Escolar Documentos
Profissional Documentos
Cultura Documentos
Instrumentation and process control systems plays a vital role in monitoring and
controlling critical parameters for safe and efficient operation of plants part
icularly in Powerplant industries. In Rain CII the different process parameters
involved in calcination&powerplants are Temperature, Pressure, Flow, Level, Vibr
ation, Speed, pH and conductivity. The different sensors and transmitters measur
e all these parameters. Some of the parameters are used for indication only and
some are used for indication and controlling purpose.
PRESSURE
The pressure sensors using in Calcination&Powerplants are manometers, pressure g
auges and pressure transmitters.
The pressure gauges may Borden tube type (for medium pressure), Bellow type (low
pressure) or Diaphragm type (from few mmWC to several atm). All these gauges ar
e used only for local indication.
The pressure transmitters are used for indication and control purpose. All trans
mitters works on the principle that the change in the capacitance due to change
in area between a fixed electrode and two diaphragms causes current which in pro
portional to the pressure of the system under test.
Units : Kg/cm2, bar, mmWC, mm HG, psi, or Pascal.
Conversions : 1Kg/cm2 = 10000mmWC.
= (10000/13.6)mmHG
= 15psi.
= 100kpa.
Pressure fundamentals:
Pressure is a force applied to or distributed over a surface. The pressure(P)of
a force(F)distributed over an area(A) is defined as:
P=F/A
Consider the following arrangement whereby multiples of equal weights compress a
volume of air with in a cylindrical container.
Not only weights exert a force. a column of liquid or gas “stacks up” and produces a
down ward push. The height of the stack likewise represents the strenght of the
downward force and is called the “head” pressure.the units of head are normally len
gth but represent a force applied over a unit area.Traditionally, the downward p
ush of this column of water was expressed as:
5 inches water gauge(or)water column
Abbreviation-5” W.G. or 5”W.C.
Manometers:
1.the “U-tube” manometer is the eldest to manufacture and most widely used type.
Measurements are taken from the topmost point of the curved surface(meniscus)
of Hg and the lowest point of H20.
2.The well manometer amplifies the smaller level movement in the larger reservoi
r by using a narrower scaled tube. This increases sensitivity of measurement in
the ratio of the areas of the tubes.
Differential head type flowmeters are the most economical of all the flow-rate d
evices.They perform well with both liquids and gassed great deal of data and exp
erience are available to support their position. Then major limitations are diff
iculty in reading low flow rates,a suare-root relationship in read out, and mobi
lity to cope with certain types of fluids(e.g:slurries)
Some of these difficulties can be evercome by other types of flowmeters,such as
the magnetic flowmeters. as the pie are shows,the effect of the measured pressur
e is to increase the height of a column of material above its equilibrium state.
The difference in pressure between the process and reference is proportional to
the height of the fluid supported.
3).Metallic Diaphragms
Gauge employing diaphragms give better and more positive indication that the Bou
rbon types of gauge for low pressure range (below 15 psi).
The principle employed simply requires that the deformed middle section of the d
iaphragm push against and deference pointer on a scale. The aneroid barometer is
an example of just such a system.
4).Force Balance
Force balance pressure transmitters are closed loop feedback device in a force b
alance ATM pressure displaces an element. The amount of displacement is detected
and the element is returned to a Null or zero displacement position by a restor
ing force, which can be pneumatic.
Force balance type transmitters have been around for a long time and are fam
iliar to many users. They are rugged and work well with high pressure.
But, they are big and can be sensitive to vibration and temperature.
In the situation above, a “force-balance” principle is employed to generate a pneuma
tic signal proportional to the diaphragm deformation.
As the force bar is deflected towards the nozzle, back pressure in the nozzle is
communicated to the output signal and the feedback bellows.
These bellows bring the force bar to a new equilibrium position.
B) Electronic Transducers
The common pressure measurement techniques are strain gauge, force balance, vari
able reluctance, capacitance, vibration wire, and solid state.
