Heating or Cooling

2-Pipe Multi-System

3-Pipe Multi-System
Simultaneous Heating & Cooling

2-Pipe Super VRF


Heating or Cooling

KX-2 systems are used extensively in offices, hotels, retail stores, fitness clubs, restaurants, and many other commercial applications. The simple pipework configuration allows easy installation, and discreet concealment of refrigerant and condensate piping. With 2-pipe systems there are no refrigerant distribution boxes, as all connections are made using branch pipe kits. Cassette and ducted internal units have condensate lift pumps, to overcome problems of routing of drain piping, allowing installation in most locations, without the need for additional pump kits. The outdoor unit is compact, the height has been reduced to 1450mm, and the access for routine service and maintenance is from the front only, allowing a number of units to be installed side by side in confined spaces. Pipe connections to the outdoor unit can be made from the front, back, right or bottom. The newly developed 570mm diameter sickle bladed fan reduces the outdoor sound level to 59dB, and the increased air volume allows operation in ambient temperatures down to -15C.

R22 & R407C

Two-PipeSystems
KX2 2-Pipe systems are applied to open plan areas, retail stores, or cellular offices, which would require heating or cooling during the same operational periods, e.g. offices which are all located on the same side of the building.

FDC-KX 2-Pipe Outdoor Unit


Unit ref. Old ref. Max Max no. indoor connect units cap. index 8 13 16 182 292 364 Nom. Cooling KW 14.00 22.40 28.00 Heating Heat pump KW 16.00 25.00 31.50 Start current Max. run current 10.2A/ph 14.6A/ph 19.0A/ph MCB rating motor D rated 16A/ph 32A/ph 32A/ph Air Volume max m3/h 5400 10800 10800 Connection o.d. sizes liq. gas 3/8 3/4 1/2 11/8 1/2 11/8 Unit Dimensions mm H 1450 1450 1450 W 690 1350 1350 D 600 600 600 150 250 275 Weight KG

FDC140 FDC224 FDC280

125 200 250

5A/ph 48A/ph 70A/ph

FDC Internal Location With planning restrictions and space limitations, it is often necessary to install a VRF unit within an enclosure inside the building. The angled fan arrangement allows high performance, low noise fans to be accomodated within the reduced depth of the unit casing, as well as providing the possibility of air discharge through a short duct addition.

FDC140 14.0kw Connectable units: 8 max

FDC224 22.4kw Connectable units: 13 max FDC280 28.0kw Connectable units: 16 max

NEW
K-MAX Super VRF from 45kw-126kw Connectable units: 40 max

One

Three-PipeSystems
Flexible control with heating and cooling at any terminal unit simultaneously, with energy recovery between warm and cool areas. The KXR system provides the client with a fully flexible comfort control system, with all the benefits of energy efficiency and reduced running costs. It is ideal where there is mixed requirement for some areas to be cooled and others to be heated, e.g. north and south sides of a glass fronted building, or retail store, where concentrations of customers or lighting levels would dictate a combination of simultaneous cooling and heating. It can help with energy costs by utilising waste heat from office equipment in one area, and utilising this heat energy to provide heating in a cool area of the building. Generally, if there is no other form of heating in a building , the KXR 3-pipe system is more suitable than a 2-pipe system. It avoids conflict between the occupants as to which mode of operation, heating or cooling, takes priority. The Mitsubishi KXR offers different pipework distribution possibilities. All internal units are required to be connected to a refrigerant Distribution Controller, which enables the units to heat or cool. The KXR-system has both individual and combined Distribution Controllers, the latter allowing several internal units to be connected, each having independent control, but reducing the number of pipe joints required on site, resulting in lower installation costs.

R22 & R407C


Air Volume max m3/h 10800 10800 Connection o.d. sizes liq. gas 1/2 11/8 1/2 11/8 Unit Dimensions mm (excluding panel) H W D 1700 1700 1350 1350 600 600 Weight KG

FDC-KXR 3-Pipe Outdoor Unit


Unit ref. Old Max Max ref. no. indoor connect units cap. index 13 16 292 364 Nom. Cooling KW 22.40 28.00 Heating Heat pump KW 25.00 31.50 Start current Max. run current 15.0A/ph 21.0A/ph MCB rating motor D rated 32A/ph 32A/ph

FDC224KXR 200 FDC280KXR 250

5A/ph 5A/ph

340 361

NEW
FDC-16
KXR with Single Distribution Controllers
The maximum connectable number of internal units has now been increased to 16 (on 28KW model) and 13 (on 22.4KW model). This allows multiples of small internal units to be connected, ideal for small cellular offices or hotel rooms.

