Huawei Technologies Co., Ltd. provides customers with comprehensive technical support
and service. If you purchase the products from the sales agent of Huawei Technologies Co.,
Ltd., please contact our sales agent. If you purchase the products from Huawei
Technologies Co., Ltd. directly, Please feel free to contact our local office, customer care
center or company headquarters.
Website: http://www.huawei.com
Trademarks
All other trademarks and trade names mentioned in this manual are the property of
their respective holders.
Notice
The information in this manual is subject to change without notice. Every effort has
been made in the preparation of this manual to ensure accuracy of the contents,
but all statements, information, and recommendations in this manual do not
constitute the warranty of any kind, express or implied.
Release Notes
Related Manuals
The following manuals provide more information about the Quidway S6502 Ethernet
Switch.
Manual Content
Quidway S6502 Ethernet Switch It provides information for the system
Installation Manual installation.
Quidway S6500 Series Ethernet It is used for assisting the users in data
Switches Operation Manual configurations and typical applications.
Quidway S6500 Series Ethernet It is used for assisting the users in using
Switches Command Manual various commands.
Organization
Quidway S6502 Ethernet Switch Installation Manual mainly introduces the hardware
features, installation, configuration and maintenance of S6502 Ethernet Switch. To
avoid any possible device damage and personal injury before the installation and
during the installation, please read the manual carefully. The manual consists of the
following chapters.
Chapter 2 Line Processing Unit The chapter introduces LPUs of S6502 Ethernet
Switch.
Intended Audience
Conventions
I. General conventions
Convention Description
Arial Normal paragraphs are in Arial.
Convention Description
Format Description
Press the key with the key name inside angle brackets. For
<Key>
example, <Enter>, <Tab>, <Backspace>, or <A>.
Press the keys in turn. For example, <Alt, A> means the
<Key1, Key2>
two keys should be pressed in turn.
Action Description
Press and hold the primary mouse button and move the
Drag
pointer to a certain position.
V. Symbols
Eye-catching symbols are also used in the manual to highlight the points worthy of
special attention during the operation. They are defined as follows:
Environmental Protection
This product has been designed to comply with the requirements on environmental
protection. For the proper storage, use and disposal of this product, national laws and
regulations must be observed.
Table of Contents
i
Installation Manual
Quidway S6502 Ethernet Switch Table of Contents
ii
Installation Manual
Quidway S6502 Ethernet Switch Table of Contents
iii
Installation Manual
Quidway S6502 Ethernet Switch Table of Contents
iv
Installation Manual
Quidway S6502 Ethernet Switch Table of Contents
v
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
³ÇÓò¹Ç¸É
MAN back bone
Íø
S8016 NE80
GE/GE Trunk GE/GE Trunk
PO
GE/FE POP
S6500 series P
GE FE GE FE
S6502 supports 1+1 redundant AC and DC power supplies. One of its slots is designed
for switching engine and the other for the LPU. Both of them can provide high-density
service ports.
Switching engine (also known as SRPU) is the core component of a S6500 switch.
Currently, following types of switching engines are available on S6502:
LS81P12TE
1-1
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
LS81T12PE
Generally the SRPU can provide these functions:
z Forwarding L2/L3 data between LPUs, when connected to LPUs through the
backplane.
z Management and route calculation. It can monitor and reset the LPU, upgrade
LPU software.
z Processing monitoring signals on the power system and fans, which are
transferred through the backplane.
In addition to these functions, the SRPU of S6502 also can provide high-density service
ports:
z LS81P12TE: provides four 10/100/1000BASE-T ports and 12 × 1000BASE-X
(SFP) ports.
z LS81T12PE: provides 12 × 10/100/1000BASE-T port and four 1000BASE-X (SFP)
ports.
Item LS81T12PE/LS81P12TE
Switching capacity 48 Gbps
Number of VLANs 4K
1-2
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
1.3 LS81P12TE
1.3.1 Specifications
Item LS81P12TE
CPU MPC8245
Boot ROM 512KB
Flash memory 32MB
SDRAM 256M
1-3
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
Item LS81P12TE
IEEE 802.3z
IEEE 802.3ab
IEEE 802.1p
IEEE 802.1Q
IEEE 802.1D
Supported standard IEEE802.1X
IEEE802.1s
IEEE802.1w
IEEE 802.3x
IEEE 802.3ad
IEEE802.3
LED Status
1-4
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
1.3.3 Cable
Maximum
Central Conn
SFP module Matching cable transmission
wavelength ector
distance
50/125 µm
550 m (1804
multimode optical
ft)
fiber cable
1000BASE-SX-SFP 850nm LC
62.5/125 µm
multimode optical 275 m (902 ft)
fiber cable
1000BASE-LX-SFP 9/125 µm single 10 km (6 mi)
1310nm LC mode optical fiber 30 km (about
1000BASE-LH-SFP cable 19 mi)
1000BASE-ZX-LR- 40 km (about
SFP 25 mi)
9/125 µm single
1000BASE-ZX-VR-
1550nm LC mode optical fiber 70 km (43 mi)
SFP
cable
1000BASE-ZX-UR-
100km (62 mi)
SFP
9/125 µm single
SFP-GE-LH70-SM1
1470nm LC mode optical fiber 70km (43 mi)
470-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1490nm LC mode optical fiber 70km (43 mi)
490-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1510nm LC mode optical fiber 70km (43 mi)
510-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1530nm LC mode optical fiber 70km (43 mi)
530-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1550nm LC mode optical fiber 70km (43 mi)
550-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1570nm LC mode optical fiber 70km (43 mi)
570-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1590nm LC mode optical fiber 70km (43 mi)
590-CW
cable
1-5
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
Maximum
Central Conn
SFP module Matching cable transmission
wavelength ector
distance
9/125 µm single
SFP-GE-LH70-SM1
1610nm LC mode optical fiber 70km (43 mi)
610-CW
cable
1000BASE-T-FD-S
- RJ45 - 100m (328 ft)
FP
Category-5 twisted pair cable is ended with RJ45 connectors, whose maximum
transmission distance is 100 m.
1.4 LS81T12PE
1.4.1 Specifications
Item LS81P12TE
CPU MPC8245
Connector RJ-45, LC
Number of ports 16
1-6
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
Item LS81P12TE
1000 Mbps full duplex (optical port)
10 Mbps half/full duplex (electric port)
Port rate
100 Mbps half/full duplex (electric port)
1000M full duplex (electric port)
IEEE 802.3z
IEEE 802.3ab
IEEE 802.1p
IEEE 802.1Q
IEEE 802.1D
Supported standard IEEE802.1X
IEEE802.1s
IEEE802.1w
IEEE 802.3x
IEEE 802.3ad
IEEE802.3
LED Status
1-7
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
Refer to 1.3.3 for information about the port cable required by an LS81T12PE.
LS81FT48A √ √
LS81FT48E √ √
LS81FT48F √ √
LS81FS24A √ √
LS81FM24A √ √
LS81GT8UA √ √
LS82GT20 √ √
LS82GT20A √ √
LS81GT48 √ √
LS81GT48A √ √
LS81T12P √ √
LS81P12T √ √
LS81GB8UA √ √
LS82GP20 √ √
LS82GP20A √ √
LS81TGX1B √ √
LS81TGX1C √ √
LS81T12PE √ √
LS81P12TE √ √
I. Front view
S6502 uses the XG high-speed bus, whose chassis is labelled with silk-printed
characters: XGbus.
1-8
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
The front panel is occupied by the power supply modules, RESET button, COM port
(for PoE management), console port, 10Base-T/100Base-TX management port and its
status LED, fan LED, card status LED.
S6502 provides two horizontal slots, with the upper for SRPU and the lower for LPU.
The SRPU is mandatory, and the lower slot can hold many types of LPU cards.
Figure 1-6 illustrates the front panel of an S6502 switch, where the LS81P12TE is
inserted in slot 0 and LS81GT8UE in slot 1.
(8)
(11)
(9)
(10)
(1) Power switch (2) Power module handle (3) RESET button
(4) COM port (5) Console port (6) Management prot
(7) Fan LED (8) Card status LED (9) Fan tray
(10) Slot 1 (11) Slot 0
Figure 1-6 The front panel of an S6502 switch
Power modules
The power modules, in 1+1 redundancy, are at the top left corner of the chassis. You
can select to be AC or DC powered. There are LED, power switch and power input
socket on a power supply module (refer to Section 4.5 for more information).
RESET button
You can reset the system with the RESET button.
COM port
Item Description
Connector RJ45
Number of connector 1
Supported standard Asynchronous EIA/TIA-232
1-9
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
Note:
S6502 switch can provide power to the powered devices (PDs) connected, such as IP
phone sets, WLAN access point (AP), through the external PoE power distribution unit
and its card supporting PoE function.
Console port
The console port matches RJ45 connector and can be connected to a PC with an
asynchronous serial port cable, for local system debugging, configuration,
maintenance, management, system software loading and so on. It also can be used to
connect to a Modem device for remote debugging, configuration, maintenance,
management and other similar tasks.
Item Description
Connector RJ45
Number of connector 1
Item Description
Connector RJ45
Number of connector 1
z 10 Mbps, half/full duplex
Port rate z 100 Mbps, half/full duplex
z MDI-X
Port cable and max
100 m (328 ft) over category-5 twisted pair cable
transmission distance
1-10
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
Item Description
Function For system software upgrade and network management
LED Status
LED Status
LED Status
1-11
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
(1) (2)
An S6502 chassis provides -48V DC input for connection with external PoE power
distribution unit.
Note:
The backplane, SRPU, power module and fan tray all are required components in
S6502.
1.6.2 Backplane
1-12
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
Note:
The S6502 supports either AC or DC input, but they cannot run concurrently. You can
choose the specific type as needed.
