VariTrane™ Single-Duct
and Fan-Powered Units
All VariTrane VAV Models with pneumatic, electronic, DDC controls and diffusers.
VAV-SVN01E-EN 3
Service Model
Number Description
4 VAV-SVN01E-EN
Service Model
Number Description
VAV-SVN01E-EN 5
Service Model
Number Description
Dual-Duct Units
Digit 1, 2, 3—Unit Type FM00 FM – Customer-supplied Digit 19—Outlet Plenum (Connection is
VDD VariTrane dual-duct actuator & controller slip & drive)
Digit 4—Development Sequence FM01 FM –Trane actuator w/ 0 none
customer-supplied controller A 1 outlet–RH
F Sixth B 1 outlet–END
PC03 PN – N.C. heating/ N.O. cooling
Digit 5, 6—Primary Air Valve w/ PVRs, DA stat C 1 outlet–LH
05 5" inlet (350 cfm) PN08 PN – N.O. heating/ N.O. cool D 2 outlets–1 RH, 1 END
06 6" inlet (500 cfm) act. only, RA stat E 2 outlets–1 LH, 1 END
08 6" inlet (900 cfm) PN09 PN – N.O. htg/clg vlvs w/ PVRs, F 2 outlets–1 RH, 1 LH
10 10" inlet (1400 cfm) DA stat G 2 outlets - END
12 12" inlet (2000 cfm) PN10 PN – N.O. htg/clg w/ PVRs (cv H 3 outlets–1 LH, 1 RH, 1 END
14 14" inlet (3000 cfm) disch), DA stat. J 4 outlets–1 LH, 1 RH, 2 END
16 16" inlet (4000 cfm)
Notes: Note: See unit drawings for outlet sizes/
Digit 7, 8—Secondary Air Valve damper information.
N.C. = Normally-closed
05 5" inlet (350 cfm) N.O. = Normally-opened
06 6" inlet (500 cfm) DA Stat = Direct-acting pneumatic t-stat Digit 20—Not Used
08 8" inlet (900 cfm) (by others)
10 10" inlet (1400 cfm) 0 N/A
RA Stat = Reverse-acting pneumatic t-stat
12 12" inlet (2000 cfm) Digit 21—Not Used
(by others)
14 14" inlet (3000 cfm) PN = Pneumatic 0 N/A
16 16" inlet (4000 cfm) FM = Factory installation of customer- Digit 22—Not Used
Digit 9—Not Used supplied controller 0 N/A
0 N/A PVR = Pneumatic Volume Regulator Digit 23—Transformer
Digit 10, 11—Design Sequence 0 None
C0 Third (factory assigned) Digit 16—Insulation 1 120/24 volt (50 VA)
Digit 12, 13, 14, 15—Controls A 1/2" Matte-faced 2 208/24 volt (50 VA)
B 1" Matte-faced 3 240/24 volt (50 VA)
ENON No Controls, Field-installed C 1/2" Foil-faced
DDC/Electric 4 277/24 volt (50VA)
D 1" Foil-faced 5 480/24 volt (50 VA)
PNON No Controls, Field-installed F 1" Double-wall
Pneumatic 6 347/24 volt (50 VA)
G 3/8" Closed-cell 7 575/24 volt (50 VA)
DD00 Trane elec actuator only
DD01 DDC – Cooling only Digit 17—Not Used Digit 24—Disconnect Switch
DD08 DDC – Constant-volume 0 N/A 0 None
discharge Digit 18—Not Used W WithToggle
DD11 LonTalk DDC Controller— 0 N/A Digit 25—Power Fuse
Cooling only 0 None
DD18 LonTalk DDC Controller— W With
Constant Volume Discharge
6 VAV-SVN01E-EN
Service Model
Number Description
VAV-SVN01E-EN 7
Service Model
Number Description
8 VAV-SVN01E-EN
Service Model
Number Description
VAV-SVN01E-EN 9
Service Model
Number Description
240 24.0 kW
Digit 30—Electric Heat Stages
0 None
1 1 Stage
2 2 Stages Equal
3 3 Stages Equal
Digit 31—Contactors
0 None
1 24-volt magnetic
2 24-volt mercury
3 PE with magnetic
4 PE with mercury
Digit 32—Airflow Switch
0 None
W With
10 VAV-SVN01E-EN
Service Model
Number Description
VAV-SVN01E-EN 11
Service Model
Number Description
12 VAV-SVN01E-EN
Service Model
Number Description
VAV-SVN01E-EN 13
Service Model
Number Description
14 VAV-SVN01E-EN
General
Information
Literature Contents y Verify that all options have been y If a discrepancy occurs between what
This manual describes the installation included, such as filters, controls, was ordered and what is received,
of VariTrane VAV units with recom- heating coils, water valves, etc. Also contact you localTrane representative
mended wiring, piping, and mounting check that the unit voltages agree with immediately.
of Single-Duct, Dual-Duct, Fan-Pow- the building parameters. y Read the appropriate section in this
ered, Low-Height terminal units and y Manually rotate the fan (if applicable) to manual for installation procedures prior
diffusers. assure that there are no obstructions to actual starting of equipment.