Stain Gauge: Stain Gauge exhibits a change in electrical resistance that is prop
ortional to a deformation that occurs when they are stretched. Thus, strain gaug
e elements can be used to convert mechanical displacement caused by pressure int
o an electronic signal, strain gauge pressure sensors are classified by the mate
rial used for the strain gauge element and the method used to mount it to a mech
anical element (diaphragm or beam) that will be deformed under pressure. In most
instances, variable resistive stain gauge elements are configured into a wheats
tone bridge. The circuit will also include other resistors to provide adjustment
capability and temperature compensation.
A strain gauge is accurate but not linear. They are inherently temperature sensi
tive and required compensation. In addition, some mechanical method must be incl
uded in the over all sensing element to provide overpressure protection.
Accuracy of strain gauge based transmitters can vary from 0.1% to 1.0%fs, depend
ing upon the amount of temperature compensation and other circuitry built into t
hem. Obviously, then, price is a function of accuracy.
Variable reluctance: Variable reluctance transmitters operate on the principle o
f a moveable element changing position within a magnetic field. As a result, ind
uctance changes to produce an output voltage that is proportional to the pressur
e applied to the movable element. The transmitters are small and accurate, but t
hey have complicated circuitry and mechanical overpressure protection is require
d.
Variable capacitance: Variable capacitance transmitters operate by having one pl
ate of a capacitor moved when a pressure is applied. The movement changes the ca
pacitance signal in proportion to the applied pressure. Capacitance based transm
itters are accurate and small in size and weight. They are simple reliable and r
emain stable over a wide temperature range. These are still the most widely used
method of measuring differential pressure.
The important member of the variable capacitance family is the differential capa
citance transducer shown below.
Different pressure applied to the external diaphragms compress silicon oil along
ceramic channels, which in turn deform the capacitor plates (up to 1mm maximum)
differently relative to the sensing diaphragm. The error inherent in the separa
te capacitance measurement are negated when the difference is taken electronical
ly. The rigid insulation is glass.
The potential damage to external diaphragms due to overpressure is significant r
educed by the moulded face of the sensor body. The diaphragm is simply pushed ba
ck into this moulding and its own shape thereby reinforced.
Vibrating wire: Vibrating wire devices rely on an applied pressure to change the
frequency of a vibration wire. The change in frequency is proportional to the a
pplied pressure. Transmitters using this measurement method are very accurate, b
ut the sensor tends to be complicated and its operation pressure range is limite
d.
Solid state: Solid state pressure sensors are usually made of a single silicon c
rystal and measure a change in resistance or capacitance a pressure is applied.
As pressure is applied, the diaphragm distorts Capacitive sensors detect the dis
tortion directly and resistive sensor detect the resulting strain in the diaphra
gm. Resistive sensors typically have four resistors in the diaphragm, connected
as a whetstone bridge. The resistors are formed by diffusion or ion implantation
inside the silicon, or deposited in a thin film on top of the silicon.
Single crystal silicon is an excellent material for sensor because it exhibits a
lmost no hysteresis and its electrical properties can be controlled with semicon
ductor processing.
Pressure tapin
gs
Differential pre
ssure tapings
The following points may prove useful in ensuring the best possible conditions f
or accurate and low maintenance operation.
• Keep corrosive or hot process material away from the transmitter.
• Avoid sediment deposit in the impulse piping.
• Balance the liquid head on both legs of the impulse piping.
• Keep impulse piping as short as possible.
• Avoid ambient temperature gradients and fluctuations.
For liquid flow measurement, tap the side of the line to avoid sediment deposits
. Mount the transmitter beside or below the taps so gases will vent into the pro
cess line.
Taps should be made to the side of the line for transmitters having side vent/dr
ains. For liquid service, the side vent/drain should be mounted upward to allow
venting of gases. For gas service, it should be mounted down to allow draining o
f any accumulated liquid.
Slope piping at least 3cm in 30cm up toward the process connection for l
iquid and steam service.
• Slope piping at least 3cm in 30cm down towards the process connections for gas s
ervice.
• Avoid high points in liquid lines and low points in gas lines.
• Keep both impulse legs at the same temperature.
• Use impulse piping of sufficient diameter to avoid friction effects.
• Vent gas from liquid piping legs.
Fill both piping legs to the same level when using sealing fluid,
Avoid purging through the transmitter. Make the purge connection close t
o the process taps and purge through equal lengths or the same size pipe.
