Você está na página 1de 4

TECHNOLOGY TO THE FORE

SWI TC H G EAR C O M P L E X

SF6-GAS CIRCUIT BREAKERS FOR OUT-DOOR USE UPTO 36kV

CG Switchgear and Control


A Business Unit of Crompton Greaves Ltd.

TECHNOLOGY TO THE FORE

SW I TC H G EAR C O M P L E X

INTRODUCTION
More than 9000 Crompton Greaves SF6 Gas Circuit Breakers with puffer type interruptors upto 420 kV have been put into service in various environments in many countries since 1983 where they are operating satisfactorily. Type SFGP SF6 Circuit Breakers are of live tank type with rated voltage of 24 & 36 kV. Each breaker consists of three puffer type interruptors, providing a high insulation as well as an excellent breaking capability, a spring operating mechanism ensuring high operational reliability. All our SF6 Gas Breakers (24 to 420 kV) adhere to the requirements of the quality standards and scope of supply of ISO 9001, 1994.

INTERRUPTER UNIT - FIG1

Absorbent

Stationary contact holder

Stationary contact Gas flow Arc Nozzel Moving arc contact Moving main contact

FEATURES

These SF6 Gas Circuit Breakers are extremely simple Piston Puffer cylinder and compact in their design owing to the fact that Main contact no gas blast valves or exhaust valves are required and the force of contact separation simultaneously Contact spring drives the puffer piston, which builds up the gas pressure according to the contact stroke. The structural simplicity results in high performance reliability and, therefore, minimal inspection and re-assembly. Also this ensures that the OPERATING MECHANISM - FIG2 maintenance time is low. Inspection is simple and Closing trigger Plunger core (closing coil) easy since the interrupting medium, which is also Roller Hook the insulating medium, is monitored with ease Interlock spring Closing latch through clearly readable pressure gauges and Link Cam roller mechanical as well as electrical interlocks. Motor The breaker opens from front as well as back panels to provide easy access to all parts of the Closing cam mechanism. The checking or replacing of fixed, Spur gear moving or arc contacts and nozzle can be done by removing only the upper terminal of the interruptor unit as and when required. This operation does not Eccentric crankshaft Ratchet wheel require the breaker to be dismantled and it takes Pawls Main shaft only a few hours to put the breaker back into Main-shaft lever service. Roller The low operating noise level of the spring charged operating mechanism used in this breaker enables Tripping spring its use in residential areas. All exposed ferrous parts are treated to give high corrosion resistance and are finally painted with polyurethane based paint Exploded schematic view of ensuring excellent finish and protection. The breaker the operating mechanism has been made extraordinarily simple and light to increase safety in the event of earthquakes.

Plunger core (tripping coil) Hook Tripping trigger Roller lever Cam shaft Crank lever Crank pin Connecting rod Push rod Tripping latch Latch arm

Closing spring

TESTS AND PERFORMANCE


The performance and reliability of these breakers and their excellent interrupting capability has been verified at renowned international testing laboratories like CESI, Italy and CPRI, India. The breakers are type tested for short circuit duties and capacitive current switching test as per IEC 56-1987

EASE OF INSTALLATION
Since these units are shipped in two parts - namely the pole unit and the mechanism - minimal site preparation is required and setup time is very low.

DESIGN
The interrupting unit (FIG.1) is puffer type and is contained in a porcelain insulator and the terminals. During interruption the puffer cylinder is quickly driven downwards with its attached parts by the operating mechanism (from the breaker "closed" position to the breaker "open" position). The gas within the puffer cylinder is compressed by the piston and blown to the arc through the nozzle achieving arc extinction. The operating mechanism (FIG.2) is an easy to handle motor charged spring type. It also permits manual operation of the breaker. High reliability has been ensured by keeping the number of components to a minimum and, therefore, maintenance required is easy and minimal.

