DESCRIPTION
TECHNICAL
GUIDE
Two-stage cooling provided by dual independent refrigeration circuits with expansion valves, filter-driers, high
and low pressure/loss of charge switches and freezestats
Hermetically sealed compressors with crankcase heaters
Two-stage heating provided by dual independent heat
exchangers with aluminized steel tubes, redundant gas
valves, spark ignition with induced draft logic
Permanently lubricated motors
CONDITIONERS
036-21035-002-D-0602
TABLE OF CONTENTS
pg.
pg.
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . . 6
LIST OF FIGURES
pg.
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . 5
18 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . 20
LIST OF TABLES
1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . 4
26 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . 23
28 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . 24
29 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . 24
036-21035-002-D-0602
D 1 HG 180 N 240 25 EC
Model Number
Description
Product Category
Product Generation
1 = 1st Generation
HG
Product Identifier
HG = Gas/Electric
HE = Electric/Electric
180
180 = 15 Tons
240 = 20 Tons
A = No Heat Installed
E = Electric Heat
N = Natural Gas
240
25
Voltage Code
Options
D = Air Cond., Single Package
GAS
25 = 208/230-3-60
46 = 460-3-60
Factory Installed
Option Code
All models are available with a wide variety of factorymounted options and field-installed accessories to make
them suitable for almost every application.
All supply air blowers are equipped with a belt drive that can
be adjusted to meet the exact requirements of the job. A high
speed drive accessory is available for applications with a
higher CFM and/or static pressure requirement.
All compressors include crankcase heat and internal pressure relief. Every refrigerant circuit includes an expansion
valve, a liquid line filter-drier, a discharge line high pressure
switch and a suction line with a freezestat and low pressure/
loss of charge switch to protect all system components. The
unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with two compressor lockout
circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls.
All units have long lasting powder paint cabinets with 750
hour salt spray test approval under ASTM-B117 procedures.
All 208/230 and 460-volt models are ETL approved. All 208/
230 and 575-volt models are CGA approved.
All models include a one-year limited parts warranty on the
complete unit. Compressors and electric heater elements
carry a five-year warranty. Aluminized steel tubular heat
exchangers carry a 10-year parts warranty.
All gas heat units are built with two heating sections for two
equal stages of capacity control. Each section includes a
durable heat exchanger with aluminized steel tubes, a redundant gas valve, spark ignition, power venting, an ignition
module for 100% shut-off and all of the safety controls
required to meet the latest ANSI standards.
036-21035-002-D-0602
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through
a knockout in the piping panel on the front of the unit.
All electric heat models are wired for a single power source
and include a bank of nickel chromium elements mounted at
the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
LONG LASTING
POWDER PAINT FINISH
ECONOMIZER HOOD
ELECTRICAL DISCONNECT
MOUNTING LOCATION
(Field installed)
KNOCKOUT FOR
SIDE CONTROL WIRING ENTRY
KNOCKOUT FOR
SIDE POWER WIRING ENTRY SIDE
2" DISPOSABLE
FILTERS
TERMINAL BLOCK
(For Single Point Power Supply
with Electric Heat)
ELECTRIC\ELECTRIC UNITS
BELT-DRIVE
BLOWER MOTOR
GAS/ELECTRIC
UNIT SHOWN
FACTORY-INSTALLED OPTIONS
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return monitor actuator
capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed option.
DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with
fully modulating spring-return monitor actuator capable
of introducing up to 100% outdoor air with nominal 1%
leakage type dampers.
036-21035-002-D-0602
operating and will drive fully closed when the blower unit
shuts down.
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit
shuts down.
ANTI-RECYCLE TIMERS - Two solid state timers prevent the compressors from short-cycling. Once a compressor is de-energized, it will remain de-energized for
approximately five minutes.
BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
FIELD-INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return monitor actuator
capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed option.
DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with
fully modulating spring-return monitor actuator capable
of introducing up to 100% outdoor air with nominal 1%
leakage type dampers.
This enthalpy system contain one sensor that monitors
the outdoor air and one sensor that monitors the return
air. The logic module compares these two values and
modulates the dampers providing the maximum efficiency of economizer system.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed option.
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
036-21035-002-D-0602
UNIT
SIZE
ESP
BLOWER
CFM
IWG
RPM
BHP
63
125
250
500
1,000
2,000
4,000
8,000
SWL
dB(A)
dB(A)
@
10Ft.2
180
8,000
1.00
1,080
4.60
99
99
89
82
84
77
72
67
89
56
240
8,000
1.00
1,120
6.65
102
102
92
85
87
80
75
70
92
59
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
MBH
EER2
IPLV3
MODEL
MBH INPUT
MBH OUTPUT
D1HG180N240
300
240
10.7
D1HG180N320
400
320
10.2
D1HG240N240
300
240
D1HG240N320
400
320
COOLING ONLY
D1HE180
D1HE240
177
223
10.0
9.7
177
10.0
10.7
D1HG180N320
177
10.0
10.7
D1HG240N240
223
9.7
10.2
D1HG240N320
223
9.7
10.2
177
10.0
10.7
D1HE180E036
177
9.9
10.6
D1HE180E054
175
9.7
9.9
D1HE180E072
175
9.7
9.9
D1HE240E018
223
9.6
10.1
D1HE240E036
223
9.6
10.1
D1HE240E054
221
9.5
9.7
D1HE240E072
219
9.5
9.7
036-21035-002-D-0602
Air On Evaporator
Coil
CFM
4500
5250
5765
6750
7200
86
83
80
77
74
71
68
WB F
Tot.1
Input
(kW)
TOT2
72
16.6
193.2
118.2
192.2
105.1
190.9
92.5
189.1
77.9
186.9
63.3
67
16.2
180.7
141.7
179.4
128.8
178.2
114.5
176.9
101.9
175.7
89.1
173.8
74.8
171.5
60.1
62
15.8
176.4
162.3
168.4
150.8
166.0
137.8
164.7
125.0
163.1
111.5
162.0
98.4
160.6
85.6
57
15.6
176.3
162.2
170.6
157.0
165.0
151.8
164.7
125.0
152.5
133.8
150.4
120.7
148.7
107.2
72
16.7
197.5
127.3
196.4
112.1
195.1
97.5
193.2
82.0
190.7
65.0
67
16.3
185.9
154.3
184.4
139.1
182.6
122.9
181.2
108.3
179.8
93.7
177.8
78.2
175.2
61.1
62
16.1
185.4
170.6
179.5
165.1
172.1
149.9
169.5
134.7
167.4
119.3
166.3
104.2
164.8
89.6
57
16.0
185.3
170.5
179.4
165.0
173.4
159.5
167.5
154.1
161.5
148.5
155.2
130.1
164.8
89.6
72
16.8
199.9
133.4
198.8
117.0
197.3
100.7
195.3
84.8
192.7
66.2
67
16.3
189.8
162.6
187.1
146.0
185.0
128.7
183.5
112.5
182.0
96.6
179.9
80.5
163.2
146.9
62
16.2
190.6
175.3
184.4
169.7
175.3
157.5
172.2
141.2
170.5
125.3
168.5
108.0
167.0
92.1
57
16.1
190.5
175.2
184.3
169.6
178.2
163.9
172.1
158.3
166.0
152.7
158.6
136.6
156.0
120.1
72
16.9
204.7
145.3
202.3
125.5
200.7
106.7
198.6
88.4
195.7
68.3
67
16.5
196.3
177.9
191.2
158.3
189.7
139.4
187.1
120.6
185.4
101.8
183.1
83.7
180.0
62.9
62
16.3
198.7
182.8
192.2
176.9
185.7
170.8
177.5
153.3
174.5
134.4
172.1
115.3
170.3
96.6
57
16.2
198.5
182.7
192.1
176.8
185.7
170.8
179.3
164.9
172.9
159.1
163.2
146.9
159.9
128.5
72
16.9
206.2
150.1
203.6
129.3
202.0
109.3
199.8
90.0
196.8
69.3
67
16.6
201.9
185.7
194.0
164.5
191.3
143.8
188.4
124.0
186.7
104.1
184.3
85.0
181.1
63.4
62
16.4
201.8
185.6
195.2
179.6
188.7
173.6
179.4
158.0
176.0
138.7
173.4
118.3
171.5
98.6
57
16.3
201.6
185.5
195.1
179.5
188.6
173.5
181.8
167.3
175.3
161.3
166.3
152.0
161.3
132.2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.
