10,5 kV Generator Output Current Transformers

SGenerator = =

45 MVA 154 kV

168.91 A

Based on generator output current 168.91 A, the optimum standard ratio for current transformer would The secondary current is 5A. The winding power changes with the length, cross-section of cable and power consu equipment; therefore, the exact values of powers shall be calculated during operation. Resistivity to Short Time Thermal Current Short circuit current of 10,5kV point is 12 kA. The fault elimination time is lower than 1 sec
1 sec as it is selected in cables part. 12 100 therefore, the exact values of powers shall be calculated during operation.

The secondary current is 5A. The winding power changes with the length, cross-section of cable and power consu

2. Current Transformers on 36 kV Side

STransformer = =

20 MVA 34.5 kV

335.09 A

Based on generator output current 335.09 A, the optimum standard ratio for current transformer would The secondary current is 5A. The winding power changes with the length, cross-section of cable and power consu equipment; therefore, the exact values of powers shall be calculated during operation. Resistivity to Short Time Thermal Current Short circuit current of 10,5kV point is 15.72 kA. The fault elimination time is lower than 1 sec
1 sec as it is selected in cables part. 15.72 100 therefore, the exact values of powers shall be calculated during operation.

The secondary current is 5A. The winding power changes with the length, cross-section of cable and power consu

3. Current Transformers in Measurement Switchgear

STransformer = =

20 MVA 34.5 kV

335.09 A

Based on generator output current 335.09 A, the optimum standard ratio for current transformer would The secondary current is 5A. The winding power changes with the length, cross-section of cable and power consu equipment; therefore, the exact values of powers shall be calculated during operation. Resistivity to Short Time Thermal Current Short circuit current of 10,5kV point is 15.72 kA. The fault elimination time is lower than 1 sec
1 sec as it is selected in cables part. 15.72 100 therefore, the exact values of powers shall be calculated during operation.

The secondary current is 5A. The winding power changes with the length, cross-section of cable and power consu

4. Current Transformers in Outgoing Switchgear

STransformer = =

20 MVA 34.5 kV

335.09 A

Based on generator output current 335.09 A, the optimum standard ratio for current transformer would The secondary current is 5A. The winding power changes with the length, cross-section of cable and power consu equipment; therefore, the exact values of powers shall be calculated during operation. Resistivity to Short Time Thermal Current Short circuit current of 10,5kV point is 15.72 kA. The fault elimination time is lower than 1 sec
1 sec as it is selected in cables part. 15.72 100 therefore, the exact values of powers shall be calculated during operation.

The secondary current is 5A. The winding power changes with the length, cross-section of cable and power consu

ratio for current transformer would be =

1250 /5-5-5 A 5P10-5P20-0,2SFs5.

section of cable and power consumption of relay and measurement

tion time is lower than 1 sec. Therefore, for a more safety system this time is chosen

section of cable and power consumption of relay and measurement equipment;

ratio for current transformer would be =

1250 /5-5-5 A 5P10-5P20-0,2SFs5.

section of cable and power consumption of relay and measurement

tion time is lower than 1 sec. Therefore, for a more safety system this time is chosen

section of cable and power consumption of relay and measurement equipment;

ratio for current transformer would be =

1250 /5-5-5 A 5P10-5P20-0,2SFs5.

section of cable and power consumption of relay and measurement

tion time is lower than 1 sec. Therefore, for a more safety system this time is chosen

section of cable and power consumption of relay and measurement equipment;

ratio for current transformer would be =

1250 /5-5-5 A 5P10-5P20-0,2SFs5.

section of cable and power consumption of relay and measurement

tion time is lower than 1 sec. Therefore, for a more safety system this time is chosen

section of cable and power consumption of relay and measurement equipment;