURE H HOME

DETAIL
CLOCK ANY
INFORMATION
SET SCREEN
SEE PAGE 37

DAYLIGHT DETAIL
SAVINGS INFORMATION
TIME SEE PAGE 38

FIGURE G

14
MARK II MENU STRUCTURE

MAIN DISPLAY

FROM FIGURE G ANY


SCREEN HOME
MENU MENU

SEE FIGURE I

DIAGNOSTICS

DETAIL DETAIL USB DETAIL


SOFTWARE 120V
INFORMATION INFORMATION LOOPBACK INFORMATION
VERSION OUTPUTS
SEE PAGE 39 SEE PAGE 43 TEST SEE PAGE 47

DETAIL DETAIL DETAIL


LAMP KEYPAD USB DRIVE
INFORMATION INFORMATION INFORMATION
TEST TEST TEST
SEE PAGE 40 SEE PAGE 44 SEE PAGE 48

120V DETAIL SERIAL DETAIL


INPUTS INFORMATION LOOPBACK INFORMATION
1 - 16 SEE PAGE 41 TEST SEE PAGE 45

120V DETAIL FLASH DETAIL


INPUTS INFORMATION MEMORY INFORMATION
17-24 SEE PAGE 42 TEST SEE PAGE 46

FIGURE H

15
MARK II MENU STRUCTURE

MAIN DISPLAY

FROM FIGURE H ANY


SCREEN HOME
MENU MENU

SEE FIGURE B
SYSTEM
SETUP

DETAIL
SINGLE
INFORMATION
PHASE
DETAIL DETAIL SEE PAGE 58
MODEL SYSTEM
INFORMATION INFORMATION
CONFIG FREQUENCY
SEE PAGE 49 SEE PAGE 53

CLEAR DETAIL
EVENT INFORMATION
DETAIL DETAIL LOG SEE PAGE 59
OPT MOTOR
INFORMATION INFORMATION
CONFIG FLA
SEE PAGE 50 SEE PAGE 54

CLEAR DETAIL
DATA INFORMATION
DETAIL DETAIL LOG SEE PAGE 60
SYSTEM CT
INFORMATION INFORMATION
LANGUAGE RATIO
SEE PAGE 51 SEE PAGE 55

DETAIL
CHANGE
INFORMATION
PASSWORD
DETAIL DETAIL SEE PAGE 61
SYSTEM SERIAL
INFORMATION INFORMATION
VOLTAGE NUMBER
SEE PAGE 52 SEE PAGE 56

FLASH DETAIL
DRIVE INFORMATION
AUTOSAVE SEE PAGE 57
16
FIGURE I
METER

METER

VOLTAGES
&
CURRENTS

FREQUENCY
&
PHASE

MIN. START
VOLTAGES

MIN. START
CURRENTS

The controller provides simultaneous 3 phase metering in True RMS. When the METER button
is pushed, the display will show existing volts and amps for all three phases. Use the key to
scroll to the next set of values, which is the current frequency (hertz) and the phase rotation.
Pressing the key again will display the Minimum MTR (motor) Start Volts for each phase.
The values shown are for the last start or current start if motor is running. Pressing the key
again will display the Maximum MTR (motor) Start Amps for each phase. The values shown
are for the last start or current start if motor is running. You may use the key to scroll back
through the various values. Press HOME to return to the main screen.

17
EVENT LOG

MENU

EVENT
LOG
(3000 EVENTS)

ENTER

MOST RECENT EVENT


EVENT EVENT #
(TIME-DATE) SEARCH MULT.

CHANGE
ENTER SEARCH MULT.
(x1 - x10 - x100)

NEXT MOST
RECENT ENTER
EVENT
(x Search Mult)

NEXT MOST
RECENT
EVENT
(x Search Mult)

NEXT MOST
RECENT
EVENT
(x Search Mult)

NEXT MOST
RECENT
ENTIRE EVENT
EVENT (x Search Mult)
LOG

ENTIRE
EVENT
LOG

The controller keeps an internal log of all events. This memory log stores the last 3000 events
in chronological order. To view the event log, press MENU. The display will show “Event
Log”. Press ENTER. The most recent event will be shown with a time/date stamp. To view
the previous event, press the key. The and keys can be used to scroll forward and
backward through the events. To search more rapidly through the events, such as looking
for a specific date, press the ENTER key while viewing any event. The event will appear
on the top line of the display. The event number and search multiplier {X1, X10, X100} will
appear on the bottom line of the display. To change the search multiplier, press the key.
The search multiplier determines how many events are skipped when the and keys
are used. Press ENTER to return to the event screen with time/date stamp or you can scroll
through the events from the current screen. Press HOME to return to the main screen when
finished viewing events.
18
DATA LOG