036-21035-002-D-0602
Air On Evaporator
Coil
CFM
4500
5250
5765
6750
7200
86
80
83
77
74
71
68
WB F
Tot.1
Input
(kW)
TOT2
72
17.7
182.9
114.7
181.9
101.4
180.6
88.8
178.8
74.6
176.5
59.9
67
17.2
171.3
137.9
170.0
124.9
168.6
110.7
167.3
98.2
165.9
85.3
153.6
141.3
162.0
56.7
62
16.9
168.5
155.1
161.0
146.8
157.0
133.5
155.8
120.9
154.0
107.4
152.9
94.4
151.5
81.5
57
16.7
168.4
155.0
162.9
149.9
157.4
144.8
151.9
139.7
144.3
129.3
142.0
116.4
140.1
103.1
72
17.9
186.9
123.8
185.8
108.5
184.3
93.6
182.4
78.7
179.9
61.6
67
17.2
176.8
150.6
174.5
135.3
172.5
118.9
171.2
104.4
169.8
89.8
142.0
116.4
165.4
57.7
62
17.2
176.9
162.8
171.1
157.4
163.0
145.6
160.3
130.7
169.8
89.8
156.8
100.3
155.2
85.4
57
17.0
176.8
162.7
171.0
157.3
165.2
152.0
159.4
146.7
157.9
115.0
147.0
126.2
144.7
110.9
72
18.0
189.8
130.4
187.9
113.1
186.4
96.8
184.4
81.0
181.7
62.8
67
17.6
189.8
130.4
177.0
142.1
175.5
125.1
173.3
108.8
171.7
92.6
169.6
76.8
167.1
58.3
62
17.2
181.7
167.2
175.7
161.7
167.3
152.7
162.6
136.7
161.0
121.0
158.9
104.1
157.2
87.9
57
17.1
181.6
167.1
175.6
161.6
169.6
156.1
163.7
150.6
157.7
145.1
158.9
104.1
147.0
115.6
72
18.1
193.5
141.3
191.0
121.6
189.4
102.8
187.3
84.5
184.0
64.8
67
17.7
189.3
174.1
181.9
154.8
179.3
135.2
176.5
116.5
174.8
97.7
172.5
79.7
169.7
59.4
62
17.4
189.1
174.0
182.9
168.3
176.7
162.5
167.9
148.7
164.7
130.2
162.1
111.0
160.3
92.4
57
17.3
189.0
173.9
182.8
168.2
176.6
162.4
170.3
156.7
164.1
151.0
158.0
145.3
150.5
124.1
72
18.1
194.9
146.0
192.2
125.4
190.6
105.3
188.4
86.0
185.3
65.9
67
17.7
192.1
176.7
183.6
159.8
180.6
139.5
177.7
119.9
175.9
100.0
173.5
80.9
170.1
59.8
62
17.5
192.0
176.6
185.6
170.8
179.3
165.0
170.7
153.7
166.0
134.3
163.2
114.1
161.1
94.1
57
17.4
191.9
176.5
185.5
170.7
179.2
164.9
172.9
159.0
166.5
153.2
160.2
147.4
151.9
127.8
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.
Nominal Rating
036-21035-002-D-0602
Air On Evaporator
Coil
CFM
4500
5250
5765
6750
7200
86
83
80
77
74
71
68
WB F
Tot.1
Input
(kW)
TOT2
72
18.3
144.7
110.9
67
18.2
161.5
133.9
62
17.8
160.1
147.3
160.1
120.8
148.6
129.3
146.6
116.7
144.7
103.3
143.6
90.2
142.1
77.4
57
17.6
160.0
147.2
154.6
142.3
149.3
137.3
143.9
132.4
138.5
127.4
143.6
90.2
131.2
98.5
72
19.0
175.6
119.6
174.6
104.6
173.3
89.2
170.9
74.9
169.1
58.3
67
18.5
166.7
145.5
164.3
131.1
162.9
115.6
160.8
100.5
169.1
58.3
157.5
70.8
154.5
53.9
62
18.1
168.0
154.6
162.2
149.2
156.6
144.0
160.8
100.5
149.0
111.6
147.1
96.0
145.6
81.1
57
17.9
167.9
154.5
162.1
149.1
156.5
143.9
150.6
126.4
145.3
133.7
138.1
120.7
135.6
106.4
72
18.9
178.6
126.3
176.5
109.2
175.1
92.4
172.6
76.9
160.8
148.0
67
18.5
170.6
154.0
166.4
137.4
165.1
121.0
162.7
104.7
161.1
88.4
158.4
72.4
156.0
54.5
62
18.2
172.4
158.6
166.6
153.3
160.6
147.8
153.7
132.3
151.2
116.5
148.9
99.7
147.3
83.7
57
18.1
172.3
158.5
166.5
153.2
160.5
147.7
154.7
142.3
148.8
136.9
141.6
127.4
137.7
111.1
72
19.1
181.9
137.0
179.3
117.6
177.7
98.1
175.3
80.7
173.0
61.6
67
18.7
179.2
164.9
171.1
149.4
168.4
130.8
165.5
112.3
163.8
93.5
160.9
75.5
158.6
55.7
62
18.5
179.1
164.8
173.1
159.3
167.1
153.8
159.0
143.8
154.4
125.6
151.8
106.7
149.9
88.0
57
18.4
179.0
164.7
173.0
159.2
167.0
153.7
160.8
148.0
154.8
142.4
148.9
136.9
140.9
119.1
72
19.2
183.1
141.7
180.4
121.3
178.7
100.7
176.7
81.5
173.1
62.3
67
18.8
181.8
167.3
173.9
155.7
169.6
135.1
166.6
115.7
164.8
95.7
161.8
76.8
159.3
56.2
62
18.6
181.3
166.8
175.3
161.2
169.5
155.9
163.4
150.3
155.7
129.7
152.8
109.7
159.3
56.2
57
18.5
181.2
166.7
175.5
161.5
169.4
155.9
163.3
150.2
157.0
144.4
150.7
138.7
143.0
123.5
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
171.1
97.2
170.0
84.4
168.4
71.2
166.2
56.6
171.1
97.2
170.0
84.4
157.3
94.2
156.0
81.3
154.4
67.8
138.1
120.7
SEN
TOT2
SEN
1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.
