Você está na página 1de 8

S&C Vista® Underground Distribution Switchgear Overcurrent Control

Outdoor Distribution

S&C Vista Underground Distribution Switchgear features or three-pole fault protection for 600-ampere main feeders
load-interrupter switches and resettable, vacuum fault and 200-ampere taps, laterals, and subloops. Fault inter-
interrupters in series with disconnect switches . . . all in a ruption is initiated by a microprocessor-based overcur-
submersible, SF6-insulated, welded-steel tank. The rent control which is housed in a watertight enclosure
switchgear includes clearly visible open gaps and integral mounted on the gear. The control features innovative
visible grounds to simplify operations, enhance safety, time-current characteristic (TCC) curves with selectable
and minimize the duration of an outage. With the optional instantaneous and definite-time delay attributes for supe-
voltage-indication feature, all routine tasks—switching, rior coordination with upstream protective devices and
voltage testing, and grounding—can be accomplished by a downstream power fuses. Standard “E” speed curves can
single person without cable handling or exposure to high also be selected. The minimum total clearing time (from
voltage. initiation of the fault to total clearing) is 40 milliseconds
The load-interrupter switches provide three-pole (2.5 cycles) allowing for easier coordination with
switching for 600-ampere main feeders, and the fault upstream circuit breakers. Integral current transformers
interrupters provide single-pole switching and single-pole provide power and current sensing.

Watertight enclosure

Overcurrent control—current transformers


(not shown) provide power and signal input
for the control
Adapter cable

User-supplied personal computer


is used to program the overcurrent
control. Allows selection of TCC
curves and single-pole or three-pole
tripping for the fault interrupters

Figure 1. User-supplied personal computer is attached to the overcurrent control for programming of the control in the field.
Selectable TCCs include E-speed, coordinating-speed tap, and coordinating-speed main curves. Coordinating-speed curves
can be tailored to the application using various instantaneous and definite-time settings.

Supersedes Photo Sheet 681-703 dated 9-3-96 ©2004

PHOTO SHEET 681-703


Page 1 of 8
S&C ELECTRIC COMPANY February 23, 2004
S&C Vista® Underground Distribution Switchgear Overcurrent Control
Outdoor Distribution

Available TCCs source-side relays with low time-dial settings. As such,


The overcurrent control was designed to meet specific the curves are faster than “E” speed and “K” speed
coordination needs. Existing pad-mounted gear with fuses power fuse TCC curves.
only coordinates with upstream relays and downstream • “Coordinating” speed main curves—with minimum
current-limiting fuses through 5,000 or 6,000 amperes, pickup settings from 100 amperes through 800
even though underground distribution systems often see amperes. These curves are used in conjunction with
higher fault currents. In response, S&C has developed fault interrupters on main feeders and have longer min-
special new “coordinating” speed TCC curves that provide imum response times and different shapes to coordi-
complete coordination with upstream circuit-breaker nate with tap-interrupter curves.
relays as well as downstream current-limiting fuses
• Time-overcurrent relay curves conforming to
through the entire range of typical fault currents . . . all the
IEEE C37.112-1996 IEEE Standard Inverse-Time
way to 12,500 amperes.
Characteristic Equations for Overcurrent Relays
The control features phase-overcurrent curves as well —U.S. Moderately Inverse Curve U1, U.S. Inverse
as ground-overcurrent curves to coordinate with source- Curve U2, U.S. Very Inverse Curve U3, U.S. Extremely
side breakers or reclosers with ground-trip settings. Sepa- Inverse Curve U4, U.S. Short-Time Inverse Curve U5,
rate curves were designed for main and tap protection to I.E.C. Class A Curve (Standard Inverse) C1, I.E.C. Class
provide complete coordination between fault interrupters B Curve (Very Inverse) C2, I.E.C. Class C Curve
applied on main feeders and those applied on associated (Extremely Inverse) C3, I.E.C. Long-Time Inverse
subloop taps. Curve C4, and I.E.C. Short-Time Inverse Curve C5.
Five families of curves are available as follows:
The coordinating-speed TCCs can be customized into
• “E” speed curves—from 25E amperes through 200E hundreds of different curves using a variety of instanta-
amperes. neous (1 ka through 8 ka) and definite-time delay (32 ms
• “K” speed curves—from 25K amperes through 200K through 96 ms) settings. The minimum total clearing time
amperes. is 40 milliseconds (2.5 cycles) to allow proper coordina-
tion with typical upstream circuit-breaker relays.
• “Coordinating” speed tap curves—with minimum
If activated, the definite-time delay attribute adds an
pickup settings from 50 amperes through 400 amperes.
intentional time delay to allow coordination with conven-
These curves are used in conjunction with fault inter-
tional power fuses located downstream. For even more
rupters feeding subloop taps and have been specifically
specialized shapes, a definite-time delay setting can be
designed to optimize coordination with load-side weak-
combined with an instantaneous trip setting.
link/backup current-limiting fuse combinations and