Receiving and Handling within the housing. Upon receiving the equipment, please
VariTrane Units are shipped completely y Claims for in-transit damage must be inspect each unit and components for
assembled with the exceptions of filed immediately with the delivery external or internal damage. Refer to
optional attenuators for fan-powered carrier. the bill of lading to insure all equipment
units and accessories. and accessories have been received.
y For hot water re-heat units, check the
Upon receiving the equipment, coil fins and make sure that coils are Contact your localTrane sales
complete the following: not damaged. representative and notify the trucking
y Locate the nameplate and refer to the company immediately of any short ship
y Locate and verify that the correct zone or damaged equipment.
model and sales order number and sensors are with the order.These will be
check that the correct units have been marked with an orange “Accessories
delivered. Enclosed” label. Store in a secure
y Inspect the control enclosures and air location until needed. Accessories lost
valve casing for dents or punctures. at the jobsite are NOT covered by
Trane’s warranty.
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual.
Read these carefully.
VAV-SVN01E-EN 15
Unit
Information
VDDF
16 VAV-SVN01E-EN
Unit
Information
VAV-SVN01E-EN 17
Unit
Installation
Figure 4
TOP VIEW
Single-Duct Hanging
Recommendations
Inlet Size A B C
5" thru 10" 23.154" (588 mm) 25.25" (641 mm) 1.376" (35 mm)
12" thru 16" 25.154" (639 mm) 37.25" (946 mm) 1.376" (35 mm)
18 VAV-SVN01E-EN
Unit
Installation
B
Primary Optional Attenuator
Flow Ring Airflow Field Installed
Tubing
F E
Air
Valve
Airflow
Discharge Outlet
FAN SIZE A B C D E F
02SQ 26.75" (679 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm)
03SQ, 04SQ, 05SQ 29.75" (756 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm)
06SQ, 07SQ 36.75" (933 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm)
Airflow
Plenum Inlet
Optional Attenuator B
Primary
Flow Ring Field Installed
Airflow
Tubing
F E
Air
TOP VIEW Valve
Parallel Electric Heat
D
A
Terminal Box
Heater
Airflow
Discharge Outlet
43.546
(1106 mm)
VAV-SVN01E-EN 19
Unit
Installation
Figure 7
E D
2. 1.
Water
Coil
1.625"
(41 mm)
A B C D E F
FAN SIZE (Elec. Heat Only)
02SQ 18.75" (476 mm) 26.75" (679 mm) 3.25" (83 mm) 41.154" (1041 mm) 35.154 (740 mm) 20.132" (511 mm)
03SQ, 04SQ 20.75" (527 mm) 26.75" (679 mm) 3.25" (83 mm) 41.154" (1041 mm) 41.154" (1041 mm) 23.875 (606 mm)
05SQ 27.25" (692 mm) 26.75" (679 mm) 3.25" (83 mm) 41.154" (1041 mm) 41.154" (1041 mm) 29.875" (759 mm)
06SQ, 07SQ 27.25" (692 mm) 26.75" (679 mm) 3.25" (83 mm) 41.154" (1041 mm) 41.154" (1041 mm) 29.875" (759 mm)
Flow Ring A B
Tubing
Air
C
Valve
Optional Attenuator
Field Installed
TOP VIEW
Airflow
Series Electric Heat
Plenum Inlet
Electric
Heater C
19.00"
(483 mm) B
20 VAV-SVN01E-EN
Unit
Installation
Figure 8
Airflow
13.00" Plenum Inlet
23.90"
(330 mm) (607 mm)
Primary
Airflow
Optional Attenuator 19.86"
Field Installed (504 mm)
24.30"
(617 mm)
3.35"
Airflow
Discharge Outlet (85 mm) TOP VIEW
31.65"
(804 mm)
Airflow
Plenum Inlet
13.00" 23.90"
(330 mm) (607 mm)
Primary
Airflow
Optional Attenuator 19.86"
Field Installed (504 mm)
24.30"
