Escolar Documentos
Profissional Documentos
Cultura Documentos
MiCOM P740
Numerical Busbar Protection
Customer benefits
• Fast fault trip
(typically 15ms)
• Adaptable to any busbar
configuration.
• Can operate with different
types of CT.
• Fibre optic cable used for
communication between
Central and Peripheral Units:
- Ensures high
communication speed
- Eliminates insulation
problems
AREVA T&D
APPLICATION One Peripheral Unit is associated with each
CT location, usually one per incomer/feeder and one
The MiCOM P740 numerical busbar protection scheme or two for each bus coupler/bus section, depending on
has been designed to protect a wide range of busbar number of CT (1 or 2). The Peripheral Units acquire
configurations. The modular scheme comprises of three the analogue signals from the associated CT and the
relays: binary signals from the auxiliary contacts of circuit
breakers and isolators. The Peripheral Units also
• Central Unit - P741
incorporate the main circuit breaker failure logic
• Peripheral Unit - P742 / P743 together with backup protection.
These units, interconnected using optic fibre cables The difference between the P742 and P743 is in the
together with the topology configurator software allow number of I/O that each can accommodate. The P743
application to all types of busbar configurations. allows for increased I/O, this is particularly useful in
double busbar applications. Especially where single
The Central Unit co-ordinates the scheme, receiving pole breakers and transfer busbar are employed, in
signals from all the peripheral units associated with the these applications the I/O requirements are large in
protected busbars and acting on these signals, initiating comparison to those required for a single busbar
a buszone protection trip when necessary. A single application where a P742 may be more suitable.
Central Unit can accommodate upto,
• 8 Zones
• 28 Peripheral Units
BB1 BB3
BB2 BB4
P740 scheme
Transfer applied for protecting
Bus double busbar with transfer bus
2 P742 or
2 P743
FUNCTIONAL OVERVIEW
87BB 87BB
87CZ 50BF CTS 50S T
/P /N
/ / / Binary
Input / output
PSL LEDs Busbar protection scheme
Central Unit P741
/ Self monitoring
50/ 50/
50BF CTS ISL
51/P 51/N
i diff (t)
Tripping
Area
%
o 90
i1 i2 0t
k =2
s-
e bia
i3 in tag Restrain
I D> 2 rcen
pe area
Is
I D> 1 i bias (t)
Differential current : i diff node (t)= i 1 + i 2 + i3 + ....... + i n
BB1
CB Closed CB Open
Dead Zone
Intertrip contact
PU1 PU2 not connected to BB1 to other end
connected = Activation
to BB1 of Dead Zone protection
PHASE OVERCURRENT AND ISOLATION AND MAINTENANCE
EARTH FAULT PROTECTION OPERATING MODE
Two independent stages each of phase overcurrent and For ease of operation or maintenance of the busbar
earth fault protection is provided in the Peripheral Units. protection system, the Central Unit and the Peripheral
These elements provide backup protection for the Units can receive specific commands designed to
individual circuits. allow system testing or other intervention without any
The two stages can be programmed as: danger of unwanted tripping.
> First stage can be programmed as definite time (DT)
delay or one of the nine inverse time (IDMT) curves In the Central Unit, a centralized command to isolate
(IEC/UK and IEEE/US). the busbars at two levels can be applied selectively
zone wise:
> Second stage can only be programmed as definite
time. > Differential protection (87 BB) in monitoring mode
(measurements active and tripping deactivated). The
Breaker Failure protection remains operational.
CIRCUIT BREAKER FAILURE > Differential protection (87 BB) and Circuit Breaker
PROTECTION (LBB) Failure protection (50 BF) in monitoring mode. The
additional local protection functions (51, 51N, etc...)
The MiCOM P740 busbar protection scheme can work remain operational.
in co-ordination with external breaker failure
protection relays. In this configuration, the receipt of an A selective two-level command may be applied
external breaker failure information results in tripping of selectively for each Peripheral Units:
all the adjacent circuit breakers, via the topological > Maintenance of bay(s) for human intervention.
recognition system knowing which breaker is connected In this state, all I/O are deactivated. The busbar
to which zone. protection is still in service, but the CB of the feeder
in service can not be tripped.
