Escolar Documentos
Profissional Documentos
Cultura Documentos
Outdoor Distribution
S&C Vista Underground Distribution Switchgear features or three-pole fault protection for 600-ampere main feeders
load-interrupter switches and resettable, vacuum fault and 200-ampere taps, laterals, and subloops. Fault inter-
interrupters in series with disconnect switches . . . all in a ruption is initiated by a microprocessor-based overcur-
submersible, SF6-insulated, welded-steel tank. The rent control which is housed in a watertight enclosure
switchgear includes clearly visible open gaps and integral mounted on the gear. The control features innovative
visible grounds to simplify operations, enhance safety, time-current characteristic (TCC) curves with selectable
and minimize the duration of an outage. With the optional instantaneous and definite-time delay attributes for supe-
voltage-indication feature, all routine tasks—switching, rior coordination with upstream protective devices and
voltage testing, and grounding—can be accomplished by a downstream power fuses. Standard “E” speed curves can
single person without cable handling or exposure to high also be selected. The minimum total clearing time (from
voltage. initiation of the fault to total clearing) is 40 milliseconds
The load-interrupter switches provide three-pole (2.5 cycles) allowing for easier coordination with
switching for 600-ampere main feeders, and the fault upstream circuit breakers. Integral current transformers
interrupters provide single-pole switching and single-pole provide power and current sensing.
Watertight enclosure
Figure 1. User-supplied personal computer is attached to the overcurrent control for programming of the control in the field.
Selectable TCCs include E-speed, coordinating-speed tap, and coordinating-speed main curves. Coordinating-speed curves
can be tailored to the application using various instantaneous and definite-time settings.
PHOTO SHEET
681-703
Page 2 of 8
February 23, 2004 S&C ELECTRIC COMPANY
Control Settings time delay attributes can be disabled if desired. When an
The parameters for the TCC curves are set using a E-speed curve is selected, only the minimum pickup level
personal computer connected to the data port of the over- for phase overcurrents is programmed into the control. As
current control. Programming of the control can be done shown in Figure 2, the settings programmed into the com-
in the shop or in the field. Refer to Figure 1. Unlike other puter can also be viewed for verification.
controls that use knobs and dials, the settings cannot be When the overcurrent control is programmed for
inadvertently or haphazardly changed by unauthorized single-pole tripping of the fault interrupter, only those
persons. Only qualified technicians have the ability to poles that have faulted will trip. The control will not
alter the settings. There is no need to purchase and install respond to ground overcurrents, but will respond to phase
new circuit cards or entirely new controls to make overcurrents whether or not a ground fault is involved.
changes. For maximum reliability, there are no mechani- For three-pole tripping of the fault interrupter, all three
cal parts such as switches and potentiometers to wear out poles will operate regardless of which pole has faulted. In
or malfunction. this case, the control will operate the fault interrupter in
The control allows a choice of single-pole or three-pole response to ground overcurrents given that a ground-fault
fault interruption, and 50- or 60-hertz operation. Input setting has been programmed into the control.
parameters for the TCCs include minimum pickup levels, The ability to program the control for three-pole trip-
instantaneous pickup levels, and definite-time delays for ping allows for three-pole protection of three-phase trans-
both phase- and ground-overcurrent curves. The ground- formers and other three-phase loads.
overcurrent circuit, and the instantaneous and definite-
Applications 1000
tional equipment.
Phase
Overcurrent Relay
Increased Load-Carrying Capability and Type: CO-9
Time Dial: 3
Improved Coordination 10 Min. Pickup Current: 720A
TIME IN SECONDS
As shown in Figure 3, the first application involves an CTI: 0.15 sec.
industrial park with 1,000- and 2,000-kva transformers
served by a single loop. Due to the kva sizes of the trans-
formers, power fuses are used at the transformers. It is 1
necessary to limit the loop to two transformers of this size
because of coordination problems between the 100E fuse
at the transformer, the 200E fuse in the pad-mounted gear,
and the utility’s phase relay at the substation which is
.1
set to pick up at 720 amperes. The coordination plot in
Figure 4 shows how this design will only coordinate
through 5,600 amperes, which is not always high enough
since many industrial parks are located at the beginning Miscoordination
of a circuit where fault currents are high. .01
100 000
10 000
100
1 000
10
When Vista switchgear is applied in the same situation,
at least twice as many transformers can be served by two CURRENT IN AMPERES
B
CO-9 Relay 200E 200E
Phase: 720A
N.O.
