Cost savings
All weatherproof outdoor enclosures allow the equipment to be located in any outdoor environment, freeing up valuable indoor floor space whilst retaining remote operation and control. There are a wide range of metering instruments available for monitoring the unit locally or remotely, ensuring efficient operation. NS Feeder pillars are available as part of a package substation with transformers and MV switch or circuit breakers. Additional cost savings are achieved through direct coupling from the transformer to the NS Feeder pillar eliminating expensive cable runs.
Safety
ASTA certified, providing IP2X operator protection under all circumstances during operation, allowing electrical systems to be fully co-ordinated minimising electrical faults. In addition to the overload and short circuit protection, each breaker can be fitted with earth fault protection.
Flexibility
The modular design enables customisation for individual requirements, and has the flexibility to suit the changing needs of the LV distribution system. Maximum flexibility is achieved by the four pole busbar system up to 3200A and the Compact NS range of moulded circuit breakers of ratings up to 630A. As a complete unit, the NS Feeder Pillar will not only provide circuit protection, but the outgoing circuits can also be controlled individually via hardwired pilots or linked to the incoming breaker. Other add-on benefits include remote monitoring and status of each breaker and also remote operation through motor mechanisms.
Add on modules for compact NS include ammeters and earth fault protection
Product Features
s s s s s s s s s
Operator protection to IP2X of BSEN 60529 Purpose built, weatherproof enclosure Four pole busbar system up to 3200A Outgoing ratings from 16A to 3200A Cable or flange connection to transformer Compact NS Breakers from 16A to 630A Compact C breakers from 800A to 1250A Provision for inclusion in package substations Wide range of accessories
Accessories
There are accessories for many functions with local and remote monitoring which include: Ammeters Voltmeters KWH meters MDIs Internal lamps 13A RCD sockets Street lighting circuits Anti condensation heaters Pillar lights on manual or door operated switches can be fitted to the integral feeder pillar instrument panel. Accessories to customise the range of circuit breakers to meet specific cabling and operational needs are also available.
Applications
s s s
Hospitals, medical centres Education, universities, shopping centres, retail parks Business parks, office buildings
s s
NS Feeder Pillars up to 3200A Transformers from 315kVA to 2000kVA Extensible and non extensible Ringmaster and MV switchgear. Automation and monitoring systems Weatherproof enclosures if required.
Enclosures
Merlin Gerin range of feeder pillar enclosures are robust, durable and secure, providing all weatherproof and vandal resistant protection. Available in six sizes, these are padlockable and manufactured from 3mm sheet steel. The steel is shot blasted and zinc metal sprayed before being coated in electrostatically charged powder paint, and cured in an oven for a hard, high gloss finish. The enclosures accommodate a variety of interiors.These weatherproof enclosures are available in dark grey to BS 381C and IP33 as standard. IP54 can be achieved with the addition of filtered ventilation and door gaskets.