036-21035-002-D-0602
Air On Evaporator
Coil
CFM
4500
5250
5765
6750
7200
86
83
80
77
74
71
68
WB F
Tot.1
Input
(kW)
TOT2
72
19.9
161.0
67
19.4
151.8
62
18.8
151.4
139.3
146.2
134.5
139.3
124.8
57
18.6
151.4
139.3
146.2
134.5
141.2
129.9
72
20.1
164.8
115.7
163.0
100.1
161.7
85.2
160.0
70.8
157.4
54.7
67
19.4
157.3
142.4
153.5
126.6
152.2
110.7
150.1
96.3
148.6
81.0
146.7
66.7
143.9
50.3
62
19.1
158.4
145.7
153.0
140.7
147.6
135.8
141.4
121.6
139.0
106.5
137.1
91.8
143.9
50.3
57
18.9
158.3
145.7
152.9
140.7
147.5
135.7
142.2
130.9
136.8
125.8
129.9
116.9
126.2
101.2
72
20.2
166.7
121.4
164.6
104.5
163.3
88.3
161.4
72.6
158.8
55.9
67
19.7
162.6
149.6
156.4
133.6
163.3
88.3
151.7
100.4
150.2
83.7
148.0
67.8
144.2
50.5
62
19.3
162.3
149.3
156.8
144.2
163.3
88.3
143.8
127.5
140.9
111.4
138.6
94.8
137.1
78.7
57
19.1
162.2
149.3
156.7
144.2
151.1
139.0
145.5
133.9
140.1
128.9
134.5
123.7
128.1
105.7
72
20.3
169.6
132.0
167.8
113.6
165.6
94.0
163.7
75.9
160.5
57.9
67
19.7
168.7
155.2
161.2
145.3
157.1
126.2
154.8
108.1
152.6
88.7
148.9
70.9
145.4
51.4
62
19.5
168.4
154.9
162.7
149.7
156.9
144.4
151.3
139.2
144.6
121.0
141.8
102.1
139.4
82.9
57
19.4
168.3
154.8
162.6
149.6
156.8
144.3
151.1
139.1
145.3
133.7
139.5
128.4
131.9
114.2
72
20.3
170.6
136.6
168.8
117.2
166.5
96.5
164.5
77.4
160.5
58.7
67
19.9
170.9
157.3
165.2
151.9
158.9
130.7
164.5
77.4
160.5
58.7
149.6
72.1
143.6
51.0
62
19.6
170.7
157.0
165.1
151.9
159.2
146.5
153.4
141.1
145.9
124.6
142.9
105.0
140.2
84.8
57
19.5
170.6
156.9
165.0
151.8
159.2
146.4
153.3
141.0
147.3
135.5
141.4
130.1
133.2
118.2
TOT2
SEN
106.8
158.3
145.7
158.8
80.6
157.2
67.7
154.2
52.8
129.4
149.8
116.0
158.8
80.6
157.2
67.7
145.7
76.8
143.9
64.1
140.5
49.0
147.0
89.6
135.6
99.6
134.0
85.5
132.6
72.8
136.0
125.1
130.7
120.3
124.9
108.0
132.6
72.8
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.
10
036-21035-002-D-0602
Air On Evaporator
Coil
86
83
80
77
74
71
68
CFM
6000
7000
8000
9000
9400
WB F
Tot.
Input
(kW)
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
72
21.9
247.8
169.2
246.6
149.6
245.2
130.5
243.1
109.8
240.1
88.6
67
21.5
232.2
203.8
230.8
184.4
229.5
163.5
228.0
145.2
226.5
126.0
224.3
105.5
221.2
84.2
62
21.1
226.6
226.6
219.6
219.6
214.0
198.6
212.7
179.2
210.9
159.5
209.7
140.2
208.1
121.0
57
20.8
226.5
226.5
219.5
219.5
212.4
212.4
205.4
205.4
197.3
192.7
194.9
173.3
192.9
153.2
72
22.0
252.8
182.7
251.6
160.2
249.8
138.1
247.7
115.6
243.7
90.7
67
21.6
238.9
222.6
236.8
200.4
234.8
176.6
233.1
154.7
231.1
132.5
228.9
110.3
220.7
83.6
62
21.3
237.8
237.8
230.4
230.4
221.3
216.3
218.5
194.2
216.8
172.0
214.7
148.9
213.0
126.7
57
21.2
237.7
237.7
230.3
230.3
222.8
222.8
215.5
215.5
208.1
208.1
201.1
187.4
198.9
165.3
72
22.1
257.7
196.6
255.3
170.4
253.6
145.1
251.1
120.5
247.0
93.0
67
21.7
245.6
241.5
241.3
215.9
239.7
189.5
236.9
164.0
234.7
138.7
232.3
114.5
217.2
82.4
62
21.5
246.7
246.7
239.0
239.0
231.2
231.2
223.7
208.5
221.1
183.5
218.6
157.5
216.4
132.3
57
21.3
246.6
246.6
238.9
238.9
231.2
231.2
223.5
223.5
215.8
215.8
206.3
200.9
203.2
175.9
72
22.3
261.3
210.1
258.2
180.4
256.4
152.0
252.6
123.4
240.7
92.4
67
21.8
254.1
254.1
245.9
230.5
243.2
201.2
239.9
173.4
237.9
144.8
234.9
117.6
62
21.6
254.0
254.0
246.1
246.1
238.1
238.1
228.2
222.7
224.6
194.4
221.6
165.6
219.2
137.4
57
21.5
253.9
253.9
245.9
245.9
238.0
238.0
230.0
230.0
222.1
222.1
214.1
214.1
206.5
185.6
72
22.4
262.5
215.1
259.2
184.4
257.4
154.7
253.4
124.9
248.5
95.7
67
21.9
256.7
256.7
247.4
235.9
244.4
205.8
240.9
177.0
238.8
147.1
235.8
118.8
62
21.7
256.6
256.6
248.5
248.5
240.4
240.4
230.9
228.6
225.8
198.7
222.6
168.8
220.2
139.3
57
21.6
256.4
256.4
248.4
248.4
240.4
240.4
232.3
232.3
224.3
224.3
216.2
216.2
207.8
189.6
1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.
11
036-21035-002-D-0602
Air On Evaporator
Coil
86
83
80
77
74
71
68
CFM
6000
7000
8000
9000
9400
WB F
Tot.
