CONTENTS
1. Specifications ................................................................................................2 2. Outline and Dimensions .................................................................................3 3. Operation .....................................................................................................5 4. Wiring Diagram..........................................................................................17 5. Refrigerant Cycle .........................................................................................22 6. Control Block Diagram.................................................................................23 7. Electric Circuit Diagram................................................................................24 8. Trouble Shooting..........................................................................................27 9. Disassembly Instructions ...............................................................................43 1) Indoor Unit..............................................................................................43 2) Outdoor Unit...........................................................................................45 3) Exploded Diagram (Indoor Unit) ...............................................................47 4) Exploded Diagram (Outdoor Unit) ............................................................50 5) Control Box Assembly ..............................................................................56
1. SPECIFICATIONS
xDSA-151L/DSA-181L/DSB-181L
MODEL ITEM Function Class Power Supply Capacity W Btu/h Dehumidification Running Current Electrical Data Power Input Starting Current Type Compressor Model Capacitor Type Indoor Outdoor Capacitor Fan Outdoor Motor Model Indoor Outdoor Refrigerant (R-22) Control Charge Q'ty Type Connection OD (Liquid/Suction) Dimensions Indoor Outdoor Net Weight Indoor Outdoor 11.7Kg 43Kg Indoor Outdoor 1,250g IC-9425DWKH6A AM12DPD05 3F/400 VAC IC-9425DWKH6A AM12DPD05 Capillary 1,450g Flare 1/4(6.35mm) 1/2(12.7mm) 1,035 x 322 x 205 800 x 615 x 277 11.7Kg 44Kg 11.7Kg 55.8Kg 1,150g IC-9425DWKC5A AM12DPD04 Indoor AC 208~230V, 60Hz 4,300 15,500 1.98l/h 6.6A 1,450W 42A Rotary RCA150A001 DSA-151L DSA-181L Cooling T AC 208~230V, 60Hz 5,100 17,500 2.3l/h 8.3A 1,785W 44A Rotary ECB185211A 30F/400 VAC Cross Flow Fan Propeller Fan 1.2F/400 VAC AC 220~240V, 50Hz 5,100 17,500 2.3l/h 9.8A 1,950W 46A RECIPRO CRDQ-0200-PFJ DSB-181L
Connecting ` Pipe
Plate Mounting `
REMOCON `
3
Grille Insert
x DSA-151L/DSA-181L/DSB-181L
Body
1 INDOOR UNIT
322
205
Filter-L Filter-R
Inlet
Inlet
277 367
x DSA-151L/DSA-181L/DSB-181L
2 OUTDOOR UNIT
Discharge Grille
615
800
Foot
Service Valve
3. OPERATION
1 PARTS OF NAME AND FUNCTION
x DSA-151L/DSA-181L/DSB-181L
Indoor Unit
Electrostatic Filter
Removes dust particles from the air.
Air In
Remote Sensor
TIM
ER ON
OF
Power Plug
x DSA-151L/DSA-181L/DSB-181L
Switch Panel
EMERGENCY
REMOTE
s There is a switch panel at inside of Front Panel. At the time of operating, open the Front Panel.
Timer (Yellow) Lights during the time reservation mode. Quick (Red) Lights during the time Quick Mode. ON (Red) Lights when the operation is going on. Air clean (Green)
Emergency switch can be used when the remote controller is lost or Testing. Remote switch is usually used by remote controller.
x DSA-151L/DSA-181L/DSB-181L
Outdoor Unit
AIR IN
AC Cover Remove cover to access the AC connection from this unit to the indoor unit.
Connection Wire Drain Hose COPPER TUBING AIR OUT Service Valves The indoor and outdoor units are connected by copper tubes which are connected here. Grounding Screw Ground the unit here.
2 REMOTE CONTROLLER
x DSA-151L/DSA-181L/DSB-181L
AUTO
ON/OFF Button Press to turn the unit on or off. TEMPERATURE Buttons Press to raise or lower the desired temperature.
MODE FAN SPEED FAN DIR.
FAN SPEED Button Press to select the fan speed (High " ", Middle " ", Low " "). MODE Button Press to cycle through the modes (Auto/Quick/Cooling/Fan/Dry) SLEEP Button Press to set the unit for the sleep mode. TIMER ON/OFF Button Press to set the unit of or on time. (0.5, 1, 1.5, 2, 2.5, 3, 4, 5, 6, 8, 10, 12, 16, 20, 24hr) TIMER ENTER/CANCEL Button Press to enter a timer setting or to cancel timer setting
FAN DIR. Button Press to select up/down direction for fan. FAN DIR. Button Press to select left/right direction for fan. TURBO/MILD Press to be colder the unit.