(617 mm)
Terminal Box
Heater
3.35"
(85 mm) TOP VIEW
Airflow
Discharge Outlet
VAV-SVN01E-EN 21
Unit
Installation
Figure 9
Low-Height Parallel10SQ
1.625" 38.95"
(41 mm) (989 mm)
Primary
Flow Ring Airflow
Tubing
Plenum
Air Inlet
Valve 5.625"
(143 mm)
38.75"
(984 mm)
5.625"
Optional Heater Terminal Box
(143 mm)
Airflow
Discharge Outlet
41.137"
(1045 mm)
TOP VIEW
22 VAV-SVN01E-EN
Unit
Installation
Figure 10
3.35"
(85 mm)
34.30"
(871 mm)
31.65"
(804 mm)
3.35"
(85 mm) 10.13" 12.85" Airflow
(257 mm) Plenum Inlet
4.00" (326 mm)
Water (102 mm) Primary
Coil TOP VIEW Airflow
Optional Attenuator 19.86"
Field Installed (504 mm)
Air
Valve
Airflow 3.35"
(85 mm)
20.00"
(508 mm)
27.00"
(686 mm)
34.30"
(871 mm)
3.35"
(85 mm)
Optional
Electric Heater TOP VIEW
Airflow
20.00"
(508 mm)
27.00"
(686 mm)
VAV-SVN01E-EN 23
Unit
Installation
Figure 11
30.30"
(770 mm)
3.35"
(85 mm)
TOP VIEW
Airflow
Discharge Outlet
19.45" 19.45"
(494 mm) 10.12" (494 mm)
(257 mm) 31.65"
31.65"
(804 mm) (804 mm)
30.30"
(770 mm)
Terminal Box
TOP VIEW
Optional
Heater
1.92"
(49 mm) Airflow
Discharge Outlet
24 VAV-SVN01E-EN
Unit
Installation
Figure 12
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on
bottom of unit.
VAV-SVN01E-EN 25
Unit
Installation
Figure 13
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
26 VAV-SVN01E-EN
Unit
Installation
Figure 14
Attenuator Installation—Low-Height Parallel Units
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
VAV-SVN01E-EN 27
Unit
Installation
Figure 15
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
OPTIONAL ATTENUATOR
FIELD INSTALLED
MOUNTING BRACKET
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
28 VAV-SVN01E-EN
Unit
Installation
Dual-Duct Units
Unit VDDF VDDF w/ Unit VDDF VDDF w/
Size Dual Wall Size Dual Wall
(lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg)
0505 54/24 68/31 1012 59/27 72/33
0506 54/24 68/31 1212 60/27 84/38
0606 54/24 68/31 0814 78/35 102/46
0508 55/25 68/31 1014 79/36 103/47
0608 55/25 69/31 1214 80/36 104/47
0510 56/25 69/31 1414 81/37 105/48
0808 56/25 70/32 0816 79/36 103/47
0610 56/25 70/32 1016 80/36 104/47
0810 57/26 70/32 1216 81/37 105/48
1010 61/28 74/34 1416 82/37 105/48
0612 57/26 70/32 1616 83/38 106/48
0812 58/26 71/32
VAV-SVN01E-EN 29
Unit
Installation
30 VAV-SVN01E-EN
Unit
Installation
VAV-SVN01E-EN 31
Unit
Setup
8" x 12"
6
Flow Sensor Differential Pressure (inches water)
0.1
0.01
10 100 1,000 10,000
Airflow (CFM)
32 VAV-SVN01E-EN
Unit
Setup
(SCR) Motor Speed Control Figure 17 – Internal Potentiometer Electrically Commutated Motor (ECM)
Adjustment Procedure. Trane offers an energy efficient ECM
In order to make units more convenient motor as a motor option. Balancing of
and efficient to balance, an SCR Max an ECM motor is accomplished
(silicone control rectifier) is provided as 120 v through electronic control adjustments
standard on all fan-powered units. on the ECM control board (see Figure
The SCR is located on the side of the 15). Potentiometer settings for a
208 v– multitude of CFM settings are given in
fan control box. To adjust the speed of 277 v
the motor, the external knob must be Charts 4–15. Other potentiometer
rotated either clockwise or settings can be determined either by