• Keep The Transmitter vertically then Connect 24 volts DC power supply ( alon
g with 250 Ohms Resistor ) and SFC to the pressure transmitter as per the
following circuit diagram.
250Ohms
+ +
_ _
• Connect the transmitter Pressure Tapping to the Pressure Source, with proper
fittings and tighten it fully.
• Switch On the 24 v DC power supply and SFC.
• Apply required pressures to the transmitter (with out any leaks) as mentioned
in the Calibration Report and note down the corresponding % out put Readings
of SFC in Before calibration column of Calibration report.
• Open the relief valve of Pressure source and allow it to stabilize. Then check
whether SFC reads zero % out put. If necessary correct LRV with the help of SFC
( Press LRV then Correct Then Enter ).
• Apply required pressure to the transmitter for Span calibration and stabili
ze the applied pressure.
• Then check whether the SFC reads 100% out put. If necessary correct URV with the
help of SFC ( Press URV then Correct Then Enter ).
• Repeat instructions 2.5 to 2.7 One or Two times for fine calibration.
• After Zero and Span calibration, check for linearity by applying different pre
ssures as mentioned in the Calibration Report and Note down the corresponding r
eadings in the after Calibration Column.
Calibration set up for Analog pressureTransmitter
Before Calibration :
• Clean the Transmitter properly
• Note down the Calibration Range of the Transmitter Form History Card.
Calibration method :
• Keep The Transmitter vertically then Connect 24volts DC power supply and Mi
lliammeter to the pressure transmitter as per the following circuit diagram.
• Connect the transmitter High Pressure Tapping to the Manometer / Pressure calib
rator as per requirement, with proper fittings and tighten it fully .
• Switch On the 24 V DC Power Supply and Multimeter.
• Apply required different pressures to the transmitter ( with out any leaks ) as
mentioned in the Calibration Report and note down the corresponding Milli amps o
ut put Readings in Before Calibration column of Calibration Report.
• Open the relief valve of pressure calibrator / Manometer and allow it to stabil
ize. Then check whether the Milliammeter reads 4mA DC. If necessary adjust it
for 4 ma.
• Apply require pressure to the transmitter HP side for Span calibration and s
tabilize the applied pressure. Then check whether the milli ammeter reads 20mA D
C. If necessary adjust it for 20 ma.
• Repeat instructions 2.5 to 2.6 One or Two times for Fine Calibration.
• After Zero and Span calibration, check for linearity by applying different pre
ssures as mentioned in the Calibration Report and Note down the corresponding r
eadings in the after Calibration Column.
TEMPERATRE
Temperature is a very important parameter in process industry. The tempe
rature sensors used in Calcination&Powerplants are Thermocouples, RTDs and Tempe
rature gauges.
Thermocouples are the temperature sensors works on the principle of “See b
ack effect”. There are different types of thermocouples such as J, K, R, S, E type
thermocouples to measure the temperature. But in Ammonia & Urea plants only ‘K’ typ
e and ‘R’ type thermocouples are under use. “K” type thermocouple is used in both plants
. “R” type thermocouple is used in Primary reformer of Ammonia plant where the tempe
rature to be measure in around 745Deg. C. “K” type thermocouple can be used to measu
re 0 – 1200 Deg. C range of temperature and the metals used are Chromel (+), and A
lumel (-) ‘R’ Type thermocouple can be used to measure 0-1482 Deg.C range of tempera
ture and the metals (or materials of construction) used ate plat. 13% Rhodium (+
) and Platinum (-). All these thermocouples are having two wires and can be used
for both indication and control purpose. Thermocouples are used for high temper
ature and are measured in mV.
RTDs (Resistance Temperature Detectors) are the temperature sensors, whi
ch works on the principle that when there is a change in the temperature of a su
bstance the resistance of the substance wills also changes. RTDs are used for in
dication and control purpose. All the RTDs are having there lead wires and are u
sed in both the plants. RTDs are used for low temperature measurements and are m
easured in Ohms.
All the temperature gauges are of bimetallic type (helical type). These
type gauges works on principle of coefficient thermal expansion. These temperatu
re gauges are used only for local indication.
Units of temperature: Deg. C or Deg. F.