KXR with Single & 4-way Distribution Controllers

These new KXR models are compatible with the latest compact cassette/ducted internal unit, the FDTQ - see page 6 for details.

KXR with 4-way Distribution Controllers

NEW
FDC-P for R407C
This new outdoor unit completes the comprehensive range of VRF multi systems available from MITSUBISHI. All units are factory processed, fully tested, and Quality Assured at the Nagoya factory in Japan.

KXR-16 with Four 4-way Distribution Controllers all internal units capable of simultaneous cooling or heating

Two

2-Pipe Super-VRF
Modular System Combination

R22 & R407C


System Reference Nom. Cooling KW 44.80 50.00 56.00 67.20 72.80 78.40 84.00 89.60 95.20 100.80 106.40 112.00 Heating Heat Pump KW 50.00 56.50 63.00 75.00 81.50 88.00 94.50 100.00 106.50 113.00 119.50 126.00 FDC224DK INVERTER 1 1 1 1 1 1 1 1 1 1 1 1 K-MAX Outdoor Unit Combinations FDC280DK FDC225BKT FDC281BKT INVERTER CONSTANT CONSTANT 1 1 1 2 2 1 3 3 2 1 Max. no. indoor units 20 20 20 30 30 30 30 40 40 40 40 40 Connectable Capacity Index min. max. 224 250 280 336 364 392 420 448 476 504 532 560 583 650 728 824 974 1020 1092 1165 1238 1311 1384 1456

K-MAX 448 K-MAX 500 K-MAX 560 K-MAX 672 K-MAX 728 K-MAX 784 K-MAX 840 K-MAX 896 K-MAX 952 K-MAX 1008 K-MAX 1064 K-MAX 1120

1 2

1 2 3

K-MAX Super VRF Large VRF systems for commercial buildings.


The K-MAX 2-pipe systems provide cooling or heating (not simultaneously) for large buildings, e.g. offices, showrooms, conference centres, dealing rooms, large retail stores, etc. The system provides the client with cost savings compared to the installation of individual systems, as there is far less refrigerant pipework from the outdoor units to inside the building. There are no refrigerant distribution boxes involved, as all connections are made using low cost branch pipe kits. The outdoor units have a small footprint, and all service access is from the front only, which is an advantage if there is a restricted space for locating the units. This space saving can also save considerable costs if steel decking is required to support units on the roof of a building. Outdoor units can be separated, where space is restricted. The INVERTER units and CONSTANT speed (fixed speed compressors) are piped together on site by the installer. All controls are integral within the units; no additional control units are required. Selection of Indoor Units The maximum number of connected units is specified above. The capacity index represent the nominal cooling performance, i.e. index 225 equates to 22.5KW cooling. Generally the connected units capacity index must be between 50% and 130% of the combined K-MAX outdoor unit capacity for each system. Any combination of standard KX2 indoor units can be connected - cassettes, ducted, wall, etc. Refrigerant Both R22 & R407C systems are available. Installation It is essential that the pipework for these systems is installed by competant and experienced engineers. The cleanliness of the pipework is of paramount importance, with every precaution taken against leakage, the ingress of moisture, and the formation of copper oxide internally on brazed joints (dry nitrogen purge). Pipework Design 3D applications engineers will provide details of pipe sizes, once the layout of the internal units is specified. Full schematic diagrams will be produced to enable the installer to follow the pipe sizing requirements.

Three

System Controls Mitsubishi has combined simplicity of installation with


the most sophisticated fuzzy logic control system, offering the client many choices of control, monitoring, and management.

Control Wiring Simplified The polarity-free two wire control loop


is connected to the indoor units (maximum 48), and then extended to the relevant group of outdoor units. All units are given address numbers, which can now be set using the new RCD remote controller. This allows the outdoor units to recognise which indoor units are connected to the pipework systems, and to perform an automatic refrigerant connection checking sequence at the commissioning stage. Group Controls and Centralised Controls can be connected at any point of the two wire loop.

