HVAC Products
Quality as a requirement
OpenAirTM damper actuators are 100% factory-
assembled and tested at our state-of-the-art,
ISO9002 certified manufacturing facility loca-
ted in Staefa, Switzerland.
Need it fast?
Same day shipping is no problem for rush
orders. Helpful customer service representati-
ves can input your order and ship within three
business days for standard shipping.
www.sibt.com
Information at your fingertips
2
Control Power Standard Feedback Adjustable Adjustable Feedback 2 Auxilia
signal supply model potentio- start/span start/span (1kΩ) with switches
meter with 2 auxi- 2 auxiliary
(1kOhm) liary switches switches
GDB Series
5 Nm for approx. Floating 3-position 24 VAC GDB131.1E GDB132.1E GDB136.
0.8 m2 damper area 230 VAC GDB331.1E GDB332.1E GDB336.
150 sec. Run Time
Modulating 0-10 VDC 24 VAC GDB161.1E GDB163.1E GDB164.1E GDB166.
(50 Hz)
GLB Series
10 Nm for approx. Floating 3-position 24 VAC GLB131.1E GLB132.1E GLB136.
Non-Spring Return Products and Accessories
GEB Series
15 Nm for approx. Floating 3-position 24 VAC GEB131.1E GEB132.1E GEB136.
3 m2 damper area 230 VAC GEB331.1E GEB332.1E GEB336.
Fl oating 3-position 24 VAC GEB131.1U GEB132.1U GEB136.1U
150 sec. Run Time Modulating 0-100-10
Modulating VDC VDC24 VAC24 VACGEB161.1E
GEB161.1U GEB163.1E GEB164.1U
GEB164.1E GEB166.
(50 Hz)
GBB Series
20 Nm for approx. Floating 3-position 24 VAC GBB131.1E GBB135.1E GBB136.
5 m2 damper area 230 VAC GBB331.1E GBB335.1E GBB336.
150 sec. Run Time Modulating 0-10 VDC 24 VAC GBB161.1E GBB163.1E GBB164.1E GBB166.
(50Hz)
GIB Series
35 Nm for approx.
6 m2 damper area Floating 3-position 24 VAC GIB131.1E GIB135.1E GIB336.1
230 VAC GIB331.1E GIB335.1E GIB336.1
150 sec. Run Time
(50Hz) Modulating 0-10 VDC 24 VAC GIB161.1E GIB163.1E GIB164.1E GIB166.1
3
y Rotary to Rotary to Floor Frame Oversized Tandem Tandem Weather Universal
linear kit linear kit mount kit mount kit shaft bracket- bracket shield Lever
w/mounting adapter 2 pt./3 pt. & modulating
bracket (to 26.5mm) Elec. tandem control
1E
1E
1E
ASK71.13 ASK71.14 ASK71.11 ASK71.11 ASK73.3 ASK75.3 ASK71.9
1E
1E
1E
E
E
ASK71.5 ASK71.6 ASK71.6 ASK71.6 ASK71.9
E
E
E
ASK71.5 ASK71.6 ASK71.6 ASK71.6 ASK71.9
E
E
E
ASK71.13 ASK71.14 ASK71.11 ASK71.11 ASK73.3 ASK75.3 ASK71.9
E
E
E
ASK71.3 ASK71.4 ASK71.1 ASK71.2 ASK74.1 ASK73.1 ASK73.2 ASK75.1 ASK71.9
E
E
E ASK71.3 ASK71.4 ASK71.1 ASK71.2 ASK74.1 ASK73.1 ASK73.2 ASK75.1 ASK71.9
4
Control Power Standard Feedback Adjustable Adjustab
signal supply model potentio- start/span start/spa
meter with 2 au
(1kOhm) ary switc
GDB Series
125 N for approx. Floating 3-position 24 VAC GDB131.2E GDB132.2E
0.8 m2 damper area 230VAC GDB331.2E GDB332.2E
150 sec. Run Time
(50 Hz) Modulating 0-10 VDC 24 VAC GDB161.2E GDB163.2E GDB164
Non-Spring return Products and Accessories
GLB Series
250 N for approx. Floating 3-position 24 VAC GLB131.2E GLB132.2E
1.5 m2 damper area 230VAC GLB331.2E GLB332.2E
150 sec. Run Time
Modulating 0-10 VDC 24 VAC GLB161.2E GLB163.2E GLB164
(50 Hz)
GEB Series
400 N for approx. Floating 3-position 24 VAC GEB131.2E GEB132.2E
3 m2 damper area 230VAC GEB331.2E GEB332.2E
150 sec. Run Time
(50 Hz) Modulating 0-10 VDC 24 VAC GEB161.2E GLB163.2E GEB164