CONVERTION FORMULAS:
BIMETALLIC THERMOMETERS:
The bimetallic thermometer is based on two simple principles. Fi
rst that metals change in volumes in response to a change in temperature and, se
condly, the coefficient of change is different for all metals. If two dissimilar
metal strips are bonded together and then heated the resultant strip will tend
to bend in the direction of metal with the lower coefficient of expansion. The d
egree of deflection is proportional to the change in temperature.
Since the amount of movement is typically rather small it is amp
lified by using a long strip of material would into a helix or a spiral. One end
of spiral is immersed in the medium to be measured and the other end is attache
d to a pointer. The bimetallic thermometer may be rugged enough to actuate a rec
order pen. The bimetallic thermometer offers the advantage of being much more re
sistant to breakage than the glass thermometer. It is however, subject to change
in calibration if handled roughly and the overall accuracy is not as good as th
e glass thermometer.
Thermocouple:
A Thermocouple is a thermoelectric temperature-measuring device. Welding, solder
ing or merely pressing two dissimilar metals together in series to produce a the
rmal electromotive force (E) forms it. When the junctions are at different tempe
ratures. The measuring, or hot, junction is inserted into the medium where the t
emperature is to be measured. The reference, or cold, junction is the open end t
hat is the open end that is normally connected to the measuring instrument’s termi
nals.
The magnitude of this voltage (E) depends on the pair of materials A+B, and diff
erence between the hot and cold junctions. T1 and T2. There fore, temperature ca
n be read directly by using a sensitive calibrated electromotive force (EMF) dev
ice.
Advantages:
• Moderate accuracy.
• Widest range (0-2000°F).
• Rugged
• Remote and versatile mounting
• Moderately stable
• Moderate cost
Disadvantages:
• Low output signal
• Calibration changed by contamination
• Electrical interference can be a problem
• Calibration is nonlinear over normal spans
• Higher installation costs(extension wires)
Advantages
• High accuracy, greatest over wide span.
• Relatively narrow spans, (10°F) can be measured.
• Reproducibility not affected by temperature change.
• Short-term reproducibility is better than that of thermocouples.
• Compensation not necessary.
• Handle suppressed ranges.
• Relatively small sizes.
Disadvantages
• More expensive.
• Limited above 1500°F.
• Less rugged.
• Self-heating may be a problem.
• Vibration can affect wire wound types.
Radiation pyrometer:
Radiation pyrometers inter temperature by collecting the thermal radiati
on from an object and focusing it on a sensor. The sensor or detector is typical
ly a photon detector. which produces an output as the radiant energy striking it
release electrical charges.
The advantage of the radiation pyrometer method is that they produce a stable no
n contact output signal. This is of particular usefulness when working with very
high process temperatures where conventional sensing elements would have very s
hort life spans. They are also useful in applications where the temperature of a
continuously moving sheet of material must be monitored. Radiation pyrometers c
an be very susceptible to ambient temperature fluctuations and often require spe
cial installation or water cooling to maintain a constant ambient.
Before Calibration :
• Clean the Transmitter properly
• Note down the Range of the Transmitter from History card.
Calibration Procedure :
• Connect 24volts DC power supply, Millimeter and Resistance Source to the Trans
mitter as per the following circuit diagram. Switch on the 24v supply.
• Apply Resistance ( As Per Standard Temperature Chart ) corresponding to differe
nt Temperatures as per requirement in Calibration Report and note down the corre
sponding out put “ma” readings in the Before Calibration column of the Calibration S
heet
I/p
+ +
Ohms 24V DC
Rh
supply
O/p -
- - +
Ma
• Apply Resistance Corresponding to 0°C and Check for 4 ma output in the Millimeter
display. If necessary adjust zero potentiometer.
• Apply Resistance Corresponding to span range and Check for 20 ma output in the
Millimeter. If necessary adjust span potentiometer.
• Repeat the Steps 2.2 to 2.3 One or Two for Fine Calibration.
• As per Calibration Chart requirement Apply Resistance corresponding to different
Temperatures and Note down the Corresponding Millimeter readings in After Calib
ration column of the Calibration Report.
Calibration for RTD (PT-100) Smart Temperature Transmitter (Make: Rosemount)
Calibration Method:
• Connect 24volts DC power supply, Decade resistance box and HART Communicator to
the transmitter as per the following circuit diagram. For three wire RTDs, short
terminals 2 and 3.