SLEEP TIMER
FAN DIR.
ON/OFF
ENTER/ CANCEL
TURBO/MILD
COVER Slide down to access most of the remote buttons. Slide down further to access the battery compartment.
AUTO
FAN Indicators Lights to indicate the fan speed. NATURAL Indicator Lights to indicate the speeds simulating a breeze. FAN DIRECTION Indicators Lights to indicate the fan direction.
TIMER Indicators (Include sleep) Lights to indicate the timer function mode. TEMPERATURE & RESERVATION TIME lndicators Lights to indicate the temperature or time.
Replacing Batteries
Open the cover after pressing the arrow direction and pulling out.
4 DESCRIPTION OF FUNCTIONS
OFF-Timer
If you set time in OFF-Timer Mode, the unit will stop at the set time.
ON OFF
SET Time
HOUR
ON-Timer
If you set time in ON-Timer Mode, the unit will run at the set time.
Unit ON
SET Time
HOUR
-1C
0C (COOLING)
( (
(3) During the time of test operating, Fan (Indoor, Outdoor) and Compressor is running regardless of room temperature.
Buzzer
If the Indoor Unit Display receive the signal of Remote Controller, you can hear the signal "beep " or "beep, beep".
10
(4) Automatic Operation If the unit is set in 'AUTO' mode, the unit operates automatically according to the room temperature to keep the room temperature comfortable. (COOLING) DSA-151L/DSA-181L/DSB-181L
H M L
+1C +2C
(RT-DT)
11
Sleep Mode
(1) When you are going to sleep, select sleep switch and the unit controls the room to the desired temperature. (The unit will not operate after 4 hour) (2) For changing the temperature.
1.0
HOUR
(3) To cancel sleep mode, press the SLEEP button again or press the MODE button once.: the SLEEP indicator will disappear in the display.
Emergency Operation
(1) When the remote controller is lost, damaged or the battery is discharged, the Emergency operation can be used to run the unit. (2) The setting conditions of Emergency operation are as follows. Operation mode: AUTO Preset temperature: 26C Fan speed: AUTO
12
0C
7C
13
Auto Mode
(1) When the room temperature is higher than 28C (Cooling Mode) !Compressor and lndoor Fan
(2) When the room temperature is lower than 28C and higher than 22C (Dehumidification Mode). (3) When the room temperature is lower than 22C (Fan only).
14
Dehumidification Mode
!Desired temperature < Room temperature
Outdoor Fan, Compressor : ON Indoor Fan : Low speed @ Desired temperature >Room temperature Compressor : 3 min/ON, 5 min/OFF Indoor Fan : 3 min 30 second/ON, 4 min 30 second/OFF Fan Speed : Low speed # Room temperature > 18C Compressor : OFF Indoor Fan : 1 min/ON, 7 min/OFF Fan speed : Low speed
15
Self-Diagnostic Function
The control will contain diagnostic test to verify the integrity of the system. (1)Error Code Display Pattern !ON LAMP: ON (Red) LED ON/OFF @ Error Code (Display in Emergency Mode only)
ERROR CODE
DISPLAY PATTEN
8 seconds
ERROR CONTENTS Room air thermistor, connector Indoor coil thermistor, connector
0.5 second
16
4. WIRING DIAGRAM
x DSA-151L
17
x DSA-181L/DSB-181L
18
Compressor Capacitor Dual Outdoor Unit Fan Motor Power Relay Terminal Block
1 1 1 1 1
19
x DSA-181L
PART NAME Fan Motor Fan Motor Capacitor Fuse Indoor Unit Fuse Transformer Stepping Motor 1 Stepping Motor 2 Terminal Block PART CODE 3964330200 3106995010 5FVGB0302R 5FVGD0402S 5EPK533110 3108004310 3108004300 3108912320 SPEC. IC-9425 KH 6C 1.2F 450VAC 0.2A 250V 3A S/B 250V 4A 6ITS 220V/15V MP28GA (L=1300mm) MP-28GA (L=400mm) SN-DBW-4P QUANTITY 1 1 1 1 1 1 2 1 REMARK
Compressor Capacitor Dual Outdoor Unit Fan Motor Power Relay Terminal Block
1 1 1 1 1
20
x DSB-181L
PART NAME Fan Motor Fan Motor Capacitor PART CODE 3108000300 3106995010 3106901100 Fuse Indoor Unit Fuse Transformer Stepping Motor 1 Stepping Motor 2 Terminal Block 5FVGB0302R 5FVGD0402S 5EPV633100 3108004310 3108004300 3108912320 3108911600 SPEC. IC-9425DWKC5C 1.2F 450VAC 0.2A 1.2F 400VAC 250V 3A S/B 250V 4A 6ITS 220V/18.3V MP28GA (L=1300mm) MP28GA (L=400mm) SN-DBW-4P 1000-4DS QUANTITY 1 1 1 1 1 1 1 2 1 1 For VDE Appliance For NON Appliance For VDE Appliance REMARK
Compressor Capacitor Dual Outdoor Unit Fan Motor Power Relay Terminal Block
21
5. REFRIGERANT CYCLE
INDOOR UNIT Evaporator
Connecting pipe
Accumulator Compressor
Capillary tube
Condenser
Dryer
Note) If the pipe length exceeds the standard length, add 30g of refrigerant per extra meter.
