Você está na página 1de 8

P R OT E C T I O N

MiCOM P740
Numerical Busbar Protection

The MiCOM P740 numerical busbar protection


scheme provides complete protection for all
types of extra / ultra high voltage busbar
configurations.

Built on a number of innovative techniques,


including CT saturation detection and dynamic
MiCOM P741 in 80TE
topology processing algorithms, the P740 offers
a unique combination of security, speed and
sensitivity.

With a typical operating time of 15ms, the P740


protection is one of the fastest in its class and
meets the most stringent requirements of extra /
MiCOM P743 in 60TE
ultra high voltage transmission systems.

The substation replica processing algorithms


ensure that P740 adapts to the dynamically
changing topology of the busbar.

The MiCOM P740 busbar differential protection


MiCOM P742 in 40TE scheme can be engineered to provide a
centralized or a distributed architecture. It also
supports easy maintenance, operation and future
expansion of the busbar.

Customer benefits
• Fast fault trip
(typically 15ms)
• Adaptable to any busbar
configuration.
• Can operate with different
types of CT.
• Fibre optic cable used for
communication between
Central and Peripheral Units:
- Ensures high
communication speed
- Eliminates insulation
problems

AREVA T&D
APPLICATION One Peripheral Unit is associated with each
CT location, usually one per incomer/feeder and one
The MiCOM P740 numerical busbar protection scheme or two for each bus coupler/bus section, depending on
has been designed to protect a wide range of busbar number of CT (1 or 2). The Peripheral Units acquire
configurations. The modular scheme comprises of three the analogue signals from the associated CT and the
relays: binary signals from the auxiliary contacts of circuit
breakers and isolators. The Peripheral Units also
• Central Unit - P741
incorporate the main circuit breaker failure logic
• Peripheral Unit - P742 / P743 together with backup protection.

These units, interconnected using optic fibre cables The difference between the P742 and P743 is in the
together with the topology configurator software allow number of I/O that each can accommodate. The P743
application to all types of busbar configurations. allows for increased I/O, this is particularly useful in
double busbar applications. Especially where single
The Central Unit co-ordinates the scheme, receiving pole breakers and transfer busbar are employed, in
signals from all the peripheral units associated with the these applications the I/O requirements are large in
protected busbars and acting on these signals, initiating comparison to those required for a single busbar
a buszone protection trip when necessary. A single application where a P742 may be more suitable.
Central Unit can accommodate upto,

• 8 Zones
• 28 Peripheral Units

BB1 BB3

BB2 BB4

P740 scheme
Transfer applied for protecting
Bus double busbar with transfer bus

2 P742 or
2 P743

P742 P743 P741 P743 P742

Peripheral Units Optical fibre Central Unit Peripheral Units

PROTECTION FUNCTIONS OVERVIEW P741 P742 P743

87BB / P Phase segregated biased current • - -


differential high speed busbar protection
87BB / N Sensitive earth fault bias current controlled • - -
busbar protection
87 CZ Check zone element (supervision) • - -
50 / 51 / P Phase overcurrent protection (2 stages) - • •
50 / 51 / N Earth overcurrent protection (2 stages) - • •
50ST Dead zone protection (short zone between CTs and CBs) • - -
CTS Current transformer supervision • • •
50BF Breaker failure protection (LBB) • • •
ISL Isolator discrepancy alarm - • •
Fibre optic signalling channel • • •
Digital inputs 8 16 24
Output relays 8 8 21
Front communication port (RS232) • • •
Rear communication port (RS485) • • •
Time synchronisation port (IRIG-B) * option - -
* Refer data sheet for model selection

Complete flexibility to suit


2>3
any busbar configuration
MANAGEMENT FUNCTIONS • Programmable scheme logic (PSL)
• Sequence of event recording (SOE)
In addition to the protection and control elements, the • Comprehensive disturbance recording (waveform
P740 scheme provides a wide range of measurement, capture)
monitoring, post fault analysis and self-diagnostic • User configurable LEDs
features:
• Local and remote communication ports
• Time synchronisation
• Circuit breaker control
• Fully customisable menu texts
• Trip circuit supervision (using PSL)
• Multi level password protection
• On-line measurement
• Test facilities
• Plant status monitoring
• Power-up diagnostics and continuous self-monitoring
• 4 alternative setting groups
of relay.
• User friendly setting and analysis software