Although the system can operate normally when one power module is working, the
S6502 still provides two slots for power modules, in attempt to support 1+1
redundancy.
The power module on the S6502 is hot-swappable.
The AC power supply module and DC power supply module of an S6502 Ethernet
switch meet the following requirements:
z AC power module and DC power module have exactly the same dimensions and
installation ports;
z AC power module and DC power module have exactly the same type of output
plug-in units located at the same position;
z AC power module and DC power module cannot be both inserted in one S6502.
I. AC power module
For AC power supply, you must use AC power module and AC power socket.
For DC power supply, you must use DC power module and DC power socket.
1-13
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
When connected to an external PoE power supply, the S6502 can supply power to
remote PD devices, such as IP phone sets and WLAN access point hosts, through its
card which support PoE function.
Note:
S6502 supports an external PoE power supply with up to 1500 W power output. A
single PSE2500-A1 power supply module can provide output power of 1250 W with
100 VAC to 140 VAC input voltage, and two modules up to 2400 W output. Three power
supply modules are required to provide output power of 2400 W if power supply
redundancy is desired. When with 200 VAC to 240VAC input voltage, a single
PSE2500-A1 power supply module can provide 2500 W output. Two power modules
are required if power supply redundancy is desired.
The fan tray is at the right side of an S6502 chassis, and directly connected to the
backplane through a connector. The fan fault signals are summarized and transmitted
from the backplane to the SRPU for further processing. The fan tray is hot-swappable.
1-14
Installation Manual
Quidway S6502 Ethernet Switch Chapter 1 Product Overview
Item S6502
Physical dimensions (H × W ×
130.5 x 436 x 400 mm (5.12 x 17.2 x 15.8 in.)
D)
Weight (fully configured) ≤44 lb (20 kg )
Number of SRPU slot 1
Number of LPU slot 1
Max GE ports 64
Max FE ports 48
MTBF (mean time between
218,000 h
failures)
Operating humidity
10% to 90%
(non-condensing)
1-15
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81FT48A
CPU MPC850
BootROM 512 KB
SDRAM 64M
Connector RJ-45
Number of interfaces 48
2-1
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81FT48A
10/100 Mbps half-/full-duplex
Interface transmission speed
MDI/MDI-X auto-sensing
IEEE802.3
IEEE802.3x
IEEE802.3ad
IEEE802.1p
Conformed standard IEEE802.1D
IEEE802.1Q
IEEE802.1X
IEEE802.1s
IEEE802.1w
Every 100 Mbps Ethernet port has a green LED. The following table describes the LED
state.
The matching cable to the interface is category-5 twisted pair with a maximum
transmission distance of 100 m (328 ft).
2-2
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81FT48E
CPU MPC8241
BootROM 512 KB
SDRAM 128M
Connector RJ-45
Number of interfaces 48
2-3
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81FT48E
IEEE802.3
IEEE 802.3ad
IEEE802.3x
IEEE802.1p
Conformed standard IEEE802.1D
IEEE802.1Q
IEEE802.1X
IEEE802.1s
IEEE802.1w
Every port has a green LED. The following table describes the LED state.
The matching cable to the interface is category-5 twisted pair with a maximum
transmission distance of 100 m (328 ft).
2-4
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
This LPU provides 48 × 10/100 Mbps auto-sensing Ethernet electrical interface service
channels. And all the interfaces support PoE, that is, to implement remote power
supply to PDs through Ethernet twisted pair cables.
Attribute LS81FT48F
CPU MPC8241
BootROM 512 KB
SDRAM 128M
Connector RJ-45
Number of
48
i8nterfaces
Maximum PoE
100m (328 ft)
distance
2-5
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81FT48F
Maximum power
Each port provides a maximum power of 15.4 W for the
each port can
connected device.
provide
IEEE802.3
IEEE802.3x
IEEE 802.3ad
IEEE802.1p
IEEE802.1D
Conformed standard
IEEE802.1Q
IEEE802.1X
IEEE802.1s
IEEE802.1w
IEEE802.3af
Every port has a green LED. The following table describes the LED state.
The matching cable to the interface is category-5 twisted pair with a maximum
transmission distance of 100 m (328 ft).
2-6
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Description
Attribute
LS81FM24A LS81FS24A
CPU MPC850
BootROM 512 KB
SDRAM 64M
Dimensions (L ×
366.7 × 340 mm (14.4 × 13.4 in.)
W)
Maximum
power 70 W
consumption
Connector MT-RJ
Number of
24
interfaces
Interface
transmission 100 Mbps full-duplex
speed
IEEE802.3
IEEE802.3x
IEEE802.3ad
IEEE802.1p
Conformed
IEEE802.1D
standard
IEEE802.1Q
IEEE802. 1X
IEEE802.1s
IEEE802.1w
2-7
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Description
Attribute
LS81FM24A LS81FS24A
Optical fiber 62.5/125 µm multimode 9/125 µm single mode optical
and maximum optical fiber cable with the fiber cable with the maximum
transmission maximum transmission transmission distance of 15 km
distance distance of 2 km (1.2 mi) (9.3)
Every 100 Mbps electrical port has a green LED. The following table describes the LED
state.
Central Maximum
Matching
Cards waveleng Connector transmission
cable
th distance
62.5/125 µm
multimode
LS81FM24A 850 nm 2 km (1.2 mi)
optical fiber
cable
MT-RJ
9/125 µm
single mode 15 km (about
LS81FS24A 1310 nm
optical fiber 9 mi)
cable
2-8
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
2.6.1 Introduction
This LPU provides 48 × 100 Mbps full duplex SFP Ethernet optical ports.
Attribute LS81FP48
CPU MPC8241
Boot ROM 512 KB
SDRAM 128M
Number of ports 48
Port transmission speed 100 Mbps full duplex
z 100BASE-FX-MM-SFP
z 100BASE-FX-SM-SFP
SFP module
z 100BASE-FX-SM-LR-SFP
z 100BASE-FX-SM-VR-SFP
2-9
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81FP48
IEEE802.3
IEEE802.3u
IEEE802.3x
IEEE802.3ad
IEEE802.1p
Conformed standard
IEEE802.1D
IEEE802.1Q
IEEE802. 1X
IEEE802.1s
IEEE802.1w
Each 100 Mbps electrical port has a green LED with it, which is described in the
following table.
LED State
OFF The link is down or no link presented.
LINK/ACT ON The link is active.
Blinking Data is being transmitted/received through the port.
Maximum
Central Matching
SFP module Connector transmission
wavelength cable
distance
multimode
100BASE-FX-MM
1310nm LC optical fiber 2 km (1.2 mi)
-SFP
cable
2-10
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Maximum
Central Matching
SFP module Connector transmission
wavelength cable
distance
100BASE-FX-SM-
1310nm 15 km (9.3 mi)
SFP
9/125 µm
100BASE-FX-SM- single mode
1310nm 40 km (24.9 mi)
LR-SFP optical fiber
cable
100BASE-FX-SM-
1550nm 70km (43 mi)
VR-SFP
This LPU provides eight 10/100/1000 Mbps auto-sensing Ethernet electrical interfaces.
Attribute LS81GT8UA
CPU MPC850
BootROM 512KB
SDRAM 64M
Connector RJ-45
Number of interfaces 8
2-11
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81GT8UA
IEEE 802.3ab
IEEE802.3
IEEE802.3x
IEEE802.3ad
IEEE802.1p
Conformed standard
IEEE802.1D
IEEE802.1Q
IEEE802.1X
IEEE802.1s
IEEE802.1w
Every port has two LEDs. The following table describes the LED state.
LED State
Off No link is present.
LINK
On A link is present.
Off No packets are transmitted/received on the port.
ACT Packets are being transmitted/received on the
Blinking
port.
The matching cable to the interface is category-5 twisted pair with a maximum
transmission distance of 100 m (328 ft).
2-12
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
This LPU provides eight 10/100/1000 Mbps auto-sensing Ethernet electrical interfaces.
Attribute LS81GT8UE
CPU MPC850
BootROM 512 KB
SDRAM 64M
Connector RJ-45
Number of interfaces 8
2-13
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81GT8UE
IEEE 802.3ab
IEEE802.3
IEEE802.3x
IEEE802.1D
Conformed standard
IEEE802.1Q
IEEE802.1X
IEEE802.1s
IEEE802.1w
Every port has two LEDs. The following table describes the LED state.
LED State
OFF No link is present.
LINK
ON A link is present.
OFF No packets are transmitted/received on the port.
ACT
Blinking Packets are being transmitted/received on the port.
The matching cable to the interface is category-5 twisted pair with a maximum
transmission distance of 100 m (328 ft).
2-14
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS82GT20
CPU MPC8241
BootROM 512 KB
SDRAM 64M
Maximum power
45 W
consumption
Connector RJ-45
Number of interfaces 20
10/100 Mbps half-/full-duplex
Interface transmission
1000 Mbps full-duplex
speed
MDI/MDI-X auto-sensing
2-15
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Every port has one LED. The following table describes the LED state.
The matching cable to the interface is category-5 twisted pair with a maximum
transmission distance of 100 m (328 ft).
2-16
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS82GT20A
CPU MPC8241
BootROM 512 KB
SDRAM 128M
Maximum power
45 W
consumption
Connector RJ-45
Number of interfaces 20
10/100 Mbps half-/full-duplex
Interface transmission
1000 Mbps full-duplex
speed
MDI/MDI-X auto-sensing
Every port has one LED. The following table describes the LED state.
2-17
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
The matching cable to the interface is category-5 twisted pair with a maximum
transmission distance of 100 m (328 ft).