+
+
Ohms Resistance
24V DC
ma
supply
ou
tput -
250 ohm
• Repeat instructions as above for the fine calibration and note the error if any.
Calibration Procedure :
• Connect 24volts DC power supply, Millimeter and Millville source to the conve
rter as per the following circuit diagram.
+ +
+
mV mV 24V DC
source ma
supply
- - Ma
+ -
• Apply Milli volts ( As Per Standard Temperature Chart ) corresponding to differ
ent Temperatures as per requirement in Calibration Report and note down the corr
esponding out put “ma” readings in the Before Calibration column of the Calibration
Sheet.
• Apply Milli volts Corresponding to 0°C and Check for 4 ma output in the Millimete
r display. If necessary adjust zero potentiometer.
• Apply the Milli volt Corresponding to span range and Check for 20 ma output in
the Millimeter. If necessary adjust span potentiometer.
• Repeat the Steps 2.2 to 2.3 One or Two for Fine Calibration.
• As per Calibration Chart requirement Apply Millie volts corresponding to differe
nt Temperatures and Note down the Corresponding Millimeter readings in After Ca
libration column of the Calibration Report.
FLOW:
Measuring fluid flow is one of the most important aspects of process control. In
fact,it may well be the most frequently measured process variable.
Flow is generally measured inferentially by measuring velocity through a known a
rea. with this indirect method, the flow measured is the volume flow rate, Qv .s
tated in its simplest terms:
Qv = A х V
In this equation, A is the cross sectional area of the pipe and V is the fluid v
elocity.
A reliable flow indication is dependent upon the correct measurement of A and V.
if for example, air bubbles are present in the fluid, the area term ′A′ of the equa
tion would be artificially high. Likewise, if the velocity is measured as a poin
t velocity at the center of the pipe, and it is used as the velocity term ′V′ of the
equation, a greater Qv than actual would be calculated because V must reflect t
he average velocity of the flow as it passes a cross section of the pipe.
The different flow sensors used in Calcination & Powerplants are
i) Flow transmitters using Orifice plates.
ii) Magnetic Flow meter (KHRONE) which works on the principle of ‘Faradays law
of electromagnetic induction; is using in Urea plant.
iii) Turbine flow meter (Bop & Reuther) is using in Urea plant.
iv) Rotameters used in both the plants (Only one Rotameter is using in Ammon
ia plant).
v) Annubar is using in Ammonia plant.
vi) Pitot Tube
vii) Ultrasonic Flow meter
All the above flow sensors are used for indication and control purpose.
Unites cu m/Lr., Lrs/m in., mm WC, Gallon/m in, M3/hr.
Differential pressure flowmeters:
Head meters are most common type of meter used to measure fluid flow rates. They
measure fluid flow indirectly by creating and measuring a differential pressure
by means of an obstruction to the fluid flow. Using well-established conversion
coefficients which depend on the type of head meter used and the diameter of th
e pipe, a measurement of the differential pressure may be translated in to a vol
ume rate.
Orifice plates:
A concentric, sharp-edged orifice plate is the simplest and least expensive of t
he head meters. acting as a primary device, the orifice plate constricts the flo
w of a fluid to produce a differential pressure across the plate. The result is
a high pressure upstream and a low pressure down stream that is proportional to
the square of the flow velocity. An orifice plate usually produces a greater ove
rall pressure loss than other primary devices. A practical advantage of this dev
ice is that cost does not increase significantly with pipe size. the four types
of orifice plates are shown below.
Flow nozzle:
Flow nozzles may be thought of as a variation on the venturi tube. The nozzle op
ening is an elliptical restriction in the flow but with no outlet area for press
ure recovery. pressure taps are located approximately ½ pipe diameter downstream a
nd 1pipe diameter upstream. The flow nozzle is a high velocity flowmeter used wh
ere turbulence is high such as in steam flow at high temperatures. the pressure
drop of a flow nozzle falls between that of the venturi tube and the orifice pla
te (30% to 95%).
Pitot tubes:
In general a pitot tube for indicating flow consists of two hollow tubes that se
nse the pressure at different places within the pipe. These tubes can be mounted
separately in the pipe or installed together in one casing as a single device.