MENU

DATA LOG

#CALLS/ MAXIMUM MINIMUM


RUN VOLTAGES
#STARTS CURRENTS

TOTAL LAST
MOTOR MAXIMUM
PHASE VOLTAGES
RUN TIME FAILURE

LAST LAST TOTAL


MOTOR PHASE UNIT RUN
RUN TIME REVERSAL TIME

LAST LAST LOCKED


MOTOR MIN/MAX
ROTOR FREQUENCY
START TRIP

LAST LOCKED MIN/MAX


ROTOR TRIP SYSTEM
CURRENTS PRESSURE

The controller keeps an internal log of historical data. This log consists of the following
data:
• No. of calls to start / No. of actual starts
• Total Motor Run Time (Hrs:Min:Sec)
• Last Motor Run Time (Min:Sec)
• Last Motor Start (Time and Date)
• Maximum Run Currents (3 Phase - Amps)
• Last Phase Failure (Time and Date)
• Last Phase Reversal (Time and Date)
• Last LR (Locked Rotor) Trip (Time and Date)
• Last LR (Locked Rotor) Trip Currents (3 Phase - Amps)
• Minimum Voltages (3 Phase)
• Maximum Voltages (3 Phase)
• Total Unit Run Time (Power On Time - Hrs:Min)
• Min/Max Frequency (Hertz)
• Min/Max Pressure
To view the data log, press MENU until “Data Log” appears on the screen. Use the and
keys to scroll through the data log information. Press HOME to return to the main screen
when finished viewing the data log. 19
PRESSURE SETTINGS - START PRESSURE

MENU

PRESSURE
SETTINGS

(ENTER OPERATOR
PASSWORD)
START
ENTER
PRESSURE

SET
ENTER START
PRESSURE

Press MENU button until “Pressure Settings” appears on the display. Press ENTER. Present
start pressure setting will be displayed. To change the pressure setting, press ENTER. Enter
the operator password. Use the and keys to set start pressure to desired setting. Press
ENTER to store the new setting. Press HOME to return to the main screen. (Note: The mini-
mum operating pressure differential (the difference between the START and STOP settings)
is 5 psi. If start pressure cannot be raised it is because the pressure is at the 5 psi differential.
Raise the STOP pressure to allow additional differential to raise the START pressure).

20
PRESSURE SETTINGS - STOP PRESSURE

MENU

PRESSURE
SETTINGS

(ENTER OPERATOR
PASSWORD)
STOP
ENTER
PRESSURE

SET
ENTER STOP
PRESSURE

Press MENU button until “Pressure Settings” appears on the display. Present stop pressure
setting will be displayed. Use the key to scroll to the stop pressure setting. The current
set point will be displayed. To change the pressure setting, press ENTER. Enter the operator
password. Use the and keys to set stop pressure to desired setting. Press ENTER to
store the new setting. Press HOME to return to the main screen. (Note: The STOP pressure
setting must be set at a pressure less than the fire pump “churn” pressure (Including minimum
suction pressure) otherwise, the pump will run continuously once started).

21
PRESSURE SETTINGS - PRESSURE RECORDING

MENU

PRESSURE
SETTINGS

(ENTER OPERATOR
PASSWORD)
PRESSURE
ENTER
RECORDING

SET
ENTER
DELTA-P

SET
ENTER AUTOMATIC
RECORDING

The pressure recording settings determine when the system pressure is recorded. This in-
formation is saved to the built in event log and the flash disk. This information will also be
printed if the controller was ordered with a printer. To set these parameters, press the MENU
button until “Pressure Settings” appears on the display. Use the key to scroll to the “Pres-
sure Recording” screen. The present settings will be displayed. Press ENTER to change the
settings. Enter the operator password. The cursor will blink next to the “Delta p” ( P) setting.
This setting refers to a variation in pressure. If the pressure deviates +/- more than the setting,
the event is recorded. Use the and keys to set the “delta p” setting. The parameters
for this setting are “OFF” or a pressure setting from 5 to 50 psi. Next to the “delta p” setting
is the automatic recording setting. This setting can be set to “Off” or “Hourly”. To change this
setting use the key to move the cursor and the or keys to change the setting. Press
ENTER to store the new settings. Press HOME to return to the main screen.