Contents
Model Name
DSA-151L
DSA-181L
DSB-181L
ID2.0 x OD3.2 x L1200 ID1.78 x OD3.2 x L600 ID2.0 x OD3.2 x L650 1300 g 1500 g 1200 g
22
Operating Mode Unit on lamp Quick lamp Air-clean lamp Flap Position Timer lamp Operation Temp. Setting ON/OFF Room air temp. Indoor coil temp. SLEEP Turbo/MILD Remote Emergency Timer Selection Signal receiver Fan Speed
Circuit for signal receiver A/D converter Beeper MICRO CONTROLLER lnitialization Clock generation DC5V DC power supply DC12V Transformer AC220V
Relay RL1
TRIAC
23
1
Indoor Unit Fan Motor
2 3 I.D.C
TERMINAL BLOCK
SWING MOTOR SWING MOTOR2 SWING MOTOR1 Display Part Control Part Signal Receiver ROOM AIR SENSOR COMP COMP
TRANSFORMER
POWER RELAY
FMC
24
Description
1. After the power ON/OFF button is pressed once, the relay and triac are turned ON or OFF per the remote control setpoint. TRIAC is controlled per the fan speed selection. RELAY is controlled per the operation mode selection.
2. If the power ON/OFF button is pressed once more, the relay and triac are turn off and the unit stops operation.
3. The unit turns on or off according to the temperature setpoint by sensing the room air temperature through thermistor.
4. If the fan speed selection is set to the auto position, the fan speed is automatically controlled according to the temperature differance between room temperature and temperature setpoint.
25
26
Trouble
Is the unit display normal? Is the power applied to the unit YES YES
NO
NO YES
8. TROUBLE SHOOTING
Is the power normal? check the voltage between L & N of terminal block NO YES
NO
Does the compressor run normally? YES Indoor unit does not run(note 1) Is the unit display mormal? YES Check the failure code according to the self diagnostic (note 2) NO NO
press the power ON/OFF button on remote controller YES NO Normal Does the beeper beep two times? check the connecting point of magnetic contactor YES NO
NO
Place the switch position to the "Remote" and then Check it once more
YES
Does control PCB status LED repeat one second "on and off"? NO Is the display all off? YES control PCB fault Micom or reset IC fault
YES
YES
Check the connector on display PCB connected to control PCB Check the display PCB itself
Check the remote signal receiver Check the connection between signal receiver and control PCB
27
Note 1) !Neither indoor unit nor outdoor unit runs. Check the following points first. (There are following case in normal operation) a. Is the timer mode set the "timer ON". b. Is the timer mode set the "timer-OFF" and the time had passed? @ Neither outdoor fan nor compressor runs while indoor fan runs. Check following points first. (There are following cases in normal operation) a. Is the temperature set point suitable? b. Has the 3 minutes time guard for compressor operated? Note 2) Please refer to page 16, Self Diagnostic-function.
Self-Diagnostic Function
x DSA-151L/DSA-181L/DSB-181L 1) Error Code 1 !Check the connector of room air thermistor. (or connecting wire) @ Check soldering of connecting on control P.C.B. (Error of soldering or short) # Check the resistance of room air thermistor. 2) Error Code 3 (Display Emergency mode) !When the compressor do not run. i) Check the voltage between N and Y of terminal block. (Indoor Unit, Outdoor Unit) ii) Check connecting wire of indoor unit and outdoor unit. iii) Check relay KI on power P .C.B @ Check fixing of indoor coil thermistor. # Check the GAS LEAKAGE of the pipe.