The P740 also offers an in-built integrated solution
for breaker failure protection. This requires all
> Intervention on the equipment for maintenance and
testing.
Peripheral Units to receive a duplication of the trip
commands generated in their associated bay.
In general the Breaker Failure protection must be
executed on a per phase basis which involves the PROGRAMMABLE SCHEME LOGIC
possibility of receiving tripping orders on a per pole
basis. Powerful programmable scheme logic (PSL) allows the
user to customize the protection and control functions.
It is also used to programme the functionality of the
CURRENT TRANSFORMER optically isolated inputs, relay outputs and LED
MISMATCH CORRECTION indications. The programmable scheme logic
comprises of gate logic and general purpose timers.
The MiCOM P740 can correct mismatch between The gate logic includes OR, AND and majority gate
current transformer ratios over a very wide range up functions, with the ability to invert the inputs and
to 40. Its associated user interface provides a range outputs, and provide feedback. The programmable
between 1 A and 30,000 A primary. scheme logic is configured using the graphical MiCOM
S1 PC based support software.
Since the current transformer ratings in a substation
may be of mixed ratios, the MiCOM P740 enables a
common base current to be defined, irrespective of PLANT STATUS
the feeder section concerned.
The settings on the Central Unit are all adjusted to this Checks and monitoring of the plant status can be
common current, known as the primary base current (Ibp). made, and an alarm raised for any discrepancy
conditions between the open and closed auxiliary
contacts of the isolators and circuit breakers.
Programmable scheme
logic editor (MiCOM S1)
6>7
MEASUREMENT FAULT RECORDER
AND RECORDING FACILITIES
Records of the last 5 faults are stored in the
The P740 series relays are capable of measuring and battery-backed memory of both the Central and
storing the values associated with a fault. All the Peripheral Units.
events, faults records and disturbance records are time
tagged to 1 ms using an internal real time clock. An Each fault record includes:
optional IRIG-B port is also provided for accurate time > Indication of the faulty zone (CU + PU)
synchronization. A lithium battery provides a back up > Protection element operated
for the real time clock and all records in the event of
> Active setting group
supply failure.
> Fault duration
> Currents and frequency (PU)
MEASUREMENTS > Faulty zone differential and bias current (CU)
The front RS232 port has been designed for use with MiCOM >> Since the launch of the P740, over 50 systems have been delivered.
S1, which fully supports functions within the relay by providing
the ability to programme the settings off-line, configure the
programmable scheme logic, extract and view event,
disturbance and fault records, view the measurement
information dynamically and perform control functions (using HARDWARE
Courier protocol).
All models within the MiCOM P740 series relays include:
The default remote communications is Courier / K-bus and can > A back-lit liquid crystal display
be converted to IEC60870-5-103.
AUTOMATION-L3-P740-BR-05.05-1021-GB - © - AREVA - 2004. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA. MiCOM is a registered trademark of AREVA. All
> 12 LEDs
> Optional IRIG-B port (CU),
> RS232 (front port) & RS485 (rear port),
DIAGNOSTICS > Fibre optic connection from the CU to the PUs,
> Download/monitor port,
Automatic tests performed including power-on diagnostics and
continuous self-monitoring ensures a high degree of reliability. > Battery (supervised),
The results of the self-test functions are stored in battery > N/O and C/O watchdog contacts
backed memory. Test features available on the user interface > Supervised +48 V field voltage
trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
provide examination of input quantities, states of the digital
> Dual rated CT inputs 1A/5A
inputs and relay outputs. A local monitor port provides digital
outputs, selected from a prescribed list of signals, including the > Universal opto inputs with progammable voltage threshold
status of protection elements.
The optically isolated inputs are independent and may be
powered from the +48V field voltage.