Escolar Documentos
Profissional Documentos
Cultura Documentos
User Manual
product icon
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will the Allen-Bradley Company be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, the Allen-Bradley Company cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Allen-Bradley Company with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of the Allen-Bradley Company is prohibited. Throughout this manual we use notes to make you aware of safety considerations. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
Attentions help you: identify a hazard avoid the hazard recognize the consequences Important: Identifies information that is especially important for successful application and understanding of the product.
ControlLogix is a trademark of the Allen-Bradley Company, Inc.
Preface
P-1
You must be able to program and operate an Allen-Bradley programmable controller (PLC) to make efficient use of your analog I/O modules. We assume that you know how to do this in this manual. If you do not, refer to the appropriate PLC programming and operations manual before you attempt to program this module.
Purpose of Manual
This manual describes how to use your ControlLogix analog I/O module. It helps you install, program, configure, calibrate and troubleshoot your module.
(INSERT ART)
P-2
P-3
Terms
This term: BOOTP Means: low level protocol that provides communications to other nodes on a TCP/IP network
P-4
1756-5.2 1756-x.x
If you need more information on these products, contact your local Allen-Bradley integrator or sales office for assistance. For more information on the documentation, refer to the Allen-Bradley Publication Index, publication SD499.
Rockwell Automation offers support services worldwide, with over 75 sales/support offices, 512 authorized distributors and 260 authorized systems integrators located throughout the United States alone, plus Rockwell Automation representatives in every major country in the world.
Table of Contents
What is ControlLogix Analog I/O?
Chapter 1 What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Compliance to European Union Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Low Voltage Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Preventing Electrostatic Discharge . . . . . . . . . . . . . . . . . . . . . . . 1-2 Removing and Inserting Under Power . . . . . . . . . . . . . . . . . . . . . 1-2 Using an I/O Module in the ControlLogix System . . . . . . . . . . . . . 1-3 Types of Analog ControlLogix I/O . . . . . . . . . . . . . . . . . . . . 1-3 Major Features of the ControlLogix Analog I/O Modules . . . . . 1-4 Using Features of Control- Logix Analog I/O Modules. . . . . . . . . . 1-5 Data Types and Connection Points . . . . . . . . . . . . . . . . . . . . . 1-5 Scaling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5 Sampling, Receiving and Producing Rela-Time Data. . . . . . . . 1-6 Inputs: Sampling and Producing Data. . . . . . . . . . . . . . . . 1-6 Outputs: Receiving and Producing Data . . . . . . . . . . . . . . 1-6 Using Features Specific to Input Modules . . . . . . . . . . . . . . . . . . 1-7 Process Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7 Sensor Type and Temperature . . . . . . . . . . . . . . . . . . . . . . . . 1-7 RTD Linearization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7 Thermocouple Linearization . . . . . . . . . . . . . . . . . . . . . . . 1-8 Using Features Specific to Output Modules . . . . . . . . . . . . . . . . . 1-8 Ramping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8 Clamping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8 Hold for Initialization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 Fault and Idle Behavior. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9 Chapter Summary and Whats Next . . . . . . . . . . . . . . . . . . . . . . . 1-9 Chapter 2 What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 Installing the ControlLogix I/O Module . . . . . . . . . . . . . . . . . . . . . 2-1 Keying the Removable Terminal Block and the Interface Module . 2-2 Connecting Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Connect grounded end of the cable . . . . . . . . . . . . . . . . . . 2-3 Connect ungrounded end of the cable . . . . . . . . . . . . . . . . 2-3 Three Types of RTBs (each RTB comes with housing) . . . . 2-4 Assembling the Removable Terminal Block and the Housing . . . . 2-5 InstallingtheRemovableTerminalBlockorInterfaceModuleontotheModule 2-6 Checking the Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7 LED indicators for input modules. . . . . . . . . . . . . . . . . . . . 2-7 LED indicators for output modules. . . . . . . . . . . . . . . . . . . 2-7
Publication 1756-6.5.9 - March 1998
ii
Removing the Removable Terminal Block from the Module . . . . . 2-8 Removing the Module from the Chassis. . . . . . . . . . . . . . . . . . . . 2-8 1756-IF6I Wiring examples. . . . . . . . . . . . . . . . . . . . . . . . . . 2-9 Voltage input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9 Current input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9 1756-IR6I Wiring examples . . . . . . . . . . . . . . . . . . . . . . . . 2-10 Three-wire RTD device . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10 Four-wire RTD device . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10 1756-IT6I Wiring examples. . . . . . . . . . . . . . . . . . . . . . . . . 2-11 Connect the Cold Junction Sensor . . . . . . . . . . . . . . . . . . 2-11 1756-IF8 Wiring examples . . . . . . . . . . . . . . . . . . . . . . . . . 2-12 Differential current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12 Differential voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12 Single-ended current. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12 Single-ended voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12 1756-IF16 Wiring examples . . . . . . . . . . . . . . . . . . . . . . . . 2-13 Differential current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13 Differential voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13 Single-ended current. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13 Single-ended voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13 1756-OF6CI Wiring examples . . . . . . . . . . . . . . . . . . . . . . . 2-14 Current output with output loads of 0-550 ohms . . . . . . . 2-14 Current output with output loads of 551-1000 ohms . . . . 2-14 1756-OF6VI Wiring example . . . . . . . . . . . . . . . . . . . . . . . . 2-15 1756-OF4 Wiring examples . . . . . . . . . . . . . . . . . . . . . . . . 2-16 Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16 1756-OF8 Wiring examples . . . . . . . . . . . . . . . . . . . . . . . . 2-17 Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17 Chapter Summary and Whats Next . . . . . . . . . . . . . . . . . . . . . . 2-18
Chapter 3 What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Configuring the Input Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Configuring the Thermocouple Module . . . . . . . . . . . . . . . . . . . . 3-1 Interface Module (IFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 Cold Junction (CJ) Disable . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Cold Junction (CJ) Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Temperature Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Real Time Sampling (RTS) . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 Target to Originator Real Packet Interval (TtoO RPI). . . . . . . . . 3-2 Producer Connection Point (CP) . . . . . . . . . . . . . . . . . . . . . . . 3-3