22
PRESSURE SETTINGS - MANUAL STOP ONLY

MENU

PRESSURE
SETTINGS

(ENTER OPERATOR
PASSWORD)
MANUAL
STOP ENTER
ONLY

SET
ENTER MANUAL
STOP

The controller can be set for manual stop only. This setting can be either “Enabled” or “Dis-
abled”. Enabling this setting will cause the Mark II to ignore any minimum run or off delay
timer settings. The minimum run or off delay timers will appear on the diplay and count down
the set times, but the controller will not stop the pump at the end of this time. The only way to
stop the pump with the manual stop only setting enabled is to press the STOP push-button.
If system pressure is low, the pump will restart when the STOP push-button is released.

To set this parameter press MENU button until “pressure settings” appears on the display. Use
the key to scroll to the “Manual Stop Only” setting. The set value will be displayed. Press
ENTER to change the setting. Enter operator password. Use the or keys to toggle the
setting. Press ENTER to store the setting. Press HOME to return to the main screen.

23
PRESSURE SETTINGS - PRESSURE UNITS

MENU

PRESSURE
SETTINGS

(ENTER OPERATOR
PASSWORD)
PRESSURE
ENTER
UNITS

SET
ENTER PRESSURE
UNITS

The Mark II can display pressure in either “psi” or “bar”. To change this setting, press MENU
until “Pressure Settings” appears on the display. Use the key to scroll to the “Pressure
Units” setting. The existing setting will be displayed. Press ENTER to change the setting.
Enter operator password. Use the or keys to toggle the setting. Press ENTER to store
the setting. Press HOME to return to main screen.

24
PRESSURE SETTINGS - LOW SUCTION & LEVEL

MENU

PRESSURE
SETTINGS

(ENTER OPERATOR
PASSWORD)
LOW
SUCT & ENTER
LEVEL

SET
ENTER CONTROL
& INPUT

SET
ENTER ON DELAY
& RESET

These settings provide for alarm or shutdown if there is a problem with the water supply to the
pump. Depending on settings, the controller will display “Low Suction Pressure” or “Reservoir
Low” if one of these conditions occur.

Press MENU until “Pressure Settings” is displayed. Use the key to scroll to the “Low Suction
& Level” setting. To change, press ENTER and enter the operator password. The settings for
“control” and “input” will be displayed. To modify the settings, press ENTER. The cursor will
flash next to the “control” setting. Use the and keys to set the desired control method
(Off, Alarm or Shutdown). Use the key to move the cursor to the “Input” setting. Use the
and keys to set the desired input (Level or Suction). Press ENTER to store the new
setting. Use the key to see the current settings for “On Delay” and “Reset”. Press EN-
TER to change these settings. Use the and keys to set the desired delay time (5 - 60
seconds). Use the key to move the cursor to the “reset” setting. Use the and keys
to set the desired reset method (Auto or Manual). Press ENTER to store the new setting.
(Note: Manual Reset will only be available if the controller was ordered with the manual reset
option). Press HOME to return to the main screen.

25
PRESSURE SETTINGS - PRESSURE CALIBRATION

MENU

PRESSURE
SETTINGS

(ENTER SUPERVISOR
PASSWORD)
PRESSURE
ENTER
CALIBRATION

ZERO
ENTER
CALIBRATION

SET
ENTER ZERO
CALIBRATION

SET
SPAN
SPAN ENTER
CALIBRATION
CALIBRATION

(Note: Pressure is calibrated at the factory. Firetrol does not recommend calibration by build-
ing service or maintenance personnel. Improper calibration could lead to a failure of the fire
pump controller to properly react to changes in system pressure.)

Press MENU until “Pressure Settings” appears on the display. Use the key to scroll to the
“Calibration” setting. Press ENTER to continue. Enter supervisor password. Press ENTER
to calibrate the Zero setting or press the key to go to the Span setting, press ENTER to
calibrate the span setting.

Zero Calibration - Display will read “Set Transducer Input to Zero Pressure”. Remove system
pressure from the sensing line. When pressure has been removed, press ENTER. Display
will read “Set Zero Pressure” ZP=0. Use the and keys to set a minimum pressure if
zero pressure cannot be obtained. Press ENTER to store the setting. Press ENTER to exit.
Press HOME to return to the main screen.

Span Calibration - Display will read “Set Transducer Input to Span Pressure”. Set system
pressure to a known pressure using a calibrated gauge or other accurate pressure measur-
ing device. Press ENTER. Display will read “Set Span Pressure” SP=100. Use the and
keys to set the pressure to match the reading on calibrated gauge or other accurate de-
vice. Press ENTER to store the setting. Press ENTER to exit. Press HOME to return to the
main screen.
26
TIMERS - ON DELAY TIME

MENU

TIMER
SETTINGS

(ENTER OPERATOR
PASSWORD)
ON
DELAY ENTER
TIME

SET ON
ENTER DELAY
TIME

Also known as sequential start time, this setting determines the amount of time the controller
waits to start the motor when a starting cause is present.