Attribute LS81GT48
CPU MPC8241
BootROM 512 KB
SDRAM 128M
Connector RJ-45
Number of interfaces 48
2-18
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81GT48
IEEE 802.3ab
IEEE802.3
IEEE802.3x
IEEE802.1p
Conformed standard IEEE802.1D
IEEE802.1Q
IEEE802.1X
IEEE802.1s
IEEE802.1w
Every port has a LED. The following table describes the LED state.
The matching cable to the interface is category-5 twisted pair with a maximum
transmission distance of 100 m (328 ft).
2-19
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81GT48A
CPU MPC8241
BootROM 512 KB
SDRAM 128M
Connector RJ-45
Number of interfaces 48
Maximum PoE
100m (328 ft)
distance
Maximum power each Each port provides a maximum power of 15.4 W for the
port can provide connected device.
2-20
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81GT48A
IEEE 802.3ab
IEEE802.3
IEEE802.3x
IEEE802.1p
IEEE802.1D
Conformed standard
IEEE802.1Q
IEEE802.1X
IEEE802.1s
IEEE802.1w
IEEE802.3af
Every port has a LED. The following table describes the LED state.
The matching cable to the interface is category-5 twisted pair with a maximum
transmission distance of 100 m (328 ft).
2-21
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81T12P
CPU MPC8241
BootROM 512 KB
SDRAM 128M
Connector RJ-45, LC
Number of interfaces 16
2-22
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81T12P
IEEE 802.3z
IEEE 802.3ab
IEEE 802.1p
IEEE 802.1Q
IEEE 802.1D
Conformed standard IEEE802.1X
IEEE802.1s
IEEE802.1w
IEEE 802.3x
IEEE 802.3ad
IEEE802.3
2-23
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Maximum
Central Conn
SFP module Matching cable transmission
wavelength ector
distance
50/125 µm
550 m (1804
multimode optical
ft)
fiber cable
1000BASE-SX-SFP 850nm LC
62.5/125 µm
multimode optical 275 m (902 ft)
fiber cable
1000BASE-LX-SFP 9/125 µm single 10 km (6 mi)
1310nm LC mode optical fiber 30 km (about
1000BASE-LH-SFP cable 19 mi)
1000BASE-ZX-LR- 40 km (about
SFP 25 mi)
9/125 µm single
1000BASE-ZX-VR-
1550nm LC mode optical fiber 70 km (43 mi)
SFP
cable
1000BASE-ZX-UR-
100km (62 mi)
SFP
9/125 µm single
SFP-GE-LH70-SM1
1470nm LC mode optical fiber 70km (43 mi)
470-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1490nm LC mode optical fiber 70km (43 mi)
490-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1510nm LC mode optical fiber 70km (43 mi)
510-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1530nm LC mode optical fiber 70km (43 mi)
530-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1550nm LC mode optical fiber 70km (43 mi)
550-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1570nm LC mode optical fiber 70km (43 mi)
570-CW
cable
9/125 µm single
SFP-GE-LH70-SM1
1590nm LC mode optical fiber 70km (43 mi)
590-CW
cable
2-24
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Maximum
Central Conn
SFP module Matching cable transmission
wavelength ector
distance
9/125 µm single
SFP-GE-LH70-SM1
1610nm LC mode optical fiber 70km (43 mi)
610-CW
cable
1000BASE-T-FD-S
- RJ45 - 100m (328 ft)
FP
The matching cable to Ethernet interface is category-5 twisted pair with a maximum
transmission distance of 100 m (328 ft).
This LPU provides 12 x 1000 Mbps full-duplex SFP interfaces and four 10/100/1000
Base-T auto-sensing Ethernet interfaces.
Attribute LS81P12T
CPU MPC8241
BootROM 512 KB
SDRAM 128M
2-25
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81P12T
Connector RJ-45, LC
Number of interfaces 16
1000 Mbps full-duplex (optical/electrical)
Interface transmission speed
10/100 Mbps half-/full-duplex (electrical)
2-26
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Refer to 2.13.3 .
Attribute LS81GB8UA
CPU MPC850
BootROM 512 KB
SDRAM 64M
Maximum power
60 W
consumption
Interface
1000 Mbps / Full-duplex
transmission speed
1000BASE-SX-GBIC
1000BASE-LX-GBIC
1000BASE-LH-GBIC
GBIC modules 1000BASE-ZX-LR-GBIC
1000BASE-ZX-VR-GBIC
1000BASE-ZX-UR-GBIC
1000BASE-T-FD-GBIC
2-27
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81GB8UA
IEEE 802.3
IEEE 802.3z
IEEE 802.3x
IEEE 802.3ad
IEEE 802.3z
Conformed standard IEEE 802.1p
IEEE 802.1Q
IEEE 802.1D
IEEE 802.1X
IEEE 802.1s
IEEE 802.1w
Note:
GBIC module is a hot-swappable connector which can connect with optical fiber. A
GBIC module provides one data receive/transmit channel.
Every 1000M GBIC port has a green LED. The following table describes the LED state.
2-28
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Maximum
Central Matching
GBIC module Connector transmission
wavelength cable
distance
50/125 µm
multimode
500 m (1640 ft)
optical fiber
1000BASE-SX- cable
850 nm
GBIC 62.5/125 µm
multimode
220 m (722 ft)
optical fiber
cable
1000BASE-LX-
10 km (6 mi)
GBIC SC
1310 nm
1000BASE-LH- 30 km (about 19
GBIC mi)
9/125 µm
1000BASE-ZX- single mode 40 km (about 25
LR-GBIC optical fiber mi)
cable
1000BASE-LX-
1550 nm 70 km (43 mi)
VR-GBIC
1000BASE-ZX-
100km (62 mi)
UR-GBIC
1000BASE-T-F
- RJ-45 - 100 m (328 ft)
D-GBIC
2-29
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81GP8UB
CPU MPC850
BootROM 512 KB
SDRAM 64M
Maximum power
15 W
consumption
2-30
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS82GP20
CPU MPC8241
BootROM 512 KB
SDRAM 64M
2-31
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS82GP20
SFP modules Refer to Table 2-27
IEEE802.3
IEEE802.3z
IEEE802.1p
IEEE802.1Q
IEEE802.1D
Conformed standard
IEEE802.3x
IEEE802.1X
IEEE802.1w
IEEE802.3ad
IEEE802.1s
2-32
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS82GP20A
CPU MPC8241
BootROM 512 KB
SDRAM 128M
Maximum power
35 W
consumption
2-33
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81TGX1B
CPU MPC8245
BootROM 512 KB
SDRAM 64M
2-34
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81TGX1B
Maximum power consumption 35 W
Connector SC
Number of interfaces 1
10 GE
Interface transmission speed
Full-duplex
IEEE 802.1p
IEEE 802.1Q
IEEE 802.1D
IEEE 802.3
IEEE 802.3x
Conformed standard
IEEE 802.3ad
IEEE 802.3ae
IEEE802.1X
IEEE802.1s
IEEE802.1w
LED State
OFF No link is present.
LINK
ON A link is present.
OFF No packets are transmitted/received on the port.
ACT
Blinking Packets are being transmitted/received on the port.
2-35
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Maximum
XENPAK Central
Connector Matching cable transmission
module wavelength
distance
10GBASE-SR- multimode optical
850nm 300 m (984 ft)
XENPAK fiber cable
10GBASE-LR-
1310 nm SC 9/125 µm single 10 km (6 mi)
XENPAK
mode optical fiber
10GBASE-ER- cable 40 km (about
1550 nm
XENPAK 25 mi)
Attribute LS81TGX1C
CPU MPC8245
BootROM 512 KB
SDRAM 64M
2-36
Installation Manual
Quidway S6502 Ethernet Switch Chapter 2 Line Processing Unit
Attribute LS81TGX1C
10GBASE-SR-XENPAK (multimode optical
fiber, 850 nm, 300 m)
10GBASE-LR-XENPAK (single mode optical
XENPAK modules
fiber, 1310 nm, 10 km)
10GBASE-ER-XENPAK (single mode optical
fiber, 1550 nm, 40 km)
IEEE 802.1p
IEEE 802.1Q
IEEE 802.1D
IEEE 802.3
IEEE 802.3x
Conformed standard
IEEE 802.3ad
IEEE 802.3ae
IEEE802.1X
IEEE802.1s
IEEE802.1w
LED State
OFF No link is present.
LINK
ON A link is present.
OFF No packets are transmitted/received on the port.
ACT
Blinking Packets are being transmitted/received on the port.
2-37
Installation Manual
Quidway S6502 Ethernet Switch Chapter 3 Installation Preparations
z Turn OFF all powers and remove all power cords before opening the chassis.
z Keep the chassis clean and dust-free.
z Keep the chassis and installation tools away from walk areas.
z Do not wear loose clothing, jewelry (including ring and necklace etc.) or any other
things that could get caught by the chassis when you install and maintain the
switch.
3.1.2 Electricity
z Look carefully for possible hazards in your work area, such as ungrounded power
extension cables, missing safety grounds, and moist floors.
z Locate the emergency power-off switch in the room before installation. Shut the
power off first when accident occurs.
z Unplug all the power cords and external cables before moving the chassis.
z Better not maintain the equipment alone when it is powered on.
z After shut off a switch, always check and make sure it is powered off.
z Do not place the switch on a moist area and avoid liquid flowing into the switch.
3.1.3 Moving
The S6502 is rather big and heavy, so follow the recommendations below when moving
them.
z Turn off all powers and remove all the power cords before moving the chassis.
z Do not move the switch alone. Work with another person.
z Move the switch slowly and stably. Never move suddenly or twist your body.
z Move the switch at stable and consistent paces with your peer. Keep balance of
your body.