iii
Configuring Thermocouple Input Channels . . . . . . . . . . . . . . . . . 3-4 Alarm Disable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Process Alarm Latch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Rate Alarm Latch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 Input Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 Sensor Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 Notch Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 Digital Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 Rate Alarm Trigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 Low Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 Configuring the RTD Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 Temperature Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 Real Time Sampling (RTS) . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 Target to Originator Real Packet Interval (TtoO RPI) . . . . . . . . 3-7 Producer Connection Point (CP) . . . . . . . . . . . . . . . . . . . . . . . 3-7 Configuring the Voltage/Current Input Modules . . . . . . . . . . . . . . 3-7 Real Time Sampling (RTS) . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 Target to Originator Real Packet Interval (TtoO RPI) . . . . . . . . 3-8 Producer Connection Point (CP) . . . . . . . . . . . . . . . . . . . . . . . 3-9 Configuring the Output Module . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 Configuring Voltage/ Current Output Modules . . . . . . . . . . . . . . 3-10 Idle to Fault Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 Target to Originator Real Packet Interval (TtoO RPI) . . . . . . . 3-10 Producer Connection Point (CP) . . . . . . . . . . . . . . . . . . . . . . 3-11
Chapter 4 What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 Calibrating Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 Calibrate Inputs Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 Input Calibration Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3 Calibrating Channels in Multiple Ranges. . . . . . . . . . . . . . . . . 4-3 Accept Input Low Calibration Service . . . . . . . . . . . . . . . . . . . 4-4 Accept Input High Calibration Service . . . . . . . . . . . . . . . . . . . 4-5 Abort Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6 Calibrating Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7 Calibrate Outputs Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8 Generate Output Low Reference Calibration Service . . . . . . . . 4-9 Generate Output High Reference Calibration Service. . . . . . . 4-10 Calibration Output Finish Service . . . . . . . . . . . . . . . . . . . . . 4-11 Abort Calibration Service . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12 Unlatching Status Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13 Using Device Object Services . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14 Set Attributes All Indirect. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
iv
Get Attributes All Indirect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16 Chapter Summary and Whats Next . . . . . . . . . . . . . . . . . . . . . . 4-16
Troubleshooting
Chapter 5 Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 Using Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 LED indicators for input modules. . . . . . . . . . . . . . . . . . . . 5-1 LED indicators for output modules. . . . . . . . . . . . . . . . . . . 5-2 Chapter Summary and Whats Next . . . . . . . . . . . . . . . . . . . . . . . 5-2 Appendix A 1756-IF6I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2 1756-IF8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3 1756-IF16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4 1756-IR6I. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5 1756-IT6I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6 1756-OF6CI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7 1756-OF6VI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8 1756-OF4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9 1756-OF8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
Specifications
Chapter
What is ControlLogix Analog I/O?
What this Chapter Contains
This chapter describes the ControlLogix analog modules and what you must know and do before you begin to use them. The following table describes what this chapter contains and its location.
For information about Compliance to European Union Directives Preventing electrostatic discharge Removal and insertion under power Using an I/O Module in the ControlLogix System Using Features of ControlLogix Analog I/O Modules Using Features Specific to Input Modules Using Features Specific to Output Modules Chapter Summary and Whats Next See page 1-1 1-2 1-2 1-3 1-5 1-7 1-8 1-9
If this product bears the CE marking, it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: EN 50081-2EMC - Generic Emission Standard, Part 2 - Industrial Environment EN 50082-2EMC - Generic Immunity Standard, Part 2 - Industrial Environment This product is intended for use in an industrial environment.
1-2
ControlLogix analog modules are sensitive to electrostatic discharge. ATTENTION: Electrostatic discharge can damage integrated circuits or semiconductors if you touch backplane connector pins. Follow these guidelines when you handle the module:
Touch a grounded object to discharge static potential Wear an approved wrist-strap grounding device Do not touch the backplane connector or
connector pins Do not touch circuit components inside the module If available, use a static-safe work station When not in use, keep the module in its static-shield bag
This module is designed to be installed or removed while chassis power is applied. ATTENTION: When you insert or remove a module while backplane power is on, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
1-3
ControlLogix analog I/O modules translate analog signals to, or from, the digital domain allowing for industrial control systems to operate on analog inputs or outputs to perform control applications. Practically speaking, an analog I/O module translates an analog signal level into, or from, a corresponding discrete representation which controllers can easily operate on for control purposes. A ControlLogix I/O module mounts in a ControlLogix chassis and uses a Removable Terminal Block (RTB) or Interface Module (IFM) to connect all field-side wiring. Before you install and use your module you should have already:
ControlLogix analog modules are compatible with ___ programmable controllers, and the SLC 5/02 modular controllers. Refer to the table below for information on using ControlLogix I/O with various Allen-Bradley programmable controllers.
1-4
Connectors pins - Input/output, power and grounding connections are made to the module through these pins by a Removable Terminal Block (RTB), see page X, or an Interface Module (IFM), see page X. Status indicators - Indicators display the status of communication and input/output. Use these indicators to help in troubleshooting. Top and bottom guides - Guides provide assistance in seating the RTB or IFM onto the module. Locking tab - The locking tab anchors the RTB or IFM on the module, maintaining wiring connections. Backplane controlbus - This backplane connector interface for the ControlLogix system connects the module to the chassis.
1-5
The following features are available on both input and output analog modules.