GBB Series
440 N for approx. Floating 3-position 24 VAC GBB131.2E
4 m2 damper area 230VAC GBB331.2E
150 sec. Run Time
Modulating 0-10 VDC 24 VAC GBB161.2E GBB163.2E GBB164
(50Hz)
5
e Feedback 2 Auxiliary Linear to Linear to Clamp Weather
n (1kΩ) with switches rotary kit rotary kit shield
xili- 2 auxiliary w/mounting with cardan
hes switches plate joint
GDB136.2E
GDB336.2E
ASK55.2
2E GDB166.2E
GLB136.2E
GLB336.2E
ASK55.2
2E GLB166.2E
GEB136.2E
GEB336.2E
ASK72.3
2E GEB166.2E
GBB135.2E GBB136.2E
GBB335.2E GBB336.2E
ASK72.2 ASK72.1 ASK75.2
2E GBB166.2E
e Feedback 2 Auxiliary Linear to Linear to Clamp Weather Setting Interface Calibration Locking
n (1kΩ) with switches rotary kit rotary kit shield unit converter Software plate
xili- 2 auxiliary w/mounting with cardan
hes switches plate joint
EB164.1U
GGA126.1E
GGA326.1E ASK79.1
ASK79.1
6
More
Solutions
GMA/GEB Series
Medium Spring Return/
Non-Spring Return
• Outside Air Dampers
• Mixing Boxes
• Return Air Dampers
• Zone Isolation Dampers
• Make-up Air Dampers
• Unit Ventilators
GCA/GBB/GIB Series
Large Spring Return/
Non-Spring Return
• Outside Air Dampers
• Rooftop Units
• Mixing Boxes
• Vortex Dampers
• Inlet Vane Dampers
• Return Air Dampers
• Zone Isolation Dampers
7
More
Benefits
Spring Return
New Features!
8
More
Performance
Non-Spring Return
GEB model
shown.
9
More
Alternatives
GEB model
shown.
10
More Mounting
Alternatives
Frame Mounting
The Frame Mounting Kit is used when actuator
cannot be directly mounted on damper shaft
due to space limitations.
Foot Mounting
Easily replace existing Honeywell, Joventa,
and Belimo modulating motors using the Foot
Mounting Kit.
11
Actuators Mounted in Tandem
OpenAir™ actuators can be mounted in tan-
dem to effectively double the torque of a
single actuator. This unique feature allows
OpenAir™ actuators to operate in a wider
range of applications.
12
Electronic Tandem Control
When critical control is needed in a modula-
ting application, one control signal can control
two actuators in a master-slave configuration.
The secondary unit can be mounted up to 5 m
away from the primary actuator.
13
OpenAir™
Accessories
Description GDB/ GEB/ G C A / G I B
GLB GMA GBB Part No.
14
Description GDB/ GEB/ G C A / G I B
GLB GMA GBB Part No.
15
OpenAir™
Accessories (continued)
Weathershield • ASK75.3
• ASK75.1
Includes cover, base plate with factory-installed
gasketing, 15 TEK self-drilling screws, and anti-
rotation (mounting) bracket. Knockouts for
connection of 1/2” conduit also included.
16
Description GDB/ GEB/ G C A / G I B
GLB GMA GBB Part No.
17
More Wiring
Options
0 to 10 V Actuators Powered
by One Transformer
Multiple OpenAir™ 0 to 10 V actuators
can be powered off of one transformer.
Power up to ten actuators off of one trans-
former
EARTH GROUND
ISOLATING CLASS II
TRANSFORMER FOR
24 VAC POWER
Sequencing of 0 to 10 V Actuators
With the settings shown, two 0 to 10 V
actuators can be sequenced such that the
first one will operate at 0 to 2 V and the
second at 2 to 10 V.
EARTH GROUND
This feature is perfect for specialized applica- ISOLATING CLASS II
TRANSFORMER FOR
tions, such as staging or minimum required 24 VAC POWER
airflow.