3-1
Installation Manual
Quidway S6502 Ethernet Switch Chapter 3 Installation Preparations
Caution:
Do not hold the power handlers, but the handles on the rear of the chassis, or put
fingers into the vent of chassis when moving the switch.
Since the power handler and vent have not been designed to bear the weight of the
entire chassis, it may hurt the switch chassis or even your body when you move the
switch by handling them.
To prevent the electric component from being damaged by the electrostatic discharge
(ESD), take ESD measures for the area where the switch is located and pay attention to
the following:
z Always wear an ESD wrist strap when installing the components, especially the
electric printed circuit boards, of the switch.
z Take the edge of the circuit board. Do not touch the components or the electric
printed circuit.
Take the following steps to use the ESD wrist strap.
Step 1: Put your hand through the wrist strap and wear it
Step 2: Strain and tighten the strap, ensure that it makes good contact with your skin.
Step 3: Insert it into the ESD wrist strap hole in the switch chassis or attach the alligator
clips to the grounding screw of the chassis.
Step 4: Make sure the ESD wrist strap is well grounded.
Note:
The ESD wrist strap is shipped with the S6502.
There is an ESD wrist strap hole on the left side of the S6502 power module. The
grounding screw is located on the bottom right corner of the chassis rear.
Caution:
For safety consideration, check the resistance of the ESD wrist strap. The resistance
between human body and the ground should be 1 to 10Mohm.
3-2
Installation Manual
Quidway S6502 Ethernet Switch Chapter 3 Installation Preparations
3.1.5 Laser
Some LPUs of S6502 have optical ports. In operating status, it is prohibited to stare into
the open optical port because the laser emitted from it has very high power density and
is harmful to your retina.
Caution:
Staring at the laser beam inside the fiber could hurt your eyes.
To ensure the normal operation and service life of a switch, a certain level of
temperature and humidity should be maintained in the equipment room. If the humidity
in the equipment room is too high and for a long time, it may go bad insulated or even
power leakage may occur. Sometimes, high humidity may result in material mechanical
performance changing or metal parts rusted. If the relative humidity is too low, the
captive screws may become loose due to the shrinkage of the insulation washers.
Meanwhile, the electrostatic is likely to be produced in the dry environment, which will
jeopardize the CMOS circuit of the switch. The higher the temperature, the greater the
damage it will do on the switch. High temperature for a long time will speed up the aging
process of the insulation materials, greatly lower the reliability of the switch and
therefore affect its service life seriously.
Dust does serious harm to the normal operation of the switch. The indoor dust
accumulated on the chassis can cause electrostatic adsorption, resulting in poor
contact between connectors or metal contact points. This happens more frequently
when the relative indoor humidity is low, which will not only shorten the service life of
the switch, but also cause communication failures.
The required specifications on dust density and particle diameter in an equipment room
are shown in the following table.
3-3
Installation Manual
Quidway S6502 Ethernet Switch Chapter 3 Installation Preparations
Mechanical active
Unit Content
material
4
≤3 x 10
Dust particle particles/m³
(No visible dust on desk in three days)
Note: Dust particle diameter ≥ 5µm
Any possible interference sources, no matter outside or inside the system, affect the
switch in use may in a way of capacitance coupling, inductance coupling, radiation of
electromagnetic wave, common impedance (including the grounding system) coupling
or conducting line (power line, signaling line and transmission line etc.).Therefore, the
following should be considered:
z Adopt effective measures to protect the power supply system against the power
grid interference.
z Separate the working ground of the switch from the ground device of the power
supply equipment or lightning-protection ground device as far as possible.
z Keep the switch far away from the radio launcher, radar launcher, and
high-frequency devices working in high currents.
If necessary, adopt electromagnetic shield.
3-4
Installation Manual
Quidway S6502 Ethernet Switch Chapter 3 Installation Preparations
A good grounding system is the basis for a switch to work stably and reliably and the
important guarantee of lightning protection, anti-interference and ESD. A switch should
be provided with good grounding system.
For better heat dissipation and equipment maintenance, it is recommended to keep the
front and back of the switch more than 1 meters inclusive away from the walls or other
devices. There can be other devices located beside the left and right of the switch.
However, you shall keep the left and right of the switch more than 0.8 meters inclusive
away from the walls. If the optional rack will be installed, the net height of equipment
room should be more than 3 meters inclusive.
Before rack-mounting a switch, make sure the rack meets the following requirements:
z Better mount a switch in an open rack. However, if you mount a switch in a closed
rack, make sure of good heat dissipation system.
z Make sure the rack stands steadily enough to well support the switch and
accessories.
z Make sure that the switch fits the rack size. Leave enough spaces beside the left
and right panels of the switch for chassis heat dissipation.
3-5
Installation Manual
Quidway S6502 Ethernet Switch Chapter 3 Installation Preparations
Measure and Long tape, ruler (of 1 meter), level, marking pen,
lineation tools powder marker and pencil
A percussion drill, several auxiliary drill bits, a vacuum
Drills
cleaner
Flat-blade screwdriver P4-75mm
Phillips screwdriver P1-100mm, P2-150mm and
P3-250mm
Fastening
General Socket wrench 5.0kgf.cm
tools
tools Box-end wrench M6
Box-end wrenches (10-12) or open-end wrench
(10-12)
Sharp-nose pliers, diagonal pliers, vices, hand-held
Small tools electric drill, file, handsaw, crowbar and rubber
hammer
Note:
The instruments and tools are not shipped with the S6502, so you need to make them
available by yourself.
3-6
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Start installation
Preparation and
confirmation
Confirm
installation site
Install cards
End of installation
Note:
The switch should be equipped with at least two sets of power supply.
4-1
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Caution:
For the safety of personnel and equipments, the switch must be well grounded. The
resistance between switch chassis and the ground should be less than 1 ohm.
4-2
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Note:
The grounding screw is located on the bottom right corner of the chassis.
Step 1: Remove the screw from the grounding hole in the switch chassis.
Step 2: Set the ground wire connector shipped with the switch around the grounding
screw.
Step 3: Fasten the grounding screw in the grounding hole on the chassis.
Step 4: Connect the other end of the ground wire to the grounding strip of the switch.
Note:
Each cabinet has a grounding strip, to which you can connect the ground wire of a
switch.
Hereafter introduced some methods for grounding the switch in different environment.
z If there is a grounding strip in the Ethernet switch installation environment, attach
one end of the yellow-green protection ground wire to the grounding screw of the
grounding strip and fasten the captive nuts. The ground wire of a switch shall be
connected to the project ground of the equipment room.
Caution:
Note that the fire main and lightning rod of a building are not suitable for grounding the
switch.
4-3
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Ethernet Switch
Grounding screw
Power input
Grounding wire
Grounding strip
z If there is no grounding strip but earth nearby and the grounding body is allowed to
be buried, you can simply hammer an angle iron or steel pipe no shorter than 0.5m
into the earth. In this case, the yellow-green protection ground wire should be
welded with the angle iron (steel pipe) and the joint should be processed against
eroding.
Ethernet Switch
Grounding screw
Power input
Grounding wire
Ground
Angle iron
Figure 4-3 Sketch of grounding when it is allowed to bury grounding body nearby in an
equipment room
z If there is no grounding strip and no grounding body can be buried, and the
Ethernet switch is AC powered, you can grounded through the PE wire of the AC
power supply. In this case, make sure that the PE wire of the AC power supply has
been well grounded at the power distribution room or AC power supply
transformer side.
4-4
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Ethernet Switch
Power transformer N
L
AC power input
(with triple cable)
Grounding screw
PE
Caution:
For lightning protection, the AC power should be led through the external lightning
device into the S6502.
(4)
The power module has AC input socket with bail latch and a power LED on its front
panel (The LED is described in 6.1.2).
Step 1: Pull up the bail latch which is on the left side of the front panel to the right.
Step 2: Insert the AC power cord which is shipped with the switch into the AC input
socket of the power supply module.
Step 3: Push back the bail latch to keep the power cord from being removed.
Step 4: Insert the other end of the power cord into the site power socket.
4-5
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Cabling rack
4-6
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Note:
Save the removed blank panel for future use.
I. Introduction
Console cable is an 8-core shielded cable. One end of the cable is a crimped RJ-45
connector, which is to be plugged into the console port of the switch. The other end is
furnished with a DB-9 (male) connector and can be inserted to the 9-core (female)
socket. The following figure illustrates the console cable.
4 CD → 1
5 GND - 5
6 RXD → 2
7 DSR → 6
8 CTS → 8
Take the following steps to connect the console cable when configuring the switch via a
terminal.
4-7
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Step 1: Plug the DB-9 female plug of the console cable to the serial port of a PC or a
terminal where the switch is to be configured.
Step 2: Connect the RJ-45 connector of the console cable to the console port of the
switch.
I. Introduction
PIN #8
PIN #1
10Base-T/100Base-TX 1000Base-T
Pinout
Signal Function Signal Function
Bi-directional data
1 Tx+ Outbound BIDA+
cable A+
Bi-directional data
2 Tx- Outbound BIDA-
cable A-
Bi-directional data
3 Rx+ Inbound BIDB+
cable B+
Bi-directional data
4 Reserved - BIDC+
cable C+
Bi-directional data
5 Reserved - BIDC-
cable C-
Bi-directional data
6 Rx- Inbound BIDB-
cable B-
Bi-directional data
7 Reserved - BIDD+
cable D+
Bi-directional data
8 Reserved - BIDD-
cable D-
4-8
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Note:
Tx refers to Outbound
Rx refers to Inbound
BI refers to Bi-directional
10Base-T/100Base-TX 1000Base-T
Pinout
Signal Function Signal Function
Bi-directional data cable
1 Rx+ Inbound BIDB+
B+
Bi-directional data cable
2 Rx- Inbound BIDB-
B-
Bi-directional data cable
3 Tx+ Outbound BIDA+
A+
Bi-directional data cable
4 Reserved - BIDD+
D+
Bi-directional data cable
5 Reserved - BIDD-
D-
Bi-directional data cable
6 Tx- Outbound BIDA-
A-
Bi-directional data cable
7 Reserved - BIDC+
C+
Bi-directional data cable
8 Reserved - BIDC-
C-
Step 1: Plug one end of the category-5 cable into an Ethernet RJ-45 jack of the switch
to be connected.