One tube measures the stagnation or impact pressure at a point in the flow. The
other tube measures only the static pressure, usually at the wall of the pipe. T
he differential pressure sensed through the Pitot tube is proportional to the sq
uare of the velocity. Installing Pitot tubes involves determining the location o
f maximum velocity with pipe traverses. Though a Pitot tube may be calibrated to
measure fluid flow to 1/2%, changing velocity profiles may cause significant er
rors. This is one reason Pitot tubes are primarily used to measured gases since
the change in the flow velocity from average to centre is not a serious draw bac
k. Pitot tubes have found limited applications in industrial markets because the
y can easily become plugged with foreign material in the fluid. Their accuracy i
s dependent on the velocity profile and they develop a very low differential pre
ssure, which is difficult to measure.
Annubar:
The annubar’s principle of operation is similar to that of a standard Pitot tube w
ithout the inaccuracy of single-point or the requirement of traversing and avera
ging. The Annubar averages the flow via multiple upstream and downstream sensor
ports and provides a differential pressure proportional to the flow rate.
The sensor is a multiple tube, rigid structure that provides dual-averaging cham
bers with a diamond-shaped cross section.
The diamond shape establishes a fixed separation point of the fluid from the sen
sor. This eliminates any shift in the low-pressure signal that would cause a cor
responding loss of flow measurement accuracy.
An Annubar can provide accurate measurement within 1% in all sizes.
It will maintain its accuracy over an extremely long period of time. The diamond
shaped flow coefficient remains stable over the long term and is unaffected by
wear, dirt or grease build up.
LEVEL
The following are the devices used to measure the level in both the Calc
ination&Power plants.
i) D. P. Transmitter
ii) Level controller is used for indication and control purpose
iii) Hydrostep which is based on the resistivity of the two substances (water
and steam) that can be used for local indication only. This is used in Ammonia
plant.
iv) Capacitive type
v) Radioactive type
vi) Purge type
vii) 3-Element Controller (Boiler Level Controller)
Level gauges used only for local indication.
Unit
: %
MESUREMENTS OF LEVEL:
DIRECT METHODS
Sight Glass
The steam boilers and similar applications, a simple device for enabling th
e level with in the boiler to be determined is the sight glass. It consists of a
tube of toughened glass connected at both ends through asbestos packed unions a
nd valves into the boiler, in which the water level is required. If the diameter
of the bore of the tube is not small enough to introduced errors due to capalir
ity the liquid will stand at the same level in the boiler and tube. The two valv
es are provided so the steam may be shut of in case of breakage of the sight gla
ss. The smaller valve at the bottom is provided for blowing out the gauge for cl
eaning purposes.
FLOAT ACTUATED MECHANISMS
The following diagrams illustrate different float types and indicators.
Float operated gauge level indicator indicated liquid level in cone or flat roof
UN-pressurized tanks. Recommended for use on tanks storing water, flue water, c
hemicals other liquid products where operations do not require extreme accuracy
cable pipe entry should be near an existing roof man hole or an inspection cover
.
The measurement of liquid level of medium and high pressure storage vessels
presence unique problems which are not encounter with standard atmospheric or l
ow pressure vessels. Butane and propane, for e.g., must be stored under pressure
to comprise them into there liquid state. The indicating gauge shown here uses
perforated tape. As long s tension is maintained, accuracy’s of 3mm over full range
can be achieved, Cam operated limit switches can be incorporated too.
Capacitive Probes
A Capacitive probe works in most liquids (and solids), as it relies upon th
e dielectric constant of the liquid to operate. As the liquid rises in the space
between two electrodes, which are in effect the two plates of a capacitor, the
variation in capacitance can be monitored and set to alarm. The nature of the li
quid must be considered. If it is non-conductive then with the vessel wall as th
e second plate. The primary electrode or the first plate only should be insulate
d from the vessel. However, if the liquid is conductive, the primary electrode m
ust be fully insulated from the vessel and the liquid, usually via a coating of
some sort. In this case, the liquid itself acts as the second plate of the capac
itor, with the insulation of the primary electrode acting as the dielectric. Pro
blems often arise from in correct in installation, build up of conductive coatin
gs, damage to insulation and false signals caused by foams.
