EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
The type of cement shall be specified in the mix design submittal and 09-SAMSS-097
A1
shall be from a Saudi Aramco approved supplier. Sec. 5.1.1
Silica fume, when used, shall not be less than 7% by weight of cement 09-SAMSS-097
A4
as a replacement. Sec. 5.1.1
09-SAMSS-097
A5 Mill test certificates shall be provided for each shipment of cement.
Sec. 5.1.1
The Limits of deleterious substances in course aggregates shall conform
to the following maximums allowable by weight of aggregates:
Coarse Fine Testing Frequency
1. Clay lumps & friable particles 5.0% 3.0% monthly
2. Gradation/Materials < No.200 1.0% 5.0% weekly 09-SAMSS-088
A6 3. 1 & 2 Combined 4.0% 6.0% Sec. 11.1
4. Los Angeles Abrasion 40% N/A monthly Table A
5. Water Absorption 2.5% monthly
6. Acid Soluble Cl 0.03% 0.06% Bi-monthly
7. Acid Soluble SO3 0.40% 0.40% Bi-monthly
8. MgSO4 Soundness 25% 25% Bi-monthly
The concrete exposure type shall correspond with the project site's SAES-Q-001
A10
exposure type. Sec. 5.1, Table 1
Test results for Saudi Aramco acceptance purposes shall be from a 09-SAMSS-097
A11
Saudi Aramco-approved independent laboratory. Sec. 18.1
Page 1 of 2
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Concrete Mix Design Approval SAIC-Q-1006 18-May-05 Civil
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
09-SAMSS-097
The actual 28-day compressive strength of the concrete cylinder
B1 Sec. 4.4.1,
samples shall meet the design compressive strength.
Table A
The concrete exposure type shall correspond with the project site's
SAES-Q-001
B2 exposure type. (Note: Obtain soils report done for the project site to
Sec. 5.1, Table 1
determine the exposure type for the project site.)
Test results for Saudi Aramco acceptance purposes shall be from a 09-SAMSS-097
B4
Saudi Aramco-approved independent laboratory. Sec. 18.1
REMARKS:
REFERENCE DOCUMENTS:
1- SAES-Q-001 -- Criteria for Design for Design and Construction of Concrete Structures, 29 October 2003
2- 09-SAMSS-088 -- Aggregates for Concrete, 01 June 2004
3- 09-SAMSS-097 -- Ready Mixed Portland Cement Concrete, 31 August 2002