Remote Control

RCD

Remote control for internal units, either individually, or as a group (up to 16). Temperature display. Programmable timer - 24 hour. Fan speed selection. Filter maintenance indication. Integral sensor (can be used as alternative to unit inbuilt sensor)

Return air temperature display. Cool / Heat Auto selection. Error message display. Check function for service engineer. Can be used as Master or Slave remote control. Control options and displays can be disabled, to provide simplified controller.

SCA-WTE

Weekly Programmable Timer Control

7 day programmable timer Three on/off times can be set for each day, to one minute timing. Automatic turn off can be programmed. Set programme can easily be overidden for one day if required. Time/day display.

Programme is memorised and restored after power interruption. Programmes can be selected for 16 groups when used with SLA-2AE Maximum 48 units can be controlled. Can be positioned and wired at any point on the 2-wire fuzzy logic control loop.

SLA-1E

Group On/Off Control

Group operation on/off control, both Common fault indication of individual unit within Group. individual units, or complete group. Can be used with external time clock. Can be positioned and wired at any point on the 2-wire fuzzy logic Overides the individual unit Remote control loop. Controller on/off function. Power Source Kit with enclosure, for Can be used in conjunction with connection to mains power supply. SLA-2AE

SLA-2AE Centralised Control

Temperature, mode, and fan speed setting of individual units or Groups of units. Groups (up to 16) can be arranged in any combination of indoor units Heating/Cooling and Auto function included.

Error message code display and fault indication Can be used with external time clock for Group on/off control. Overides individual unit Remote Controller selection. Power Source Kit with enclosure, for connection to mains power supply.

Remote Control & Monitoring


Up to 8 indoor unit menus displayed at any time. Display of service data, refrigerant temperatures and error codes. Facility to connect to remote site monitoring via modem.

PC Windows QSS-NET Control & Monitoring System

Four

Wall controller option hard wired Reduced height slim construction Low profile attractive grey/white fascia panel Fresh air and branch duct facility Low noise 33dBA on smaller models New shape swing louvers for optimum control of air distribution Anti-smudge design of air discharge Fault diagnosis Condensate Lift Pump included Optional SPACE COLLAR for restricted ceiling voids

Condensate lift pump included

FDT with Space Collar for restricted ceiling voids

FDT-KX 4-Way Cassette


FDT-KX
Unit ref. Old ref. Power Supply Nom. Cooling KW UK. Cooling KW UK Sensible Cooling KW Heating Heat pump KW Air Volume max m3/h Connection o.d. sizes liq. gas Unit Dimensions mm (excluding panel) H W D Unit depth in ceiling mm Weight KG

FDT 28 FDT 36 FDT 45 FDT 56 FDT 71 FDT 90 FDT 112 FDT 140

25 32 40 50 63 80 100 125

1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A

2.80 3.60 4.50 5.60 7.10 9.00 11.20 14.00

2.67 3.44 4.30 5.35 6.78 8.60 10.70 13.37

2.42 3.01 3.76 4.21 5.18 6.32 8.20 9.65

3.20 4.00 5.00 6.30 8.00 10.00 12.50 16.00

720 720 900 900 960 1260 1680 1800

1/4 1/4 1/4 3/8 3/8 3/8 3/8 3/8

1/2 1/2 1/2 5/8 5/8 5/8 3/4 3/4

260 260 260 260 260 260 320 320

840 840 840 840 840 840 840 840

840 840 840 840 840 840 840 840

260 260 260 260 260 260 320 320

31 31 31 31 31 35 35 37

FDTS-KX Single Discharge Cassette


FDTS-KX
Unit ref. Old ref. Power Supply Nom. Cooling KW UK. Cooling KW UK Sensible Cooling KW Heating Heat pump KW Air Volume max m3/h Connection o.d. sizes liq. gas Unit Dimensions mm (excluding panel) H W D Unit depth in ceiling mm Weight KG

FDTS 45 FDTS 71

40 63

1ph/5A 1ph/5A

4.50 7.10

4.33 6.84

3.66 5.27

3.20 4.00

840 1080

1/4 3/8

3/8 5/8

194 194

1040 650 1300 650

194 194

23 30

Wall controller option hard wired

Condensate Lift Pump included

Slim height construction - only 198mm Fresh air and branch duct facility Low noise 38dBA on smaller models Condensate Lift Pump included Fault diagnosis

For controls and accessories please refer to page 4

Five

Fits 600 x 600 ceiling opening Wall controller option hard wired Compact construction Low profile attractive white fascia panel Fresh air duct facility Low noise 33dBA on smaller models Swing louvers for optimum control of air distribution Fascia panel - extra width option for access in solid ceilings Ducted horizontal air discharge possible Fault diagnosis Condensate Lift Pump included