Scaling
The ControlLogix analog module scales analog values in different terms depending on the data types being used to interface with the module. You must choose one of the following types of scaling:
1-6
1-7
The following features are available only with analog input modules. Most features are only available in floating point mode.
Process Alarms
Process alarms are set at four user configurable alarm trigger points:
LowAlarmTrigger LowLowAlarmTrigger HighAlarmTrigger HighHighAlarmTrigger Each process alarm can be monitored in ladder logic for abnormal behavior. How should we show this? Here or somewhere with a set of other ladder logic as well? You may configure an Alarm Deadband to work with these process alarms. The deadband allows the process alarm status bit to remain set, despite the alarm condition disappearing, as long as the input data remains within the deadband and the process alarm.
1-8
Thermocouple Linearization Thermocouple modules measure a millivolt input signal and linearize it into a temperature value; the value is expressed in oC or oF based on the selected module Temperature Mode. Note: The junction of field wires with the terminations of an RTB generates a small voltage. This thermoelectric effect alters the input signal. To accurately measure the input signal, you must use a cold junction sensor (CJS) to account for the increased voltage. See Chapter 2 for information about how to mount a CJS to your module. If you use an IFM to connect wiring to your thermocouple module, you do not need to attach the CJS. The IFM compensates an additional voltage.
The following features are available only with analog output modules. Most features are only available in floating point mode.
Ramping
Ramping limits the speed at which an analog output signal can change. This prevents fast transitions in output from damaging the devices that an output controls. Ramping is possible in the following situations:
Run mode ramping - This ramping occurs during the normal run
mode and begins operation between the current output level and any new output value received. Ramp to idle mode - This ramping occurs when the current output value changes to the Idle Value after an Idle Command is received from the controller. Ramp to fault mode - This ramping occurs when the current output value changes to the Fault Value after a fault occurs.
Clamping
Clamping allows you to select the maximum range limits an output should ever reach in the control process. This is a safety feature.
1-9
Initial conection is established after power-up A new connection is established after a fault occurs There is a transition to Run mode from Idle state Fault and Idle Behavior
If you lose direct control of the outputs through a fault or the controller switching to idle mode, the outputs will transition to a safe state. Each output can be configured to hold last state or go to a specific value designated by the Fault State or Idle State bits.
using an I/O module in the ControlLogix system using features of analog I/O modules using features specific to input or output modules
Move on to Chapter 2 to learn how to install and wire your module.
1-10
Chapter
Installing the ControlLogix I/O Module
What this Chapter Contains
This chapter describes how to install ControlLogix modules, key the RTB or IFM, connect the input and output wiring to an RTB and IFM, and seat an RTB or IFM to the module. The following table describes what this chapter contains and its location.
For information about Installing the ControlLogix I/O Module Keying the Removable Terminal Block and the Interface Module Connecting Wiring Assembling the Removable Terminal Block and the Housing Installing the Removable Terminal Block or Interface Module onto the Module Checking the Indicators Removing the Removable Terminal Block from the Module Removing the Module from the Chassis Chapter Summary and Whats Next See page 2-1 2-2 2-3 2-5 2-6 2-7 2-8 2-8 2-18
You can install or remove the module while chassis power is applied. ATTENTION: The module is designed to support Removal and Insertion Under Power (RIUP). However, when you remove or insert an RTB with field-side power applied, unintended machine motion or loss of process control can occur. Exercise extreme caution when using this feature.
!
(INSERT ART)
2-2
Key the RTB or IFM in order to prevent inadvertantly making the wrong wire connections to your module. Use a unique keying pattern for each module.
2-3
Connecting Wiring
You can use an RTB or IFM to connect wiring to you module. If you are using an RTB, follow the directions below to conect wires to the RTB. An IFM has been prewired before you received it. If you are using an IFM to connect wiring to the module, skip this section and move to Chapter 4. For all ControlLogix analog modules, except the 1756-IR6I, we recommend using Belden 8761 cable to wire the RTB. For the 1756-IR6I module, we recommend using Belden 9533 or 83503 cable to wire the RTB. The RTB terminations can accomodate 14-22 gauge shielded wire. Before wiring the RTB, you must connect ground wiring. Connect grounded end of the cable 1. Ground the drain wire. Important: We recommend grounding the drain wire at the field-side. If you cannot ground at the field-side, ground at an earth ground on the chassis as shown below.
(INSERT ART)
2. Connect the insulated wires to the field-side. Connect ungrounded end of the cable 1. Cut the foil shield and drain wire back to the cable casing and apply shrink wrap. 2. Connect the insulated wires to the RTB (see next page).
2-4
Refer to the table below for the Figure and page number of the specific wiring diagram for each ControlLogix I/O module.
Catalog Number 1756-IF6I 1756-IR6I 1756-IT6I Wiring Connections Page 2-9 Page 2-10 Page 2-11 Catalog Number 1756-IF8 1756-IF16 1756-OF6CI Wiring Connections Page 2-12 Page 2-13 Page 2-14 Catalog Number 1756-OF6VI 1756-OF4 1756-OF8 Wiring Connections Page 2-15 Page 2-16 Page 2-17
2-5
Housing covers the wired RTB to protect wiring connections when the RTB is seated on the module.
2-6
Installing the Removable Terminal Block or Interface Module onto the Module
Install the RTB or IFM onto the module to connect wiring. ATTENTION: Shock hazard exists. If the RTB is installed onto the module while the field-side power is applied, the RTB will be electrically live. Do not touch the RTBs terminals. Failure to observe this caution may cause personal injury. The RTB is designed to support Removal and Insertion Under Power (RIUP). However, when you remove or insert an RTB with field-side power applied, unintended machine motion or loss of process control can occur. Exercise extreme caution when using this feature. It is recommended that field-side power be removed before installing the RTB onto the module.