counterclockwise depending on the interpolating from these tables or by
desired speed adjustment. 347 v using the following equation:
Figure 16 – SCR
VAV-SVN01E-EN 33
Unit
Setup
VPxF 03SQ
Motor Min CFM: 160
Motor Max CFM: 1085
% TENS UNITS % TENS UNITS
CFM L/sec Setting Switch Switch CFM L/sec Setting Switch Switch
160 76 1 0 1 627 296 51 5 1
170 80 2 0 2 637 300 52 5 2
179 84 3 0 3 646 305 53 5 3
188 89 4 0 4 655 309 54 5 4
198 93 5 0 5 665 314 55 5 5
207 98 6 0 6 674 318 56 5 6
216 102 7 0 7 683 323 57 5 7
226 107 8 0 8 693 327 58 5 8
235 111 9 0 9 702 331 59 5 9
244 115 10 1 0 711 336 60 6 0
254 120 11 1 1 721 340 61 6 1
263 124 12 1 2 730 345 62 6 2
272 129 13 1 3 739 349 63 6 3
282 133 14 1 4 749 353 64 6 4
291 137 15 1 5 758 358 65 6 5
300 142 16 1 6 767 362 66 6 6
310 146 17 1 7 777 367 67 6 7
319 151 18 1 8 786 371 68 6 8
328 155 19 1 9 795 375 69 6 9
338 159 20 2 0 805 380 70 7 0
347 164 21 2 1 814 384 71 7 1
356 168 22 2 2 823 389 72 7 2
366 173 23 2 3 833 393 73 7 3
375 177 24 2 4 842 397 74 7 4
385 181 25 2 5 852 402 75 7 5
394 186 26 2 6 861 406 76 7 6
403 190 27 2 7 870 411 77 7 7
413 195 28 2 8 880 415 78 7 8
422 199 29 2 9 889 419 79 7 9
431 204 30 3 0 898 424 80 8 0
441 208 31 3 1 908 428 81 8 1
450 212 32 3 2 917 433 82 8 2
459 217 33 3 3 926 437 83 8 3
469 221 34 3 4 936 442 84 8 4
478 226 35 3 5 945 446 85 8 5
487 230 36 3 6 954 450 86 8 6
497 234 37 3 7 964 455 87 8 7
506 239 38 3 8 973 459 88 8 8
515 243 39 3 9 982 464 89 8 9
525 248 40 4 0 992 468 90 9 0
534 252 41 4 1 1001 472 91 9 1
543 256 42 4 2 1010 477 92 9 2
553 261 43 4 3 1020 481 93 9 3
562 265 44 4 4 1029 486 94 9 4
571 270 45 4 5 1038 490 95 9 5
581 274 46 4 6 1048 494 96 9 6
590 278 47 4 7 1057 499 97 9 7
599 283 48 4 8 1066 503 98 9 8
609 287 49 4 9 1076 508 99 9 9
618 292 50 5 0 1085 512 100 0 0
34 VAV-SVN01E-EN
Unit
Setup
VPxF 04SQ
Motor Min CFM: 220
Motor Max CFM: 1510
% TENS UNITS % TENS UNITS
CFM L/sec Setting Switch Switch CFM L/sec Setting Switch Switch
220 104 1 0 1 872 411 51 5 1
233 110 2 0 2 885 417 52 5 2
246 116 3 0 3 898 424 53 5 3
259 122 4 0 4 911 430 54 5 4
272 128 5 0 5 924 436 55 5 5
285 135 6 0 6 937 442 56 5 6
298 141 7 0 7 950 448 57 5 7
311 147 8 0 8 963 454 58 5 8
324 153 9 0 9 976 461 59 5 9
337 159 10 1 0 989 467 60 6 0
350 165 11 1 1 1002 473 61 6 1
363 171 12 1 2 1015 479 62 6 2
376 178 13 1 3 1028 485 63 6 3
389 184 14 1 4 1041 491 64 6 4
402 190 15 1 5 1054 497 65 6 5
415 196 16 1 6 1067 504 66 6 6
429 202 17 1 7 1080 510 67 6 7
442 208 18 1 8 1093 516 68 6 8
455 215 19 1 9 1106 522 69 6 9
468 221 20 2 0 1119 528 70 7 0
481 227 21 2 1 1132 534 71 7 1
494 233 22 2 2 1145 540 72 7 2
507 239 23 2 3 1158 547 73 7 3
520 245 24 2 4 1171 553 74 7 4
533 251 25 2 5 1184 559 75 7 5
546 258 26 2 6 1197 565 76 7 6
559 264 27 2 7 1210 571 77 7 7
572 270 28 2 8 1223 577 78 7 8
585 276 29 2 9 1236 584 79 7 9
598 282 30 3 0 1249 590 80 8 0
611 288 31 3 1 1262 596 81 8 1
624 294 32 3 2 1275 602 82 8 2
637 301 33 3 3 1288 608 83 8 3
650 307 34 3 4 1302 614 84 8 4
663 313 35 3 5 1315 620 85 8 5
676 319 36 3 6 1328 627 86 8 6
689 325 37 3 7 1341 633 87 8 7
702 331 38 3 8 1354 639 88 8 8
715 338 39 3 9 1367 645 89 8 9
728 344 40 4 0 1380 651 90 9 0
741 350 41 4 1 1393 657 91 9 1
754 356 42 4 2 1406 663 92 9 2