FUNCTIONAL OVERVIEW

Fibre optic Remote Local Fault records Disturbance


signaling comm. port Communication Record
channel
Measurements
Self monitoring

87BB 87BB
87CZ 50BF CTS 50S T
/P /N

/ / / Binary
Input / output
PSL LEDs Busbar protection scheme
Central Unit P741

X Fibre optic Remote Local Fault records Disturbance


signaling comm. port Communication Record
channel
Measurements

/ Self monitoring

50/ 50/
50BF CTS ISL
51/P 51/N

Binary PSL LEDs


Input / output Busbar protection scheme
Peripheral Unit P742 / P743

(Description of ANSI code nos. see Protection Function Overview)

Speed, Sensitive & Secure:


P740 the ultimate in busbar protection
BUSBAR DIFFERENTIAL PROTECTION

The primary protection element of the P740 scheme is


the phase segregated biased current differential
protection. The technique is based on the numerical
application of Kirchoff's Law for the selective detection
and ultra high-speed isolation of a faulty section of the
busbar.

The analysis is carried out in the Central Unit (CU)


which communicates with the Peripheral Unit (PU) to
get the current flowing in individual circuits and to
implement the tripping of circuits as decided by it.
This reliable, high speed communication is achieved
via a direct optical connection utilising a 2.5 Mbps CT saturation detection
data rate.

The P740 employs biased differential algorithms, in


which the differential current is compared with a bias
current. This characteristic ensures stability of the
protection for external fault even with differing CT
tolerances and errors which otherwise could lead to
spurious operation.

To increase the security of the differential protection,


the biased differential element is supervised by a
global check zone element. This ensures stability
even under erroneous status of the auxiliary contact of
plant isolators and circuit breakers.

The MiCOM P740 also employs an innovative, ultra


high-speed, secure CT saturation detection
algorithm. This ensures stability when CTs become
saturated, particularly under external fault conditions.
Universal on-line topology processing This algorithm combine a simulation of the flux built up
in the core of the CTs with a recursive consistence
variation control. This technique can detect CT
To ensure adaptability of the relay to any type of
saturation in less than 2ms.
busbar configuration the P740 is built with a universal
topology processing algorithm. This algorithm
determines the optimum tripping zone on-line based
on the status of the plant isolator and breakers.
This ensures that minimum part of the busbar is
isolated for any fault in it. Bias differential characteristics

i diff (t)
Tripping
Area
%
o 90
i1 i2 0t
k =2
s-
e bia
i3 in tag Restrain
I D> 2 rcen
pe area
Is
I D> 1 i bias (t)
Differential current : i diff node (t)= i 1 + i 2 + i3 + ....... + i n

Operating current : i diff (t) = i diff node (t) = Σ i

Restraining current : i bias(t) = i 1 + i2 + i3 + ....... + in = Σ i


4>5
DUAL CHARACTERISTICS
idiff s -k
To provide stability for severe through faults and at the bia
Trip tage
same time detect low current internal faults, the P740 rc en
Pe
is equipped with dual characteristics. One phase
segregated differential protection and another
ID>2 Restrain
sensitive earth current differential protection. IS
ID>1
ibias
MULTIPLE TRIPPING CRITERIA Enable Block
SEF Block threshold
idiff
The MiCOM P740 maintains the highest level of
stability, under all conditions including a hardware Trip
failure and incoherent signals applied from external kN
bia s -
plant equipment or generated by power system. ntage
Perce
IDN >2
Any tripping order must therefore be made conditional ISN Restrain kNmin =0.2
on the simultaneous occurrence of 5 or 6 criteria: IDN >1
ibias
> Magnitude criteria; confirmation of two simultaneous
Dual characteristics
thresholds per zone:
• Exceeding the bias slope characteristic (k)
• Exceeding differential operating current threshold
CONTINUOUS SUPERVISION
(ID>2).
OF CURRENT CIRCUITS
> Exceeding the supervision threshold (ID>1).
> Signal quality criteria: The P740 detects any abnormality in the current circuit
• No CT saturation detected by continuously monitoring it. Under normal operating
• Current variation detected on at least two conditions the differential current will be negligible. An
Peripheral Units anomaly is detected by a threshold, ID>1, which can
> Time or angular criterion. be set to alarm from 1% of the primary basis current
The measurement elements on 2 samples taken at (Ibp).
1200 Hz. A first sample for the initial measurement
and a second sample for trip confirmation.
> Check zone supervision. DIFFERENTIAL CURRENT SETTING
The zone element(s) are only permitted to trip if the
order is confirmed by the check zone element. When switching operations are carried out in the
> Local criteria (optional) substation, incorrect topology replicas may occur. In
The Peripheral Units can be set to only authorise this case, a differential current appears. The
tripping if there is confirmation by local overcurrent differential elements of the MiCOM P740 are allowed
criteria. to operate only if the differential current reaches a
threshold ID>2which is set above the highest load
current.
DEAD ZONE OR BLIND SPOT
PROTECTION
ADDITIONAL ULTRA HIGH SPEED
The current transformers surrounding the busbars EXTERNAL FAULT BLOCKING
define the limits of the main zones. When the circuit
breaker is opened a dead zone or blind spot is created The ultra high-speed saturation detection is carried out
between the CB and the associated CT. The P740 in each PU and can generate a control signal from the
detects this condition automatically and provides moment of the first sample (0.4 ms).
protection for this zone also.