Before installing the RTB, make certain: field-side wiring of the RTB has been completed. the RTB housing is snapped into place on the RTB. the RTB housing door is closed. the locking tab at the top of the module is unlocked.
(INSERT ART)
2-7
The indicators show CAL status (green) and a bi-colored LED for module OK (red/green) During power up, an indicator test is done. The OK indicator turns red for 1 second and then turns to flashing green if it has passed the self-test. LED indicators for input modules.
LED indicators OK This display: Steady green light Means: The inputs are being multicast and in normal operating state. The module has passed internal diagnostics but has not established communication. Previously established communication has timed out. The module must be replaced. The module is in calibration mode.
OK OK OK CAL
Flashing green light Flashing red light Steady red light Flashing green light
This display: Flashing green light Steady green light Flashing red light Steady red light Flashing green light
Means: The module has passed internal diagnostics but has not established communication. The outputs are in a normal operating state. Previously established communication has timed out. The module must be replaced. The module is in calibration mode.
2-8
If you need to remove the module from the chassis, you must first remove the RTB from the module. ATTENTION: Shock hazard exists. If the RTB is removed from the module while the field-side power is applied, the module will be electrically live. Do not touch the RTBs terminals. Failure to observe this caution may cause personal injury. The RTB is designed to support Removal and Insertion Under Power (RIUP). However, when you remove or insert an RTB with field-side power applied, unintended machine motion or loss of process control can occur. Exercise extreme caution when using this feature. It is recommended that field-side power be removed before removing the module.
(INSERT ART)
2-9
Current input
(INSERT ART)
2-10
2-11
2-12
Differential voltage
(INSERT ART)
Single-ended current
(INSERT ART)
Single-ended voltage
(INSERT ART)
2-13
Differential voltage
(INSERT ART)
Single-ended current
(INSERT ART)
Single-ended voltage
(INSERT ART)
2-14
2-15
2-16
Voltage
(INSERT ART)
2-17
Voltage
(INSERT ART)
2-18
installing the module keying the module wiring the RTB installing the RTB or IFM onto the module removing the module Move on to Chapter 3 to understand how to program your module.
Chapter
Configuring the ControlLogix Analog I/O Module
What this Chapter Contains
This chapter describes how to configure ControlLogix analog modules. The following table describes what this chapter contains and its location.
For information about See page
Because of the many analog devices available and the wide variety of possible configurations, you must configure both your I/O module and the channels of each module. You may choose to use the default configuration for your module and channels rather than write configuration that is specific to your application. This chapter is designed to explain how to configure your modules and channels, with the explanations broken up for input and output modules. At the beginning of each new section there is a chart providing default values for each configurable point.
The thermocouple module (Cat. No. 1756-IT6I), due its temperature sensitivity, has more configurable points than any other ControlLogix analog module. The following table displays the module default values for the thermocouple module.
Configurable Feature Iterface Module Cold Junction Disable Cold Junction Offset Temperature Mode Real Time Sampling Target to Originator Real Packet Interval Producer Connection Point Module Default 0 0 0.00 0 100 100,000 0xA0
3-2
If you are using an IFM to connect wiring to the module, you must account for the IFM in configuration. Use the configuration screen on page 3- to set this feature.
Temperature Mode
A thermocouple module can measure temperature in Fahrenheit or Celsius degrees. Use the Temperature Mode to designate a temperature value. Use the configuration screen on page 3- to set the temperature mode.
3-3
3-4
Configuration defaults exist for thermocouple input channels just as defaults do for module-wide configurable features. The following table displays the channel default values for the thermocouple module.
Configurable Feature Alarm Disable Process Alarm Latch Rate Alarm Latch Input Range Sensor Type Notch Filter Digital Filter Rate Alarm Trigger Low Signal High Signal Low Engineering High Engineering Low Alarm Trigger High Alarm Trigger Low Low Alarm Trigger High High Alarm Trigger Alarm Deadband Calibration Bias Channel Default 0 0 0 4 0 2 0 0.00% -10.00 78.00 -12.00 78.00 -12.00 78.00 -12.00 78.00 0.00 0.00
Alarm Disable
The Alarm Disable feature disables all alarms for a channel. Use the configuration screen on page 3- to turn off all alarms.
3-5
Input Range
The Input Range feature selects the minimum and maximum signals that are detectable on a specific channel. Use the configuration screen on page 3- to determine the Input Range.
Sensor Type
The Thermocouple module allows you to configure a Sensor Type that linearizes the analog signal into a temperature value. Thermocouple modules support nine sensor types: B,C, E, J, K, N, R, S, & T. Each sensor type may be configured for specific high and low values of signals that are linearized. The following chart displays the default high and low values for each sensor.
Sensor Type Low Signal High Signal B 250.0 1820.0 0.0 2315.0 C E -270.0 1000.0 J -210.0 1200.0 K -270.0 1372.0 N -270.0 1300.0 R -50.0 1768.1 S -50.0 1768.1 T -270.0 400.0
Note:
The low and high default values for channel alarms are the same on each sensor as the low and high default values for input signals.
Use the configuration screen on page 3- to choose a Sensor Type and its configuration.
Notch Filter
The Notch Filter removes occurrences of the selected frequency and tis octaves in the input signal. This feature filters out line noise. Use the configuration screen on page 3- to configure the Notch Filter. What the heck is this all about?
3-6
Digital Filter
The Digital Filter adjusts firmware delays and provides smooth input transitions. Use the configuration screen on page 3- to adjust your digital filter times.
Low Signal
What is this? The lowest signal at which inputs may be sent to the module and still have communication? Something to do with rates?
The following table displays the module default values for the RTD module.