PHOTO SHEET
681-703
Page 2 of 8
February 23, 2004 S&C ELECTRIC COMPANY
Control Settings time delay attributes can be disabled if desired. When an
The parameters for the TCC curves are set using a E-speed curve is selected, only the minimum pickup level
personal computer connected to the data port of the over- for phase overcurrents is programmed into the control. As
current control. Programming of the control can be done shown in Figure 2, the settings programmed into the com-
in the shop or in the field. Refer to Figure 1. Unlike other puter can also be viewed for verification.
controls that use knobs and dials, the settings cannot be When the overcurrent control is programmed for
inadvertently or haphazardly changed by unauthorized single-pole tripping of the fault interrupter, only those
persons. Only qualified technicians have the ability to poles that have faulted will trip. The control will not
alter the settings. There is no need to purchase and install respond to ground overcurrents, but will respond to phase
new circuit cards or entirely new controls to make overcurrents whether or not a ground fault is involved.
changes. For maximum reliability, there are no mechani- For three-pole tripping of the fault interrupter, all three
cal parts such as switches and potentiometers to wear out poles will operate regardless of which pole has faulted. In
or malfunction. this case, the control will operate the fault interrupter in
The control allows a choice of single-pole or three-pole response to ground overcurrents given that a ground-fault
fault interruption, and 50- or 60-hertz operation. Input setting has been programmed into the control.
parameters for the TCCs include minimum pickup levels, The ability to program the control for three-pole trip-
instantaneous pickup levels, and definite-time delays for ping allows for three-pole protection of three-phase trans-
both phase- and ground-overcurrent curves. The ground- formers and other three-phase loads.
overcurrent circuit, and the instantaneous and definite-

Figure 2. Overcurrent-control settings.

PHOTO SHEET 681-703


Page 3 of 8
S&C ELECTRIC COMPANY February 23, 2004
S&C Vista® Underground Distribution Switchgear Overcurrent Control
Outdoor Distribution

Applications 1000

Two applications of S&C Vista Underground Distribution Transformer- Subloop Fuse


Switchgear are described below. Each shows how the Primary Fuse (200E, Standard
(100E, Standard Speed)
switchgear improves coordination and reliability using Speed)
the same or fewer units of gear than required with tradi- 100

tional equipment.
Phase
Overcurrent Relay
Increased Load-Carrying Capability and Type: CO-9
Time Dial: 3
Improved Coordination 10 Min. Pickup Current: 720A

TIME IN SECONDS
As shown in Figure 3, the first application involves an CTI: 0.15 sec.
industrial park with 1,000- and 2,000-kva transformers
served by a single loop. Due to the kva sizes of the trans-
formers, power fuses are used at the transformers. It is 1
necessary to limit the loop to two transformers of this size
because of coordination problems between the 100E fuse
at the transformer, the 200E fuse in the pad-mounted gear,
and the utility’s phase relay at the substation which is
.1
set to pick up at 720 amperes. The coordination plot in
Figure 4 shows how this design will only coordinate
through 5,600 amperes, which is not always high enough
since many industrial parks are located at the beginning Miscoordination
of a circuit where fault currents are high. .01

100 000
10 000
100

1 000
10
When Vista switchgear is applied in the same situation,
at least twice as many transformers can be served by two CURRENT IN AMPERES

Figure 4. Miscoordination between 100E transformer fuse


and 200E subloop fuse.