BB1

Dead zone protection

CB Closed CB Open

Dead Zone

Intertrip contact
PU1 PU2 not connected to BB1 to other end
connected = Activation
to BB1 of Dead Zone protection
PHASE OVERCURRENT AND ISOLATION AND MAINTENANCE
EARTH FAULT PROTECTION OPERATING MODE

Two independent stages each of phase overcurrent and For ease of operation or maintenance of the busbar
earth fault protection is provided in the Peripheral Units. protection system, the Central Unit and the Peripheral
These elements provide backup protection for the Units can receive specific commands designed to
individual circuits. allow system testing or other intervention without any
The two stages can be programmed as: danger of unwanted tripping.
> First stage can be programmed as definite time (DT)
delay or one of the nine inverse time (IDMT) curves In the Central Unit, a centralized command to isolate
(IEC/UK and IEEE/US). the busbars at two levels can be applied selectively
zone wise:
> Second stage can only be programmed as definite
time. > Differential protection (87 BB) in monitoring mode
(measurements active and tripping deactivated). The
Breaker Failure protection remains operational.
CIRCUIT BREAKER FAILURE > Differential protection (87 BB) and Circuit Breaker
PROTECTION (LBB) Failure protection (50 BF) in monitoring mode. The
additional local protection functions (51, 51N, etc...)
The MiCOM P740 busbar protection scheme can work remain operational.
in co-ordination with external breaker failure
protection relays. In this configuration, the receipt of an A selective two-level command may be applied
external breaker failure information results in tripping of selectively for each Peripheral Units:
all the adjacent circuit breakers, via the topological > Maintenance of bay(s) for human intervention.
recognition system knowing which breaker is connected In this state, all I/O are deactivated. The busbar
to which zone. protection is still in service, but the CB of the feeder
in service can not be tripped.
The P740 also offers an in-built integrated solution
for breaker failure protection. This requires all
> Intervention on the equipment for maintenance and
testing.
Peripheral Units to receive a duplication of the trip
commands generated in their associated bay.
In general the Breaker Failure protection must be
executed on a per phase basis which involves the PROGRAMMABLE SCHEME LOGIC
possibility of receiving tripping orders on a per pole
basis. Powerful programmable scheme logic (PSL) allows the
user to customize the protection and control functions.
It is also used to programme the functionality of the
CURRENT TRANSFORMER optically isolated inputs, relay outputs and LED
MISMATCH CORRECTION indications. The programmable scheme logic
comprises of gate logic and general purpose timers.
The MiCOM P740 can correct mismatch between The gate logic includes OR, AND and majority gate
current transformer ratios over a very wide range up functions, with the ability to invert the inputs and
to 40. Its associated user interface provides a range outputs, and provide feedback. The programmable
between 1 A and 30,000 A primary. scheme logic is configured using the graphical MiCOM
S1 PC based support software.
Since the current transformer ratings in a substation
may be of mixed ratios, the MiCOM P740 enables a
common base current to be defined, irrespective of PLANT STATUS
the feeder section concerned.
The settings on the Central Unit are all adjusted to this Checks and monitoring of the plant status can be
common current, known as the primary base current (Ibp). made, and an alarm raised for any discrepancy
conditions between the open and closed auxiliary
contacts of the isolators and circuit breakers.

