Escolar Documentos
Profissional Documentos
Cultura Documentos
AC Motor Drive
Distribution Transformer
system w
G M Lo
Three-phase TL
electric utility
Control
system
System fault
Load
50
40
30
20
10
10
20
30
400 300 200 100 0 100 200 300 400
1.6 10
4
2 10
sequence component because the transfer
4
1.2 10
8000
impedance is null. The non-faulted phases show
A
B
i
i
4000
0
the same magnitude and direction in their voltage
C
i
4000
8000
change. These voltage changes are half of the
1.2 10
1.6 10
4
4
value of the magnitude of the voltage change in
2 10
4
2.9 2.96 3.02 3.08 3.14 3.2
i. 10
5.
8
3.26 3.32 3.38 3.44 3.5 the faulted phase.
Fig.10.Phase voltages during a type A sag at the 22 kV bus In this case, the voltage sag is a DR sag. A single
500 phase to ground fault involving phase R causes a
400
DR sag. However the Dyn transformer change the
300
200
character of the unbalanced sag.
I
i 100
4
2 10
J 0
i 4
1.6 10
Q 100 1.2 10
4
i
200 8000
A
i 4000
300
B 0
i
400
C 4000
i
500 8000
3 3.1 3.2 3.3 3.4 3.5
4
6. 1.2 10
i . 10 80
4
1.6 10
300
i 100
200
400
50
320
5. Effect of voltage sags on adjustable
240
160
speed drives
I
i 80
J
i 0
The responses of ASDs to voltage sags conditions
Q
i
80
can significantly affect the industrial processes
160
240
that use them. The general layout for PWM ASDs
320 has a rectifier, a DC bus and an inverter. During a
400
2.95 3 3.05
i . 10
3.1
6.
80
3.15 3.2 3.25
voltage sag, the response of the electronic ASDs
Fig.13.Phase voltages at the 400 V bus. depends on the hardware design, the controller
150
software, and the control system response time.
Voltage sags cause a decrease of the DC bus
F
2.36
i
100
voltage in the ASD. During very brief sags it may
G
i
2.36
be possible to supply the energy from the DC bus
H
i 50
capacitor. During longer sags periods, the DC bus
2.36
X2i 500
200
X3i
100
0.73 p.u. 400 400
1.95 2 2.05 2.1
t[s] 1.95 −5 2.15
i ⋅4 ⋅10
0
1.95 2 2.05 2.1 2.15 Fig 22. Decrease of the DC bus voltage under different
load conditions (1.0 p.u., 0.5 p.u. and no load)
Fig.18.Shape of the sag in the secondary side
40
At the occurrence of a three-phase or balanced 1,0 p.u
sag, no energy is supplied from the AC-supply
into the DC bus because of the reverse biased 20 0,5 p.u
diode rectifier. All the energy needed to drive the
load is taken from the electric energy stored in the No load
load torque, the mechanical speed and the inverter Fig 23. Increase of the DC bus current under different
and motor efficiency [15], [16], [17], [18], [19]. load conditions (1.0 p.u., 0.5 p.u. and no load)
600
Case II- Sag due to a phase-to-phase fault
Vdc [V]
450
Sag CT propagated down from 22 kV bus is a DR
300 Discharge of
sag at 400 V. Under these conditions the three-
the capacitor phase rectifier is single phased during the voltage
150
t[s
sag event. Since the output power has to be
0
1.95 2 2.05 2.1 2.15
supplied via two phases, this mode increases the
rms input current of the ASD during the sag
Fig 19. Decrease of the DC bus voltage under sag event.
120.5
w[rad/s] IR, IS, IT [A] Imax =2.8 p.u. Imax =7.6 p.u.
100
120
t[s]
119.5
1.95 2 2.05 2.1 2.15
100 t [s]
Fig 20. Speed of the motor during the sag event under
the effect of the vector control system 1.98 2 2.02 2.04 2.06 2.08 2.1 2.12 2.14
If the supply voltage recovers before the dc bus Fig 24. Line currents during the sag event
voltage reaches the under-voltage protection 600
supply. 450
0,93 p.u.
300
IR, IS, IT [A]
100
150
t [s]
0
0
1.95 2 2.05 2.1 2.15
Under the
discharge of the
capacitor the
100
currents are null t [s] Fig 25. Decrease of the DC bus voltage under sag
1.99 2 2.02 2.04 2.06 2.08 2.1 6. Commercial ASD during voltage sags
Fig 21. Line currents during the sag event Some experimental analysis were carried out to verify
the results obtained by using the transients program. In
this section, an experimental analysis is discussed for a
Case II- Sag due to a phase-to-ground fault
commercial available 400 V, 50 Hz, 12 kVA PWM
Sag DR propagated down from 22 kV bus is a CS adjustable speed drive. The analysis platform
sag at 400 V.The dc-link voltage under a voltage includes 11 kW induction motor, three-phase and
sag event is directly dependent on both the output programmable supply voltage to produce the
power and the effective inductance (including two voltage sags and electrical brake to permit motor
source inductance and dc-link inductance). operation under different load levels.