Press MENU until “Timers” is displayed. The current setting will be displayed, to change the
setting press ENTER. Enter operator password. The cursor will flash next to the timer set-
ting. Use the and keys to set the desired on delay time (timer range is 0 - 60 seconds).
Press ENTER to store the new setting. Press HOME to return to the main screen.

27
TIMERS - MINIMUM RUN TIME

MENU

TIMER
SETTINGS

(ENTER OPERATOR
PASSWORD)
MINIMUM
RUN ENTER
TIME

SET MIN.
ENTER RUN
TIME

This setting determines the length of time the motor runs once started. The default setting is
10 minutes. This timer prevents short-cycling of the motor. The controller will stop the motor
after this timer expires, providing all starting causes have been satisfied.

Press MENU until “Timers” is displayed. Use the key to scroll to the “Min Run Time” set-
ting. The current value will be displayed. To change, press ENTER and enter the operator
password. The cursor will flash next to the timer setting. Use the and keys to set the
desired minimum run time (timer range is 0 - 60 minutes). Press ENTER to store the new
setting. Press HOME to return to the main screen.

28
TIMERS - OFF DELAY TIME

MENU

TIMER
SETTINGS

(ENTER OPERATOR
PASSWORD)
OFF
DELAY ENTER
TIME

SET OFF
ENTER DELAY
TIME

This setting determines the length of time the motor runs after the starting cause is satisfied.
The default setting is zero. This timer is in lieu of, not in addition to, the minimum run timer.
The minimum run time must be set to zero for the off delay time to be active.

Press MENU until “Timers” is displayed. Use the key to scroll to the “Off Delay Time” set-
ting. The current value will be displayed. To change, press ENTER and enter the operator
password. The cursor will flash next to the timer setting. Use the and keys to set the
desired off delay time (timer range is 0 - 60 minutes). Press ENTER to store the new setting.
Press HOME to return to the main screen.

29
TIMERS - WEEKLY TEST TIME

MENU

TIMER
SETTINGS

(ENTER OPERATOR
PASSWORD)
WEEKLY
TEST ENTER
TIME

SET
TEST
HOUR

ENTER

SET
TEST
DAY

SET
TEST
FREQUENCY

SET
TEST
DURATION

The controller is supplied with a weekly test timer which will automatically start, exercise the
motor and stop. To set the weekly test timer, press MENU until “Timers” is displayed. Use
the key to scroll to the “Weekly Test” setting. The existing setting will be displayed, press
ENTER to change the settings. Enter the operator password. The cursor will flash on the
hour that the test is to start. Use the and keys to set the desired hour. Use the key
to advance the cursor to the day setting. Use the and keys to set the desired day that
the test will occur. Use the key to advance the cursor to the test duration setting. Use the
and keys to set the desired length of time to run the motor (timer range is 1 - 30 min-
utes). Use the key to advance the cursor to the frequency setting. This setting determines
how often the test is performed. Use the and keys to set the desired frequency (set-
ting can be 0 thru 4 weeks. 0 = Off (do not run test). 1 = Run test at set day and time every
week. 2 = Run test at set day and time every other week. 3 = Run test at set day and time
every third week. 4 = Run test at set day and time every 4th week (monthly)). Press ENTER
to store the value. Press HOME to return to the main screen.
30
ALARM LIMITS - UNDER VOLTAGE

MENU

ALARM
LIMITS

(ENTER OPERATOR
PASSWORD)
UNDER
ENTER
VOLTAGE

SET
ENTER UNDER
VOLTAGE

To set the Under Voltage alarm limit, press MENU until the “Alarm Limits” screen appears.
Use the key to scroll to the “Under Voltage” screen. The set values will be shown. Press
ENTER to change the setting. Enter the operator level password. Use the and keys
to change the value. Press ENTER to store the setting. Press HOME to return to the main
screen. Following are the available ranges:

Under Voltage-
Voltage Frequency (Hz) Range
2300 60 1955 - 2299 / Off
3300 60 2805 - 3299 / Off
4160 60 3536 - 4159 / Off
5500 60 4675 - 5499 / Off
6000 60 5100 - 5999 / Off
6300 60 5355 - 6299 / Off
6600 60 5610 - 6599 / Off
6900 60 5865 - 6899 / Off