767 362 43 4 3 1419 670 93 9 3
780 368 44 4 4 1432 676 94 9 4
793 374 45 4 5 1445 682 95 9 5
806 381 46 4 6 1458 688 96 9 6
819 387 47 4 7 1471 694 97 9 7
832 393 48 4 8 1484 700 98 9 8
845 399 49 4 9 1497 706 99 9 9
859 405 50 5 0 1510 713 100 0 0
VAV-SVN01E-EN 35
Unit
Setup
VPxF 05SQ
Motor Min CFM: 280
Motor Max CFM: 1850
36 VAV-SVN01E-EN
Unit
Setup
VPxF 06SQ
Motor Min CFM: 530
Motor Max CFM: 2100
VAV-SVN01E-EN 37
Unit
Setup
VSxF 03SQ
Motor Min CFM: 200
Motor Max CFM: 1100
38 VAV-SVN01E-EN
Unit
Setup
VSxF 04SQ
Motor Min CFM: 275
Motor Max CFM: 1500
VAV-SVN01E-EN 39
Unit
Setup
VSxF 05SQ
Motor Min CFM: 350
Motor Max CFM: 2050
40 VAV-SVN01E-EN
Unit
Setup
VSxF 06SQ
Motor Min CFM: 700
Motor Max CFM: 2500
VAV-SVN01E-EN 41
Unit
Setup
LPxF 08SQ
Motor Min CFM: 100
Motor Max CFM: 460
42 VAV-SVN01E-EN
Unit
Setup
LPxF 09SQ
Motor Min CFM: 250
Motor Max CFM: 1025
VAV-SVN01E-EN 43
Unit
Setup
LSxF 08SQ
Motor Min CFM: 100
Motor Max CFM: 460
44 VAV-SVN01E-EN
Unit
Setup
LSxF 09SQ
Motor Min CFM: 240
Motor Max CFM: 950
VAV-SVN01E-EN 45
Unit
Setup
LSxF 10SQ
Motor Min CFM: 400
Motor Max CFM: 1800
46 VAV-SVN01E-EN
Wiring
Diagrams
SINGLE TB4
G
PHASE L1 N
L1 N
Optional
ORG
Door
RED
PUR
BRN
BLU
YEL
Disconnect
Switch
Contactor
Notes: 3rd Stage
FACTORY INSTALLED
Optional
1. FIELD INSTALLED Transformer
OPTIONAL
Auto Reset Air Flow
2. Actual heater wiring diagrams are supplied Thermal Cutout Switch
L1 L2 L3
with each unit (3-stage shown). G
PUR
BRN
BLU
YEL
6. If transformer is not ordered, a separate 24-volt 24V Input from 24V Output to
power supply is required for operation of unit controls. Controller Controller
VAV-SVN01E-EN 47
Wiring
Diagrams
SINGLE G
TB4
PHASE Manual Reset L1 N
LINE Cutout Optional
VOLTAGES Contactors Fuse
STAGES
208 1
240 2
277 3
347
480
PE Switch
1st Stage
HEATER
CONTACTORS
P.E. with Magnetic Contactors (PEMA) Auto Reset Air Flow
Thermal Cutout Switch
P.E. with Mercury Contactors (PEME)
P.E. Switch
2nd Stage
L1 N
P.E. Switch G
3rd Stage
Optional
Door
Disconnect
Switch
G
THREE Manual Reset Optional
PHASE STAGES Cutout
Contactors Fuse L1 L2 L3
LINE 1
VOLTAGES TB4
2
208
3
480
575
HEATER
CONTACTORS PE Switch
P.E. with Magnetic Contactors (PEMA) 1st Stage
P.E. with Mercury Contactors (PEME)
P.E. Switch
FACTORY INSTALLED 2nd Stage
1. L1 L2 L3 N
FIELD INSTALLED
OPTIONAL G
N
2. Actual heater wiring diagram is supplied P.E. Switch
with each unit (3-stage shown). 3rd Stage
48 VAV-SVN01E-EN
Wiring
Diagrams
SINGLE
PHASE TB4
G
LINE STAGES L1 L2 N
VOLTAGES Contactor Manual Reset Optional
1 Cutout Fuse
208 1st Stage
2
240
277
347
480
HEATER
CONTACTORS
Magnetic Contactors (MAGN)
Mercury Contactors (MERC)
Contactor
2nd Stage
Optional
Air Flow Auto Reset
Switch Thermal Cutout
L1 L2 N
Optional
WHT
Door
PUR
BRN
BLK
OR
Disconnect
Switch
Contactor
G
1st Stage
THREE TB4
L1 L2 L3 N
PHASE
LINE STAGES Manual Reset Optional
VOLTAGES 1 Cutout Fuse
2
208
480
575
HEATER
CONTACTORS
Magnetic Contactors (MAGN) Contactor
2nd Stage
Mercury Contactors (MERC)
Notes:
Optional
FACTORY INSTALLED Auto Reset Air Flow
1. FIELD INSTALLED Thermal Cutout Switch L1 L2 L3 N
OPTIONAL G
BRN
WH
OR
Optional
Door
5. Heater Line Fuses, Airflow Switch, and Door Disconnect
Switch
Interlocking Disconnect are optional.
