Você está na página 1de 2

Catalog Number Notes Type

FEATURES & SPECIFICATIONS

TM

INTENDED USE Provides minimum of 90 minutes of illumination for rated wattage upon loss of AC power. Unique design for light and heavy industrial applications, as well as heavy commercial environments. Superior performance lamp heads are ideal for higher mounting heights. CONSTRUCTION Rugged front and navy back (std. colors) .140 thick, injection-molded thermoplastic (large back housing is .187 thick, compressionmolded composite). Vertical orientation, designed for pole or column mounting. Also suitable for wall, I-beam and unistrut mounting. Ceiling and pendant mounting with accessory equipment available on some models. Easy installation with epoxy-coated, corrosion-resistant, 12-gauge steel mounting bracket shipped standard. U.S. Patent No. 6,135,624 - Mounting Bracket Utility patent. Conduit entry points located on top and both sides of unit. Maintenance made easy by tool-less lamp replacement, hinged front cover, printed circuit board mounting shelf and battery belt. U.S. Patent No. D419,097 - Design patent. OPTICS U.S. Patent No. 6,193,395 - Lamp Head Utility patent. Full range of lamp options available from 9W to 50W in sealed-beam or composite versions of incandescent, krypton or halogen lamps. Composite lamps feature unique fieldadjustable beam spread (by turning lamp bezel). Standard lamp is 9W krypton for 6V and 12V. Standard lamp is 18W incandescent for 24V. ELECTRICAL Brownout protection is standard feature of self-diagnostics. AC/LVD reset prevents battery damage from deep discharge. Current limiting charger. Thermal protection prevents overheating and charger failure. Thermal compensation provides optimum charge voltage relative to ambient temperature. Dual voltage input capacity 120/277. Battery: Sealed, maintenance-free, lead-calcium battery with capacity of 18W to 450W for 90 minutes of emergency operation. Available in 6V, 12V or 24V. Low-voltage disconnect prevents excessively deep discharge that can permanently damage battery. Premium and Ultimate options offer high-temperature batteries (IND618, IND1236 and IND12100 only). UL listed from 0 C to 55 C (32F to 131F) (Premium) or -40 C to 55 C (-40F to 131F) (Ultimate). Diagnostics (with Select, Premium and Ultimate packages): US Patent No. 6,502,044 - Self Diagnostics utility patent. Single multi-chromatic LED indicator displays two-state charging, test activation and three-state diagnostic status.

Industrial Emergency Lighting Unit

IND6/12/24
6, 12 or 24 Volts Sealed Lead-Calcium or Ni-Cad Battery

Self-diagnostic testing for five minutes every 30 days and 30 minutes every six months. Diagnostic evaluation of lamp, AC to DC transfer, charging and battery condition. Load learning capability self-calibrates to DC load at first test, enabling it to detect a lamp failure on future tests. May be re-calibrated at any time by holding down test switch for 15 seconds. LISTING UL Listed. Damp location listing. Meets UL 924, NFPA 101, NFPA 101NEC and OSHA illumination standards. WARRANTY Three-year warranty.

ORDERING INFORMATION

For shortest lead times, configure product using standard options (shown in bold). Example: IND12100 H5012S SEL

Family

Housing color

Lamp type (2 heads) 6 Volts PAR36 Composite

Options (blank) Damp location 10 C to 40 C (50 F to 104 F).


XTRA Extra package. Features remote test, time delay and damp location 10 C to 40 C (50 F to 104 F).4

IND618 18W IND654 54W


IND6100 100W1 12 Volts IND1236 36W

6 Volts

(blank) Gray front/ Navy back


W White

(blank) 9W/6V krypton


H1206 12W/6V halogen

Accessories
Order as separate items. ELA RTT Remote test transmitter4 ELA WG2M ELA WGLG ELA BS ELA IND PM Wire guard - small (18W-100W)8 Wireguard - large (150450W)8 Banding strap Pendant mount kit for IND618/654/6100 1236/1254/12100/241006

H2006 20W/6V halogen


12 Volts PAR36 Composite

SEL Select package. Features self-diagnostics, time delay, audible failure indication and damp location 10 C to 40 C (50 F to 104 F).
PREM Premium package. Features high-temperature ni-cad battery (IND618 and IND1236 only) or high-temperature lead calcium battery (IND12100 only), self-diagnostics, time delay, audible failure indication and damp location. UL listed for 0 C to 55 C (32 F to 131 F).5,7 ULT Ultimate package. Features heater, thermostat and battery blanket with a high temperature ni-cad battery (IND618 and IND1236 only) or high-temperature lead-calcium battery (IND12100 only), self-diagnostics, time delay, audible failure indication and damp location. UL listed for -40 C to 55oC (-40 F to 131 F).5,7
NOTES: 1 2 3 4 5 6 7 8 DL listed for indoor applications. Not suitable for ceiling mount. Required for ceiling mount. Must order a Remote transmitter (ELA RTT). One per job required. Only available on IND618, IND1236 and IND12100. ELA IND PM accessory cannot be used with the IND12100 PREM or IND12100 ULT. IND12100 PREM and IND12100 ULT come in a larger housing size. See spec sheet ELA-WG.