B
CO-9 Relay 200E 200E
Phase: 720A

N.O.

50E 100E

1000 KVA 2000 KVA

Figure 3. Subloop protection provided by conventional (fused) pad-mounted switchgear.

PHOTO SHEET
681-703
Page 4 of 8
February 23, 2004 S&C ELECTRIC COMPANY
1000
units of gear. See Figure 5. Full coordination is also
achieved—through 12,500 amperes—by using a 400- Tap Interrupter (Phase)
Min. Pickup Current: 400A
ampere coordinating-speed curve. As shown in Figure 6, Transformer-
Def. Time Delay: 4 cycle
Primary Fuse
the tap-interrupter curve includes a 4-cycle definite-time (100E, Standard
delay to coordinate with the 100E standard-speed fuse 100 Speed)
protecting the 2,000-kva transformer. Phase
Overcurrent Relay
Type: CO-9
Improved Circuit Reliability and Reduced Time Dial: 3
Equipment Needs 10 Min. Pickup Current: 720A
CTI: 0.15 sec.

TIME IN SECONDS
As shown in Figure 7, the second application involves the
use of conventional pad-mounted gear to tap a main
feeder to serve two commercial parks. The settings of the
phase- and ground-overcurrent relays at the utility’s sub- 1
station are 720 amperes and 480 amperes, respectively.
Three 1,500-kva transformers, each protected by an inter-
nal current-limiting fuse rated 100C (which is the largest
internal fuse available), are used to serve three buildings.
.1
The largest tap fuse that will carry the load of two trans-
formers and coordinate with the substation relays is 140K.
Refer to Figure 8. Thus, it is necessary to establish two
loops to serve the load.
.01
The total demand of the commercial park is 3,000 kva,

100 000
10 000
100

1 000
10
and three such commercial parks could be connected to
one main feeder without exceeding the capacity of a CURRENT IN AMPERES

13.2-kv circuit. However, the reliability of this design may Figure 6. Coordinating-speed tap curve with definite-time
delay coordinates completely with 100E transformer fuse.

B
CO-9 Relay 400A 400A
Phase: 720A

N.O.

50E 100E 50E 100E

1000 KVA 2000 KVA 1000 KVA 2000 KVA

Figure 5. Vista switchgear provides increased load-carrying capability in a single subloop.

PHOTO SHEET 681-703


Page 5 of 8
S&C ELECTRIC COMPANY February 23, 2004
S&C Vista® Underground Distribution Switchgear Overcurrent Control
Outdoor Distribution

be questionable, depending on the length of the main 1000

feeder and the history of cable failures. The solution until


now has been to bring a second circuit into the area to
Subloop Fuse
serve one of the commercial parks . . . obviously very Transformer (140K)
expensive. Weak-Link Fuse
100
(100A)
With Vista switchgear, there is a better solution involv- Phase
ing the installation of a “main” fault interrupter with a Overcurrent Relay
Type: CO-9
phase-overcurrent rating of 450 amperes and ground-over- Time Dial: 3
current rating of 400 amperes. Refer to Figure 9. When a 10
Min. Pickup Current: 720A
main interrupter is used on the main feeder, not only is an CTI: 0.15 sec.