Configurable Feature Temperature Mode Real Time Sampling Target to Originator Real Packet Interval Producer Connection Point Module Default 0 100 100,000 0xA0
Temperature Mode
A thermocouple module can measure temperature in Fahrenheit or Celsius degrees. Use the Temperature Mode to designate a temperature value. Use the configuration screen on page 3- to set the temperature mode.
3-7
The following ControlLogix analog voltage/current input modules share configurable features and use the same configuration information:
3-8
Configurable Feature Real Time Sampling Target to Originator Real Packet Interval Producer Connection Point
3-9
3-10
Configuration of output modules mirrors that of input modules in the fact that you can configure the module and specific channels on each module. Use the following information to configure your output module. The following ControlLogix analog voltage/current input modules share configurable features and use the same configuration information:
3-11
3-12
Chapter
Calibrating the ControlLogix Analog I/O Module
What this Chapter Contains
This chapter describes how to configure ControlLogix analog modules. The following table describes what this chapter contains and its location.
For information about Calibrating input modules Calibrating output modules Unlatching status Getting all attributes Sending all attributes Chapter summary and whats next See page
Input calibration is a mult-step process that involves multiple services being sent to the module. The following text and flow chart describe the process itself. A more detailed description of each step follows the flow chart. The Calibrate Inputs service switches the module into a calibrating mode. This initiates input calibration and faults all module points if a real-time connection is currently open. Input channels have specific calibration points, low and high, which you must input to the module. Some modules support calibration in multiple ranges. You have a choice of services that sample specified channels for the input module. Send for a sample using one of the following:
4-2
This flow chart provides a brief overview of the input calibration process.
4-3
4-4
4-5
4-6
Abort Calibration
This service transitions the module out of the calibration state and returns it to the operating state prior to beginning Calibrating Inputs. This service also sets the Bad Calibration status for any channel which had a calibration error at the time of the abort. Use the following screen to trigger Abort Calibration.
(INSERT ART)
4-7
Output calibration is a mult-step process that involves multiple services being sent to the module. The following text and flow chart describe the process itself. A more detailed description of each step follows the flow chart. The Calibrate Outputs service switches the module into a calibrating mode. This initiates output calibration and faults all module points if a real-time connection is currently open. Output channels output at specific reference points, low and high, which you must set to the module. You have a choice of services that set reference points for the output module. Set your reference point using one of the following:
4-8
This flow chart provides a brief overview of the output calibration process.
(INSERT ART)
4-9
4-10
4-11
4-12
4-13
The Unlatch Status service can be directed to either the Analog Input Point or Analog Output Point Object to unlatch latched status bits. Alarms can be unlatched for a single point at a time, either a single alarm at a time or all latchable alarms on the channel simultaneously. When an alarm is unlatched, it is clear and can be recalculated. If the alarm condition no longer exists, the alarm will clear. But if the alarm is still active, it will remain set and never clear despite the unlatching. Use the following screen to unlatch status bits.
(INSERT ART)
4-14
ControlLogix analog I/O modules support the following two services to the Device Object:
4-15
This service is used to send data to the module. Once a connection has been established, use this service to send one of the following three types of configuration information to the module:
4-16
This service retrieves module data. You can obtain two different types of information. Use this service to get one of the following:
Chapter
Troubleshooting
Chapter Objectives
In this chapter you will learn about the indicators on the ControlLogix analog I/O module, and how to use them to troubleshoot the module. Each ControlLogix analog I/O module has indicators which provide indication of module status. ControlLogix modules use the following: LED indicators for input modules.
LED indicators OK This display: Steady green light Means: The inputs are being multicast and in normal operating state. The module has passed internal diagnostics but has not established communication. The outputs are in a normal operating state. Previously established communication has timed out. The module must be replaced. The module is in calibration mode.
Using Indicators
OK OK OK OK CAL
(INSERT ART)
Flashing green light Steady green light Flashing red light Steady red light Flashing green light
5-2
Troubleshooting
OK OK OK OK CAL
(INSERT ART)
Flashing green light Steady green light Flashing red light Steady red light Flashing green light
Appendix
Specifications
For Specifications for: 1756-IF6I 1756-IF8 1756-IF16 1756-IR6I 1756-IT6I 1756-OF6CI 1756-OF6VI 1756-OF4 1756-OF8 Refer to: Page A-2 Page A-3 Page A-4 Page A-5 Page A-6 Page A-7 Page A-8 Page A-9 Page A-10