Step 2: Plug the other end of the cable into an RJ-45 port of the peer device.
I. Introduction
Before connecting the fibers, make sure the type of the connector and the fiber match
that of the optical port.
Fiber connectors are indispensable passive components in optical fiber communication
system. Their application enables the removable connection between optical channel,
4-9
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
which makes optical system debugging and maintenance more convenient and transit
dispatching more flexible. Among multiple fiber connectors, only SC, LC, and MT-RJ
will be introduced here.
z MT-RJ fiber connector: It integrates two channels of light sources into a single
fiber, which reduces the actual ports that are in use of a connector.
z SC fiber connector
z LC fiber connector
Step 1: Remove the fiber cover and clean the fiber end.
Step 2: Remove the optical port cover of the switch. Insert one end of the fiber into the
optical port of the switch.
Step 3: Connect the other end of the fiber to the corresponding device.
4-10
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Caution:
When the optical port has not been connected with a fiber connector or its dustproof
cover is open, there might be some invisible radiation emitted from the optical port. So
do not stare into the optical port directly.
Cover the optical port if there is no connector plugged in.
If the chassis of a switch stands alone, you do not have to care about the inside or
outside cabinet cabling. All the port service cables can run along the left side of the
chassis (cabling channel), and the chassis power cords can run upward or downward
based on the specific conditions in the equipment room (lightning protection box,
terminal bar etc).
For the switches are mounted in a 19-inch standard rack, the service cables can be
bound to the cable binding rack at the left side of the chassis and be arranged to run on
the cable rack or in the raised floor according to the situation in an exchange equipment
room (whether the signal cable of the room is accessed from the cable rack on the top
of the chassis or the cable channel under the floor.) Collect all the transit data signal
cable connectors and locate them on the floor of the chassis instead of any places
outside the chassis for fear of unexpected damage. The power cords run out of the rear
left of the chassis and either on the cable rack or in the raised floor as near as possible
based on the specific conditions in the equipment room (lightning protection box,
terminal bar etc).
Correctly edit the label and paste it to a proper place on the bound cables.
4-11
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Twisting
Bending
z The radius of the curve at which a cable is bent should be no less than twice of the
cable’s diameter. At the point where a cable runs out of a connector, the radius of
the curve at which the cable is bent should be no less than five times of its
diameter.
z Cables of different type (that is, power cord, signal cable, ground wire, etc.) should
run and be bound separately in a cabinet. They cannot be bound together. If they
are close to each other, you can cable them in a crossing way. For parallel cabling,
the space between power cord and signal cable should be no less than 30mm;
z The cable binding rack and cable channel inside and outside a cabinet should be
smooth and stretch no sharp points.
z The metal hole through which a cable runs should have a smooth and fully surface
or an insulating bush;
z Use the right type of ties to bind the cables. Do not bind any cables with tied ties.
Huawei technologies provides the following types of ties: 100*2.5mm, 150*3.6mm,
300*3.6mm, 530*9mm, and 580*13mm;
z Bind the cables with ties and cut the extra parts. Trim the cut and leave no sharp
points. See the following figure:
4-12
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
z Before bending the cables, bind them first. Mind that no tie binds the bended part
of any cables, for fear of cable core breaking due to excessive stress. See the
following figure.
z The spare cables or excessive parts should be folded and bound and located at
right places in a cabinet or on the cable channel. In the so-called right places, the
running device will not be affected or damaged and the cables will not be damaged,
either.
z 220V power cord and -48V power cord cannot be tied on the guides of any mobile
components;
z Keep excessive parts of power cords for those mobile components, such as
ground wire of doors, to free the cables from possible stress. When installing these
components, make sure the excessive cables will not touch heat source, sharp
point, or keen edges. Use high temperature cables near the heat sources;
4-13
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
z For the cable terminals fixed with screw thread, the screws or nuts should be
fastened and prevented from loosing. See the following figure;
z Fix the terminal of harder power cords to free the terminal and the cable from
stress;
z No tapping screw can be used to fasten the cabling terminals;
z The power cords of the same type and in the same direction should be bound
together and kept clean and straight;
Follow the parameters defined in the following table for binding cables with ties.
30 200~300
4-14
Installation Manual
Quidway S6502 Ethernet Switch Chapter 4 Hardware Installation
Caution:
Confirm that you have turned off the power before checking, otherwise, improper
connection will hurt people or the component of the switch.
After installing the switch, please check if the items listed in the following table are
normal.
Power cord
SRPU
LPU
Fan Frame
4-15
Installation Manual
Quidway S6502 Ethernet Switch Chapter 5 System Debugging
Switch
To console port
To serial port
Console cable
PC
Figure 5-1 Configuration environment
Step 1: Plug the DB-9 female plug of the console cable to the serial port of the PC or the
terminal where the switch is to be configured.
Step 2: Connect the RJ-45 connector of the console cable to the console port of the
switch.
Parameter requirements:
z Bits per second: 9600
z Data bits: 8
z Parity: none
z Stop bits: 1
z Flow control: none
z Emulation: VT100
Taking the PC running Windows98 HyperTerminal as an example, this section
introduces how to set the terminal parameters.
5-1
Installation Manual
Quidway S6502 Ethernet Switch Chapter 5 System Debugging
Step 1: Start the PC and run the terminal emulator (such as Terminal on Windows3.1
and the HyperTerminal on Windows95/Windows98/Windows 2000/Windows
NT/Windows XP/Windows ME).
Step 2: Set the parameters for Windows98 HyperTerminal as follows:
1) Click Start > Program > Accessories > Communications > HyperTerminal to enter
the HyperTerminal window, and then click the Hypertrm icon to establish a new
connection. The system will pop up the Connection Description window.
2) Input the name of the new connection and click <OK>. Then there pops up the
interface as shown in the following figure. Select the serial port to be used from the
Connect using drop down list.
5-2
Installation Manual
Quidway S6502 Ethernet Switch Chapter 5 System Debugging
3) After selecting serial ports, click <OK>. The following interface will pop up for
setting serial port parameters. Set the baud rate to 9600, data bits to 8, parity
check to none, stop bits to 1 and flow control to none.
5-3
Installation Manual
Quidway S6502 Ethernet Switch Chapter 5 System Debugging
4) After setting serial port parameters, click <OK>. Then the system will enter the
HyperTerminal dialogue box as shown in the following figure.
In the above dialogue box, select the Properties icon to enter the properties window.
Click Settings to set the attributes (see the following figure). In this interface, select
terminal emulation mode VT100 and then click <OK>.
Figure 5-6 Setting terminal emulation mode in the property setting window
5-4
Installation Manual
Quidway S6502 Ethernet Switch Chapter 5 System Debugging
Caution:
Before powering on the switch, confirm where the power switch of the equipment room
is located, so that you will be able to power off in case of accidence.
You are recommended to check as follows after powering on the switch to ensure the
configurations thereafter.
z After a switch is powered on, the heat dissipation system starts working. You can
hear the noise as the fan rotates and feel air flow out from the vent.
z Check if any system indicator on the SRPU indicates abnormal condition.
As the switch is started, the configuration terminal will yield the following output:
Starting......
RAM Line....OK
System is booting................
******************************************
* *
* Quidway S6502 BOOTROM, Version 500 *
5-5
Installation Manual
Quidway S6502 Ethernet Switch Chapter 5 System Debugging
* *
******************************************
Copyright(C) 2001-2008 by HUAWEI-3COM TECHNOLOGIES CO.,LTD.
Creation date: Feb 23 2005, 09:36:37
CPU type : MPC8245
CPU Clock Speed : 300Mhz
BUS Clock Speed : 33Mhz
Flash Size : 32MB
Memory Size : 256MB
The displaying of the above indications indicates the completion of the switch
auto-booting.
Press <Enter> and you will get the following output. By this time, you can start
configuring the switch.
<Quidway>
Note:
The S6502 provides a variety of command views. For the specific descriptions on the
configuration commands and command line interfaces, refer to Quidway S6500 Series
Ethernet Switches Operation Manual and Quidway S6500 Series Ethernet Switches
Command Manual.
5-6
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
After the switch is powered on and the system is normal, the booting information will be
displayed on the configuration terminal. If the configuration system has failed, the
configuration terminal may display illegible characters or nothing at all.
1) No display on the terminal screen
After power on, if there is no information displayed on the terminal, check if:
z The power system works normally.
z SRPU works normally.
z The console cable has been connected to the console port in the SRPU.
If there is no problem in the above checking, there might be some other faults as
follows:
z Serial port connected to the console cable is wrong. (The port in use is not the one
set on the terminal.)
z Configuration terminal parameter setting errors. (Parameter setting requirements:
Set the baud rate to 9600, data bits to 8, parity check to none, stop bits to 1, flow
control to none, and select VT100 as terminal emulation mode.)
z There is something wrong with the console cable.
2) Illegible display on the terminal screen
If the configuration terminal displays illegible characters, the configuration terminal
settings are likely to contain errors. Check the settings one by one. (Set the baud rate to
9600, data bits to 8, parity check to none, stop bits to 1, flow control to none, and select
VT100 as terminal emulation mode.)
6-1
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
If the power LED is off, there may be something wrong with the system power supply.