VAV-SVN01E-EN 49
Wiring
Diagrams
SINGLE G
TB4
PHASE Manual Reset
L1 L2 N
LINE Cutout Optional
Contactors
VOLTAGES Fuse
STAGES
208 1 PE Switch
1st Stage
240 2
277 3
347
480
L1 L2 N
Optional
WHT
BLK
Door
Disconnect
Switch
115 to 277V
Output to Motor
G
THREE Manual Reset Optional
PHASE STAGES Contactors Cutout Fuse L1 L2 L3 N
LINE 1
VOLTAGES TB4
2
208
3
480
575 PE Switch
1st Stage
HEATER
CONTACTORS
P.E. with Magnetic Contactors (PEMA)
P.E. with Mercury Contactors (PEME) P.E. Switch
2nd Stage
NOTE:
L1 L2 L3 N
FACTORY INSTALLED G
1.
FIELD INSTALLED
N
OPTIONAL Optional
Air Flow Auto Reset
Switch Thermal Cutout
2. Actual heater wiring diagram is supplied
with each unit (1 and 2-stage shown).
Optional
Door
3. Load carrying P.E. Switches or Contactors Disconnect
Switch
are supplied depending upon amp drawn.
WHT
BLK
50 VAV-SVN01E-EN
Wiring
Diagrams
}
GREEN GREEN
GROUND L1 N GROUND L1 N 5.
5.
SCREW SCREW
TRANSFORMER TRANSFORMER
6.
} Y DISCONNECT BK W DISCONNECT BK W
24V
24V
TO VAV BL BK SWITCH NO BK SWITCH
C
CONTROLLER BR
2. 2.
R
NC
BK W BK W
BK DUCT PRESSURE BK
BK BK
MOTOR 2 4 SWITCH MOTOR 2 4
BK BK
RELAY RELAY
BR FUSE BR FUSE
1 4. 1
4.
3 3
24V 24V
R R
W W
W W
MOTOR MOTOR
TERMINAL TERMINAL
SPEED SPEED
BLOCK BLOCK
CONTROL CONTROL
W-COM
W-COM
BK
BK
FAN CONTROL BOX FAN CONTROL BOX
W BK W BK
BR BR BR BR
CAPACITOR MOTOR CAPACITOR MOTOR
FAN FAN
3. 3.
}
DISCONNECT, LOCK OUT AND TAG GREEN
ALL ELECTRIC POWER INCLUDING N
DUCT PRESSURE MAIN CONTROL GROUND L1 5.
REMOTE DISCONNECTS BEFORE
SERVICING. SCREW
6.
DISCHARGE MOTOR START/RUN
CAPACITORS BEFORE SERVICING.
FAILURE TO DISCONNECT POWER DISCONNECT BK W
SWITCH
BEFORE SERVICING CAN CAUSE BK NO NO
SEVERE PERSONAL INJURY OR DEATH.
C C 2.
BK
CAUTION NC NC
BK W
USE COPPER CONDUCTORS ONLY!
P.E. SWITCH-1 P.E. SWITCH-2
UNIT TERMINALS ARE NOT DESIGNED BK BK
TO ACCEPT OTHER TYPES OF
BK
CONDUCTORS. NO
FAILURE TO DO SO MAY CAUSE 6. BK FUSE
DAMAGE TO THE EQUIPMENT.