A-2
Specifications
1756-IF6I Specifications
Module Location Resolution +/-10.5V range 0 to 10.5V range 0 to 5.25V range 0-21mA range Input Impedance Open Circuit Detection Time Normal Mode Noise Rejection Common Mode Noise Rejection Channel Bandwidth Settling Time to 5% of Full Scale Calibrated Accuracy at 25oC Module Scan Time for all Channels Overvoltage Capability Input Offset Drift with Temperature Number of Inputs Input Range Gain Drift with Temperature Backplane Current Module Conversion Method Thermal Dissipation Power Dissipation Module Non-linearity Module Repeatability Effect of Incorrect Terminal Connection Module Error over Full Temp. Range Module Temporary Deviation Inductive Load Capacitive Load Isolation Voltage Channel to channel User to system Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Conductors Wire Size 100% tested at 2715V dc for 1s 100% tested at 2715V dc for 1s 0 to 60 oC (32 to 140oF) -40 to 85oC (-40 to 185 oF) 5 to 95% noncondensing 14 gauge (2mm2) stranded maximum 1 22 gauge (0.456mm2) stranded minimum 3/64 inch (1.2mm) insulation maximum 22, 3 5 inch-pounds (0.5Nm) maximum Electronic User defined 20 Position RTB (1756-TBNH or TBSH) 1 1/8 inch (3.2mm) maximum 1756 ControlLogix Chassis Approximately 16 bits across each range shown below 343V/bit 171V/bit 86V/bit 0.34A/bit >10M Voltage, 249 Current Upscale reading within 5s >60dB at 60Hz 120dB at 60Hz, 100dB at 50Hz 0 to 15Hz (-3dB) <80ms Better than 0.1% of range <25ms floating point <10ms integer 120V AC/DC continuous at room temperature Voltage 8V AC/DC with on-board current resistor 2V/degree C typical 6 individually isolated channels +/-10.5V, 0-10.5V, 0-5.25V, 0-21mA 35 ppm/degree C typical Voltage 45 ppm/degree C typical Current 250mA @5V dc & 125mA @ 24V dc
Category RTB Screw Torque (Cage clamp) Module Keying RTB Keying Field Wiring Arm and Housing Screwdriver Width for RTB
Specifications
A-3
1756-IF8 Specifications
Module Location Resolution Voltage Current Input impedance Voltage Current Open circuit detection time Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time to 5% of full scale Calibrated accuracy at 25oC Module scan time for all channels Overvoltage capability Input offset drift with temperature Number of Inputs Input voltage range Gain drift with temperature Isolation Voltage Channel to channel User to system Backplane Current Module Conversion Method Thermal Dissipation Power Dissipation Module Non-linearity Module Repeatability Effect of Incorrect Terminal Connection Module Error over Full Temp. Range Module Temporary Deviation Inductive Load Capacitive Load Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Conductors Wire Size Category RTB Screw Torque (Cage clamp) Module Keying RTB Keying Field Wiring Arm and Housing Screwdriver Width for RTB 0 to 60 oC (32 to 140oF) -40 to 85oC (-40 to 185 oF) 5 to 95% noncondensing 14 gauge (2mm2) stranded maximum 1 3/64 inch (1.2mm) insulation maximum 12, 3 5 inch-pounds (0.5Nm) maximum Electronic User defined 20 Position RTB (1756-TBNH or TBSH) 1 1/8 inch (3.2mm) maximum +/-2% +/-2LSB <~0.006%> 1/2 hour +/-4LSB <~0.012%> at minimum filter Sigma-delta ADC 1756 ControlLogix Chassis 15 bits plus sign bipolar (16 bits) 320.435V/cnt 640.869A/cnt >10MHz <20 <20 Upscale reading within 5s >60dB at 60Hz 120dB at 60Hz, 100dB at 50Hz 0 to 15Hz (-3dB) <80ms Better than 0.1% of range <25ms 120V AC/DC continuous at room termperature 2V/degree C typical 16 single ended or 8 differential +/-10.5V maximum 35 ppm/degree C typical 100% tested at 2546V dc for 1s 100% tested at 2546V dc for 1s
A-4
Specifications
1756-IF16 Specifications
Module Location Resolution Voltage Current Input impedance Voltage Current Open circuit detection time Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time to 5% of full scale Calibrated accuracy at 25oC Module scan time for all channels Overvoltage capability Input offset drift with temperature Number of Inputs Input voltage range Gain drift with temperature Isolation Voltage Channel to channel User to system Backplane Current Module Conversion Method Thermal Dissipation Power Dissipation Module Non-linearity Module Repeatability Effect of Incorrect Terminal Connection Module Error over Full Temp. Range Module Temporary Deviation Inductive Load Capacitive Load Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Conductors Wire Size Category RTB Screw Torque (Cage clamp) Module Keying RTB Keying Field Wiring Arm and Housing Screwdriver Width for RTB 0 to 60 oC (32 to 140oF) -40 to 85oC (-40 to 185 oF) 5 to 95% noncondensing 14 gauge (2mm2) stranded maximum 1 3/64 inch (1.2mm) insulation maximum 12, 3 5 inch-pounds (0.5Nm) maximum Electronic User defined 36 Position RTB (1756-TBCH or TBS6H)1 1/8 inch (3.2mm) maximum +/-2% +/-2LSB <~0.006%> 1/2 hour +/-4LSB <~0.012%> at minimum filter Sigma-delta ADC 1756 ControlLogix Chassis 15 bits plus sign bipolar (16 bits) 320.435V/cnt 640.869A/cnt >20k 249 Upscale reading within 5s >80dB at 60Hz 120dB at 60Hz, 100dB at 50Hz 0 to 200Hz (-3dB) *See user manual 4ms *See user manual Better than 0.1% of range <35ms *See user manual 30V AC/DC continuous at room termperature 2V/degree C typical 16 single ended or 8 differential +/-10.5V maximum 35 ppm/degree C typical Not isolated 100% tested at 2500V dc for 1s
Specifications
A-5
1756-IR6I Specifications