Test A
For this evaluation test the ASD was subjected to
DR voltage sag for a duration of 100 ms
( U R = 90∠0º , U S = 203∠ − 101º , UT = 203∠ − 100,46º ).
It is a no load test. During the sag the line
currents are null. The rectifier diodes cease to
conduct because are reverse biased due to
reduction in the phase voltages.
Origin of 3
the sag 2
Test B
The ASD was subjected to DR voltage sag for a Fig. 30.Waveforms of the supply line currents during the sag
duration of 100 ms ( U R = 70∠0º , U S = 230∠ − 101º ,
U T = 230∠ − 100,46º ). During the sag, the rectifier
is single phased and the line currents are
increased. The dc-link voltage reduction under no
load and single phase behaviour is slight.
Origin of
the sag
Test D
End of the
The ASD is set to trip when the dc voltage drops
sag 0,76 times the nominal value. This evaluation test
was conducted to show how the ASD goes to stop
as the dc voltage falls bellow the DC bus trip
Fig. 28.Waveforms of the supply line currents during the sag voltage. The response of the ASD can be seen in
figure 32.
compatibility”. Proceedings of ninth international
conference on harmonics and quality of power.
Orlando- Florida-Oct.2000.
[7] J. Lamoree et al. “Voltage sag analysis case
studies”. IEEE Transactions on Industry
Applications, vol. 30, July/August 1994.
[8] M. F. McGranaghan et al. “Voltage sags in
industrial systems”. IEEE Transactions on
Industry Applications, vol. 29, March/April 1993.
[9] G. Yalcinkaya et al.” Characterization of
voltage sags in industrial distribution systems”.
Fig.32.Motor line voltages and supply line voltages IEEE Transactions on Industry Applications, vol.
Acknowledgement 34, July/August 1998.
[10] M. H. J. Bollen. “Characterisation of voltage
The authors gratefully acknowledge The Regional sags experienced by three-phase adjustable speed
plan of Research and Development FICYT for their drives”. IEEE Transactions on Power Delivery,
technical and financial support during this study. vol. 12, October 1997.
Conclusions [11] J. Durán G. et al. “Effect of voltage sags on
In this paper, the effect of voltage sag on ASD´s has adjustable-speed drives: a critical evaluation and
been evaluated both experimentally and by an approach to improve performance “ IEEE
simulation. The power system components for Transactions on Industry Applications, vol. 35,
voltage sag studies have been modelled and Nov/Dec 1999.
simulated by using a transients program. This paper [12] R. Langley et al. “Voltage Sag ride-through
also gives a review of results from the effect of the testing of adjustable speed drives using a
winding connections of the transformer, the kind controllable dynamic dynamometer” Proceedings
of fault, the resulting kind of sag and the load torque of 8th international conference on harmonics and
on the dc voltage and input current fluctuations. The quality of power. Vol 1. Atenas. Grecia 1998
model and the results can be used during the design [13] A. Van Zyl et al. “Voltage sag ride-through
task of the mitigation devices and ride-through for adjustable-speed drives with active rectifiers”.
alternatives. IEEE Transactions on Industry Applications, vol.
34, Nov/Dec 1998.
References
[14] M. H. J. Bollen. “The use of Electromagnetic
[1] M. H. J. Bollen et al. “ Characterization of Transient Programs for voltage sag analysis”
three-phase unbalanced dips (as easy as one-two- Proceedings of 8th international conference on
three ?)”. Proceedings of ninth international harmonics and quality of power. Vol 1. Atenas.
conference on harmonics and quality of power. Grecia1998
Orlando- Oct.2000.
[15] M. H. J. Bollen. “The influence of motor
[2] N. Kagan et al. “ Influence of rms variation reacceleration on voltage sags”. IEEE
measurement protocols on electrical system Transactions on Industry Applications, vol. 31,
performance indices for voltage sags and swells”. July/August 1995.
Proceedings of ninth international conference on
harmonics and quality of power. Orlando-Florida- [16] L. Guasch et al. “ Effects of unsymmetrical
Oct.2000. voltage sag types E, F and G on induction
motors”. Proceedings of ninth international
[3] N. S. Tunaboylu et al. “Voltage disturbance conference on harmonics and quality of power.
evaluation using the missing voltage technique” Orlando- Florida-Oct.2000.
Proceedings of 8th international conference on
harmonics and quality of power. Vol 1. Atenas. [17] A. von Jouanne et al. “Ride-through
Grecia 1998. alternatives for ASDs”. Part I, II, III. Web page
Darnell.com. Powerpulse.
[4] L. Zhang et al. “Characteristic of voltage dips
(sags) in power systems”. IEEE Transactions on [18] K. Stockman et al. “Embebed solutions to
Power Delivery, vol. 15, April 2000. protect textile processes against voltage sags”
[5] M. H. J. Bollen et al. “Assessment of the [19]G. Newman et al. “Voltage sag ride through
number of voltage sags experienced by a large improvement of modern ac drives: review of
industrial customer”. IEEE Transactions on methods and a case study”
Industry Applications, vol. 33, Nov./Dec. 1997.
[6] J. M. de Carvalho et al. “Electric power
system under voltage sag – a tool for achieving