Enclosure selection
shell size (mm) 2110 1830 1550 1270 990 710 functional space (mm) 1995 1715 1435 1155 875 595
Feeder pillar
A 559 559
1582 1270
100
50
235
482
C cable connected
(end view)
B
flange connected
(end view)
100
foundations
(supplied by customer)
105
feeder pillar
(front view)
6 HOLES 16 dia
32
10 HOLES 32 dia
482 116
490
30
89 235 89 89 89 89 89 89 89
Doors 1 2 2 2 2 2
Dimensions A B cable & flange connected 740 710 1020 990 1300 1270 1580 1550 1860 1830 2140 2110
25 B
105
25
31
610
100 105 32
MAXIMUM
482
dimensions A= refer to table B= refer to table C=to suit cable bending radius
25 B
105
25
31
Breaker cabinet
A B 310 703
fabricated foot
(optional extra)
50
D 100
1070
32 235 50
200
Doors 1 1 1
Dimensions (mm) A B C flange connected only 776 430 460 656 310 460 656 310 370
25 B
25
32
490
89 235 89
89
89
89
89
89
89
610 MAXIMUM
NS-FT3
MDI
Aux. Equip
Specification
Location Enclosure doors open Phase busbar rating Neutral busbar rating Short circuit level Incoming units Outgoing breakers Load indication Circuit protection Incoming cable entry Gland plates Outgoing cable entry outdoor (flange connected) enclosure to IP33 IP2X under normal operating conditions 3200A full or half busbar rating 50kA 1 second Masterpact ACBs Compact MCCB & NS also off-load disconnectors Compact MCCBs and NS provision - see accessories adjustable overload protection Below vertical undrilled below vertical
Incoming unit
reference rating (A) 3000 3000 2500 2000 2000 1600 1600 1250 1000 1000 800 800 800 630 400 250 M32 ACB disconnector M25 ACB M20 ACB disconnector M16 ACB disconnector C1251N M10 ACB C1000N M08 ACB C800N disconnector NS 630 NS 400 NS 250
Accessories
Pillar
Padlocking devices Internal light 13A sockets Ammeters Voltmeters Kilowatt hour meters Maximum demand indicators Anti-condensation heater Thermostat
Compact MCCB
toggle padlocking device NS motor mechanisms terminal shrouds NS VIGI earth leakage module NS ammeter module NS current transformer module NS disconnectable neutral links cable termination spreaders C800-1251 earth fault unit shunt release (MX) undervoltage release (MN) NS electronic trip unit (STR 22SE) NS selective trip unit (STR 23SE) NS universal trip unit (STR 53UE)
Masterpact ACB
instantaneous protection (STR 18) selective protection (STR 38) universal protection (STR 58) padlocking devices dialpact modules electrical operating mechanism undervoltage release instantaneous (MN) undervoltage release time delayed (MNR) shunt release (MX) closing release (XF) auxiliary switches
Circuit breaker feeder pillar Panel types - cable connected pillars NS-FC3
LV distribution pillar supplies up to 3200A
Aux. Equip
Specification
Location Enclosure doors open Phase busbar rating Neutral busbar rating Short circuit level Incoming units Outgoing breakers Load indication Circuit protection Incoming cable entry Gland plates Outgoing cable entry Accessories outdoor (cable connected) enclosure to IP33 IP2X under normal operating conditions 3200A full or half busbar rating 50kA 1 second Masterpact ACBs Compact mccb & NS also off-load disconnectors Compact mccbs and NS provision - see accessories adjustable overload protection below vertical provision - see accessories below vertical As per NS-FT3
Incoming unit
reference rating (A) 3000 3000 2500 2000 2000 1600 1600 1250 1000 1000 800 800 800 630 400 250 M32 ACB disconnector M25 ACB M20 ACB disconnector M16 ACB disconnector C1251N M10 ACB C1000N M08 ACB C800N disconnector NS 630 NS 400 NS 250 Max. No. of SC 960mm phase neutral 4 2 4 2 3 2 2 1 3 2 2 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 SC 300mm sq SC 300mm sq SC 185mm sq
SX - C3
LV cabinet supplies up to 3000A
N/E link
Specification
Location Phase busbar rating Neutral busbar rating Short circuit level Incomer
outdoor IP33 enclosure tx mounted only up to 1600A up to 800A up to 50KA 1 second TP&N Off-load disconnector outdoor IP33 enclosure tx mounted only up to 3000A up to 1500A 50KA 1 second N/A
Load indication Outgoing units Circuit protection Outgoing cable entry Outgoing cable size
provision - see accessories 2 - TP Compact C MCCBS Adjustable overload & short circuit below vertical up to 7 x SC 600mm sq
Gland plates
undrilled
provision - see accessories TP Masterpact ACB type H1 standard - STR28D overload & short circuit optional - STR38ST incorporating earth fault below vertical up to 7 x SC 600mm sq (800-1600A) up to 11 x SC 600mm sq (2000-2500A) up to 3 x SC 960mm sq per phase &... up to 2 x SC 960mm on neutral (3000A only) undrilled
pillars
1600 800
60439 - 1 60947 - 2
60439 - 1 60947 - 2
Note: for ambient temperature in excess of those defined as normal in BSEN 60439 - 1, please consult the manufacturer.