Check if:
z The switch power has been turned on.
z The power cord has been properly connected.
z The source voltage is correct.
LED Description
ON The fan works normally.
OK The fan fails to work or has not been
OFF
installed yet.
The fan works abnormally or has not been
ON
FAIL installed yet.
OFF The fan works normally.
The LEDs of LPUX (X ranges from 1 to 2 in the S6502) show the state of these cards
respectively.
6-2
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
LED Description
The card fails to work or has not been
ON/OFF
RUN inserted.
Blinking The card works normally.
The card works normally or has not been
OFF
ALM inserted.
ON The card works abnormally.
z If a card ALM LED stays on, there must be something wrong with the
corresponding card. When you reset the card, the ALM LED will turn on. After
normal booting, it will be off.
z When resetting the card, if the ALM LED stays off, the card may have not been
connected with the power source. Check if the card has been properly installed.
Caution:
Step 1: Wear the ESD wrist strap and loosen the captive screw in the module to be
replaced using the screwdriver.
Step 2: Pull the module to be replaced until it slides out of the slot.
Caution:
Because the S6502 power module is heavy, use both hands to pull it out. Hold the
module in one palm and gently pull the handle with the other hand. Install a blank filler
panel on the chassis for dust-proof and heat dissipation if you will not install another
module in this position.
6-3
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Caution:
Install the power module with caution. Note the direction of the panel. During the
process of inserting, if the pin terminal springs up, the system will give an alarm and the
pin cannot be seated into the hole. To avoid breaking or cranking the power terminals,
if the power module has not been inserted in properly, you should slide it out and insert
again.
Step 6: Fasten the captive screws (loosened in Step 1) to fix the power module on the
chassis.
Caution:
If the captive screws cannot be fastened, the power module may not have been
properly seated. Check it carefully.
SRPU and LPUs of the S6502 can be installed and removed basically in the same way.
This section describes the general measures of installing and removing these cards.
Cards of the S6502 are hot-swappable.
I. Required tools
Step 1: Wear the ESD wrist strap and loosen the captive screws on the card with Philip
screwdriver.
6-4
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Step 2: Hold the ejector levers on the card with both hands and press them toward both
sides of you to separate the connectors of the card from the motherboard.
Step 3: Gently slide the card along the guides out of the slot.
Step 4: Put the removed card into the package.
Step 1: Wear ESD wrist strap and loosen the screws and remove the blank filler panel.
Step 2: Hold the ejector levers of the card with both hands and push them outward,
align the card with the guides in the chassis and slide it gently into the slot. Push the
card until the positioning pin on its handle bar touches the hole in the chassis.
Step 3: Press the ejector levers inward and seat the pin on the handle bar into the
positioning hole in the chassis.
Step 4: Fasten the captive screws to fix the card.
Caution:
Do not touch any naked wire, terminal or any part of the product with a dangerous
voltage label to avoid hurting human body.
I. Required tools
6-5
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Step 1: Wear the ESD wrist strap. Loosen the captive installation screws in the fan
frame. Hold the fan frame with one hand, and pull the handle of the frame outward with
the other, making the fan frame pin disconnected from the backplane.
Caution:
If you want to replace the fan frame of an operating switch, wait till the fan stops rotating
before pulling the fan out of the chassis. Since the fan may be still rotating, do not put
your hand into the fan frame for fear of hurting.
Step 2: Slide the fan frame gently along the guides of the slot and pull it out.
Step 3: Put the removed fan frame into the package.
Step 4: Hold the fan frame to be installed with one hand at the handle and the other
hand at the bottom. Slide it gently along the guide into the slot. Push the fan frame until
its positioning pin touches the hole in the chassis.
Step 5: Fasten the captive installation screws.
Caution:
Install a new fan frame soon after removing the old one to ensure that the switch can
work normally.
6-6
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Note:
z Please note that the BOOTROM version must match the host software version
when BOOTROM and host software are being loaded. It is not recommended to
load BOOTROM program frequently, BOOTROM program loading is allowed only
when the host software to be loaded does not match the existing BOOTROM
version.
z Using Boot Menu can only load the SRPU BOOTROM program and host software.
To load LPU BOOTROM, you must use the command line.
If your terminal is directly connected to the switch, you can load BOOTROM and host
software locally.
Before proceeding to load the software, make sure that your terminal is correctly
connected to the switch.
Note:
The steps that you should take to load BOOTROM program and host software are the
same, except that in a BOOTROM program loading process you need to press <Ctrl
+U> and <Enter> after accessing the BOOTROM menu and will view a different prompt
message. BOOTROM loading steps are described below as an example.
I. Boot Menu
After power on, the switch will run BOOTROM program first and the terminal will display
the following information:
******************************************
* *
* Quidway S6502 BOOTROM, Version 500 *
* *
******************************************
6-7
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Note:
To access Boot Menu, press <Ctrl+B> within 5 seconds after the screen prompts
“Press Ctrl-B to enter Boot Menu...” Otherwise, the system will start executing the
program decompression. At this time if you want to access Boot Menu, you will have to
reboot the switch.
If entering the program decompression process, you will have to wait a long time for the
system to get ready, since the program file is rather big in size and many commands
needs to be registered in that case.
Enter the BOOTROM password. After entering the correct password (no password is
set for the switch by default), the system will access Boot Menu:
Caution:
While using the switch, keep in mind the modified BOOTROM password.
Boot Menu
1: Download application file to flash
2: Select application file to boot
3: Display all files in flash
4: Delete file from flash
5: Modify bootrom password
6-8
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
0: Reboot
Enter your choice(0-5):
1) Introduction to XModem
XModem is a file transfer protocol widely used due to its simplicity and good functions.
XModem transfers files via the console port, supporting data packets of 128 bytes and
1KB. With respect to reliability, it supports checksum, CRC, and error packet
retransmission mechanism. Normally, the maximum number of retransmission
attempts is ten.
XModem transmission is completed by the receiving program and sending program.
The receiving program initiates packet checking method negotiation by sending the
negotiation character. If the negotiation passes, the sending program starts packet
transmission. Upon the receipt of a complete packet, the receiving program checks it
using the agreed-upon checking method. If the check succeeds, the receiving program
sends an acknowledgement character; if the check fails, it sends a reject character.
Upon the receipt of the acknowledgement, the sending program continues to send the
next packet; upon the receipt of the reject, it retransmits the packet.
2) Loading SRPU BOOTROM
Follow these steps to download the BOOTROM program:
Step 1: Press <Ctrl+U> and <Enter> in Boot Menu displayed in the section “I. Boot ” to
access the BOOTROM loading menu shown below:
SRPU bootrom update menu:
Step 2: Enter <3> to download the BOOTROM program using XModem. The system
displays the following download speed setting menu:
Please select your download baudrate:
1. 9600
2. 19200
3. 38400
4. 57600
5. 115200*
0. Return
Enter your choice (0-5):5
6-9
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Step 3: Choose an appropriate download baud rate. Type <5> as shown in the above
example to choose the baud rate of 115200 bps. Press <Enter>. The system displays
the following information:
Are you sure to update your bootrom?(Y/N)
Step 4: The system begins to download if you enter <Y>; it returns to the program
downloading menu if you enter <N>. If you enter <Y>, the system displays the following
information:
Download baudrate is 115200 bps. Please change the terminal's baudrate to
115200 bps and select XMODEM protocol.
Press enter key when ready.
Note:
You do not need to modify the HyperTerminal’s baud rate if you have chosen 9600 bps,
and thus can skip Steps 5 and 6 and proceed to Step 7 directly. At this time, the system
will not display the above information.
Step 5: Enter File > Properties in the HyperTerminal window, click <Configure> in the
popup dialog box, select the baud rate of 115200bps in the console port configuration
dialog box.
6-10
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
6-11
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Step 6: Click the Disconnect icon to disconnect HyperTerminal from the switch and
then click the Connect icon to re-establish the connection using the new baud rate
setting.
Note:
After changing the baud rate setting, you must disconnect and reconnect the terminal
emulation program to validate the new configuration.
Step 7: Press <Enter> to start program loading. The system displays the following
information:
Now please start transfer file with XMODEM protocol
If you want to exit, Press <Ctrl+X>
Waiting ... CCCCC
Step 8: Select Transfer > Send File in the HyperTerminal window, and in the popup
dialog box similar to the following figure, click <Browse>, select the software you need
to download, and set the protocol to XModem.
app
6-12
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
app
After completing the downloading, the system displays the following information:
Downloading ...CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCdone!
Are you sure to update SRPU bootrom? Yes or No(Y/N)y
Step 10: Enter <Y> to start file downloading and <N> to return to the program
downloading menu. Suppose you enter <Y>. The system starts BOOTROM program
downloading and upon its completion automatically starts BOOTROM loading. The
system displays the following information upon the completion of the entire process:
SRPU bootrom is updating now......
Get flash Type......FLASH_M29W040B
Erasing flash......done!
Programming flash......done!
Checking flash......done!
Step 11: Enter <3> to return to Boot Menu. Then enter <0> in Boot Menu to reboot the
system and the following information will be prompted:
Rebooting...
Please change the terminal's baudrate to 9600 bps!
6-13
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Step 12: Reset HyperTerminal’s baud rate to 9600 bps with reference to Steps 5 and 6
described above.
Note:
You do not need to reset the HyperTerminal’s baud rate and can skip the last step if you
have chosen 9600 bps. In this case, the system does not display the prompt message
“Please change the terminal's baudrate to 9600 bps!” as shown in Step 11.
The subsequent steps are the same as those for loading BOOTROM, except for the
prompt messages.
1) Introduction to TFTP
Trivial File Transfer Protocol is a TCP/IP protocol used for file transmission between
clients and servers. It uses UDP to provide unreliable data stream transfer service.