Input
(kW)
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
72
23.5
234.3
164.0
233.1
144.3
231.4
125.3
229.5
105.0
224.1
82.9
67
23.1
219.5
197.9
218.2
178.6
216.8
158.0
215.4
139.5
213.8
120.5
211.6
100.5
207.9
79.0
62
22.7
216.3
216.3
209.2
209.2
202.8
192.5
200.8
173.0
199.0
153.8
197.8
134.4
196.1
115.2
57
22.4
216.2
216.2
209.4
209.4
202.5
202.5
195.6
195.6
188.6
188.6
183.6
166.8
181.7
147.3
72
23.6
239.6
178.5
237.5
154.8
235.9
132.6
233.6
110.8
229.0
85.7
67
23.2
226.1
216.7
223.7
194.8
222.4
171.7
219.9
149.1
217.9
126.9
215.6
105.2
202.3
76.7
62
22.9
226.6
226.6
219.4
219.4
212.1
212.1
206.1
187.9
204.5
165.7
202.4
142.9
200.5
120.9
57
22.7
226.5
226.5
219.3
219.3
212.1
212.1
204.9
204.9
197.6
197.6
189.7
181.0
187.2
158.7
72
23.7
243.3
191.1
240.9
165.0
239.2
139.6
236.6
115.0
230.0
87.4
67
23.4
234.9
234.9
240.9
165.0
226.3
183.8
223.3
158.3
221.5
133.1
217.7
108.2
215.9
82.0
62
23.1
234.8
234.8
227.2
227.2
219.8
219.8
211.4
202.2
208.4
176.9
205.8
151.2
203.8
126.1
57
22.9
234.7
234.7
227.1
227.1
219.6
219.6
212.3
212.3
204.8
204.8
197.2
197.2
191.1
169.0
72
23.8
246.7
204.4
243.5
174.9
241.6
146.4
237.6
117.6
237.9
91.6
67
23.5
241.6
241.6
232.3
224.0
229.2
194.9
226.0
167.3
224.0
139.0
220.8
111.6
209.5
79.8
62
23.2
241.5
241.5
233.8
233.8
226.1
226.1
218.4
218.4
211.5
187.7
208.5
159.2
206.3
131.1
57
23.1
241.3
241.3
233.7
233.7
225.8
225.8
218.1
218.1
210.4
210.4
202.8
202.8
194.3
179.2
72
23.9
247.4
208.8
245.2
179.6
242.5
149.1
238.2
119.1
230.7
89.8
67
23.6
243.9
243.9
234.8
230.5
230.3
199.4
227.7
171.5
224.8
141.3
221.5
112.7
62
23.3
243.8
243.8
236.0
236.0
228.3
228.3
220.5
220.5
212.7
192.2
210.2
163.0
207.1
133.0
57
23.2
243.7
243.7
235.9
235.9
228.0
228.0
220.2
220.2
212.4
212.4
204.7
204.7
196.1
183.3
1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.
Nominal Rating
12
036-21035-002-D-0602
Air On Evaporator
Coil
86
83
80
77
74
71
68
CFM
6000
7000
8000
9000
9400
WB F
Tot.
Input
(kW)
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
72
25.1
220.4
158.8
219.1
138.9
217.6
119.8
215.4
100.1
209.0
77.7
67
24.5
207.2
192.5
205.4
173.0
203.8
152.5
202.3
133.9
200.7
114.9
198.3
95.3
193.8
73.5
62
24.0
205.6
205.6
198.9
198.9
191.0
186.5
188.7
167.2
187.2
148.1
185.5
128.4
183.8
109.4
57
23.7
205.5
205.5
198.8
198.8
192.1
192.1
185.4
185.4
178.4
178.4
172.2
160.8
170.7
141.6
72
25.2
225.1
172.3
223.0
149.3
221.4
127.0
219.0
105.4
213.8
80.6
67
24.6
214.0
211.5
210.3
189.1
208.8
165.4
206.4
143.4
204.4
120.2
201.9
99.8
199.4
75.6
62
24.3
215.0
215.0
208.1
208.1
201.1
201.1
194.3
182.2
191.9
159.7
189.6
137.0
187.1
114.4
57
24.1
214.9
214.9
208.0
208.0
201.0
201.0
193.9
193.9
186.9
186.9
178.1
174.5
175.3
152.4
72
25.4
228.5
185.3
226.0
159.4
224.2
134.0
221.6
109.3
218.8
79.6
67
24.9
222.5
222.5
214.9
203.8
212.5
177.9
209.4
152.5
207.5
127.3
203.5
102.3
62
24.5
222.4
222.4
215.2
215.2
208.0
208.0
199.6
196.6
195.4
170.8
192.5
145.2
189.9
119.8
57
24.4
222.3
222.3
215.1
215.1
208.0
208.0
200.7
200.7
193.4
193.4
186.0
186.0
178.8
163.0
72
25.5
231.2
198.0
229.1
169.8
226.4
140.7
223.5
113.1
219.6
81.7
67
25.0
228.3
228.3
219.6
217.8
215.1
188.8
212.6
161.9
209.7
133.0
205.9
105.8
62
24.7
228.2
228.2
220.8
220.8
213.7
213.7
206.2
206.2
199.0
182.0
195.6
153.5
192.7
124.8
57
24.5
228.1
228.1
220.7
220.7
213.6
213.6
206.1
206.1
198.6
198.6
191.0
191.0
182.5
172.5
72
25.6
232.2
203.0
230.0
173.6
227.2
143.3
224.2
114.5
183.7
72.1
67
25.1
230.4
230.4
223.1
223.1
216.0
193.2
213.5
165.3
210.5
135.2
206.9
106.6
62
24.8
230.3
230.3
222.9
222.9
215.6
215.6
208.1
208.1
200.1
185.9
196.5
156.4
193.5
126.7
57
24.6
230.1
230.1
222.8
222.8
215.3
215.3
208.0
208.0
200.4
200.4
192.8
192.8
183.6
176.0
1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.
13
036-21035-002-D-0602
Air On Evaporator
Coil
86
83
80
77
74
71
68
CFM
6000
7000
8000
9000
9400
WB F
Tot.
Input
(kW)
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
TOT2
SEN
72
26.5
206.3
153.2
204.4
132.6
203.2
114.2
199.3
94.3
192.0
71.9
67
25.8
194.2
186.8
192.1
167.5
190.9
147.2
188.9
128.2
187.2
109.1
184.6
90.1
178.8
178.8
62
25.4
194.1
194.1
187.6
187.6
181.4
181.4
176.2
161.3
187.2
109.1
172.9
122.4
171.1
103.4
57
24.9
194.0
194.0
187.6
187.6
181.1
181.1
174.5
174.5
167.9
167.9
161.1
154.8
158.9
135.4
72
26.6
210.3
166.6
207.7
142.9
205.6
120.4
203.9
99.6
203.6
77.1
67
26.1
202.9
202.9
197.0
183.2
195.0
159.4
192.4
137.5
190.6
115.3
187.6
93.6
62
25.6
202.8
202.8
196.1
196.1
189.2
189.2
181.6
175.7
178.9
153.5
176.5
130.8
173.6
108.1
57
25.4
202.7
202.7
196.0
196.0
189.3
189.3
182.5
182.5
175.7
175.7
168.5
168.5
163.0
146.0
72
26.7
213.4
179.5
211.3
154.3
208.9
128.1
206.0
103.0
202.7
77.4
67
26.3
209.5
209.5
201.7
198.1
198.1
171.2
195.8
147.1
193.1
121.2
187.9
96.1
147.9
57.4
62
25.9
209.4
209.4
202.6
202.6
195.5
195.5
195.8
147.1
182.1
164.4
179.9
139.4
176.9
113.6
57
25.7
209.3
209.3
202.5
202.5
195.6
195.6
188.6
188.6
181.5
181.5
174.2
174.2
166.9
156.4
72
26.8
216.3
192.6
213.6
163.7
210.8
134.7
207.5
106.3
203.7
77.6
67
26.5
214.7
214.7
207.8
207.8
201.3
183.1
198.1
155.6
195.0
126.8
190.2
98.8
62
26.1
214.6
214.6
207.7
207.7
200.6
200.6
193.5
193.5
185.5
175.4
182.2
146.9
178.8
118.3
57
26.0
214.5
214.5
207.6
207.6
200.6
200.6
193.4
193.4
186.2
186.2
178.8
178.8
170.6
166.6
72
26.9
217.7
198.2
214.4
167.4
211.4
137.3
207.9
107.6
204.6
77.8
67
26.6
216.6
216.6
209.6
209.6
202.3
187.2
198.9
158.9
195.7
128.9
187.8
96.9
62
26.2
216.4
216.4
209.5
209.5
202.4
202.4
195.2
195.2
186.6
178.8
183.0
149.8
179.5
120.1
57
26.1
216.4
216.4
209.4
209.4
202.3
202.3
195.1
195.1
187.8
187.8
180.4
180.4
171.9
170.6
1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.