C 4.
NC
P.E. SWITCH
NOTES: W
1. FACTORY INSTALLED
BY OTHERS MOTOR
OPTIONAL OR ALTERNATE CIRCUITRY TERMINAL
SPEED
BLOCK
CONTROL
2. DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
W-COM
VAV-SVN01E-EN 51
Wiring
Diagrams
}
MOTOR
4. L1 N 4.
BK
GR
Y GR
GREEN
GREEN
BK
GROUND
BK
W
BK
W
SCREW
W
SCREW
TERMINAL
RED RED BLOCK
TERMINAL
BLOCK
DISCONNECT 2 4 2.
SWITCH 3. DISCONNECT
SWITCH W
2. FUSE BL
BK
W
G
R
BK
3. W
ECM
FUSE 1
24V 3 BOARD Y
MOTOR 5.
BK
RELAY
3. NO BL POWER
NEUT. 24V
FACTOR
BL CORRECTION
}
RED RED
CHOKE
C
Y TO VAV NC
CONTROLLER
24V
BL DUCT
PRESSURE Y
BK
W
G
R
SWITCH ECM
24V
BK BL
TRANSFORMER BOARD
TRANSFORMER
POWER FACTOR
CORRECTION CHOKE FAN CONTROL BOX
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
CAUTION
USE COPPER CONDUCTORS ONLY!
GR
GREEN
BK
POWER FACTOR
BK NO NO CORRECTION CHOKE
C BK C NEUT. 24V
Y
24V
NC NC BL RED RED
BK
NOTES: NO
BK
W
G
R
ECM
1. FACTORY INSTALLED C
BOARD
BY OTHERS NC
OPTIONAL OR ALTERNATE CIRCUITRY
P.E. SWITCH
2. DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
EXTERNAL TO CONTROL BOX. FAN CONTROL BOX
3. FUSE IS OPTIONAL.
52 VAV-SVN01E-EN
Wiring
Diagrams
FAN
BR MOTOR 2
BR W FAN 3.
L1 N (SIZE 10 ONLY)
BK MOTOR
W BK
3.
LINE VOLTAGE 5. CAPACITOR
GREEN BR
OR FROM HEATER TERMINAL BR
GROUND BR W
2. L1 N
SCREW W BK
BR
MOTOR
SPEED GREEN
2.
CONTROL GROUND BK
DISCONNECT MOTOR
BK SCREW
W SWITCH SPEED
W W BK W
2. CONTROL
TERMINAL
W W
BLOCK
2. TERMINAL
4. BK W DISCONNECT BLOCK
W
BR W
FUSE BK W SWITCH
BR W
W
BK
4. BK
}
W or BR Y
FUSE BK BK
24V
BK TO VAV
BK BL
2 4 MOTOR CONTROLLER 6. BK 2 4
BR
RELAY
R
TRANSFORMER NO 24V
BR BL
BL Y
BL C
1 24V 3
NC
TRANSFORMER 1 24V 3
R
DUCT
MOTOR
PRESSURE
RELAY
SWITCH
FAN CONTROL BOX
FAN CONTROL BOX
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
CAUTION
USE COPPER CONDUCTORS ONLY!
LINE VOLTAGE 5. BR
3.
BR
OR FROM HEATER TERMINAL
}
BK
UNIT TERMINALS ARE NOT DESIGNED CAPACITOR W
TO ACCEPT OTHER TYPES OF L1
BR
N BK
CONDUCTORS. W
CAPACITOR
FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT. GREEN
GROUND MOTOR
SCREW SPEED
CONTROL
6. W W
BK W
TERMINAL
BLOCK
BK NO NO 2.
DISCONNECT W
C BK C BK W
SWITCH BR
W
NC NC 4.
BK
BK
NOTES:
NO
1. FACTORY INSTALLED
BK
BY OTHERS
C
OPTIONAL OR ALTERNATE CIRCUITRY NC
4. FUSE IS OPTIONAL.
VAV-SVN01E-EN 53
Wiring
Diagrams
4.
LINE VOLTAGE
LINE VOLTAGE 4. OR FROM HEATER TERMINAL
}
OR FROM HEATER TERMINAL FAN FAN
MOTOR MOTOR 2 FAN FAN
}
BK
GR GR
GREEN W GREEN
Y W
BK
W
GROUND BK GROUND
BK
BK
W
SCREW
BK
SCREW
W
BK
W
NEUT. 24V
TERMINAL TERMINAL
BLOCK RED RED BLOCK
DISCONNECT 2.