For some organic based oils such as hydraulic fluid, the low dielectric con
stant means that the probe sensitivity has to be increased, which can also lead
to false alarms.
To over come some of the problems mentioned above, a RF (radio frequency) c
apacitance system is available the radio frequency excites the two electrodes, o
ne of which may again be the vessel wall of appropriate. An electronic control b
ox monitors the capacitance caused by the level of the liquid between the probes
and the resistance caused by any coating, the later being measured and then eli
minated by the electronics.
Pressure Operated Level Gauging
Bottom Mounted Transmitter
In open vessels the pressure transmitter mounted near the bottom of the tan
k will measure the pressure corresponding to the height of the fluid above it.
The connection is made to the high-pressure side of the transmitter. The lo
w-pressure side is vented to atmosphere. If zero point of the desired level rang
e is above the transmitter, zero suppression of the range must be made. This adj
ustment is limited to 500 percent of the span on the 1151 DP and 500 percent of
the span on the 1151 GP.
Example
Let X = vertical distance between the minimum and maximum measurable levels
Equal to 500 inches.
Y = vertical distance between the transmitter datum line and the minimum m
easurable level equal to 100 inches
SG = specific gravity of the fluid equal to 0.9
H = maximum head pressure to be measured in inches of water.
E = head pressure produced by y expressed in inches of water.
Range = e to e + h, h = (X). (SG) = 450 inches WG,
Then e = (y).(SG) = 90 inches WG,
Range = 90 to 540 inches WG,
Top Mounted Transmitter
A “bubblier” system using a top mounted pressure transmitter can be used in open ves
sels. This system consists of an air supply, a pressure regulator, a constant fl
ow meter, a pressure transmitter and tube extending down into the vessel.
Air is bubbled through the tube at a constant flow rate the pressure required to
maintain flow is determined by the vertical height of the liquid above the tube
opening times the specific gravity.
Examples
Let X = Vertical distance between the minimum and maximum measurements levels eq
ual to 100 inches.
SG = Specific gravity of the fluid = 1.1
H = Maximum head pressure to be measured in inches of water.
Range = zero to h
Then h = (X).(SG)=100 inches WG
Range = 0 to 110 inches WG
CLOSED VESSELS
In closed vessels the pressure above the liquid will affect the pressure measur
ed at the bottom. The pressure at the bottom of the vessel is equal to the heigh
t of the liquid multiplied by the specific gravity of the liquid plus the vessel
pressure.
To measure true level, the vessel pressure must be subtracted from the meas
urement. This is accomplished by making a pressure tap at the top of the vessel
and connecting this to the low side of a differential pressure transmitter. Vess
el pressure is now equally applied to both high and low sides of the transmitter
. The resulting differential pressure is proportional to liquid heights multipli
ed by specific gravity.
DRY LEG
If the gas above the liquid does not condense, the piping for the low side of th
e transmitter will remain empty. Calculations for determining the range will be
the same as those shown for open vessel bottom mounted transmitter.
WET LEG
If the gas above the liquid condenses, the piping for low side of the transmitte
r will slowly fill up with liquid. To eliminate this potential error the pipe is
purposely filled with a convenient reference fluid.
The reference fluid will exert a head pressure on the low side of the transmitte
r, and zero elevation of the range must be made.
Example (wet leg)
Let X = vertical distance between the minimum and maximum measurable levels equa
l 500 inches
Y = Vertical distance between the transmitter datum; line and the minimum
measurable level equal 50 inches
Z = Vertical distance between the top of the liquid in the wet leg and the
transmitter datum line level 600 inches.
SG1 = Specific gravity of the fluid equal 1.0
SG2 = Specific gravity of the fluid in the wet leg equal 1.1
H = Maximum head pressure to be measured in inches of water
E = head pressure produced by y expressed in inches of water
S = Head pressure produced by z expressed in inches of water
Range = e – s to h + e – s
Then h = (X) (SG1) = 500 inches WG
E = (Y)(SG1) = 50 inches WG
S = (z) (SG2) = 660 inches WG
Range = -610 to –110 inches WG
THE APPLICATION OF DIAPHARGM SEALS TO ELECTRONIC PRESSURE TRANSMITTER:
The measurement of process pressure and differential pressure is not always a si
mple procedure. For reasons of temperature, corrosive attack, clogging, sanitati
on, or non-contamination, transmitters often cannot be allowed to come in to dir
ect contact with the process fluid. When such conditions exist. Diaphragm seals
frequently are installed to solve the problem. If not properly applied, however
the seals may cause additional problems. While the addition of a diaphragm seal
does not affect transmitter accuracy directly, factors such as capillary length,
mounting position and fill fluid introduce variables that inter with each other
.