31
ALARM LIMITS - OVER VOLTAGE

MENU

ALARM
LIMITS

(ENTER OPERATOR
PASSWORD)
OVER
ENTER
VOLTAGE

SET
ENTER OVER
VOLTAGE

To set the Over Voltage alarm limit, press MENU until the “Alarm Limits” screen appears.
Use the key to scroll to the “Over Voltage” screen. The set values will be shown. Press
ENTER to change the setting. Enter the operator level password. Use the and keys
to change the value. Press ENTER to store the setting. Press HOME to return to the main
screen. Following are the available ranges:

Over Voltage-
Voltage Frequency (Hz) Range
2300 60 Off / 2301 - 2530
3300 60 Off / 3301 - 3630
4160 60 Off / 4161 - 4576
5500 60 Off / 5501 - 6050
6000 60 Off / 6001 - 6600
6300 60 Off / 6301 - 6930
6600 60 Off / 6601 - 7260
6900 60 Off / 6901 - 7590

32
ALARM LIMITS - VOLTAGE IMBALANCE

MENU

ALARM
LIMITS

(ENTER OPERATOR
PASSWORD)
VOLTAGE
ENTER
IMBALANCE

SET
ENTER VOLTAGE
IMBALANCE

To set the Voltage Imbalance alarm limit, press MENU until the “Alarm Limits” screen appears.
Use the key to scroll to the “Voltage Imbalance” screen. The present values will be shown.
Press ENTER to change the setting. Enter the operator level password. Use the and
keys to change the value. Press ENTER to store the setting. Press HOME to return to
the main screen. Following are the available ranges:

Voltage Imbalance-
Setting is in percentage. The setting range is from OFF to 4%.

33
ALARM LIMITS - FREQUENCY

MENU

ALARM
LIMITS

(ENTER OPERATOR
PASSWORD)
FREQUENCY
ENTER
IMBALANCE

SET
ENTER FREQUENCY
IMBALANCE

To set the Frequency alarm limit, press MENU until the “Alarm Limits” screen appears. Use
the key to scroll to the “Frequency” screen. The present will be shown. Press ENTER to
change the setting. Enter the operator level password. Use the and keys to change
the value. Press ENTER to store the setting. Press HOME to return to the main screen.
Following are the available ranges:

Frequency -
60 Hz 50 Hz
Lo / Hi Lo /Hi
58 / 62 48 / 52
59 / 61 49 / 53
Off Off

34
ALARM LIMITS - MOTOR OVERLOAD

MENU

ALARM
LIMITS

(ENTER OPERATOR
PASSWORD)
MOTOR
ENTER
OVERLOAD

SET
ENTER MOTOR
OVERLOAD

To set the Motor Overload alarm limit, press MENU until the “Alarm Limits” screen appears.
Use the key to scroll to the “Motor Overload” screen. The set value will be shown. Press
ENTER to change the setting. Enter the operator level password. Use the and keys
to change the value. Press ENTER to store the setting. Press HOME to return to the main
screen. Following are the available ranges:

Motor Overload -
This value is set in amps - from 100% to 150% of the motor FLA.
(example: Motor FLA = 124 Amps - setting range = Off/124 Amps to 186 Amps)

Note: To view the Motor FLA for which the Mark II is set, see “System Setup” Menu.

35
ALARM LIMITS - REVERSE PHASES

MENU

ALARM
LIMITS

(ENTER OPERATOR
PASSWORD)
REVERSE
ENTER
PHASES

SET
ENTER PHASE
ROTATION

The Mark II is designed to indicate phase loss and/or phase reversal. Separate LED’s
indicate POWER ON and PHASE REVERSAL. If external alarms are wired, these failures
will also be indicated at the remote alarm location. The Mark II is factory programmed for the
standard ABC phase relationship. If voltage is available on all three phases and the PHASE
REVERSAL LED comes on, proceed with the following:
Press MENU until the “Alarm Limits” screen appears. Use the key to scroll to the “Re-
verse Phases” screen. The existing phase rotation setting will be displayed (ex..ABC). Press
ENTER to change the setting. Enter the “operator” password. Use the or key to change
the setting (ex..ACB). Press ENTER to store the setting. Press HOME to return to the main
screen. The alarm should clear.

Note: This method cannot be used to clear a phase reversal on controllers with Model Number
FTA1900.

