Tank ID
Terminal Name
Page 2 of 11
Western Australia
8 Edison Circuit, Rockingham WA 6168
Tel (08) 9528 1888
Fax (08) 9528 1588
mail@petrospection.com.au
www.petrospection.com.au
Company Name
EXAMPLE
Tank ID - Terminal Name
This table gives volumes in litres for millimetres of product measured over the dip plate.
The tank is a vertical "in/out" lapped tank with a fixed roof, an internal blanket and a coned up floor.
The first red highlighted area on page 4 of the table is below the high point of the floor.
In this zone the average values from the bottom of the page should not be used.
Intermediate volumes in the zone should be interpolated from the nearest values in the table.
Accurate volumes cannot be obtained from the tables within the zone of partial displacement
of the blanket, which is also highlighted in red on the table.
Refer to the Floating Blanket Correction Table (page 3) for the zone levels and treatment of
the blanket in the calculation of tank volumes.
A 100NB Water Drain draws from a sump located adjacent to the tank shell.
Page 3 of 11
Western Australia Reference: PS060000
8 Edison Circuit, Rockingham WA 6168
Tel (08) 9528 1888
Fax (08) 9528 1588
mail@petrospection.com.au
www.petrospection.com.au
Company Name
EXAMPLE
Tank ID - Terminal Name
This tank is equipped with a floating blanket, the weight of which has been given to us as: 2,236 kg
Between the following dips the blanket is only partially afloat and accurate volumes may not be calculated:
For dips below the lower limit the blanket does not affect the tank volume and the volume may be read from
the main tank table against the product dip.
For dips above the upper limit the following table should be consulted with the density of the tank contents
at tank temperature. The correction obtained should be deducted from the volumes obtained for the
product dip in the main table. Note that the density used is in air, at tank temperature, not at 15 degrees C.
0.670 3,337 3,332 3,327 3,322 3,318 3,313 3,308 3,303 3,298 3,293
0.680 3,288 3,283 3,279 3,274 3,269 3,264 3,259 3,255 3,250 3,245
0.690 3,241 3,236 3,231 3,227 3,222 3,217 3,213 3,208 3,203 3,199
0.700 3,194 3,190 3,185 3,181 3,176 3,172 3,167 3,163 3,158 3,154
0.710 3,149 3,145 3,140 3,136 3,132 3,127 3,123 3,119 3,114 3,110
0.720 3,106 3,101 3,097 3,093 3,088 3,084 3,080 3,076 3,071 3,067
0.730 3,063 3,059 3,055 3,050 3,046 3,042 3,038 3,034 3,030 3,026
0.740 3,022 3,018 3,013 3,009 3,005 3,001 2,997 2,993 2,989 2,985
0.750 2,981 2,977 2,973 2,969 2,966 2,962 2,958 2,954 2,950 2,946
0.760 2,942 2,938 2,934 2,931 2,927 2,923 2,919 2,915 2,911 2,908
0.770 2,904 2,900 2,896 2,893 2,889 2,885 2,881 2,878 2,874 2,870
0.780 2,867 2,863 2,859 2,856 2,852 2,848 2,845 2,841 2,838 2,834
0.790 2,830 2,827 2,823 2,820 2,816 2,813 2,809 2,806 2,802 2,798
0.800 2,795 2,792 2,788 2,785 2,781 2,778 2,774 2,771 2,767 2,764
0.810 2,760 2,757 2,754 2,750 2,747 2,744 2,740 2,737 2,733 2,730
0.820 2,727 2,724 2,720 2,717 2,714 2,710 2,707 2,704 2,700 2,697
Page 11 of 11
TANK CALIBRATION - ISO 7507
The above critical levels are the heights in the tank, relative to the dip plate, at which the volume per unit area changes.
This is the base data from which the tank calibration table is constructed. These levels and volumes have been
corrected for thermal and liquid head expansion of the tank shell, but not for meniscus effect on the dip tape.