28
Rating voltage Check the voltage between L and N of terminal block under 90%
Rating voltage more than 90% Check the indoor unit display is the display all off? NO Self Diagnostic function is ON YES NO Check according to self Diagnostic function NO
YES Press the ON/OFF switch of Remote Control Is the indoor unit display all off?
Pull out the power plug and then insert the power plug after 5 seconds
29
Rating Voltage more than 90% Open or short Check the winding resistance of Indoor unit fan motor Normal Check the fan motor capacitor Change of fan motor
Run again
30
Rating voltage Check the voltage between L and N of outdoor unit terminal under 90%
31
Rating voltage more than 90% Rating voltage Check the voltage between N and Y of outdoor unit terminal less than 90% Check the connecting wire between indoor and outdoor.
Rating voltage more than 90% Check the magnetic contactor Check the wiring of outdoor unit NG Change the magnetic contactor.
Open or Short
32
Rating voltage Check the voltage between L and N of outdoor unit terminal under 90%
33
BD1
AC 220V + CE1 VAR POWER TRANS DC 12V 3 CC3 0.1 7805 2 CE3 100/25V CC2 0.1 1 + 3 7812 2 CC1 1 1000/35V
CE2 470/16V
DESCRIPTION
DC Power Supply in circuit needs +12V and +5V. +12V is used for Compressor Driving Relay, Triac Driving Photo Triac, Buzzer Driving Swing, Sweep Motor, and LED Display. AC voltage of secondary Power Transformer is rectified by Bridge Diode, and it is filtering by Main Condensor CE1. Filtered DC voltage is about +17V, is regulated +12V DC by Regulator IC7812. And it is regulated +5V DC by Regulator IC7805. VAR is surge filter and CE2, CE3, CC2, CC3 is Noise filter.
35
Oscillation (2)
19 20 X-TAL 8MHz
DESCRIPTION
Oscillatory Frequency drive Micom, it is made up 8MHz X-TAL oscillatory Freqency. Ocillatory wave is as following Fig 2-1.
VDD-10%
VSS+10%
Fig 2-1
36
Sensor(3)
Room temperature and Evaporator temperature Sensor Input
R20 12.7K
EVA: SENSOR
1 2 3 4
CN8 ROOM: SENSOR
MICOM
DESCRIPTION
Number 24, 25 of Micom is Terminal of A/D convertor Input. Room temperature and Evaporator temperature is sensing by change of Thermister Resistance, Micom is put in 5V by ratio between R18 (12.7K) and R20 (12.7K). Relation between temperature and voltage is following Table 3-1. CC8, CC9 is Noise filter.
Temperature (C) -5 0 15 25 40
Voltage (V) No. 24, 25 1.12 1.37 2.22 2.79 3.52 Table 3-1
37
12V
R5 100
L AC220V
MICOM
38
SN1
0.1F/120OHM
TO MOTOR
DESCRIPTION
Number 38 Terminal of Micom is put out Pulse Output, by way of Buffer it is driving Photo Triac TLP560 and then Triac SM3JZ47 is supplied Trigger Signal. Trigger Test of Triac is detected Zero Cross Part of AC input and it is triggered from Zero Cross part to Time delay part according to Fan Speed. (Ref. Fig 4-1) SN1 is Snubber.
AC220V
TRIGGER LOW SPEED LOW SPEED MEDIUM SPEED MEDIUM SPEED HIGH SPEED HIGH SPEED
MOTOR INPUT
Fig 4-1
38
13
R15 1K EMERGENCY S/W CC6 0.01
MICOM
DESCRIPTION
There are three Mode according to SW position as following Table 6-1.
39
MICOM
21
DESCRIPTION
MICOM Power is supplied 5V at Number 42 using Digital, Number 22 using Reference of A/D Converter. CE2 is Ripple filter and CC1 is Noise filter.
40
Reset (7)
5V
5V
MICOM
18 CC3 104
R9 1K +
7042P
2
RESET IC
DESCRIPTION
Voltage less than about 0.8V put in Micom Terminal of Number 18 and then Micom reset. Reset IC detect Power ON and Voltage less than 4.2V, and then send Reset Signal. There is a Manual Reset S/W to reset manually if necessary.
t
DELAY TIME FOR POWER ON H RESET
L POWER ON
41
30
R14 1K
Test
MICOM 29
28 27
CA1
DESCRIPTION
Selecting Function is as following Table 9-1.