TIME IN SECONDS
additional circuit not required but the reliability of the
system is substantially improved through increased
sectionalization. Due to better coordination and the
1
higher continuous-current capability of the switchgear,
only two units of gear are required to serve the entire load
Ground
at each commercial park where previously three units Overcurrent Relay
were required. Figures 10 and 11 show the improved Type: CO-9
coordination for the phase current and ground current, Time Dial: 2.5
.1
Min. Pickup Current: 480A
respectively. CTI: 0.15 sec.

.01

100 000
10 000
100

1 000
10

CURRENT IN AMPERES

Figure 8. Coordination between 140K subloop fuse,


upstream relay, and 100A (C16) transformer weak-link fuse.

CO-9 Relay
Phase: 720A
Ground: 480A

B
140K 140K 140K 140K 140K

COMMERCIAL
PARK

N.O. N.O.

100C 100C 100C

1500 KVA 1500 KVA 1500 KVA


COMMERCIAL PARK

Figure 7. Commercial parks supplied by conventional (fused) pad-mounted switchgear.

PHOTO SHEET
681-703
Page 6 of 8
February 23, 2004 S&C ELECTRIC COMPANY
CO-9 Relay MAIN PROTECTOR
Phase: 720A Phase: 450A
Ground: 480A Ground: 400A

B
TAP PROTECTOR
Phase: 350A
Ground: 300A

COMMERCIAL
PARK

COMMERCIAL PARK

N.O.

100C 100C 100C

1500 KVA 1500 KVA 1500 KVA

Figure 9. Addition of a fault interrupter on the main feeder provides increased reliability.

1000 1000

Tap Interrupter Main Interrupter (Phase)


Tap Interrupter
(Phase) Min. Pickup
(Ground) Main Interrupter (Ground)
Min. Pickup Current: 450A
Min. Pickup Min. Pickup
Current: 350A Current: 300A Current: 400A
100 100

Phase
Transformer Overcurrent Relay
Weak-Link Fuse Type: CO-9 Ground
(100A) Time Dial: 3 Overcurrent Relay
10 Min. Pickup Current: 720A 10 Type: CO-9
Time Dial: 2.5
TIME IN SECONDS
TIME IN SECONDS

CTI: 0.15 sec.


Min. Pickup Current: 480A
CTI: 0.15 sec.

1 1

.1 .1

.01 .01
100 000
100 000

10 000
10 000

100
100

1 000
1 000

10
10

CURRENT IN AMPERES CURRENT IN AMPERES

Figure 10. Complete coordination between upstream phase Figure 11. Complete coordination between upstream
relay, feeder interrupter (phase TCC), and subloop tap inter- ground relay, main feeder interrupter (ground TCC), and
rupter (phase TCC). subloop tap interrupter (ground TCC).

PHOTO SHEET 681-703


Page 7 of 8
S&C ELECTRIC COMPANY February 23, 2004
S&C Vista® Underground Distribution Switchgear Overcurrent Control
Outdoor Distribution

Event Recording have faulted, the magnitude of the fault, and whether or
The overcurrent control features an event log that cap- not a ground overcurrent was involved. This information
tures the last twelve operations of a fault interrupter. As can be accessed via a personal computer connected to the
shown in Figure 12, the event log indicates which poles data port of the control.

View Menu INTERRUPTER 1: <select number>


1. View event report (last 12 events)
2. View load current
3. View relay settings
4. View relay self-test
9. Switch to Main Menu
= View FI 1 > 1
View FI 1> 1
Elapsed
*Eve* **Faulted Poles** **** * Amperes *****
**Time**
# 1 2 3 G 1 2 3 G (Seconds)
1 X X X 4 2040 1829 1908 0.019
2 X X 24 1926 18 1908
3 X X 2010 22 18 1992

Press <ENTER> for menu

Figure 12. Event log showing last three events that caused the fault interrupter to operate.

Printed in U.S.A.

PHOTO SHEET
681-703
Page 8 of 8
February 23, 2004 S&C ELECTRIC COMPANY

Você também pode gostar