2) Loading SRPU BOOTROM
Step 1: Connect the switch to the PC from where the file is to be downloaded, via the
10/100Base-TX interface for loading. The IP address of the PC is required. At the same
time, the switch is connected to a PC (which can be the same one as that holding the
file for downloading) via the console port.
Step 2: Run the TFTP Server program on the PC connected to the Ethernet port, and
specify the path for program loading.
Caution:
z TFTP Server program is not shipped with the Quidway series switches.
z When loading BOOTROM and host software, you must use a crossover cable to
connect to the Ethernet port for upgrading.
6-14
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Step 3: Run terminal emulation program on the PC that is connected to the console port.
Start the switch, access Boot Menu, and then enter download protocol menu.
To download the BOOTROM program, press <Ctrl+U> and <Enter> to access the
menu for BOOTROM downloading when the system displays: “Enter your choice(0-5):”
1. Set TFTP protocol parameter
2. Set FTP protocol parameter
3. Set XMODEM protocol parameter
0. Return to boot menu
Step 4: In the download protocol menu, type <1> to select TFTP protocol to download
BOOTROM or host software. Press <Enter>. The system displays the following
information:
Load File name
Switch IP address
Server IP address
Step 5: Input the TFTP parameter values and press <Enter>. The system displays the
following information:
Are you sure to update SRPU bootrom? Yes or No(Y/N)
Step 6: Enter <Y> to start file downloading and <N> to return to the program
downloading menu. Suppose you enter <Y>. The system starts BOOTROM program
downloading and upon its completion automatically starts BOOTROM loading. The
system displays the following information upon the completion of the entire process:
Prepare for loading...OK!
Loading....................................................done!
SRPU bootrom is updating now......
Get flash Type......FLASH_M29W040B
Erasing flash......done!
Programming flash......done!
Checking flash......done!
3) Loading host software
Follow these steps to download the host software of the switch.
Step 1: Select <1> in Boot Menu. The system displays the following information:
1. Set TFTP protocol parameter
2. Set FTP protocol parameter
3. Set XMODEM protocol parameter
0. Return to boot menu
Enter your choice(0-3):1
6-15
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Select <1>. The subsequent steps are the same as those for loading BOOTROM,
except for the displayed prompt messages.
1) Introduction to FTP
A switch can be used via Ethernet port as an FTP server or a client to provide another
approach for software loading and file configuration. An example of a switch being used
as an FTP client is given below.
2) Loading SRPU BOOTROM
Step 1: Connect the switch to the PC from where the file is to be downloaded, via the
10/100Base-TX interface on SRPU for loading. The IP address of the PC is required. At
the same time, the switch is externally connected to a PC (that can be the same one as
that the downloaded file is located) via a console port.
Step 2: Run the FTP Server program on the PC that is connected to the Ethernet port,
and specify the path for program loading.
Caution:
z FTP Server program is not shipped with the Quidway series switches.
z When loading BOOTROM and host software, you must use a crossover cable to
connect to the Ethernet port for upgrading.
Step 3: Run terminal emulation program on the PC connected to the console port. Start
the switch, access Boot Menu, and then enter download protocol menu.
To download the BOOTROM program, press <Ctrl+U> and <Enter> to access the
menu for BOOTROM downloading when the system displays: ”Enter your choice
(0-5):”
Enter your choice(0-5):
6-16
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Step 4: In the download protocol menu, type <2> to select FTP protocol to download
BOOTROM and host software. Press <Enter>. The system displays the following
information:
Load File name
Switch IP address
Server IP address
FTP User Name
FTP User Password
Step 5: Enter the FTP parameter values. The system displays the following information:
Are you sure to update SRPU bootrom? Yes or No(Y/N)
Step 6: Enter <Y> to start file downloading and <N> to return to the program
downloading menu. Suppose you enter <Y>. The system starts program downloading
and upon its completion, starts writing to Flash. The system displays the following
information after completing the writing operation:
Prepare for loading...OK!
Loading....................................................done!
SRPU bootrom is updating now......
Get flash Type......FLASH_M29W040B
Erasing flash......done!
Programming flash......done!
Checking flash......done!
3) Loading host software
Follow these steps to download the host software:
Step 1: Select <1> in Boot Menu. The system displays the following information:
1. Set TFTP protocol parameter
2. Set FTP protocol parameter
3. Set XMODEM protocol parameter
0. Return to boot menu
Enter your choice(0-3):3
If your terminal is connected to the switch by a network, you can load BOOTROM and
host software remotely via commands which can also be used in local software loading.
6-17
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
I. Loading by FTP
Run FTP Server on a local PC, provided you have configured username and password
and have set the correct file directory. Suppose the IP address of the PC is 10.10.110.1.
Log onto the switch via Telnet or the console port, to send the host program to the
switch using FTP. Connect the PC and switch with a crossover cable if your terminal is
connected to the switch via console port locally.
Note:
The S6502 supports dual image booting, that is, usually the switch boots with the main
image (i.e. the primary file), but it uses the backup image (i.e. the backup file) when the
primary one is in error. Refer to 6.3.4 Booting the Switch with Dual Images for details.
The S6502 also supports the upgrade of combined BOOTROM file, that is, upgrading
the BOOTROM of all boards using one combined BOOTROM file. Refer to 6.3.5
Loading Combined BOOTROM File for details.
Suppose that the main boot file is SWITCH002.app; the active host software is
SWITCH001.app; the LPU BOOTROM program is LPUbtm.app; LPU occupies slot 3
and SRPU occupies slot 0. You can follow these steps after logging onto the switch.
Step 1: Download the software to the switch using FTP.
<Quidway> ftp 10.10.110.1
Trying ...
Press CTRL+K to abort
Connected.
220 WFTPD 2.0 service (by Texas Imperial Software) ready for new user
User(none):lyt
331 Give me your password, please
Password:
230 Logged in successfully
Note:
You may also download two copies of host software, with one as the primary and the
other as the backup.
6-18
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
<Quidway> reboot (Make sure that you have saved other configurations before
rebooting, otherwise, they might not survive a reboot.)
BOOTROM and host software loading is complete now. Note that you must reboot the
switch to validate host software downloading. If Flash memory space is not enough,
you can delete some of the program files in Flash after completing the BOOTROM
loading. (You are recommended to delete the host program that is no longer in use.)
Then upload the host program to the switch using FTP. Note that power-off must be
prevented during loading process.
Using TFTP is similar to using FTP in remote and local loading via commands. The only
difference is that it is TFTP that you use when loading software to the switch. In this
case, the switch can only be used as a TFTP client to download the software to its
Flash memory from the TFTP server. The remaining steps after downloading are the
same as those with remote loading using FTP.
The S6502 supports dual image booting: usually the switch boots with the main image
(i.e. the primary file), but it uses the backup image (i.e. the backup file) when the main
image is in error. BOOTROM 400 or above version is required to support dual image
booting.
Refer to 6.3.3 Loading Software Remotely and Locally via Commands for loading dual
images to the switch using commands. The following introduces the setting of dual
images in Boot menu.
Step 1: Enter Boot menu.
6-19
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
BOOT MENU
1. Download application file to flash
2. Select application file to boot
3. Display all files in flash
4. Delete file from flash
5. Modify bootrom password
0. Reboot
Enter your choice(0-5): 2
Step 2: Enter <2> to turn to the menu for choosing the active booting file.
File Number File Size(bytes) File Name
========================================================
1. 4 snmpboots
2. 1972 SWITCH100.cfg
3. 1012 taskswitch.log
4. 631736 Btm400.btm
5. 199696 8241btm.app
6. 2427 vrpcfg.txt
7. 6048565 SWITCH200.app
8(*). 5639172 SWITCH000.app
9(-). 203460 SWITCH100.app
The system shows all the files in the flash memory, where the one with an asterisk (*) is
the primary file and the one with a hyphen (-) is the backup file.
Step 3: Reset the primary and backup files.
z Set the primary file.
Enter the serial number of the desired primary file when the terminal shows the
following information:
Please input the primary application file number to boot :9
Press <Enter> and the system displays the primary file name you have chosen. Enter
<Y> to acknowledge and <N> to reset.
The primary file you selected is SWITCH100.app, are you sure? Yes or No(Y/N):Y
Enter <Y> (as an example) and the terminal shows this information:
On reboot, SWITCH100.app will become the default primary application file to
boot!
6-20
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
You can set the backup file in almost the same way as setting the primary file. The
terminal shows the following information in this case:
Please input the backup application file number :7
The file you selected is SWITCH200.app, are you sure? Yes or No(Y/N)y
On reboot,SWITCH200.app will become the backup application file to boot!
Step 3: Decide if to run the primary file immediately. Enter <Y> and the system begins
to reboot.
Do you want to run SWITCH100.app now?Yes or No(Y/N)?Y
press Ctrl+B to enter Boot Menu... 5
Auto-booting....................
Note:
z If you specify only the primary file, and set no backup file, the system boots with the
primary file. If the primary file is in error, the system randomly chooses an
application file for booting.
z If you specify only the backup file, and set no primary file, the system boots with the
backup file.
z If you specify neither the primary file nor the backup file, the system randomly
chooses an application file for booting.
Since the S6502 supports multiple types of cards of and these cards use different
versions of BOOTROM, you are required to use the appropriate BOOTROM file when
upgrading the BOOTROM of a card. The upgrading fails if the BOOTROM file does
match the card.
To avoid the inconvenience caused by different BOOTROM files in upgrading, in
BOOTROM version 400 and the following BOOTROM, we combine the BOOTROM
files of all cards (including LPU and SRPU) into one, that is, the BOOTROM released in
6-21
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
the future will have only one file *.BTM, which can be used to upgrade BOOTROM of all
cards.