14
036-21035-002-D-0602
CFM
MOTOR
PULLEY
(TURNS
OPEN)3
4500
4
ESP
BHP
5250
KW
ESP
6000
3
6750
BHP
KW
ESP
BHP
KW
ESP
7200
3
BHP
KW
ESP
BHP
KW
6.05
0.9
2.4
2.1
0.6
2.9
2.6
0.3
3.4
3.0
870
5.5
1.0
2.5
2.2
0.7
3.0
2.7
0.4
3.5
3.1
915
4.5
1.1
2.6
2.4
0.8
3.1
2.8
0.5
3.6
3.2
0.2
4.1
3.7
965
3.5
1.2
2.7
2.5
0.9
3.2
2.9
0.6
3.7
3.3
0.4
4.4
3.9
0.2
5.0
4.5
980
3.0
1.3
2.9
2.6
1.0
3.4
3.0
0.7
3.8
3.4
0.5
4.5
4.0
0.3
5.1
4.6
1010
2.0
1.4
3.0
2.7
1.1
3.6
3.2
0.8
4.0
3.6
0.6
4.7
4.2
0.4
5.4
4.8
1040
1.0
1.6
3.2
2.9
1.3
3.8
3.4
1.0
4.4
3.9
0.8
5.0
4.5
0.6
5.6
5.0
6.0
1.2
2.7
2.5
0.9
3.2
2.9
0.6
3.7
3.3
0.4
4.4
3.9
0.2
5.0
4.5
980
5.5
1.3
2.9
2.6
1.0
3.4
3.0
0.7
3.8
3.4
0.5
4.5
4.0
0.3
5.1
4.6
1025
4.5
1.4
3.1
2.8
1.2
3.6
3.2
0.9
4.1
3.7
0.7
4.8
4.3
0.4
5.5
4.9
1065
3.5
1.6
3.4
3.0
1.4
3.9
3.5
1.1
4.5
4.0
0.9
5.1
4.6
1125
2.0
1.9
3.6
3.2
1.7
4.4
3.9
1.4
5.0
4.5
1.2
5.8
5.2
1170
1.0
2.1
3.9
3.5
1.9
4.7
4.2
1.6
5.5
4.9
6.04
1.0
2.5
2.2
0.7
3.0
2.7
0.4
3.5
3.1
915
5.0
1.1
2.6
2.4
0.8
3.1
2.8
0.5
3.6
3.2
0.2
4.1
3.7
965
4.0
1.2
2.7
2.5
0.9
3.2
2.9
0.6
3.7
3.3
0.4
4.4
3.9
0.2
5.0
4.5
980
3.5
1.3
2.9
2.6
1.0
3.4
3.0
0.7
3.8
3.4
0.5
4.5
4.0
0.3
5.1
4.6
1015
2.5
1.4
3.0
2.7
1.1
3.6
3.2
0.8
4.0
3.6
0.6
4.7
4.2
0.4
5.4
4.8
1050
1.5
1.5
3.1
2.8
1.2
3.7
3.3
0.9
4.2
3.8
0.7
4.9
4.4
0.5
5.7
5.1
1065
1.0
1.6
3.4
3.0
1.4
3.9
3.5
1.1
4.5
4.0
0.9
5.1
4.6
6.0
1.3
2.9
2.6
1.0
3.4
3.0
0.7
3.8
3.4
0.5
4.5
4.0
0.3
5.1
4.6
1045
4.5
1.6
3.2
2.9
1.3
3.8
3.4
1.0
4.4
3.9
0.8
5.0
4.5
0.6
5.6
5.0
1065
4.0
1.7
3.4
3.0
1.4
3.9
3.5
1.1
4.5
4.0
0.9
5.1
4.6
1125
2.5
1.9
3.6
3.2
1.7
4.4
3.9
1.4
5.0
4.5
1.2
5.8
5.2
1170
1.5
2.1
3.9
3.5
1.8
4.7
4.2
1.6
5.5
4.9
1190
1.0
2.2
4.0
3.6
1.9
4.8
4.3
1.7
5.6
5.0
1.
2.
3.
4.
Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2 T/A filters and a dry evaporator coil.
Refer to the Static Resistance table.
DO NOT close the pulley below one turn open.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been
deducted from the total static pressure of the blower.
5. The factory setting.
15
036-21035-002-D-0602
CFM
MOTOR
PULLEY
(TURNS
OPEN)3
6000
4
ESP
BHP
7000
KW
8000
ESP
BHP
KW
ESP
9000
BHP
KW
ESP
9400
BHP
KW
ESP
BHP
KW
6.05
1.3
3.6
3.0
0.7
4.3
3.7
0.2
5.1
4.3
900
5.0
1.4
3.8
3.2
0.9
4.7
4.0
0.4
5.6
4.7
930
4.0
1.6
4.1
3.4
1.1
5.0
4.2
0.6
5.9
5.0
0.1
6.7
5.7
950
3.0
1.7
4.2
3.6
1.3
5.1
4.3
0.8
6.0
5.1
0.2
6.9
5.8
980
2.0
1.9
4.5
3.8
1.5
5.4
4.5
1.0
6.3
5.3
0.4
7.2
6.1
0.1
8.5
7.1
995
1.5
2.1
4.6
3.9
1.6
5.5
4.7
1.1
6.4
5.4
0.5
7.5
6.3
0.2
8.6
7.3
1015
1.0
2.2
4.8
4.0
1.7
5.7
4.8
1.2
6.6
5.6
0.7
7.8
6.6
6.0
1.7
4.2
3.6
1.3
5.1
4.3
0.8
6.0
5.1
0.2
6.9
5.8
980
5.0
1.9
4.5
3.8
1.5
5.4
4.5
1.0
6.3
5.3
0.4
7.2
6.1
0.1
8.5
7.1
995
4.5
2.1
4.6
3.9
1.6
5.5
4.7
1.1
6.4
5.4
0.5
7.5
6.3
0.2
8.6
7.3
1025
3.5
2.3
4.9
4.1
1.8
5.8
4.9
1.3
6.7
5.7
0.7
8.0
6.7
1050
2.5
2.5
5.1
4.3
2.0
6.1
5.1
1.4
7.1
6.0
0.9
8.4
7.0
1065
2.0
2.6
5.3
4.4
2.1
6.3
5.3
1.5
7.3
6.2
1.0
8.6
7.2
1100
1.0
2.9
5.6
4.7
2.3
6.8
5.7
1.8
7.9
6.6
6.05
1.3
3.6
3.0
0.7
4.3
3.7
0.2
5.1
4.3
900
5.0
1.4
3.8
3.2
0.9
4.7
4.0
0.4
5.6
4.7
930
4.0
1.6
4.1
3.4
1.1
5.0
4.2
0.6
5.9
5.0
0.1
6.7
5.7
950
3.5
1.7
4.2
3.6
1.3
5.1
4.3
0.8
6.0
5.1
0.2
6.9
5.8
965
2.5
1.9
4.5
3.8
1.5
5.4
4.5
1.0
6.3
5.3
0.4
7.2
6.1
0.1
8.5
7.1
995
2.0
2.1
4.6
3.9
1.6
5.5
4.7
1.1
6.4
5.4
0.5
7.5
6.3
0.2
8.6
7.3
1015
1.5
2.2
4.8
4.0
1.7
5.7
4.8
1.2
6.6
5.6
0.6
7.8
6.6
1025
1.0
2.3
4.9
4.1
1.8
5.8
4.9
1.3
6.7
5.7
0.7
8.0
6.7
6.0
1.7
4.2
3.6
1.3
5.1
4.3
0.8
6.0
5.1
0.2
6.9
5.8
980
5.0
1.9
4.5
3.8
1.5
5.4
4.5
1.0
6.3
5.3
0.4
7.2
6.1
0.1
8.5
7.1
995
4.5
2.1
4.6
3.9
1.6
5.5
4.7
1.1
6.4
5.4
0.5
7.5
6.3
0.2
8.6
7.3
1015
4.0
2.2
4.8
4.0
1.7
5.7
4.8
1.2
6.6
5.6
0.6
7.8
6.6
1025
3.5
2.3
4.9
4.1
1.8
5.8
4.9
1.3
6.7
5.7
0.7
8.0
6.7
1050
3.0
2.5
5.1
4.3
2.0
6.1
5.1
1.4
7.1
6.0
0.9
8.4
7.0
1065
2.5
2.6
5.3
4.4
2.1
6.3
5.3
1.5
7.3
6.2
1.0
8.6
7.2
1100
1.5
2.9
5.6
4.7
2.3
6.8
5.7
1.8
7.9
6.6
1120
1.0
3.1
5.8
4.9
2.5
7.0
5.9
1.9
8.3
6.9
1.