Condensate Lift Pump included

FDTQ-KX Single Discharge Compact Cassette


FDTQ-KX
Unit ref. Old ref. Power Supply Nom. Cooling KW 2.20 2.80 3.60 UK. Cooling KW 2.11 2.67 3.44 UK Sensible Cooling KW 1.94 2.42 3.01 Heating Heat pump KW 2.50 3.20 4.00 Air Volume max m3/h 420 420 420 Connection o.d. sizes liq. gas 1/4 1/4 1/4 1/2 1/2 1/2 Unit Dimensions mm (excluding panel) H W D 250 250 250 570 570 570 565 565 565 Unit depth in ceiling mm 250 250 250 Weight KG FDTQ 22 FDTQ 28 FDTQ 36 20 25 32 1ph/5A 1ph/5A 1ph/5A 22 22 22

For controls and accessories please refer to page 4

FDQM-KX Ducted
FDQM-KX Ducted
Unit ref. Old ref. Power Supply Nom. Cooling KW 2.20 2.80 3.60 UK. Cooling KW 2.11 2.67 3.44 UK Sensible Cooling KW 1.94 2.42 3.01 Heating Heat pump KW 2.50 3.20 4.00 Air Volume max m3/h 420 420 420 Connection o.d. sizes liq. gas 1/4 1/4 1/4 1/2 1/2 1/2 Unit Dimensions mm H 250 250 250 W 570 570 570 D 565 565 565 Unit depth in ceiling mm 250 250 250 Weight KG FDQM 22 FDQM 28 FDQM 36 20 25 32 1ph/5A 1ph/5A 1ph/5A 20 20 20

Wall controller option hard wired Compact construction Duct connection - rectangular Fresh air duct facility Low noise 33dBA on smaller models Duct resistance 30 Pa Fault diagnosis Condensate Lift Pump included up to 600mm lift

Condensate Lift Pump included

Six

Wall controller option hard wired Fresh air facility Low noise levels Circular spigots for easy duct connection Return air filter not included High fan performance Fault diagnosis Condensate Lift Pump included

Condensate Lift Pump included

FDUM-KX Ducted Horizontal


FDUM-KX
Unit ref. Old ref. Power Supply Nom. Cooling KW UK. Cooling KW UK Sensible Cooling KW Heating Heat pump KW Air Volume max m3/h External static pressure max. Connection o.d. sizes liq. gas Unit Dimensions mm H W D Unit depth in ceiling mm Weight KG

FDUM 45 FDUM 56 FDUM 71 FDUM 90 FDUM 112 FDUM 140

40 50 63 80 100 125

1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A

4.50 5.60 7.10 9.00 11.20 14.00

4.30 5.35 6.78 8.60 10.70 13.37

3.76 4.21 5.18 6.32 8.20 9.65

5.00 6.30 8.00 10.00 12.50 16.00

828 828 1080 1188 1692 2052

85Pa 85Pa 85Pa 85Pa 90Pa 90Pa

1/4 3/8 3/8 3/8 3/8 3/8

1/2 5/8 5/8 5/8 3/4 3/4

299 299 299 299 350 350

750 750 950 950 1370 1370

635 635 635 635 635 635

299 299 299 299 350 350

34 34 40 40 57
59

For controls and accessories please refer to page 4

FDR-KX Ducted Cassette


FDR-KX
Unit ref. Old ref. Power Supply Nom. Cooling KW UK. Cooling KW UK Sensible Cooling KW Heating Heat pump KW Air Volume max m3/h External static pressure max. Connection o.d. sizes liq. gas Unit Dimensions mm (excluding panel) H W D Unit depth in ceiling mm Weight KG

FDR 45 FDR 56 FDR 71 FDR 90 FDR 112 FDR 140

40 50 63 80 100 125

1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A

4.50 5.60 7.10 9.00 11.20 14.00

4.30 5.35 6.78 8.60 10.70 13.37

3.76 4.21 5.18 6.32 8.20 9.65

5.00 6.30 8.00 10.00 12.50 16.00

840 840 1080 1200 1680 2040

85Pa 85Pa 85Pa 80Pa 80Pa 80Pa

1/4 3/8 3/8 3/8 3/8 3/8

1/2 5/8 5/8 5/8 3/4 3/4

355 355 355 355 406 406

750 950 950 750 1370 1370

635 635 635 635 635 635

355 355 355 355 406 406

37 37 43 43 59 61

Condensate Lift Pump included

Wall controller option hard wired Bottom return air Fresh air and exhaust air duct facility Low noise 36dBA on smaller models Can be supplied with or without ceiling panel Condensate Lift Pump included Fault diagnosis