36
CLOCK SET

MENU

(ENTER OPERATOR
PASSWORD)
CLOCK
ENTER
SET

SET HOUR
ENTER (24 HR
FORMAT)

SET
YEAR

SET
MINUTE

SET
DATE

SET
MONTH

Press MENU button until “Clock Set” appears on the display. Press the ENTER key to change
the settings. Enter the operator password. The time and date will appear with a flashing cur-
sor over the hour (hour is in 24 hour format). Use the and keys to set the current hour.
Use the key to move the cursor to the minute setting. Use the and keys to set
the current minute. Use the key to move the cursor to the month setting. Use the and
keys to set the current month. Use the key to move the cursor to the date setting. Use
the and keys to set the current date. Use the key to move the cursor to the year
setting. Use the and keys to set the current year. When settings are satisfactory, press
ENTER to return to the main screen.

37
CLOCK SET - DAYLIGHT SAVINGS TIME

MENU

CLOCK
SET

(ENTER OPERATOR
PASSWORD)
DAYLIGHT
SAVING ENTER
TIME

SET
ENTER DAYLIGHT
SAVING

The Mark II can automatically adjust the clock for daylight savings time. If this setting is set
to “enable’ the time will automatically reset as required.

Press MENU button until “Clock Set” appears on the display. Use the key to scroll to the
“Daylight Savings” screen. Press the ENTER key to change the settings. Enter the operator
password. Use the and keys to enable or disable this setting. Press ENTER to store
the new setting. Press HOME to return to the main menu.

38
DIAGNOSTICS - SOFTWARE VERSION

MENU

DIAGNOSTICS

SOFTWARE
VERSION

To view the loaded software version press MENU until the “Diagnostics” screen appears. Use
the key to scroll to the “Software Version” screen. The loaded revision level will be shown.
Press HOME to return to the main screen.

39
DIAGNOSTICS - LAMP TEST

MENU

DIAGNOSTICS

PERFORM ALL
LAMP ENTER LED'S
TEST ON

ANY KEY

To perform a lamp test, press MENU until the “Diagnostics” screen appears. Use the key
to scroll to the “Perform Lamp Test” screen. Press ENTER to perform the test. All Mark II
LED’s should illuminate. Press any key to end the test. Press HOME to return to the main
screen.

40
DIAGNOSTICS - 120VAC INPUTS 1-16

MENU

DIAGNOSTICS

120VAC
INPUTS
1-16

To view 120VAC inputs (1-16) to the Mark II press MENU until the “Diagnostics” screen ap-
pears. Use the key to scroll to the “120VAC Inputs 1-16” screen. This screen displays the
status of the first 16 120VAC inputs to the Mark II. A zero designates no input, a 1 indicates
an input is present. Not all inputs are used on all controllers. The inputs read from left to right
and are designated as follows:
1 - User 1 2 - User 2
3 - User 3 4 - User 4
5 - User 5 6 - User 6
7 - User 7 8 - User 8
9 - Not Used 10 - Automatic Start
11 - Weekly Test Push-button 12 - Control Voltage Present
13 - Not Used 14 - Not Used
15 - Not Used 16 - Not Used

41
DIAGNOSTICS - 120VAC INPUTS 17-24

MENU

DIAGNOSTICS

120VAC
INPUTS
17-24

To view 120VAC inputs (1-16) to the Mark II press MENU until the “Diagnostics” screen ap-
pears. Use the key to scroll to the “120VAC Inputs 1-16” screen. This screen displays the
status of 120VAC inputs 17 thru 24 into the Mark II. A zero designates no input, a 1 indicates
an input is present. Not all inputs are used on all controllers. The inputs read from left to right
and are designated as follows:
17 - Not Used
18 - Not Used 19 - Deluge Valve Open
20 - Interlock 21 - Manual Stop
22 - Emergency Run 23 - Remote Start
24 - Local Start

42
DIAGNOSTICS - 120VAC OUTPUTS

MENU

DIAGNOSTICS

120VAC
OUTPUTS

To view 120VAC outputs from the Mark II press MENU until the “Diagnostics” screen appears.
Use the key to scroll to the “120VAC Outputs” screen. This screen displays the status
of 120VAC output from the Mark II. A zero designates no output, a 1 indicates an output is
present. Not all outputs may be used on all controllers. The outputs read from left to right
and are designated as follows:
1 - Motor Run1 (1CR) 2 - Not Used
3 - Audible Alarm 4 - Alarm Relay
5 - User 1 6 - User 2
7 - User 3 8 - User 4
9 - User 5 10 - User 6
11 - User 7 12 - User 8
13 - Weekly Test Timer Solenoid 14 - Phase Reversal
15 - Phase Reversal 16 - Phase Failure
17 - AC Common 18 - AC Common

43
DIAGNOSTICS - KEYPAD TEST

MENU

DIAGNOSTICS

KEYPAD FACTORY
TEST USE
ONLY

The Keypad Driven Output is a diagnostic tool to be used only by factory service techni-
cians.