2.
3.
4.
Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2 T/A filters and a dry evaporator coil.
Refer to the Static Resistance table.
DO NOT close the pulley below one turn open.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have
been deducted from the total static pressure of the blower.
5. The Factory Setting.
16
036-21035-002-D-0602
CFM
MOTOR
PULLEY
(TURNS
OPEN)3
4500
ESP
BHP
5250
4
KW
ESP
BHP
6000
KW
ESP
BHP
6750
KW
ESP
BHP
7200
KW
ESP
BHP
KW
6.05
0.9
2.4
2.2
0.7
3.0
2.7
0.5
3.2
2.9
870
5.5
1.0
2.5
2.3
0.8
3.1
2.8
0.6
3.5
3.1
0.2
4.1
3.7
915
4.5
1.1
2.6
2.4
0.9
3.4
3.0
0.7
3.7
3.3
0.3
4.4
3.9
0.2
4.5
4.0
965
3.5
1.2
2.9
2.6
1.0
3.6
3.2
0.8
4.0
3.6
0.5
4.7
4.2
0.4
4.9
4.4
980
3.0
1.3
3.0
2.7
1.1
3.7
3.3
0.9
4.1
3.7
0.6
4.8
4.3
0.5
5.1
4.6
1010
2.0
1.4
3.1
2.8
1.2
3.8
3.4
1.0
4.2
3.8
0.7
5.0
4.5
0.6
5.4
4.8
1040
1.0
1.5
3.2
2.9
1.3
3.9
3.5
1.1
4.5
4.0
0.9
5.2
4.7
0.7
5.7
5.1
6.0
1.2
2.9
2.6
1.0
3.6
3.2
0.8
4.0
3.6
0.5
4.7
4.2
0.4
5.0
4.4
980
5.5
1.3
3.0
2.7
1.1
3.7
3.3
0.9
4.1
3.7
0.6
4.8
4.3
0.5
5.1
4.6
1025
4.5
1.5
3.2
2.9
1.3
3.9
3.5
1.1
4.5
4.0
0.8
5.1
4.6
0.7
5.6
5.0
1065
3.5
1.6
3.4
3.0
1.4
4.0
3.6
1.2
4.7
4.2
1.0
5.5
4.9
1095
3.0
1.7
3.5
3.1
1.5
4.2
3.8
1.3
4.9
4.4
1.2
5.7
5.1
1130
2.0
1.9
3.7
3.3
1.7
4.5
4.0
1.5
5.1
4.6
1170
1.0
2.1
3.9
3.5
2.0
4.7
4.2
1.8
5.5
4.9
6.05
1.0
2.4
2.2
0.8
3.1
2.8
0.6
3.5
3.1
0.2
4.1
3.7
915
5.0
1.1
2.6
2.4
0.9
3.3
3.0
0.7
3.7
3.3
0.3
4.4
3.9
0.2
4.5
4.0
965
4.0
1.2
2.9
2.6
1.0
3.6
3.2
0.8
4.0
3.6
0.5
4.7
4.2
0.4
5.0
4.4
980
3.5
1.3
3.0
2.7
1.1
3.7
3.3
0.9
4.1
3.7
0.6
4.8
4.3
0.5
5.1
4.6
1040
2.0
1.5
3.2
2.9
1.3
3.9
3.5
1.1
4.5
4.0
0.9
5.3
4.7
0.7
5.7
5.1
1065
1.0
1.6
3.3
3.0
1.4
4.0
3.6
1.2
4.7
4.2
1.0
5.5
4.9
6.0
1.3
2.9
2.6
1.1
3.7
3.3
0.9
4.1
3.7
0.6
4.8
4.3
0.5
5.1
4.6
1040
4.5
1.5
3.2
2.9
1.3
3.9
3.5
1.1
4.5
4.0
0.9
5.3
4.7
0.7
5.7
5.1
1065
4.0
1.6
3.4
3.0
1.4
4.0
3.6
1.2
4.7
4.2
1.0
5.5
4.9
1095
3.5
1.7
3.5
3.1
1.5
4.2
3.8
1.3
4.9
4.4
1.2
5.7
5.1
1130
2.5
1.9
3.7
3.3
1.7
4.5
4.0
1.5
5.1
4.6
1170
1.5
2.1
3.9
3.5
2.0
4.7
4.2
1.8
5.5
4.9
1190
1.0
2.2
4.0
3.6
2.1
4.8
4.3
2.0
5.7
5.1
1.
2.
3.
4.
Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2 T/A filters and a dry evaporator coil.
Refer to the Static Resistance table.
DO NOT close the pulley below one turn open.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been
deducted from the total static pressure of the blower.