Seven

Wall controller option hard wired Attractive light beige casing Adjustable air louver for optimum air distribution Low noise - 37dBA on smaller models High cooling performance Fault diagnosis Condensate Lift Pump optional accessory with integral fail-safe protection

FDK-KX Wall Mounted


FDK-KX
Unit ref. Old ref. Power Supply Nom. Cooling KW UK. Cooling KW UK Sensible Cooling KW Heating Heat pump KW Air Volume max m3/h Connection o.d. sizes liq. gas Unit Dimensions mm H W D Weight KG

FDK 22 FDK 28 FDK 36 FDK 45 FDK 56 FDK 71

20 25 32 40 50 63

1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A

2.20 2.80 3.60 4.50 5.60 7.10

2.11 2.67 3.44 4.30 5.35 6.78

1.94 2.42 3.01 3.76 4.21 5.18

2.50 3.20 4.00 5.00 6.30 8.00

450 540 600 690 1020 1260

1/4 1/4 1/4 1/4 3/8 3/8

1/2 1/2 1/2 1/2 5/8 5/8

375 375 375 375 375 375

930 930 930 930 1148 1436

194 194 194 194 194 194

19 19 19 19 20 22

For controls and accessories please refer to page 4

FDK-KX Condensate Pump Accessory


The FDK lift pump accessory is designed to allow condensate drain water to be pumped upwards into a suspended ceiling, without the need for any pipe connections showing beneath the unit. The kit includes extensions for the refrigerant piping also, allowing all pipework to be routed through the top of the unit. The complete assembly is enclosed in a matching extension to the unit casing. A wiring loom is provided, for connection to the unit control board; this includes a fail safe shut-off should the pump be flooded for any reason. The pump is almost silent in operation, and will lift up to 1000mm, measured from the bottom of the unit..

Eight

Wall controller option hard wired, can be fitted within top of unit if required Slim construction - only 225mm deep Low noise 33dBA on smaller models Fault diagnosis

FDFL-KX Floor Mounted


FDFL-KX
Unit ref. Old ref. Power Supply Nom. Cooling KW UK. Cooling KW UK Sensible Cooling KW Heating Heat pump KW Air Volume max m3/h Connection o.d. sizes liq. gas Unit Dimensions mm H W D Weight KG

FDFL 28 FDFL 45 FDFL 71

25 40 63

1ph/5A 1ph/5A 1ph/5A

2.80 4.50 7.10

2.67 4.30 6.78

2.42 3.76 5.18

3.20 5.00 8.00

720 840 1080

1/4 1/4 3/8

1/2 1/2 5/8

630 630 630

1196 225 1196 225 1481 225

32 32 40

FDFU-KX Concealed Floor Unit


FDFU-KX
Unit ref. Old ref. Power Supply Nom. Cooling KW UK. Cooling KW UK Sensible Cooling KW Heating Heat pump KW Air Volume max m3/h Connection o.d. sizes liq. gas Unit Dimensions mm H W D Weight KG

FDFU 28 FDFU 45 FDFU 56 FDFU 71

25 40 50 63

1ph/5A 1ph/5A 1ph/5A 1ph/5A

2.80 4.50 5.60 7.10

2.67 4.30 5.35 6.78

2.42 3.76 4.21 5.18

3.20 5.00 6.30 8.00

720 840 840 1080

1/4 1/4 3/8 3/8

1/2 1/2 5/8 5/8

630 630 630 630

1077 1077 1077 1362

225 225 225 225

25 25 25 32

Wall controller option hard wired Slim construction - only 225mm Low noise 36dBA on smaller models Easy access for installation and servicing Fault diagnosis

Nine

Wall controller option hard wired Low noise levels on smaller models Unit can be installed up to adjacent wall to conceal all pipe connections Adjustable air louver for optimum air distribution Return air filter included Can be partially recessed into ceiling if required Fault diagnosis