50E 100E
PHOTO SHEET
681-703
Page 4 of 8
February 23, 2004 S&C ELECTRIC COMPANY
1000
units of gear. See Figure 5. Full coordination is also
achieved—through 12,500 amperes—by using a 400- Tap Interrupter (Phase)
Min. Pickup Current: 400A
ampere coordinating-speed curve. As shown in Figure 6, Transformer-
Def. Time Delay: 4 cycle
Primary Fuse
the tap-interrupter curve includes a 4-cycle definite-time (100E, Standard
delay to coordinate with the 100E standard-speed fuse 100 Speed)
protecting the 2,000-kva transformer. Phase
Overcurrent Relay
Type: CO-9
Improved Circuit Reliability and Reduced Time Dial: 3
Equipment Needs 10 Min. Pickup Current: 720A
CTI: 0.15 sec.
TIME IN SECONDS
As shown in Figure 7, the second application involves the
use of conventional pad-mounted gear to tap a main
feeder to serve two commercial parks. The settings of the
phase- and ground-overcurrent relays at the utility’s sub- 1
station are 720 amperes and 480 amperes, respectively.
Three 1,500-kva transformers, each protected by an inter-
nal current-limiting fuse rated 100C (which is the largest
internal fuse available), are used to serve three buildings.
.1
The largest tap fuse that will carry the load of two trans-
formers and coordinate with the substation relays is 140K.
Refer to Figure 8. Thus, it is necessary to establish two
loops to serve the load.
.01
The total demand of the commercial park is 3,000 kva,
100 000
10 000
100
1 000
10
and three such commercial parks could be connected to
one main feeder without exceeding the capacity of a CURRENT IN AMPERES
13.2-kv circuit. However, the reliability of this design may Figure 6. Coordinating-speed tap curve with definite-time
delay coordinates completely with 100E transformer fuse.
B
CO-9 Relay 400A 400A
Phase: 720A
N.O.
TIME IN SECONDS
additional circuit not required but the reliability of the
system is substantially improved through increased
sectionalization. Due to better coordination and the
1
higher continuous-current capability of the switchgear,
only two units of gear are required to serve the entire load
Ground
at each commercial park where previously three units Overcurrent Relay
were required. Figures 10 and 11 show the improved Type: CO-9
coordination for the phase current and ground current, Time Dial: 2.5
.1
Min. Pickup Current: 480A
respectively. CTI: 0.15 sec.
.01
100 000
10 000
100
1 000
10
CURRENT IN AMPERES
CO-9 Relay
Phase: 720A
Ground: 480A
B
140K 140K 140K 140K 140K
COMMERCIAL
PARK
N.O. N.O.
PHOTO SHEET
681-703
Page 6 of 8
February 23, 2004 S&C ELECTRIC COMPANY
CO-9 Relay MAIN PROTECTOR
Phase: 720A Phase: 450A
Ground: 480A Ground: 400A
B
TAP PROTECTOR
Phase: 350A
Ground: 300A
COMMERCIAL
PARK
COMMERCIAL PARK
N.O.
Figure 9. Addition of a fault interrupter on the main feeder provides increased reliability.
1000 1000
Phase
Transformer Overcurrent Relay
Weak-Link Fuse Type: CO-9 Ground
(100A) Time Dial: 3 Overcurrent Relay
10 Min. Pickup Current: 720A 10 Type: CO-9
Time Dial: 2.5
TIME IN SECONDS
TIME IN SECONDS
1 1
.1 .1
.01 .01
100 000
100 000
10 000
10 000
100
100
1 000
1 000
10
10
Figure 10. Complete coordination between upstream phase Figure 11. Complete coordination between upstream
relay, feeder interrupter (phase TCC), and subloop tap inter- ground relay, main feeder interrupter (ground TCC), and
rupter (phase TCC). subloop tap interrupter (ground TCC).
Event Recording have faulted, the magnitude of the fault, and whether or
The overcurrent control features an event log that cap- not a ground overcurrent was involved. This information
tures the last twelve operations of a fault interrupter. As can be accessed via a personal computer connected to the
shown in Figure 12, the event log indicates which poles data port of the control.
Figure 12. Event log showing last three events that caused the fault interrupter to operate.
Printed in U.S.A.
PHOTO SHEET
681-703
Page 8 of 8
February 23, 2004 S&C ELECTRIC COMPANY