5. The Factory Setting.
17
036-21035-002-D-0602
CFM
MOTOR
PULLEY
(TURNS
OPEN)3
600
ESP
BHP
7000
KW
ESP
8000
BHP
KW
ESP
BHP
9000
4
9400
KW
ESP
BHP
KW
ESP
BHP
KW
6.05
0.4
2.1
1.8
0.1
2.3
2.0
900
5.0
0.8
3.2
2.7
0.5
3.5
2.9
0.2
3.8
3.2
930
4.0
1.1
4.1
3.4
0.9
4.5
3.8
0.6
4.9
4.1
0.1
5.1
4.3
950
3.0
1.3
4.6
3.9
1.1
5.1
4.3
0.8
5.5
4.6
0.4
5.9
5.0
980
2.0
1.6
5.3
4.5
1.4
5.8
4.9
1.2
6.3
5.3
0.7
6.9
5.8
0.2
7.3
6.1
1015
1.0
1.9
5.9
5.0
1.7
6.5
5.5
1.5
7.0
5.9
1.0
7.7
6.5
0.6
8.2
6.9
6.0
1.3
4.6
3.9
1.1
5.1
4.3
0.8
5.5
4.6
0.4
5.9
5.0
980
5.0
1.6
5.3
4.5
1.4
5.8
4.9
1.2
6.3
5.3
0.7
6.9
5.8
0.2
7.3
6.1
1010
4.0
1.8
5.8
4.9
1.7
6.3
5.3
1.5
6.9
5.8
1.0
7.5
6.3
0.5
7.9
6.7
1020
3.5
1.9
6.1
5.1
1.8
6.5
5.5
1.6
7.1
6.0
1.1
7.8
6.6
0.6
8.3
7.0
1035
3.0
2.0
6.2
5.2
1.9
6.8
5.7
1.7
7.4
6.2
1.2
8.1
6.8
0.7
8.6
7.3
1050
2.5
2.1
6.4
5.4
2.0
7.0
5.9
1.8
7.6
6.4
1.3
8.3
7.0
1075
2.0
2.3
6.6
5.5
2.1
7.2
6.0
1.9
7.8
6.6
1.5
8.6
7.2
1100
1.0
2.4
6.7
5.6
2.2
7.3
6.1
2.1
7.9
6.7
6.05
0.4
2.1
1.8
0.1
2.3
2.0
900
5.0
0.8
3.2
2.7
0.5
3.5
2.9
0.2
3.8
3.2
930
4.0
1.1
4.1
3.4
0.9
4.5
3.8
0.6
4.9
4.1
0.1
5.1
4.3
950
3.5
1.3
4.6
3.9
1.1
5.1
4.3
0.8
5.5
4.6
0.4
5.9
5.0
980
2.5
1.6
5.3
4.5
1.4
5.8
4.9
1.2
6.3
5.3
0.7
6.9
5.8
0.2
7.3
6.1
1015
1.5
1.9
5.9
5.0
1.7
6.5
5.5
1.5
7.0
5.9
1.0
7.7
6.5
0.6
8.2
6.9
1025
1.0
2.0
6.1
5.1
1.8
6.6
5.6
1.6
7.3
6.1
1.1
7.9
6.7
0.7
8.6
7.3
6.0
1.3
4.6
3.9
1.1
5.1
4.3
0.8
5.5
4.6
0.4
5.9
5.0
980
5.0
1.6
5.3
4.5
1.4
5.8
4.9
1.2
6.3
5.3
0.7
6.9
5.8
0.2
7.3
6.1
1015
4.0
1.9
5.9
5.0
1.7
6.5
5.5
1.5
7.0
5.9
1.0
7.7
6.5
0.6
8.2
6.9
1035
3.5
2.0
6.2
5.2
1.9
6.8
5.7
1.7
7.4
6.2
1.2
8.1
6.8
0.7
8.6
7.3
1050
3.0
2.1
6.4
5.4
2.0
7.0
5.9
1.8
7.6
6.4
1.3
8.3
7.0
1080
2.0
2.3
6.6
5.5
2.1
7.2
6.0
1.9
7.8
6.6
1.5
8.6
7.2
1100
1.5
2.4
6.7
5.6
2.2
7.3
6.1
2.1
7.9
6.7
1120
1.0
2.5
6.8
5.7
2.3
7.4
6.2
2.2
8.1
6.8
1.
2.
3.
4.
Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2 T/A filters and a dry evaporator coil.
Refer to the Static Resistance table.
DO NOT close the pulley below one turn open.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been
deducted from the total static pressure of the blower.
5. The Factory Setting.
18
036-21035-002-D-0602
Std.
15 Ton
HP FRAME
O/D
(in.)
PITCH
BORE DESIGNDIA
(in.)
NATION
(in.)
965/1190
Std.
870/1025
950/1120
184T
7.5
213T
89.5
91
1VP56
1VP68
5.35
6.75
4.3-
5.5-
1-3/8
6.52
PITCH
PITCH
BORE DESIGDIA
LNGTH. QTY.
(in.) NATION
(in.)
(in.)
O/D
(in.)
BK90
8.75
8.4
BX70
71.8
BK80
7.75
7.4
BX68
69.8
BK120
11.75
11.4
1-3/16
BX83
84.8
BK110
10.75
10.4
1-3/16
BX80
81.8
1-1/8
5.32
BELT
(NOTCHED)
850/1065
High
Spd.
Acs.
High
Spd.
Acs.
20 Ton
MOTOR1
BLWR
RANGE
(RPM)
1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base.
2. DO NOT close this pulley below 1 turn.
5765
7200
6000
7000
9400
0.1
0.1
0.1
0.1
0.1
0.1
18kW
0.1
0.1
0.1
0.1
0.1
0.1
36kW
0.1
0.2
0.3
0.1
0.2
0.3
54kW
0.2
0.3
0.4
0.2
0.3
0.4
72kW
0.2
0.4
0.6
0.2
0.4
0.6
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.3
0.5
0.2
0.3
0.5
WET COIL
ELECTRIC HEAT
OPTIONS
(DHE models only)
EXONOMIZER OPTION
HORIZONTAL DUCT
20 TON
CONN.2
1. Deduct theses resistance values from the available unit ESP values listed in the respective blower performance table except for Horizontal Duct Connections.
2. Add these values due to less airflow resistance.
MOTOR
SPEED
0.2
0.3
0.4
0.5
0.6
CFM
kW
CFM
kW
CFM
kW
CFM
kW
CFM
kW
HIGH2
5250
0.83
4500
0.85
4200
0.88
3750
0.93
3000
0.99
MEDIUM
4900
0.77
3900
0.79
3500
0.82
2900
0.85
LOW
4400
0.72
3700
0.74
3000
0.78
1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
2. The factory setting.
19
036-21035-002-D-0602
DHG180
DHG240
COND. FAN
MOTORS
(#1 & #2)
SUPPLY AIR
BLOWER
MOTOR
RLA
LRA
RLA
LRA
HP
(ea.)
FLA
(ea.)
HP
FLA
MIN.
CIRCUIT
AMPACITY
(AMPS)
208/230-3-60
28.6
274
14.3
137
4.1/4.2
11.8
77.8/77.0
POWER
SUPPLY
#1
#2
MIN. WIRE
MAX. TIME
DELAY FUSE
SIZE (AMPS)
90
4
8
SIZE1
75C
460-3-60
14.4
138
7.2
69
2.1
5.9
42.7
50
208/230-3-60
28.6
274
28.6
274
4.1/4.2
7.5
18.6
98.6/96.8
110
460-3-60
14.4
138
14.4
138
11
2.1
7.5
9.3
52.2
60
1. Although these sizes are based on copper conductors aluminum wire can be use3d. Refer to the National Electric Code to determine the proper size
VOLTAGE
POWER SUPPLY
VOLTAGE
POWER SUPPLY
MIN.
MAX.
208/230-3-60
187
253
460-3-60
414
506
MIN.
MAX.
208/230-3-60
187
253
460-3-60
414
506
575-3-60
518
506
POWER
SUPPLY
#1
RLA
DHE180
DHE240
#2
LRA
RLA
LRA
COND. FAN
MOTORS
(#1 & #2)
SUPPLY AIR
BLOWER
MOTOR
HP
(ea.)
FLA
(ea.)
HP
MIN. WIRE
MAX. TIME
DELAY FUSE
SIZE (AMPS)
FLA
MIN.
CIRCUIT
AMPACITY
(AMPS)
SIZE1
75C
208/230-3-60
28.6
274
14.3
137
3.6
11.8
77.0
90
460-3-60
14.4
138
7.2
69
2.0
5.9
42.7
50
575-3-60
11.4
116
5.7
58
1.4
5.2
30.7
35
208/230-3-60
28.6
274
28.6
274
3.6
7.5
18.6
98.6
110
460-3-60
14.4
138
14.4
138
2.0
7.5
9.3
52.2
60
575-3-60
11.4
116
11.4
116
1.4
7.5
7.5
40.2
45
1. Although these sizes are based on copper conductors aluminum wire can be used. Refer to the National Electric Code to determine the proper size.