18
2-position 24 V Actuators
Wired in Parallel
Two actuators can be wired in parallel to ef-
fectively double the torque or may be moun-
ted separately and operated in parallel.
EARTH GROUND
ISOLATING CLASS II
TRANSFORMER FOR
24 VAC POWER
3-position Actuators
Wired in Parallel
Two actuators can be wired in
parallel to effectively double
the torque or may be mounted
separately and operated in parallel.
19
Submittal
Summary OpenAir™ GMA Series
Spring Return, Direct-Coupled
Electronic Damper Actuators
Dimensions
Specifications
N474
20
Wiring Diagrams
Dual Auxiliary
Elec. Tandem
24 VDC±15%
24 VAC±20%
Input Signal
0 to 10 VDC
Input Signal
Modulating
Offset and
Selectable
3-position
2-position
Product
Feedback
Switches
Inversion
Position
Control
Number Span
GMA121.1E ● ●
GMA126.1E ● ● ●
GMA321.1E ● ●
GMA326.1E ● ● ●
GMA131.1E ● ●
GMA132.1E ● ● ●
GMA136.1E ● ● ●
GMA161.1E ● ● ●
GMA163.1E ● ● ● ●
GMA164.1E ● ● ● ● ●
GMA166.1E ● ● ● ●
21
Submittal
Summary OpenAir™ GCA Series
Spring Return, Electronic Damper
Actuators
Dimensions
Specifications
22
Wiring Diagrams
Dual Auxiliary
24 VAC±20%
0 to 10 VDC
Offset and
3-position
2-position
Product
Feedback
Switches
Position
Number
Span
GCA121.1E ● ●
GCA126.1E ● ● ●
GCA321.1E ● ●
GCA326.1E ● ● ●
GCA131.1E ● ●
GCA135.1E ● ● ● ●
GCA161.1E ● ● ●
GCA163.1E ● ● ● ●
GCA164.1E ● ● ● ● ●
GCA166.1E ● ● ● ●
23
Submittal
Summary OpenAir™ GDB Series
Non-Spring Return,
Electronic Damper Actuators
Dimensions
Specifications
Torque 5 Nm
Runtime for 90° 150 sec. (50 Hz)
opening and closing
Frequency 50/60 Hz
Power consumption 24 VAC
Running 3 VA (modulating)
Running 2 VA (3-position)
Holding 1 W (modulating)
Power consumption 230 VAC
Running 2 VA
Angle of rotation 90° nominal, 95° max.
Shaft dimensions 8 to 16 mm Dia.
6 to 12.8 mm Sq.
30 mm min. length
Operating temperature -30 to +55 °C
Storage temperature -30 to +60 °C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP54
CE Conformity
Electromagnetic
Compatibility (EMC) 89/336/EEC
Emissions standards IEC/EN 61000-6-3
5 Nm
Immunity standards IEC/EN 61000-6-2
24 VAC and 230 VAC
Material Durable plastic Modulating
Gear Lubrication Silicone free 3-position Control
Dimensions 137 mm H x 70 mm
W x 60 mm D
Dimensions shown in mm
Weight 0.48 kg
N474
24
Wiring Diagrams
Dual Auxiliary
24 VAC±20%
0 to 10 VDC
3-position
Product Feedback
Span and
Switches
Position
Number
Offset
GDB131.1E ● ●
GDB132.1E ● ● ●
GDB136.1E ● ● ●
GDB331.1E ● ●
GDB332.1E ● ● ●
GDB336.1E ● ● ●
GDB161.1E ● ● ●
GDB163.1E ● ● ● ●
GDB164.1E ● ● ● ● ●
GDB166.1E ● ● ● ●
25
Submittal
Summary OpenAir™ GLB Series
Non-Spring Return,
Electronic Damper Actuators
Dimensions
Specifications
Torque 10 Nm
Runtime for 90° 150 sec. (50 Hz)
opening and closing
Frequency 50/60 Hz
Power consumption 24 VAC
Running 3 VA (modulating)
Running 2 VA (3-position)
Holding 1 W (modulating)
Power consumption 230 VAC
Running 2 VA
Angle of rotation 90° nominal, 95° max.
Shaft dimensions 8 to 16 mm Dia.
6 to 12.8 mm Sq.