SWITCH 3. DISCONNECT
SWITCH W
2. 2 4 FUSE BL
3. BK
W Y
FUSE
BK
W
G
R
ECM
5.
1
24V 3 BOARD
NO BL
MOTOR BL
NEUT. 24V
} TO VAV
DUCT
PRESSURE Y
BK
W
G
R
Y SWITCH ECM
24V
CONTROLLER
BK BL
24V
BK BL
BOARD
TRANSFORMER
TRANSFORMER
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
CAUTION
USE COPPER CONDUCTORS ONLY! Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT OTHER TYPES OF
CONDUCTORS.
LINE VOLTAGE 4.
FAILURE TO DO SO MAY CAUSE FAN FAN
DAMAGE TO THE EQUIPMENT. OR FROM HEATER TERMINAL MOTOR MOTOR 2
(SIZE 10 ONLY)
}
GR
GREEN W
GROUND BK
BK
W
BK
SCREW
W
NC NC
NEUT. 24V
P.E. SWITCH-1 P.E. SWITCH-2 Y
BK RED RED
24V
BK BL
NOTES: TRANSFORMER
1. FACTORY INSTALLED
BK
W
G
R
BY OTHERS ECM
NO
OPTIONAL OR ALTERNATE CIRCUITRY BOARD
C
2. DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED NC
EXTERNAL TO CONTROL BOX.
P.E. SWITCH
3. FUSE IS OPTIONAL.
FAN CONTROL BOX
4. DETERMINED BY MOTOR VOLTAGE ON ORDER.
VOLTAGE FOUND ON UNIT NAMEPLATE.
54 VAV-SVN01E-EN
Maintenance
Periodic maintenance of the VariTrane Figure 27 – Standard Motor Removal Figure 28 – Low-Height Motor Removal
product is minimal, but necessary for
efficient operation. Routine mainte-
nance consists of inspecting/replacing
the air filters of the fan-powered
terminals.
Motors
Both the PSC (permanent split capaci-
tor) and the ECM (Electrically Commu-
tated Motor) require no lubrication
during its normal life of operation.
FanWheel:
Periodically, the fan wheel should be
inspected for dirt or debris and cleaned
as necessary.
Standard height fan-powered series
Filter and parallel fan motors are replaceable
The filter on fan-powered terminals will through the filter opening and the
need to be inspected/replaced routinely standard sliding side access panel. To
depending on the environmental access the fan motor, the fan housing
conditions of the plenum. must be detached by removing the
Water Coil mounting bolts that hold the housing to
Water coils should be inspected and the the fan board. Removing the entire
fins should be cleaned periodically. housing allows the fan motor, fan
housing, and fan wheel to be re-aligned
Water coils have been provided with an
on a workbench or floor and prevent
access panel as standard to assist with
any possible fan wheel rubbing that
inspection and cleaning.
may occur. Removing the housing will
Fan Motor Replacement provide access to the motor shaft set
screw that holds the fan wheel to the
motor shaft.
WARNING
The low-height fan assembly was
Hazardous Voltage designed with an inlet ring that assists
w/Capacitors! with removal of the fan motor. To
Disconnect all electric power, including access the fan motor assembly, the
remote disconnects and discharge all bottom panel must be removed. The
motor start/run capacitors before inlet ring is held in place by six bolts
servicing. Follow proper lockout/tagout and three motor mount bolts. Remove
procedures to ensure the power cannot these bolts and the motor and fan
be inadvertently energized. Verify with wheel will come out of the fan housing.
an appropriate voltmeter that all
capacitors have discharged. Failure to
disconnect power and discharge
capacitors before servicing could result
in death or serious injury.
WARNING
Rotating Components!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. Failure to
disconnect power before servicing
could result in death or serious injury.
VAV-SVN01E-EN 55
Installation
of Diffusers
56 VAV-SVN01E-EN
Maintenance/
Service Log
VAV-SVN01E-EN 57
Maintenance/
Service Log
58 VAV-SVN01E-EN
Notes
VAV-SVN01E-EN 59
Literature Order Number VAV-SVN01E-EN
File Number SL-TD-000-VAV-SVN01E-EN-0606
Supersedes SL-TD-000-VAV-SVN01D-EN-0905
Trane
Stocking Location Inland
An American Standard Company
www.trane.com
For more information contact Trane has a policy of continuous product and product data improvement and reserves the right to change
your local district office or design and specifications without notice. Only qualified technicians should perform the installation and
e-mail us at comfort@trane.com servicing of equipment referred to in this publication.