Note the following items upon upgrading using the combined BOOTROM file:
1) Upgrading BOOTROM version 400 or higher
BOOTROM version 400 or higher can be upgraded by a single BOOTROM file or the
combined BOOTROM file. And you are recommended to use the combined one.
2) The host software is required to support the combined BOOTROM file
Using the combined file to upgrade BOOTROM of cards requires the support of the
host software to the combined BOOTROM file. Host software of the latest version
recognizes the single file and the combined file automatically. The versions of the host
software that support upgrading by combined file are: version 052 and higher, version
1001 and higher.
3) Upgrading BOOTROM version 360 or lower
BOOTROM version 360 and lower can not recognize the combined BOOTROM file, so
you can upgrade them by using single files. If you intend to upgrade them by using the
combined file, you need to upgrade BOOTROM online through the command line on
the host software that supports the combined file, and you cannot upgrade the
combined BOOTROM file by using Boot Menu; otherwise, the system prompts you that
there are upgrading file errors and the BOOTROM cannot be upgraded.
4) Naming the combined BOOTROM file
For differentiation convenience, the single BOOTROM file is named *.app, and the
combined BOOTROM file is named *.btm.
Note:
If the host software does not support the combined BOOTROM file and the upgrading
fails, try to upgrade BOOTROM of every card by using single BOOTROM files.
Predefined conditions: the SRPU on slot 0 of the S6502 is LS81P12TE; the LPU on slot
1 is LS81FT48A; the combined BOOTROM file is S6502btm.btm; the version of the
host software which supports the combined BOOTROM file is S6502.app. Both the
online upgrading of command line and the upgrading through Boot Menu use FTP
mode.
1) Upgrading BOOTROM Version 306 or Lower
6-22
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Note:
z You can use either the command line (see this example) or Boot Menu to upgrade
the host software to the version that supports the combined BOOTROM file, and
upgrade BOOTROM of all cards using the combined BOOTROM file through
command line.
z You also can upgrade the BOOTROM of every card by using single BOOTROM files
through command line and Boot Menu.
Step 1: Download the host software that supports the combined BOOTROM file and the
combined BOOTROM file on the switch using FTP.
<Quidway> ftp 10.10.110.1
[ftp] get S6502.app S6502.app
[ftp] get S6502btm.btm S6502btm.btm
[ftp] bye
Step 2: Specify S6502.app as the application software applied by the switch during the
next boot.
<Quidway> boot boot-loader primary S6502.app
Step 3: Reboot the switch to make the S6502.app effective.
<Quidway> reboot
Step 4: Upgrade the BOOTROM of the LPU and SRPU using the combined file.
<Quidway> boot bootrom S6502btm.btm slot 0 1
please wait ...
Bootrom is updated!
After the above operation, you can complete the upgrading of the BOOTROM.
2) Upgrading version 400 or higher
BOOTROM version 400 and higher can recognize the combined BOOTROM file
automatically. The host software is also required to support the combined BOOTROM
file if you want to upgrade the BOOTROM of all cards.
z Online upgrading through command line
The way of upgrading through command line is omitted here since it is the same as that
described in the section Upgrading BOOTROM Version 306 or Lower.
z Upgrading the combined BOOTROM through Boot Menu
6-23
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Note:
Using Boot Menu, you can only upgrade the BOOTROM of an SRPU. And use the
command line if you need to upgrade the BOOTROM of the LPU.
Step 1: After entering Boot Menu, the system prompts you: “Enter your choice (0-5):”.To
enter the BOOTROM upgrading menu, press <Ctrl + U> and <Enter>.
1. Set TFTP protocol parameter
2. Set FTP protocol parameter
3. Set XMODEM protocol parameter
0. Return to boot menu
Enter your choice(0-3): 2
Step 2: Type <2> to choose upgrading through FTP, press <Enter>, and begin to set the
related parameters of FTP protocol.
Load File name :S6502btm.btm
Switch IP address :1.1.1.3
Server IP address :1.1.1.2
FTP User Name :6506
FTP User Password :123
Are you sure you want update FAB64 bootrom? Yes or No(Y/N)y
6-24
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Caution:
Ensure to use the appropriate version of BOOTROM file during upgrading the
BOOTROM of every card by single BOOTROM files; otherwise, the switch crashes.
You can choose either the command line or Boot Menu mode to upgrade by using
single BOOTROM file. You are recommended to use the command line mode to
complete the online upgrading. Here takes the command line mode as an example.
Predefined conditions: the card on slot 0 of the S6502 is LS81SRPUA, and its
corresponding BOOTROM file is SRPUbtm.app; the card LS81FT48A is on slot 1, and
its corresponding BOOTROM file is LPUbtm.app. This example introduces online
upgrading through FTP mode; you can also upgrade BOOTROM through the TFTP
mode, which is omitted here.
Follow these steps to upgrade:
Step 1: Download single BOOTROM file to the switch through FTP.
<Quidway> ftp 10.10.110.1
[ftp] get SRPUbtm.app SRPUbtm.app
[ftp] get LPUbtm.app LPUbtm.app
[ftp] bye
Step 2: Load single BOOTROM files to every card.
<Quidway> boot bootrom SRPUbtm.app slot 0
<Quidway> boot bootrom LPUbtm.app slot 1
After the above operation, you can complete the upgrading of the BOOTROM on every
card.
6-25
Installation Manual
Quidway S6502 Ethernet Switch Chapter 6 Switch Monitoring and Maintenance
Please contact the local agent of Huawei Technologies if the BOOTROM password or
user password of the switch is lost.
6-26
Installation Manual
Quidway S6502 Ethernet Switch Appendix A Lightning Protection of the Switch
Caution:
Lightning arrester will not be shipped with the switch. You should purchase it by
yourself if needed.
If an outdoor AC power cord should be directly led to the switch, please serially connect
the lightning arrester for AC power (Socket Strip with Lightning Protection) before you
plug AC power cord into the switch, thus to prevent the possible damage to the switch
due to lightning strike. You can use cable clips and screws to fasten the lightning
arrester for AC power on the cabinet, workbench or the wall of equipment room.
Grounding and polarity indicator (red) :
On means that the lines are wrongly connected
(either the ground wire is not well connected, or the live and zero lines are wrongly connected).
Please check the power supply circuit.
Power switch
Normal operation indicator (green):
On means that the arrester works normally. Otherwise, it
means that the protection circuit has been damaged.
Mainboard
A-1
Installation Manual
Quidway S6502 Ethernet Switch Appendix A Lightning Protection of the Switch
Caution:
z Make sure that the arrester is well grounded before using the lightning arrester for
power.
z After inserting AC power cord plug of switch into the socket of lightning arrester, if
the green LED is on and the red LED does not alarm, it means that the lightning
arrester of power is running and the function of lightning protection has taken effect.
z Pay adequate attention if the red LED is on. You should correctly locate the problem,
whether it is caused because the ground wire of the arrester is not well grounded or
because the live and zero wires are connected in reverse direction. You may check
that in the following way. When the red LED is on, use a multimeter to examine
polarity at the power socket of the arrester. If it is same to that of the power socket in
the equipment room, it means that arrester is not well grounded. If it is adverse to
that of the power socket in the equipment room, it means that the power socket of
the arrester is set to the reverse polarity. In this case, you should open the power
socket of arrester to correct polarity. After that, if the red LED still alarms, it means
that the arrester is not well grounded yet.
Note:
Lightning arrester for network port is specially designed for the Ethernet port of
10/100M electrical interface (RJ-45 connector is adopted in this case).
Caution:
Lightning arrester for network port will not be provided along with the switch, and you
should purchase it by yourself if needed.
If an outdoor network cable should be led 6 to the switch, please serially connect the
lightning arrester for network port before you plug this cable into the interface on the
switch, in case of the possibility that the switch may be damaged due to lightning strike.
I. Required tools
A-2
Installation Manual
Quidway S6502 Ethernet Switch Appendix A Lightning Protection of the Switch
z Multimeter
z Tilted wire cutter
Step 1: Tear the protection paper at one side of the double faced adhesive tape apart
from the tape, and stick the tape on the surface of the arrester. Tear the protection
paper at another side apart from the tape, and stick the arrester onto the chassis of the
switch. The arrester should be attached on the chassis as close to the grounding screw
as possible.
Step 2: According to the distance to the grounding screw of the switch, cut the ground
wire of the arrester, and securely tightening its ground wire to the grounding screw of
the switch.
Step 3: Use the multimeter to measure whether the ground wire of the arrester contacts
well with the grounding screw of chassis.
Step 4: According to the instruction of arrester for network port, connect the arrester
with switch by the cables (be carefully with the cable direction. Outdoor network cable
should be inserted into the arrester‘s IN end, and the cable connected to the switch
should be inserted into the arrester’s OUT end). When you do that, observe whether
the arrester indicators normally display.
Note:
The instruction of lightning arrester for network port contains the technical
specifications, installation and maintenance guide of the arrester. Please carefully read
it before installing the arrester.
A-3
Installation Manual
Quidway S6502 Ethernet Switch Appendix A Lightning Protection of the Switch
Fully consider the following items in the installation process, otherwise, the
performance of the lightning arrester for network port will be affected:
z Lightning arrester for network port is installed in reverse direction. In practice, the
“IN” end should be connected to the outdoor network cable and the “OUT” end to
the network port on the switch.
z Lightning arrester for the network port is not well grounded. The ground wire for
the arrester should be as short as possible, so to ensure its good contact with the
grounding screw of the switch. After the connection, use the multimeter to confirm
that.
z The lightning arrester for the network port is not installed completely. If the switch
has more than one network ports to interconnect with other devices via cables
outdoor, you should install lightning arresters for all these network ports for
protection.
A-4