FDE-KX Ceiling Mounted


FDE-KX
Unit ref. Old ref. Power Supply Nom. Cooling KW Uk. Cooling KW UK Sensible Cooling KW Heating Heat pump KW Air Volume max m3/h Connection o.d. sizes liq. gas Unit Dimensions mm H W D Weight KG

FDE 36 FDE 45 FDE 56 FDE 71 FDE 112 FDE 140

32 40 50 63 100 125

1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A

3.60 4.50 5.60 7.10 11.20 14.00

3.44 4.30 5.35 6.78 10.70 13.37

3.01 3.76 4.21 5.18 8.20 9.65

4.00 5.00 6.30 8.00 12.50 16.00

840 840 840 1080 1680 2040

1/4 1/4 3/8 3/8 3/8 3/8

1/2 1/2 5/8 5/8 3/4 3/4

184 184 184 184 239 239

1000 1000 1000 1000 1260 1470

650 650 650 650 650 650

22 22 22 27 34 40

For controls and accessories please refer to page 4

FDTW-KX 2-Way Cassette


FDTW-KX
Unit ref. Old ref. Power Supply Nom. Cooling KW Uk. Cooling KW UK Sensible Cooling KW Heating Heat pump KW Air Volume max m3/h Connection o.d. sizes liq. gas Unit Dimensions mm (excluding panel) H W D Unit depth in ceiling mm Weight KG

FDTW 28 FDTW 45 FDTW 56 FDTW 71 FDTW 90 FDTW 112 FDTW 140

25 40 50 63 80 100 125

1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A 1ph/5A

2.80 4.50 5.60 7.10 9.00 11.20 14.00

2.67 4.30 5.35 6.78 8.60 10.70 13.37

2.42 3.76 4.21 5.18 6.32 8.20 9.65

3.20 5.00 6.30 8.00 10.00 12.50 16.00

840 840 840 960 1140 1680 1920

1/4 1/4 3/8 3/8 3/8 3/8 3/8

1/2 1/2 5/8 5/8 5/8 3/4 3/4

280 280 280 330 330 345 345

817 817 817 1054 1054 1524 1524

620 620 620 620 620 620 620

280 280 280 330 330 345 345

26 26 26 35 35 49 49

Condensate Lift Pump included

Wall controller option hard wired Ceiling panel included Fresh air and exhaust air duct facility Low noise 36dBA on smaller models All service access through ceiling panel Condensate Lift Pump included Fault diagnosis

Ten

3D Air Sales Ltd is the distributor in the UK and Eire of Mitsubishi Heavy Industries air conditioning and heat pump systems. The KX2 and KXR systems represent the latest technology of energy efficient multi systems for commercial applications. The advanced technology is manifested in a state-of-the-art automatic control system, constantly self adjusting to suit the varying needs of each individual area within the building, whilst providing the occupants with a stable and comfortable environment. It is important that the systems are configured and applied correctly. 3D technical and sales staff can assist with the selection of equipment, and provide layout diagrams and pipework schematics for consultants and contractors. Installation must be carried out by competent engineers, with every care being taken to ensure non-contamination of the refrigerant pipework. It is essential to purge pipework with dry nitrogen when making brazed joints. Mitsubishi Heavy Industries has a long established reputation of quality and reliability, with an extensive history of developing refrigeration and air conditioning products, electronic control systems, compressor technology, automotive air conditioning and applied equipment.

Technical information on all Mitsubishi Heavy Industries air conditioning products can be found on the 3D website at:

www.3dair.co.uk
3D Air Sales Ltd
Sales & Marketing 850 Brighton Road, Purley, Surrey CR8 2BH Tel: 020 8668 1112 Fax: 020 8668 1113 Email: sales@3dair.co.uk

3D Air Sales Ltd


Sales & Accounts Administration, Spare Parts Sales, Warehouse, Technical Troubleshooting, Warranty Anglia House, Priors Way, Coggeshall, Essex CO6 1TL Tel: 01376 565 505 Fax: 01376 565 525

3D Air Sales Ltd Scotland


McGregor House,South Bank Business Park, Kirkintilloch, Glasgow G66 1XF Tel: 0141 777 5007 Fax: 0141 777 5009 Email: 3dairscot@edet.wiz.net.uk

3D Air Sales Ireland Ltd


Unit 21, Western Industrial Estate, Naas Road, Dublin 12 Tel: 00 353 (0) 1450 9433 Fax: 00 353 (0) 1450 9799 Email: micclan1@eircom.net