Module Location Sensors Supported 1756 ControlLogix Chassis Resistance 4-4020 100, 200, 500, 1000 Platinum, alpha=385 100, 200, 500, 1000 Platinum, alpha=3916 120 Nickel, alpha=672 100, 120, 200, 500 Nickel, alpha=618 10 Copper Approximately 16 bits across each input range 7.7m/bit, 15m/bit, 30m/bit, 60m/bit 0.1% of full scale at 25oC Out of range reading reported <5s 120dB at 60Hz, 100db at 50Hz 60dB at 60Hz DC to 15Hz (-3dB) <80ms <25ms floating point <10ms integer 6 isolated channels 4-487, 4-1000, 4-2000, 4-4020 24V AC/DC continuous at room temperature 10m/degree C 50 ppm/degree C typical 250mA @ 5V dc & 150mA @ 24V dc 100% tested at 2715V dc for 1s 100% tested at 2715V dc for 1s 0 to 60 oC (32 to 140oF) -40 to 85oC (-40 to 185 oF) 5 to 95% noncondensing 14 gauge (2mm2) stranded maximum 1 22 gauge (0.456mm2) stranded minimum 3/64 inch (1.2mm) insulation maximum 22, 3 5 inch-pounds (0.5Nm) maximum Electronic User defined 20 Position RTB (1756-TBNH or TBSH) 1 1/8 inch (3.2mm) maximum
Resolution in Ranges 487, 1000 2000, 4020 Accuracy Open Wire Detection Open Wire Detection Time Common Mode Noise Rejection Normal Mode Noise Rejection Channel Bandwidth Settling Time to 5% of Range Module Scan Time for all Channels Number of Inputs Signal Input Range Overvoltage Capability Input Offset Drift with Temperature Gain Drift with Temperature Backplane Current Isolation Voltage Channel to channel User to system Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Conductors Wire Size
Category RTB Screw Torque (Cage clamp) Module Keying RTB Keying Field Wiring Arm and Housing Screwdriver Width for RTB
A-6
Specifications
1756-IT6I Specifications
Module Location Supported Thermocouple Types Resolution Accuracy @ 25oC (-12 to +78mV Range) (-12 to +30mV Range) Accuracy (Cold Junction Sensor) Local CJ Sensor Uncertainty Remote CJ Sensor Open Circuit Detection Open TC Detection Time Normal Mode Noise Rejection Common Mode Noise Rejection Channel Bandwidth Settling Time to 5% of Full Scale Calibrated Accuracy at 25oC Overvoltage Capability Input Offset Drift with Temperature Gain Drift with Temperature Backplane Current Number of Inputs Input Voltage Ranges Module Scan Time for all Channels Isolation Voltage Channel to channel User to system Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Conductors Wire Size 1756 ControlLogix Chassis B, E, J, K, R, S, T, N, C 16 bits (1.4V typical) 0.7V/bit on high resolution range 0.1% FSR (+/-90V) @ 25oC 0.1% FSR (+/-42V) @ 25oC
From +/-0.3 up to +/-3.2oC, depending on channel +/-0.3oC Upscale reading 5s typical 60dB at 60Hz 120dB at 60Hz, 100dB at 50Hz 0 to 15Hz (-3dB) <80ms Better than 0.1% of range 120V AC/DC continuous at room temperature 0.5V/degree C typical 65 ppm/degree C typical 250mA @ 5V dc & 125mA @ 24V dc 6 individually isolated channels -12mV to +78mV -12mV to +30mV (high resolution range) <25ms floating point <10ms integer 100% tested at 2715V dc for 1s 100% tested at 2715V dc for 1s 0 to 60 oC (32 to 140oF) -40 to 85oC (-40 to 185 oF) 5 to 95% noncondensing 14 gauge (2mm2) stranded maximum 1 22 gauge (0.456mm2) stranded minimum 3/64 inch (1.2mm) insulation maximum 22, 3 5 inch-pounds (0.5Nm) maximum Electronic User defined 20 Position RTB (1756-TBNH or TBSH) 1 1/8 inch (3.2mm) maximum
Category RTB Screw Torque (Cage clamp) Module Keying RTB Keying Field Wiring Arm and Housing Screwdriver Width for RTB
Specifications
A-7
1756-OF6CI Specifications
Module Location Current Resolution Open Circuit Detection Output Overvoltage Protection Output Short Circuit Protection Drive Capability Output Settling Time Calibrated Accuracy at 25oC Module Scan Time for all Channels Input Offset Drift with Temperature Number of Outputs Output Current Range Gain Drift with Temperature Backplane Current Isolation Voltage Channel to channel User to system Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Conductors Wire Size 1756 ControlLogix Chassis 13 bits across 21mA (2.7A) None 24V AC/DC continuous at room temperature Electronically current limited to 21mA or less 20mA maximum into loads of 500 or less. Loads of 1000 or less may be achieved with alternate field terminations. <2ms to 95% of final value with resistive loads Better than 0.1% of range from 4mA to 21mA <25ms floating <10ms integer 1 A/degree C typical 6 individually isolated channels 0 to 21mA 60 ppm/degree C typical 250mA @ 5V dc & 300mA @ 24V dc 100% tested at 2715V dc for 1s 100% tested at 2715V dc for 1s 0 to 60 oC (32 to 140oF) -40 to 85oC (-40 to 185 oF) 5 to 95% noncondensing 14 gauge (2mm2) stranded maximum 1 22 gauge (0.456mm2) stranded minimum 3/64 inch (1.2mm) insulation maximum 22, 3 5 inch-pounds (0.5Nm) maximum Electronic User defined 20 Position RTB (1756-TBNH or TBSH) 1 1/8 inch (3.2mm) maximum
Category RTB Screw Torque (Cage clamp) Module Keying RTB Keying Field Wiring Arm and Housing Screwdriver Width for RTB
A-8
Specifications
1756-OF6VI Specifications