30 mm min. length
Operating temperature -30 to +55 °C
Storage temperature -30 to +60 °C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP54
CE Conformity
Electromagnetic
Compatibility (EMC) 89/336/EEC
Emissions standards IEC/EN 61000-6-3
10 Nm
Immunity standards IEC/EN 61000-6-2
24 VAC and 230 VAC
Material Durable plastic Modulating
Gear Lubrication Silicone free 3-position Control
Dimensions 137 mm H x 70 mm
W x 60 mm D
Dimensions shown in mm
Weight 0.48 kg
N474
26
Wiring Diagrams
Dual Auxiliary
24 VAC±20%
0 to 10 VDC
3-position
Product Feedback
Span and
Switches
Position
Number
Offset
GLB131.1E ● ●
GLB132.1E ● ● ●
GLB136.1E ● ● ●
GLB331.1E ● ●
GLB332.1E ● ● ●
GLB336.1E ● ● ●
GLB161.1E ● ● ●
GLB163.1E ● ● ● ●
GLB164.1E ● ● ● ● ●
GLB166.1E ● ● ● ●
27
Submittal
Summary OpenAir™ GEB Series
Non-Spring Return,
Electronic Damper Actuators
Dimensions
Specifications
Torque 15 Nm
Frequency 50/60 Hz
Runtime for 90° 150 seconds (50 Hz)
Power consumption 24 VAC
Running 4 VA (3-position)
Running 6 VA (modulating)
Holding 1.5 W (modulating)
Power consumption 230 VAC
Running 3 VA
Angle of rotation 90° nominal, 95° max.
Shaft dimensions 6 to 20.5 mm Dia.
6.4 to 13 mm Sq.
20 mm min. length
Operating temperature -32 to +55 °C
Storage temperature -32 to +70 °C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP54
CE Conformity
Electromagnetic
Compatibility (EMC) 89/336/EEC
Emissions standards IEC/EN 61000-6-3
Immunity standards IEC/EN 61000-6-2
15 Nm
Material Die cast aluminum alloy
24 VAC and 230 VAC
Gear Lubrication Silicone free Modulating
Dimensions shown in mm Dimensions* 192 mm H x 81 mm 3-position
W x 63 mm D
Weight 1.1 kg
N474
28
Wiring Diagrams
Dual Auxiliary
24 VAC±20%
Input Signal
0 to 10 VDC
Offset and
Selectable
3-position
Product
Feedback
Switches
Position
Number
Span
GEB131.1E ● ●
GEB132.1E ● ● ●
GEB136.1E ● ● ●
GEB331.1E ● ●
GEB332.1E ● ● ●
GEB336.1E ● ● ●
GEB161.1E ● ● ●
GEB163.1E ● ● ● ●
GEB164.1E ● ● ● ● ●
GEB166.1E ● ● ● ●
29
Submittal
Summary OpenAir™ GBB Series
Non-Spring Return,
Electronic Damper Actuators
Dimensions
Specifications
Torque 20 Nm
Runtime for 90° 150 sec. (50Hz)
Frequency 50/60 Hz
Power consumption 24 VAC
Running 5 VA (3-position)
Running 4 VA (modulating)
Holding 1 W (modulating)
Power consumption 230 VAC
Running 8 VA
Angle of rotation 90° nominal, 95° max.
Shaft dimensions 8 to 25.6 mm Dia.
6 to 18 mm Sq.
20 mm min. length
Operating temperature -32 to 55 °C
Storage temperature -40 to 70 °C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP54
CE Conformity
Electromagnetic
Compatibility (EMC) 89/336/EEC
Emissions standards IEC/EN 61000-6-3
Immunity standards IEC/EN 61000-6-2
20 Nm
Material Die-cast aluminum alloy 24 VAC and 230 VAC
Gear Lubrication Silicone free Modulating
W x 72 mm D
Dimensions shown in mm Weight 2.0 kg
N474
30
Wiring Diagrams
Dual Auxiliary
24 VAC±20%
0 to 10 VDC
3-position
Product Feedback
Span and
Switches
Position
Number
Offset
GBB131.1E ● ●
GBB135.1E ● ● ● ●
GBB136.1E ● ● ●
GBB331.1E ● ●
GBB335.1E ● ● ● ●
GBB336.1E ● ● ●
GBB161.1E ● ● ●
GBB163.1E ● ● ● ●
GBB164.1E ● ● ● ● ●
GBB166.1E ● ● ● ●
31
Submittal
Summary OpenAir™ GIB Series
Non-Spring Return,
Electronic Damper Actuators
Dimensions
Specifications
Torque 35 Nm
Runtime for 90° 150 sec. (50Hz)
Frequency 50/60 Hz
Power consumption 24 VAC
Running 10 VA (3-position)
Running 6 VA (modulating)
Holding 2 W (modulating)
Power consumption 230 VAC
Running 13 VA
Angle of rotation 90° nominal, 95° max.