44
DIAGNOSTICS - SERIAL LOOPBACK TEST

MENU

DIAGNOSTICS

SERIAL FACTORY
LOOPBACK USE
TEST ONLY

The Serial Loopback Test is a diagnostic tool to be used only by factory service technicians.

45
DIAGNOSTICS - FLASH MEMORY TEST

MENU

DIAGNOSTICS

FLASH FACTORY
MEMORY USE
TEST ONLY

The Flash Memory Test is a diagnostic tool to be used only by factory service technicians.

46
DIAGNOSTICS - USB LOOPBACK TEST

MENU

DIAGNOSTICS

USB FACTORY
LOOPBACK USE
TEST ONLY

The USB Loopback Test is a diagnostic tool to be used only by factory service technicians.

47
DIAGNOSTICS - USB DRIVE TEST

MENU

DIAGNOSTICS

USB FACTORY
DRIVE USE
TEST ONLY

The USB Drive Test is a diagnostic tool to be used only by factory service technicians.

48
SYSTEM SETUP - MODEL CONFIGURATION

MENU

SYSTEM
SETUP

MODEL FACTORY
CONFIG USE
ONLY

To view the controller model configuration press MENU until the “System Setup” screen ap-
pears. Press the key to scroll to the “Model Configuration” screen. The existing value
will be shown.

The model configuration supplies information vital to the operation of the Mark II. The model
configuration can only be changed by factory service technicians.

49
SYSTEM SETUP - OPTION CONFIGURATION

MENU

SYSTEM
SETUP

OPTION FACTORY
CONFIG USE
ONLY

To view the controller option configuration press MENU until the “System Setup” screen ap-
pears. Press the key to scroll to the “Option Configuration” screen. The present value
will be shown.

The option configuration supplies information vital to the operation of the Mark II. The model
configuration can only be changed by factory service technicians.

50
SYSTEM SETUP - SYSTEM LANGUAGE

MENU

SYSTEM
SETUP

(ENTER OPERATOR
PASSWORD)
SYSTEM
ENTER
LANGUAGE

SELECT
ENTER SYSTEM
LANGUAGE

This setting determines the language which is displayed on the Mark II screens.

To change the controller system language, press MENU until the “System Setup” screen ap-
pears. Press the key to scroll to the “System Language” screen. The set value will be
shown. Press ENTER and input operator password, use the S and T arrows to select the
desired language. Press ENTER to accept the change.

51
SYSTEM SETUP - SYSTEM VOLTAGE

MENU

SYSTEM
SETUP

SYSTEM FACTORY
VOLTAGE USE
ONLY

To view the controller system voltage configuration press MENU until the “System Setup”
screen appears. Press the key to scroll to the “System Voltage” screen. The set value
will be shown. This value should match the voltage being supplied to the controller.

The system voltage setting supplies information vital to the operation of the Mark II. The
system voltage can only be changed by factory service technicians.

52
SYSTEM SETUP - SYSTEM FREQUENCY

MENU

SYSTEM
SETUP

SYSTEM FACTORY
FREQUENCY USE
ONLY

To view the controller system frequency (hertz) configuration press MENU until the “System
Setup” screen appears. Press the key to scroll to the “System Frequency” screen. The
present value will be shown. This value should match the voltage frequency being supplied
to the controller.

The system frequency setting supplies information vital to the operation of the Mark II. The
system frequency can only be changed by factory service technicians.

53
SYSTEM SETUP - MOTOR FLA

MENU

SYSTEM
SETUP

MOTOR FACTORY
FLA USE
ONLY

To view the controller Motor FLA configuration press MENU until the “System Setup” screen ap-
pears. Press the key to scroll to the “Motor FLA” screen. The set value will be shown.

The motor FLA setting supplies information vital to the operation of the Mark II. The motor
FLA can only be changed by factory service technicians.

54
SYSTEM SETUP - CT RATIO

MENU

SYSTEM
SETUP

CT FACTORY
RATIO USE
ONLY

To view the controller CT Ratio configuration press MENU until the “System Setup” screen
appears. Press the key to scroll to the “CT Ratio” screen. The set value will be shown.

The CT ratio setting supplies information vital to the operation of the Mark II. The CT ratio
can only be changed by factory service technicians.

55
SYSTEM SETUP - SERIAL NUMBER

MENU

SYSTEM
SETUP

SERIAL FACTORY
NUMBER USE
ONLY

To view the controller Serial Number press MENU until the “System Setup” screen appears.
Press the key to scroll to the “Serial Number” screen. The present value will be shown.