Module Location Voltage Resolution Output Impedance Open Circuit Detection Time Output Overvoltage Protection Output Short Circuit Protection Output Settling Time Calibrated Accuracy at 25oC Module Scan Time for all Channels Output Offset Drift with Temperature Gain Drift with Temperature Number of Outputs Output Voltage Range Backplane Current Isolation Voltage Channel to channel User to system Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Conductors Wire Size 1756 ControlLogix Chassis 14 bits across 21V (1.3mV) (13 bits across 10.5V +sign bit) <1 None 24V AC/DC continuous at room temperature Continuous with electronic current limiting <2ms to 95% of final value with resistive loads Better than 0.1% of range <25ms floating point <10ms integer 60 V/degree C typical 50 ppm/degree C typical 6 individually isolated channels +/- 10.5V maximum 250mA @ 5V dc & 175mA @ 24V dc 100% tested at 2715V dc for 1s 100% tested at 2715V dc for 1s 0 to 60 oC (32 to 140oF) -40 to 85oC (-40 to 185 oF) 5 to 95% noncondensing 14 gauge (2mm2) stranded maximum 1 22 gauge (0.456mm2) stranded minimum 3/64 inch (1.2mm) insulation maximum 22, 3 5 inch-pounds (0.5Nm) maximum Electronic User defined 20 Position RTB (1756-TBNH or TBSH) 1 1/8 inch (3.2mm) maximum
Category RTB Screw Torque (Cage clamp) Module Keying RTB Keying Field Wiring Arm and Housing Screwdriver Width for RTB
Specifications
A-9
1756-OF4 Specifications
Module Location Voltage Resolution Output Impedance Open Circuit Detection Time Output Overvoltage Protection Output Short Circuit Protection Output Settling Time Calibrated Accuracy at 25oC Module Scan Time for all Channels Output Offset Drift with Temperature Gain Drift with Temperature Backplane Current Number of Outputs Output Voltage Range Isolation Voltage Channel to channel User to system Module Conversion Method Thermal Dissipation Power Dissipation Module Non-linearity Module Repeatability Module Ripple Effect of Incorrect Terminal Connection Module Error over Full Temp. Range Module Temporary Deviation Inductive Load Capacitive Load Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Conductors Wire Size 0 to 60 oC (32 to 140oF) -40 to 85oC (-40 to 185 oF) 5 to 95% noncondensing 14 gauge (2mm2) stranded maximum 1 22 gauge (0.456mm2) stranded minimum 3/64 inch (1.2mm) insulation maximum 22, 3 5 inch-pounds (0.5Nm) maximum Electronic User defined 20 Position RTB (1756-TBNH or TBSH) 1 1/8 inch (3.2mm) maximum 5.5W maximum +/-2LSB <~0.006%> 1/2 hour SAM 30V ac/dc on voltage 8V ac/dc on current +/-4LSB <~0.012%> at minimum filter 1756 ControlLogix Chassis 16 bits across 21V (320V) (15 bits across 10.5V +sign bit) <1 Not provided voltage, 1s current 24V AC/DC continuous at room temperature Continuous with electronic current limiting <2ms to 95% of final value with resistive loads Better than 0.1% of range <25ms floating point <10ms integer 65 V/degree C typical 50 ppm/degree C typical 250mA @ 5V dc & 175mA @ 24V dc 6 individually isolated channels +/- 10.5V maximum 100% tested at 2150V dc for 1s 100% tested at 2150V dc for 1s R-Ladder DAC Sample/Hold
Category RTB Screw Torque (Cage clamp) Module Keying RTB Keying Field Wiring Arm and Housing Screwdriver Width for RTB
A-10
Specifications
1756-OF8 Specifications
Module Location Voltage Resolution Output Impedance Open Circuit Detection Time Output Overvoltage Protection Output Short Circuit Protection Output Settling Time Calibrated Accuracy at 25oC Module Scan Time for all Channels Output Offset Drift with Temperature Gain Drift with Temperature Backplane Current Number of Outputs Output Voltage Range Isolation Voltage Channel to channel User to system Module Conversion Method Thermal Dissipation Power Dissipation Module Non-linearity Module Repeatability Module Ripple Effect of Incorrect Terminal Connection Module Error over Full Temp. Range Module Temporary Deviation Inductive Load Capacitive Load Environmental Conditions Operating Temperature Storage Temperature Relative Humidity Conductors Wire Size 0 to 60 oC (32 to 140oF) -40 to 85oC (-40 to 185 oF) 5 to 95% noncondensing 14 gauge (2mm2) stranded maximum 1 22 gauge (0.456mm2) stranded minimum 3/64 inch (1.2mm) insulation maximum 22, 3 5 inch-pounds (0.5Nm) maximum Electronic User defined 20 Position RTB (1756-TBNH or TBSH) 1 1/8 inch (3.2mm) maximum 5.5W maximum +/-2LSB <~0.006%> 1/2 hour SAM 30V ac/dc on voltage 8V ac/dc on current +/-4LSB <~0.012%> at minimum filter 1756 ControlLogix Chassis 16 bits across 21V (320V) (15 bits across 10.5V +sign bit) <1 Not provided voltage, 1s current 24V AC/DC continuous at room temperature Continuous with electronic current limiting <2ms to 95% of final value with resistive loads Better than 0.1% of range <25ms floating point <10ms integer 65 V/degree C typical 50 ppm/degree C typical 250mA @ 5V dc & 175mA @ 24V dc 6 individually isolated channels +/- 10.5V maximum 100% tested at 2150V dc for 1s 100% tested at 2150V dc for 1s R-Ladder DAC Sample/Hold
Category RTB Screw Torque (Cage clamp) Module Keying RTB Keying Field Wiring Arm and Housing Screwdriver Width for RTB
Index
T
Types of block I/O, 1-3
Index
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the worlds leading technology companies.
Worldwide representation.
Argentina Australia Austria Bahrain Belgium Brazil Bulgaria Canada Chile China, PRC Colombia Costa Rica Croatia Cyprus Czech Republic Denmark Ecuador Egypt El Salvador Finland France Germany Greece Guatemala Honduras Hong Kong Hungary Iceland India Indonesia Ireland Israel Italy Jamaica Japan Jordan Korea Kuwait Lebanon Malaysia Mexico Netherlands New Zealand Norway Pakistan Peru Philippines Poland Portugal Puerto Rico Qatar Romania Russia-CIS Saudi Arabia Singapore Slovakia Slovenia South Africa, Republic Spain Sweden Switzerland Taiwan Thailand Turkey United Arab Emirates United Kingdom United States Uruguay Venezuela Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
PN 955129-24
Copyright 1997 Allen-Bradley Company, Inc. Printed in USA