Shaft dimensions 8 to 25.6 mm Dia.
6 to 18 mm Sq.
20 mm min. length
Operating temperature 32 to +55 °C
Storage temperature 40 to +70 °C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP54
CE Conformity
Electromagnetic
Compatibility (EMC) 89/336/EEC
Emissions standards IEC/EN 61000-6-3
Immunity standards IEC/EN 61000-6-2
Material Die-cast aluminum alloy
Gear lubrication Silicone free
Dimensions 300mm H x 120 mm
W x 72 mm D 35 Nm
Weight 2.0 kg 24 VAC and 230 VAC
Modulating
3-position
Dimensions shown in mm
N474
32
Wiring Diagrams
Dual Auxiliary
24 VAC±20%
0 to 10 VDC
Modulating
3-position
Product Feedback
Span and
Switches
Position
Number
Offset
GIB131.1E ● ●
GIB135.1E ● ● ● ●
GIB136.1E ● ● ●
GIB331.1E ● ●
GIB335.1E ● ● ● ●
GIB336.1E ● ● ●
GIB161.1E ● ● ●
GIB163.1E ● ● ● ●
GIB164.1E ● ● ● ● ●
GIB166.1E ● ● ● ●
33
Submittal
Summary OpenAir™ GDB Series
Non-Spring Return, Linear movement
Electronic Damper Actuators
Dimensions
Specifications
Force 125 N
Runtime for 60 mm 150 sec. (50 Hz)
opening and closing
Frequency 50/60 Hz
Power consumption 24 VAC
Running 3 VA (modulating)
Running 2 VA (3-position)
Holding 1 W (modulating)
Power consumption 230 VAC
Running 2 VA
Stroke 60 mm nominal,
64 mm max.
Operating temperature -30 to +55 °C
Storage temperature -30 to +60 °C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP40
CE Conformity
Electromagnetic
Compatibility (EMC) 89/336/EEC
Emissions standards IEC/EN 61000-6-3
Immunity standards IEC/EN 61000-6-2
Material Durable plastic
Gear Lubrication Silicone free
Dimensions 137 mm H x 70 mm
W x 60 mm D
Weight 0.48 kg 125 N
24 VAC and 230 VAC
Modulating
3-position Control
Dimensions shown in mm
N474
34
Wiring Diagrams
Dual Auxiliary
24 VAC±20%
0 to 10 VDC
3-position
Product Feedback
Span and
Switches
Position
Number
Offset
GDB131.2E ● ●
GDB132.2E ● ● ●
GDB136.2E ● ● ●
GDB331.2E ● ●
GDB332.2E ● ● ●
GDB336.2E ● ● ●
GDB161.2E ● ● ●
GDB163.2E ● ● ● ●
GDB164.2E ● ● ● ● ●
GDB166.2E ● ● ● ●
35
Submittal
Summary OpenAir™ GLB Series
Non-Spring Return, Linear movement
Electronic Damper Actuators
Dimensions
Specifications
Force 250 N
Runtime for 60 mm 150 sec. (50 Hz)
opening and closing
Frequency 50/60 Hz
Power consumption 24 VAC
Running 3 VA (modulating)
Running 2 VA (3-position)
Holding 1 W (modulating)
Power consumption 230 VAC
Running 2 VA
Stroke 60 mm nominal,
64 mm max.