The serial number supplies information vital to record keeping. The serial number can only
be changed by factory service technicians.

56
SYSTEM SETUP - FLASH DRIVE AUTOSAVE
MENU

SYSTEM
SETUP

(ENTER OPERATOR
PASSWORD)
FLASH
DRIVE ENTER
AUTOSAVE

SET
ENTER AUTOSAVE
FUNCTION

The controller is supplied standard with a host USB port. The autosave function of the Mark II is
disabled by default. To enable the autosave function, press MENU until the “System Setup” screen
appears. Press the T key to scroll to the “Flash Drive Autosave” screen. The current status will be
displayed. To change the setting press the ENTER key and input the operator password. Use the T
or S keys to enable or disable the feature. Press ENTER to confirm your selection.

When enabled, a log of all events are written to a USB Flash Disk (aka Flash Drive or Memory Stick).
The log is automatically written to the disk on a daily basis at the end of each day (0:00). This record
is broken down into monthly files on the disk. Each file consists of one month’s worth of data, broken
down into individual days. For example the recorded data for the month of August, 2007 would have
a file named “2007-08.txt”. The data is recorded in text (.txt) format and can be viewed with any text
editor, but the recommended method is to import the data into a spreadsheet program such as Micro-
soft® Excel®. This allows for easier sorting and searching of the data.

Data can be written to the flash disk at any time by pressing the SAVE TO DISK button on the Mark
II interface. Enter the “operator” password. The display will show “Disk Save Active” while the file is
being written to the disk, the time and date will reappear when the save is complete. The name of
the file written to the disk will be “Savedisk.txt”. This file will contain the contents of the Event Log, the
Data Log and the System Setup. When using the SAVE TO DISK function, any previous “Savedisk.
txt” file on the flash disk will be overwritten with the new file.

A DISK ERROR message will be given if a flash disk is not inserted into the USB port and data is
attempting to write to the disk. To clear this error, insert a disk into the port and press the SAVE TO
DISK push-button on the Mark II. A DISK FULL ERROR will occur if insufficient space remains on the
disk for a file attempting to write to the disk. To clear this error, insert a different flash disk and press
the SAVE TO DISK push-button on the Mark II. A DISK NEAR FULL message will be given prior to
DISK FULL ERROR and a different disk should be inserted at that time.

When the autosave feature is enabled, a flash disk should be left in the USB port at all times. Under
normal conditions, a small capacity flash drive would hold many years worth of data (approx. 1MB /
Year).

57
SYSTEM SETUP - SINGLE PHASE MODE

MENU

SYSTEM
SETUP

SINGLE FACTORY
PHASE USE
MODE ONLY

To view the Single Phase Mode setting press MENU until the “System Setup” screen appears.
Press the key to scroll to the “Single Phase Mode” screen. The set value will be shown.

The Single Phase Mode setting supplies information vital to the operation of the Mark II. The
Single Phase Mode setting can only be changed by factory service technicians.

58
SYSTEM SETUP - CLEAR EVENT LOG

MENU

SYSTEM
SETUP

CLEAR FACTORY
EVENT USE
LOG ONLY

The Event Log contains historical information regarding events surrounding the controller
operation.

The Event Log can only be cleared by factory service technicians.

59
SYSTEM SETUP - CLEAR DATA LOG

MENU

SYSTEM
SETUP

CLEAR FACTORY
DATA USE
LOG ONLY

The Data Log contains historical information regarding events surrounding the controller
operation.

The Data Log can only be cleared by factory service technicians.

60
SYSTEM SETUP - CHANGE PASSWORDS

MENU

SYSTEM
SETUP

ENTER

CHANGE
PASSWORD

(ENTER
PASSWORD)

ENTER
NEW
PASSWORD

CONFIRM
ENTER NEW
PASSWORD

The controller is shipped with pre-programmed passwords. Each password “level” can change
it’s own level and any level below it. This manual only details level 1 “operator”, and level 2
“supervisor” functions. Any settings that cannot be changed with a level 1 or level 2 password
will require a factory trained service technician.

To change the Password, press MENU until the “System Setup” screen appears. Press the
key to scroll to the “Change Password” screen. Press ENTER to change the password.
Enter the “level password”. Use the and keys to select the password level to change.
Enter the new password. Confirm the new password. Press ENTER to store the new pass-
word.

Note: If passwords are changed, then forgotten, costs may be incurred for a factory service
technician to visit the job site to reset the password.

61

Você também pode gostar