SHORT JS6 JS5 JS4 JS3 Skip Mild Heat 50Hz Table 9-1
42
9. DISASSEMBLY INSTRUCTIONS
1 INDOOR UNIT
PROCEDURES 1. Stop the Air conditioner and disconnect the power cord from the wall outlet. PHOTOS
2. Removing the Insert Grille and Frame. !Loosen three screws for fixing the the Insert Grille and Frame. (Pull out the frame cap before loosening three screws) (Fig 1) @ Loosen three screws at the Drain Pan. # Remove the Insert Grille and Frame.
Fig 1
3. Removing the Control Box. After doing above procedures: !Disconnect indoor room and coil thermistors. (Fig 3) @ Disconnect the fan motor lead wire from connection at the main PCB. (Fig 3) # Disconnect the swing motor connection wire. $ Loosen a screw for fixing ground wire. % Loosen two screws for fixing the body.
Fig 2
Fig 3
4. Removing the Drain Pan. After doing above procedures: !Loosen a screw for fixing body. (Fig 4) @ Unhook the right part of Drain Pan.
Fig 4
5. Removing the Indoor Coil. After doing above procedures: !Loosen four screws for fixing indoor coil at left and right side. (Fig 5) @ Loosen a screw for fixing the bracket tube at the back side. (Fig 6) # Remove the indoor coil. (Fig. 6-1)
Fig 5
6. Removing the fan motor. After doing above procedures: !Loosen two screws for fixing holder moter at left and right side. (Fig 7, 8) @ Loosen a screw for fixing fan motor and blower. # Renove the fan motor.
Fig 6
Fig 6-1
43
PROCEDURES 7. Removing the blower. After doing above procedures: !Loosen a screw for fixing holder bearing. @ Remove the blower.
PHOTOS
Fig 7
Fig 8
44
2 OUTDOOR UNIT
DSA-151L
PROCEDURES 1. Basic Procedures !Stop the air conditioner and pull out power plug from wall outlet. @ Remove CABINET TOP COVER. (Loosen ten screws) # Remove CABINET SIDE COVER. (Loosen six screws) $ Remove CABINET FRONT. (Loosen six screws) PHOTOS
Fig 1
2. Removing Fan Motor (Fig 4) !Do basic procedure. (! ~$) @ Loosen nut for fixing fan by spanner. # Remove spring washer and plain washer. $ Remove fan. % Remove fan stopper. ^ Disconnect Motor lead wire from control box. & Loosen four screws for fixing Motor bracket and then remove the Motor.
Fig 2
Fig 3 3. Removing Motor Capacitor and Compressor Capacitor !Do basic procedure.(! ~$) @ Diconnect lead wire from the Motor capacitor and compressor capacitor. # Loosen two screws for fixing the capacitor bracket. $ Remove Motor capacitor and compressor capacitor.
Fig 4
4. Removing Magnetic Contactor. (Fig 5) !Do basic procedure ! . ~@ @ Disconnect lead wire from Magnetic Contactor. # Remove Magnetic contactor. (Loosen four screws)
Fig 5
5. Removing Overload Protector. (Fig 6,7) ! Do basic procedure ! ~#. @ Remove terminal cover. # Disconnect lead wire from overload protector. $ Remove overload protector.
Fig 6
Fig 7
45
DSA-181L/DSB-181L
PROCEDURES 1. Basic Procedures !Stop the air conditioner and pull out power plug from wall outlet. @ Remove CABINET TOP COVER. (Loosen ten screws) # Remove CABINET SIDE COVER. (Loosen six screws) $ Remove CABINET FRONT. (Loosen six screws) PHOTOS
Fig 1
2. Removing Fan Motor (Fig 4) !Do basic procedure. (! ~$) @ Loosen nut for fixing fan by spanner. # Remove spring washer and plain washer. $ Remove fan. % Remove fan stopper. ^ Disconnect Motor lead wire from control box. & Loosen four screws for fixing Motor bracket and then remove the Motor.
Fig 2
Fig 3 3. Removing Motor Capacitor and Compressor Capacitor. !Do basic procedure.(! ~$) @ Diconnect lead wire from the Motor capacitor and compressor capacitor. # Loosen two screws for fixing the capacitor bracket. $ Remove Motor capacitor and compressor capacitor.