Operating temperature -30 to +55 °C
Storage temperature -30 to +60 °C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP40
CE Conformity
Electromagnetic
Compatibility (EMC) 89/336/EEC
Emissions standards IEC/EN 61000-6-3
Immunity standards IEC/EN 61000-6-2
Material Durable plastic
Gear Lubrication Silicone free
Dimensions 137 mm H x 70 mm
W x 60 mm D
Weight 0.48 kg 250 N
24 VAC and 230 VAC
Modulating
3-position Control
Dimensions shown in mm
N474
36
Wiring Diagrams
Dual Auxiliary
24 VAC±20%
0 to 10 VDC
3-position
Product Feedback
Span and
Switches
Position
Number
Offset
GLB131.2E ● ●
GLB132.2E ● ● ●
GLB136.2E ● ● ●
GLB331.2E ● ●
GLB332.2E ● ● ●
GLB336.2E ● ● ●
GLB161.2E ● ● ●
GLB163.2E ● ● ● ●
GLB164.2E ● ● ● ● ●
GLB166.2E ● ● ● ●
37
Submittal
Summary OpenAir™ GEB Series
Non-Spring Return, Linear movement
Electronic Damper Actuators
Dimensions
Specifications
Force 400 N
Frequency 50/60 Hz
Runtime for 57mm 150 seconds (50 Hz)
Power consumption 24 VAC
Running 4 VA (3-position)
Running 6 VA (modulating)
Holding 1.5 W (modulating)
Power consumption 230 VAC
Running 3 VA
Stroke 57 mm nominal,
60 mm max.
Operating temperature -32 to +55 °C
Storage temperature -32 to +70 °C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP40
CE Conformity
Electromagnetic
Compatibility (EMC) 89/336/EEC
Emissions standards IEC/EN 61000-6-3
Immunity standards IEC/EN 61000-6-2
Material Die cast aluminum alloy
Gear Lubrication Silicone free
Dimensions 212 mm H x 81 mm
W x 60 mm D
Weight 0.9 kg
400 N
24 VAC and 230 VAC
Modulating
3-position
Dimensions shown in mm
N474
38
Wiring Diagrams
Dual Auxiliary
24 VAC±20%
Input Signal
0 to 10 VDC
Offset and
Selectable
3-position
Product
Feedback
Switches
Position
Number
Span
GEB131.2E ● ●
GEB132.2E ● ● ●
GEB136.2E ● ● ●
GEB331.2E ● ●
GEB332.2E ● ● ●
GEB336.2E ● ● ●
GEB161.2E ● ● ●
GEB163.2E ● ● ● ●
GEB164.2E ● ● ● ● ●
GEB166.2E ● ● ● ●
39
Submittal
Summary OpenAir™ GBB Series
Non-Spring Return, Linear movement
Electronic Damper Actuators
Dimensions
Specifications
Force 440 N
Runtime for 70mm 150 sec. (50Hz)
Frequency 50/60 Hz
Power consumption 24 VAC
Running 5 VA (3-position)
Running 4 VA (modulating)
Holding 1 W (modulating)
Power consumption 230 VAC
Running 8 VA
Stroke 70 mm nominal,
75 mm max.
Operating temperature -32 to 55°C
Storage temperature -40 to 70°C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP40
CE Conformity
Electromagnetic
Compatibility (EMC) 89/336/EEC
Emissions standards IEC/EN 61000-6-3
Immunity standards IEC/EN 61000-6-2
Material Die-cast aluminum alloy
Gear Lubrication Silicone free
Dimensions 373 mm H x 100 mm
W x 67.5 mm D
Weight 2.0 kg
440 N
24 VAC and 230 VAC
Modulating
3-position
Dimensions shown in mm
N474
40
Wiring Diagrams
Dual Auxiliary
24 VAC±20%
0 to 10 VDC
3-position
Product Feedback
Span and
Switches
Position
Number
Offset
GBB131.2E ● ●
GBB135.2E ● ● ● ●
GBB136.2E ● ● ●
GBB331.2E ● ●
GBB335.2E ● ● ● ●
GBB336.2E ● ● ●
GBB161.2E ● ● ●
GBB163.2E ● ● ● ●
GBB164.2E ● ● ● ● ●
GBB166.2E ● ● ● ●
41
Submittal
Summary OpenAir™ GDB, VAV Compact
Controller Non-Spring Return,
Electronic Damper Actuators
Dimensions
Specifications
Torque 5 Nm
Runtime for 90° 150 sec. (50 Hz)
opening and closing
Frequency 50/60 Hz
Power consumption 24 VAC
Running 3 VA
Running+Calibration 7.5 VA
Holding 1W
Vnom range 1.00 ... 2.55
Vmin range -20% ... 100%
Vmax range 20% ... 120%
Differential
pressure range 0 Pa ... 300 Pa
Accuracy (dP=2% ...