GUARANTEED TECHNICAL PARTICULARS 24 / 36 kV SF6 GAS CIRCUIT BREAKER


UNITS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. TYPE REFERENCE RATED VOLTAGE RATED LIGHTNING IMPULSE WITHSTAND VOLTAGE RATED POWER FREQUENCY WITHSTAND CREEPAGE DISTANCE (TOTAL) APPLICABLE STANDARDS TYPE OF MECHANISM RATED NORMAL CURRENT RATED SHORT CIRCUIT BREAKING CURRENT RATED SHORT CIRCUIT MAKING CURRENT RATED OPERATING SEQUENCE RATED FREQUENCY RATED BREAK TIME RATED CLOSING TIME RATED CLOSING / TRIPPING VOLTAGE CURRENT OF CLOSING / TRIPPING COIL FIRST POLE TO CLEAR FACTOR RATED DURATION OF SHORT CIRCUIT RATED CABLE CHARGING BREAKING CURRENT AND OVER VOLTAGE. RATED SINGLE CAPACITOR BANK BREAKING CURRENT AND OVER VOLTAGE. RATED OUT OF PHASE BREAKING CURRENT AUXILLIARY CONTACTS SF6 GAS PRESSURE (AT 20 C) -NORMAL -GAS FEED ALARM -LOCKOUT : : : : : : : : : : : : : : : : : : : : : : : : : kV kVp kV mm A kAp kA Hz ms ms V A sec A / pu A / pu kA Kg / cm2 Kg / cm2 Kg / cm2 6.25 24 kV 36 kV 20-SFGP-25A 30-SFGP-25A 30-SFGP-40A 24 36 150 200 60 80 600 916 IEC 56, BS 5311 & JEC 181 SPRING CLOSING / TRIPPING 1250, 1600, 2000 25 & 40 25 62.5 62.5 & 100 O-0.3 sec-CO-15 sec-CO 50 / 60 80 100 110 / 220 VDC 5 at 110 VDC 1.5 3 50, <2.5 440, <2.5 6.25 & 10 5 NO + 5 NC 5 4.5 4

OPTIONALS
1. 2. 3. 4. 5. 6. 7. CREEPAGE DISTANCE CLOSING / TRIPPING COIL VOLTAGE CLEARANCE OF LIVE PARTS TO GROUND ALTITUDE ABOVE SEA LEVEL AUXILLIARY CONTACTS LIGHTNING IMPULSE WITHSTAND VOLTAGE EARTHQUAKE WITHSTAND (SEISMIC ACCELERATION) 25, 31, 35 mm / kV 24 / 30 / 60 / 110 / 125 / 220 VDC AS PER CUSTOMER SPECIFICATION UPTO 2500 M 10 NO & 10 NC 250 kVp 0.3 g / 0.5 g

FOUNDATION PLAN DETAILS


250 50 FOUNDATION BOLT (M24400) LOCATION

GENERAL OUTLAY

B
80

A
450 900

2
480 1100

3 C G

DETAILS OF TERMINAL PAD (MATERIAL - AL, 22 THK)


15, 4 HOLES 14, 4 HOLES

E 40

44.5

CONDUCTOR SIDE

150

40

BREAKER SIDE

40

16

44.5 140

60

1. 2. 3. 4. 5.

INTERRUPTER SUPPORT PORCELAIN BASE FRAME MECHANISM HOUSING SUPPORT STRUCTURE

DIMENSIONS (mm)
A 20-SFGP-25A (24 kV) 30-SFGP-25A (36 kV) 30-SFGP-40A (36 kV) 600 750 750 B 1560 1860 1860 C 3349 3819 4079 D 680 680 680 E 1025 1225 1290 F 522 672 976 G 2783 3103 3103 H 502 502 502 TOTAL WEIGHT (Kg) 675 750 750

GAS SYSTEM
A-Phase B-Phase C-Phase Temperature compensated pressure switch

Arcing column Stop valve

15

Gas pipe Pressure gauge Stop valve Blind cap

CG Switchgear and Control


A Business Unit of Crompton Greaves Ltd.

Switchgear Complex A-3, MIDC, Ambad, Nashik - 422 010 India Tel: (+91) 253 382271 to 75 Ext 107/108/110 Fax: (+91) 253 382219/381247 E-mail: exports@cglmail.com (Exports) mktg@cglmail.com (General) URL: www.cgswgear.com

The Thapar Group


CG-S&C/EXP/Cat.No.SF6-102/3/01/2000

Regd. Office : 6th Floor, CG House, Dr. Annie Besant Road, Prabhadevi, Mumbai -400 025, India.
Data subject to change

Você também pode gostar