Fig 4
4. Removing Magnetic Contactor. (Fig 5) !Do basic procedure ! . ~@ @ Disconnect lead wire from Magnetic Contactor. !Remove Magnetic contactor. (Loosen four screws)
Fig 5
46
47
48
No 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
PART CODE 3100000200 3102900100 3102900300 3100001000 3107800100 3104395400 3108004300 3108912320 3107400300 3107800200 3107800400 3107500200 3105500400 3104500300 3108004310
PART NAME FILTER PRE L ASSY HINGE R-A HINGE L-A M-PCB ASSY LINK VER CAM F-PCB ASSY MOTOR STEPPING TERMINAL BLOCK EVA BRKT L LINK VER A LINK VER C EMBLEM PLT WINDOW SWITCH PLATE MOUNTING MOTOR STEPPING
SPEC
REMARK
49
50
51
No
PART NAME PIPE DISCHARGE ASSY PIPE DISCHARGE ASSY PIPE FILTER PIPE TURN PIPE CAPILLARY COMPRESSOR ASSY COMPRESSOR ASSY SERVICE VALVE-LIQ SERVICE VALVE-GAS POWER RELAY TERMINAL BLOCK FOOT CUSHION COMP BOLT RUBBER CUSHION WASHER PLAIN NUT LOCK BOLT HEX SCREW TAPPING SCREW TAPPING
Q'TY 1 1 1 1 1 1 1 1 1 1 1 4 3 3 3 3 4 4 10 CU CU
1 4 1 8 5
21 3100016600 22 23 24 3104400700 3104400600 3104400800 3100030AE0 25 3107120010 26 27 28 29 30 31 32 33 34 35 36 37 3105400200 3105400100 5SC0202700 3108912320 3102101000 3107140010 3101500200 7400208411 7392801211 7342602011 7112501211 8112401211 ECB 185211A
1 4 1 2
RCA150A001
G7L-2A-TUB SN-DBW-4P NR
52
DSB-181L
53
54
No 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
PART CODE 3100016400 3104400700 3104400600 3104400800 3107120000 3105400200 3105400100 5SC0202700 3108912320 3102101000 3106000110 3101500200 7400208041 7392801211 7342602011
PART NAME PIPE DISCHARGE ASSY PIPE FILTER PIPE TURN PIPE CAPILLARY COMPRESSOR SERVICE VALVE-LIQ SERVICE VALVE-GAS POWER RELAY TERMINAL BLOCK FOOT CUSHION BOLT COMP RUBBER CUSHION WASHER PLAIN NUT HEX BOLT HEX
Q'TY 1 1 1 1 1 1 1 1 1 4 3 3 3 3 4 CU CU
1 4 1 8
SPEC CU
3 8
REMARK
T0.8
T0.8
CRDQ-0200-PFJ
1 4 1 2
G7L-2A-TUB SN-DBW-4P NR
55
56
DSA-151L/DSA-181L/DSB-181L
No PART NAME SPEC DSA-151L/DSA-181L 1 2 CONTROL BOX ASSY DSB-181L BOX CONTROL-2 ABS (VERSION2) DWA-5423 3 4 5 6 7 8 9 10 11 12 13 PCB TRANS ASSY DWA-220V SCREW TAPPING CAPACITOR IDM SCREW TAPPING TERMINAL BLOCK SCREW TAPPING HARNESS POWER HARNESS EARTH HARNESS COMP SIGNAL T2S TRS 4X12 MFZN EAF-45125 (1.2F/450V) T2S TRS 4X24 MFZN SN-DBW-4P T2S TRS 3X16 MFZN UL1015 #16/18 UL1015 #18 UL1015 #18 1 1 3 1 1 1 2 1 1 1 5EPV633110 7122401211 3106900210 7141402411 3108912320 7111301611 3102704010 3102797910 3102704410 1 1 1 3100058210 3100506900 5EPK633110 QTY 1 PART CODE 3100058320 REMARK
31013A24B1 1 1 1 1 1 1 1 1 1 1 1 3101200300 3104300120 3104300110 3102704900 3104300210 3104300300 3104300400 3104896000 3102704510 3102707000 3103400200
DSA-151L/DSA-181L 14 15 16 17 18 19 20 21 22 CONTROL PCB ASSY DSB-181L (COOL/50Hz) HARNESS CONNECTING POWER PCB ASSY LED PCB ASSY SWITCH PCB ASSY SENSOR ID ASSY HARNESS LED PCB HARNESS SWITCH PCB KNOB SWITCH UL 1007 #26 DSA-151L/DSA-181L/DSB-181L 15/18K 15/18K PEM-KD43C-D1 UL 1007 #26 UL 1007 #26 ABS
57
http://www.dwe. daewoo.co.kr
Service Manual
Model: DSA-151L DSA-181L DSB-181L