100%, Vn =1, T=25°C) ±2.5 %
Time constant 1s
Angle of rotation 90° nominal, 95° max.
Shaft dimensions 8 to 16 mm Dia.
6 to 12.8 mm Sq.
30 mm min. length
Operating temperature 0 to +50 °C
Storage temperature -25 to +70 °C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP54
Material Durable plastic
CE Conformity 5 Nm
Electromagnetic 24 VAC
Compatibility (EMC) 89/336/EEC Modulating
Emissions standards IEC/EN 61000-6-3 3-position Control
Immunity standards IEC/EN 61000-6-2
Gear Lubrication Silicone free
Dimensions shown in mm
Dimensions 137 mm H x 70 mm
W x 60 mm D
Weight 0.54 kg
N474
42
Wiring Diagrams
0 to 10 VDC
differential
open/close
3-position
Product
Y1 and Y2
pressure
Number sensor
signal
GDB181.1E/3 ● ● ● ● ●
43
Submittal
Summary OpenAir™ GLB, VAV Compact
Controller Non-Spring Return,
Electronic Damper Actuators
Dimensions
Specifications
Torque 10 Nm
Runtime for 90° 150 sec. (50 Hz)
opening and closing
Frequency 50/60 Hz
Power consumption 24 VAC
Running 3 VA
Running+Calibration 7.5 VA
Holding 1W
Vnom range 1.00 ... 2.55
Vmin range -20% ... 100%
Vmax range 20% ... 120%
Differential
pressure range 0 Pa ... 300 Pa
Accuracy (dP = 2% ...
100%, Vn=1, T=25° C) ±2.5 %
Time constant 1s
Angle of rotation 90° nominal, 95° max.
Shaft dimensions 8 to 16 mm Dia.
6 to 12.8 mm Sq.
30 mm min. length
Operating temperature 0 to +50 °C
Storage temperature -25 to +70 °C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP54
Material Durable plastic
CE Conformity 10 Nm
Electromagnetic 24 VAC
Compatibility (EMC) 89/336/EEC Modulating
Emissions standards IEC/EN 61000-6-3 3-position Control
Immunity standards IEC/EN 61000-6-2
Gear Lubrication Silicone free
Dimensions shown in mm
Dimensions 137 mm H x 70 mm
W x 60 mm D
Weight 0.54 kg
N474
44
Wiring Diagrams
0 to 10 VDC
differential
open/close
3-position
Product
Y1 and Y2
pressure
Number sensor
signal
GLB181.1E/3 ● ● ● ● ●
45
Submittal
Summary OpenAir™ ASV,
VAV Controller
Dimensions
Specifications
Frequency 50/60 Hz
Power consumption 24 VAC
Running 3 VA
Running+Calibration 7.5 VA
Holding 1W
Vnom range 1.00 ... 2.55
Vmin range -20% ... 100%
Vmax range 20% ... 120%
Differential
pressure range 0 Pa ... 300 Pa
Accuracy (dP=2% ...
100%, Vn =1, T=25° C) ±2.5 %
Time constant 1s
Operating temperature 0 to +50 °C
Storage temperature -25 to +70 °C
Ambient humidity <95% RH,
non-condensing
Pre-cabled connection 0.75 mm2, 0.9 m long
Enclosure IP54
CE Conformity 24 VAC
Electromagnetic Modulating
Compatibility (EMC) 89/336/EEC 3-position Control
Emissions standards IEC/EN 61000-6-3
Immunity standards IEC/EN 61000-6-2
Material Durable plastic
Dimensions 135 mm H x 68 mm
W x 45 mm D
Weight 0.28 kg
Dimensions shown in mm
N474
46
Wiring Diagrams
0 to 10 VDC
differential
open/close
3-position
Product
Y1 and Y2
pressure
Number sensor
signal
ASV181.1E/3 ● ● ● ● ●
47
Submittal
Summary OpenAir™ GGA F&S Series
Spring Return,
Electronic Damper Actuators
Dimensions
Specifications
Dimensions shown in mm
N474
48
Wiring Diagrams
Dual Auxiliary
24 VAC±20%
Temperature
2-position
Product
Switches
Number
sensor
GGA126.1E ● ● ● ●
GGA326.1E ● ● ● ●
49
Siemens Building Technologies AG
HVAC Products
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 24 24
Fax +41 41-724 35 22
www.sibt.com