Programmable scheme
logic editor (MiCOM S1)

6>7
MEASUREMENT FAULT RECORDER
AND RECORDING FACILITIES
Records of the last 5 faults are stored in the
The P740 series relays are capable of measuring and battery-backed memory of both the Central and
storing the values associated with a fault. All the Peripheral Units.
events, faults records and disturbance records are time
tagged to 1 ms using an internal real time clock. An Each fault record includes:
optional IRIG-B port is also provided for accurate time > Indication of the faulty zone (CU + PU)
synchronization. A lithium battery provides a back up > Protection element operated
for the real time clock and all records in the event of
> Active setting group
supply failure.
> Fault duration
> Currents and frequency (PU)
MEASUREMENTS > Faulty zone differential and bias current (CU)

The measurements provided, which may be viewed in


primary or secondary values, can be accessed via
DISTURBANCE RECORDER
the back lit liquid crystal display. They are also
accessible via the communication ports. The following
The Central and Peripheral units of the P740 have
instantaneous parameters can be viewed:
independent disturbance recording facility. The
> Central unit (P741 Peripheral Units can record 4 analogue and 32 digital
• Differential current Idiff / phase / zone channels, whereas the Central unit stores 8 analogue
• Bias current Ibias / phase / zone and 32 digital channels in addition to 1 time channel.
• Check zone Idiff / phase
> Specific analogue channels
> Peripheral units (P742 & P743) • Ibias / Idiff (CU)
• Phase currents IA IB IC • IA, IB, IC, IN (PU)
• Neutral current IN
> Maximum duration of one record and number of
• Sequence currents
records
• Frequency
• 1.2s per record and 8 records (CU)
• up to 10.5s per record and minimum of
20 records (PU)
EVENT RECORDER
Disturbance records can be extracted from the relay
Up to 250 time tagged event records are stored in
via the remote communications and saved in the
battery backed memory, and can be extracted via the
COMTRADE format. These records may be examined
communication port or be viewed on the front panel
using MiCOM S1 or any other standard COMTRADE
display.
viewer.

Disturbance record viewed in MiCOM S1


Device Track Record
LOCAL AND REMOTE
>> Low impedance biased differential busbar protection, MBCZ,
COMMUNICATIONS
launched in 1988 and over 800 cubicles sold
>> Over 200 DIFB, medium impedance biased differential busbar
Two communication ports are available as standard; a rear
protection scheme delivered since its launch in 1992.
port providing remote communications and a front port
>> Medium impedance biased differential busbar protection with linear current
providing local communications.
combination, DIFB CL, launched in 1996. Over 70 cubicles delivered.

The front RS232 port has been designed for use with MiCOM >> Since the launch of the P740, over 50 systems have been delivered.
S1, which fully supports functions within the relay by providing
the ability to programme the settings off-line, configure the
programmable scheme logic, extract and view event,
disturbance and fault records, view the measurement
information dynamically and perform control functions (using HARDWARE
Courier protocol).
All models within the MiCOM P740 series relays include:
The default remote communications is Courier / K-bus and can > A back-lit liquid crystal display
be converted to IEC60870-5-103.

AUTOMATION-L3-P740-BR-05.05-1021-GB - © - AREVA - 2004. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA. MiCOM is a registered trademark of AREVA. All
> 12 LEDs
> Optional IRIG-B port (CU),
> RS232 (front port) & RS485 (rear port),
DIAGNOSTICS > Fibre optic connection from the CU to the PUs,
> Download/monitor port,
Automatic tests performed including power-on diagnostics and
continuous self-monitoring ensures a high degree of reliability. > Battery (supervised),
The results of the self-test functions are stored in battery > N/O and C/O watchdog contacts
backed memory. Test features available on the user interface > Supervised +48 V field voltage

trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
provide examination of input quantities, states of the digital
> Dual rated CT inputs 1A/5A
inputs and relay outputs. A local monitor port provides digital
outputs, selected from a prescribed list of signals, including the > Universal opto inputs with progammable voltage threshold
status of protection elements.
The optically isolated inputs are independent and may be
powered from the +48V field voltage.

Our policy is one of continuous development. Accordingly


AREVA T&D Worldwide Contact Centre: the design of our products may change at any time. Whilst
http://www.areva-td.com/contactcentre/ every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is
Tel.: +44 (0) 1785 250 070 intended for information purposes only. Its contents do not
constitute an offer for sale or advise on the application of
any product referred to in it. We cannot be held responsible
www.areva-td.com for any reliance on any decisions taken on its contents
without specific advice.
www.areva-td.com/protectionrelays

Você também pode gostar