IND1254 54W IND12100 100W2


IND12150 150W2 IND12300 300W2 IND12450 450W2 24 Volts IND24100 100W2 IND24450 450W1,2

(blank) 9W/12V krypton


H1212 12W/12V halogen

H2012 20W/12V halogen


PAR36 Sealed-Beam H3512S 35W/12V halogen

H5012S 50W/12V halogen


24 Volts PAR36 Composite (blank) 18W/24V incand. H2024 20W/24V halogen PAR36 Sealed-Beam N5024S 50W/24V incand.

ELA IND CM1 Ceiling mount kit for IND6183 ELA IND CM2 Ceiling mount kit for IND654/1236/12543 ELA IND CM3 Ceiling mount kit for IND61003 ELA IND R3 Pre-pack to install third head

Emergency

Sheet #: IND6-12-24

INUE-100

IND6-12-24 INDURA Industrial Emergency Lighting Units, 6/12/24 Volts


SPECIFICATIONS
ELECTRICAL Primary Circuit
Type IND618 IND654 IND6100 IND1236 IND1254 IND12100 IND12150 IND12300 IND12450 IND24100 IND24450 Volts 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277 120 277 AC Input1 Amps Watts .163 19.6 .069 .172 .075 .171 .064 .174 .078 .174 .078 .174 .074 .359 .168 .290 .130 .33 .15 .33 .15 .773 .327 19.11 20.64 20.78 20.5 17.7 20.9 21.61 20.88 21.6 20.88 20.49 43.08 46.54 34.8 36.1 39.96 43.77 39.6 41.55 92.76 90.58 Output Volts 6 6 6 12 12 12 12 12 12 24 24 Watts Output 1-1/2hr. 2hr. 3hrs. 18 54 100 36 54 100 150 300 450 100 450 13.5 40 75 27 40 75 112 225 337 75 337 9 27 50 18 27 50 75 150 225 50 225 4hrs. 6 20 37 13 20 37 56 112 168 37 168
12-1/2 (31.8)
1/4 (6.0) 2-1/4 (57.0) 2-3/4 (7.0) 3/4 (1.9)

MOUNTING
All dimensions are in inches (millimeters). Shipping weight: IND618 - 13 lbs. IND654 - 18 lbs. IND6100 - 23 lbs. IND1236 - 18 lbs. IND1254 - 18 lbs. IND12100 - 27 lbs.
Large Housing (100W PREM and ULT; 150-450W)
18 (45.7) 16 (40.6)

IND12150 - 45 lbs. IND12300 - 72 lbs. IND12450 - 75 lbs. IND24100 - 27 lbs. IND24450 - 75 lbs.

13-1/4 (33.7)

16 (40.6)

Small Housing (18-54W; 100W Standard, XTRA, and SEL)


12 (31.0) 8-5/8 (22.0) 9 (22.9)
3/8 (10.0)

Mounting bracket
8-3/8 (21.3) 1 (2.5) 2-1/4 (5.7) 8 (20.3)

BATTERY High-Temperature Nickel-Cadmium


Voltage 6/12/24 Shelf life2 3 yrs. Expected life3 10 yrs. Maintenance4 none

Operating temperature5 32o-131oF (0o-55oC) Operating temperature5 60o-90oF (16o-32oC) Operating temperature5 32o-131oF (0o-55oC)

PHOTOMETRICS
ELA IND K0906 One (1) 9 Watt Krypton In Vertical, Base Up Position HORIZONTAL 6 4 6 4 2 1 0.5 0.3 0 2 4 6 VERTICAL VERTICAL 6 4 2 1 0.5 0.3 0 2 4 6 10 20 30 40 Ft. 10 20 30 Ft. 1 0.5 0.3 1 0.5 0.3 ELA IND K0912 One (1) 9 Watt Krypton In Vertical, Base Up Position . HORIZONTAL .

Lead-Calcium
Voltage 6/12/24

Shelf life2 1 yr.

Expected life3 5-8 yrs.

2 0 2 4 6

Maintenance4 none

High-Temperature Lead-Calcium
Voltage 6/12/24 Shelf life2 1 yr.

Expected life3 5-8 yrs.

Maintenance4 none

6 4 2 0 2 4 6

NOTES: 1 Add 0.3 amps, 31W for models with ULT option. 2 At 77F (25C). 3 Based on normal room temperatures and conditions. 4 All life safety equipment, including emergency lighting for path of egress must be maintained, serviced, and tested in accordance with all National Fire Protection Association (NFPA) and local codes. Failure to perform the required maintenance, service, or testing could jeopardize the safety of occupants and will void all warranties. 5 Optimum ambient temperature range where unit will provide rated capacity for 90 minutes. Higher and lower temperatures affect life and capacity.

PERFORMANCE DIAGRAMS
25.5'
Center-to-center spacing* yields 25.5'.

KEY FEATURES

FLOOD

IND K0906 Medium Distribution

3'

Center-to-center spacing* yields 26'.

MEDIUM

SPOT

12-gauge epoxy-coated steel mounting bracket included with each unit.

Field-adjusted beam pattern for composite lamps.

ELA RTT Order remote transmitter separately.

*Note: Meets Life Safety Code standard minimum illuminance of 0.1 FC and average illuminance of 1.0 FC. Assumes space of 200'L x 200'W x 30'H, mounting height: 12', ceiling height: 30', and reflectances: 10/10/10. Analysis based on independently tested photometrics.

26'

IND K0912 Medium Distribution 3'

Lithonia Lighting

Sheet #: IND6-12-24

2004-2011 Acuity Brands Lighting, Inc. All rights reserved. Rev. 1/10/11

Emergency Lighting Systems One Lithonia Way, Conyers, GA 30012 Phone: 800-334-8694 Fax: 770-981-8141 www.lithonia.com