The interaction between capillary and filled fluid manifests itself in temperatu
re effects and time response the temperature effects are a function of the fille
d fluid coefficient of expansion, fill fluid volume and diaphragm stiffness. As
the fill fluid undergoes a temperature change it expands or the contracts the re
sulting volume change flexes the diaphragm. This flexure increases or decreases
the pressure in the seal and capillary system and is seen by transmitter as an o
utput shift disregarding diaphragm stiffness, it can be set that for any given s
ystem, the longer the capillary, the greater fill volume and the greater tempera
ture effect. It follows logically that to minimize the effects of the temperatur
e capillary length should be kept as short s possible.
Nucleonic Gauging
The system operate on simple, non contacting, nuclear principle: gamma radiation
will penetrate any material, but is absorbed in proportion to the amount of mas
s it penetrate.
A small gamma radiation source is safely housed in a shielded holder mounted out
side the process vessel. When the shutter mechanism is opened, a collimated radi
ation beam is emitted. This gamma energy penetrates vessel walls, spans across t
he entire width of the vessel and is received by a detector also extremely mount
ed directly opposite the portion of the radiation beam. The detector senses the
radiation change and produces a signal used to indicate an alarm, operate a reco
rder or perform various control functions.
Because all system components are external to the process, measurement is truly.
“Non contacting” the systems are therefore not affected by product temperature, pre
ssure, corrosiveness, abrasiveness, or viscosity or by vessel size, shape of con
struction, installation does not require wall modifications or down time, and ma
intenance is minimal.
VIBRATION
Vibration is process parameter used in ammonia plant. There are two type of vibr
ation sensors used to measure vibration namely axial Displacement sensors and An
gular vibration sensors. To measure the vibration of a body a vibration pickup c
oil is placed near the vibrating body.
SPEED
Speed parameter is measured by digital tachometer. This parameter can be
observed in T.G Area.
ANALYZERS
Analyzers are the instruments that are used to measure the concentration
of the sample in a sample in a given mixture. These instruments can give thee q
ualitative and quantitative information of the sample under test. The different
analyzers used in Rain CII Carbon India Limited are
i) pH Analyzers
ii) Conductivity Analyzers
iii) Infrared Analyzers
iv) Thermal conductivity Analyzers
v) Oxygen Analyzers
vi) Flue Gas Analyzers
SWITCHES
Switch is a switching device and not a measuring instrument. The scale is provid
ed primary for guidance to assist setting. All types of switch are used to trip
and alarm purposes. Some of the switches are connected to the DCS panel for alar
m indication and some are connected to the shutdown system for tripping the plan
t. There is Pressure, Temperature, Level and Flow switches &belt conveyor safety
switches are used in calcination&power Plants.
TRANSMITTERS
A transmitter may be described as a device used in a control system, whi
ch senses and control a process variable (i.e. temperature, pressure level, and
flow. Etc.) to an electrical signal which is proportional to the value of the se
nsed variable. The electrical output is frequently at 0-20ma or 4-12mA. Transmit
ting transducers are devices that convert the measured variable into a transmitt
able signal, either pneumatic or electrical.
By taking the advantage of microprocessor technology, a lot of transmitt
er manufactures come our which a new generation of transmitters which allow digi
tal communication, they are called “smart Transmitters”. Two basic types of Smart Tr
ansmitters are currently available. The first system replaces the analog signal
by a digitized 4ma or 20mA signal at the baud rate of 200 using the frequency fo
r data communication. The second uses high frequency superimposed on the analog
4-20mA signal for data communication. Calibration in measuring range, Zero point
correction, disturbance monitoring and remote diagnostics are possible using sm
art Transmitters in conjunction with a process system or specific portable progr
ammer called “communicator”.