20
036-21035-002-D-0602
POWER
SUPPLY
208-3-60
180A25
230-3-60
180A46
460-3-60
180A58
575-3-60
208-3-60
240A25
230-3-60
240A46
460-3-60
240A58
575-3-60
HEATER OPTION
1
MIN. CIRCUIT
AMPACITY
(AMPS)
MAX. TIME
DELAY FUSE
SIZE (AMPS)
77.0
90
125
STAGES
AMPS
13.5
37.5
E036
27.0
75.1
111.8
E054
40.6
112.6
158.7
175
E072
54.1
150.1
168.1
200
E018
18.0
43.3
77.0
90
E036
36.0
86.6
126.3
150
E054
54.0
129.9
147.9
175
E072
72.0
173.2
191.2
225
E018
18.0
21.7
42.7
50
E036
36.0
43.3
63.1
70
E054
54.0
65.0
74.0
90
E072
72.0
86.6
95.6
110
E018
18.0
17.3
30.7
35
E036
36.0
34.6
50.7
60
E054
54.0
52.0
59.3
70
E072
72.0
69.3
76.7
90
E018
13.5
37.5
96.8
110
E036
27.0
75.1
118.1
125
E054
40.6
112.6
165.0
175
E072
54.1
150.1
174.4
200
E018
18.0
43.3
96.8
110
E036
36.0
86.6
132.5
150
E054
54.0
129.9
154.2
175
E072
72.0
173.2
197.5
225
E018
18.0
21.7
52.2
60
E036
36.0
43.3
66.3
70
E054
54.0
65.0
77.1
90
E072
72.0
86.6
98.7
110
E018
18.0
17.3
40.2
45
E036
36.0
34.6
53.1
60
E054
54.0
52.0
61.7
70
E072
72.0
69.3
79.0
90
MODEL
kW
E018
VOLTAGE
kW CAP. MULTIPLIER
208
208
1.00
240
230
0.92
480
460
0.92
600
575
0.92
21
036-21035-002-D-0602
CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT1
UNIT TERMINAL
TERMINALS
BLOCK 1TB2
NOT USED
COM
A1
A2
T
Y1
ADD
JUMPER
Y2
W1
W2
W2
G
B
X
W2
R
Y1
Y2
W1
W2
G
B
X
A1
A2
Y3
RH
RC
24 VOLT
TRANSFORMER
24 VOLT
A1 TRANSFORMER
A2
POWER WIRING
L1
LINE VOLTAGE
TERMINAL
L2
BLOCK 2TB
L3
IN CONTROL BOX
TO REMOTE SENSOR
2THO4702224 IF USED
1Electronic programmable thermostat 2ET04700224 (includes subbase).
2Terminal block 1TB- located on relay board in 24-volt section of the unit control box.
3Second stage heating is not required on units with a single stage electric heater.
4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers
when the thermostat switches to the set-back position.
NOTE: Fans switch must be in "ON" position for minimum ventilation during heater operation.
Refer to the
ELECTRICAL DATA
tables to size the
power wiring, the
fuses and the
disconnect switch.
GROUND LUG
MODELS
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
(Two Per Unit)
CONDENSER
COILS
(Two Per Unit)
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS
CHARGE
MODEL SIZE
15 TON
20 TON
180
240
15 x 15
18 x 15
Fan Motor HP
7.5
Rows Deep
Economizer
160
Economizer with
Power Exhaust
245
Motorized Damper
150
13.5
13.5
15.5
20.0
30
30
1
5765
3
13
36.0
DHG
(Gas/Electric)
1900
2100
240Mbh
2100
2300
320Mbh
2140
OPTIONS
1
Electric Heater
(DHE only)
7000
3
43.3
11
15.0
20.0
System #1
29/9
23
System #2
14/8
23/12
ACCY.
2340
18kW
25
36kW
30
54kW
35
72kW
15
Refrigerant 22
(lbs./oz.)
BASIC
UNIT
40
Roof Curb
175
Barometric Damper
45
185
45
Wood Skid
220
220
22
036-21035-002-D-0602
BLOWER
ACCESS
BLOWER MOTOR
ACCESS
BLOWER
COMPARTMENT
ACCESS
(Auxiliary)
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
OPTIONAL COIL
GUARD KIT
DOT PLUG
(For pressure
Drop Reading)
GAS HEAT
ACCESS
VENT AIR
OUTLET
HOODS
COMBUSTION
AIR INLET
HOOD
(C)
GAS SUPPLY
ENTRY
)
Ton n)
(15 To
/4" " (20
1
4
6-3/8"
12536-1/
1
7-1/8"
9-3/4"
5-7/8"
n)
To n)
(15 20 To
"
4 (
-1/ 4"
24 5-1/
3
33"
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
RETURN
AIR
2-3/4"
(B)
POWER WIRING
ENTRY
RETURN AIR
3-3/4"
SUPPLY AIR
SUPPLY
AIR
21-1/2"
OUTDOOR AIR
OUTDOOR AIR
(Economizer)
(B)
POWER WIRING
ENTRY
(D)
GAS SUPPLY
ENTRY
NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.
(A)
CONTROL WIRING
ENTRY
11-1/2"
11-1/8"
92"
46-5/8"
CONTROL BOX
35"
ACCESS
FRONT
VIEW
CONDENSER
COILS
21"
5"
8-1/8"
46-5/8"
9-1/4"
12-1/2"
(A)
CONTROL WIRING
ENTRY
9-3/4"
LOCATION
CLEARNANCE
Front
36
Back
24 (Less Economizer)
49 (With Economizer
24 (Less Economizer)
36 (With Economizer)
36
Below Unit1
Above Unit2
72 With 36 Maximum
Horizontal Overhang (For
Condenser Air Discharge)
HOLE
A
USED FOR
Control Wiring
3-5/8 KO
3 NPS (Fem.)
Front
Bottom
Power Wiring
Front
Bottom
2-3/8 KO
1-11/16 Hole
Three (3) feet above any force air inlet located within 10
horizontal feet (excluding those integral to the unit).
23
036-21035-002-D-0602
C O N D E N S E R S E C T IO N
G A U G E L IN E
A C C E S S
E V A P O R A T O R
S E C T IO N
D O T P L U G
(F o r p re s s u re
d r o p r e a d in g )
4 0 -3 /8 "
F IL T E R
A C C E S S
S U P P L Y
A IR
R E T U R N
A IR
5 -1 /2 "
C O M P R E S S O R
A C C E S S
1 " N P T F E M A L E
C O N D . D R A IN
C O N N E C T IO N
O U T D O O R
A IR
S U P P L Y A IR
A C C E S S
4 0 -1 /2 "
1 8 -5 /8 "
R E A R
V IE W
2 7 -3 /4 "
R E T U R N A IR
A C C E S S
O U T D O O R A IR
C O M P A R T M E N T
A C C E S S
5 -1 /8 "
2 8 -5 /8 " (1 5 T o n s )
3 9 -5 /8 " (2 0 T o n s )
Remove the side panels from the supply and return air
compartments to gain access to the bottom supply and
return air duct covers.
2.Remove and discard the bottom duct covers. Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.
3.Replace the side supply and return air compartment
panels.
For side duct application:
1.
24
036-21035-002-D-0602
S U P P L Y A IR
C O M P A R T M E N T
P O W E R E X H A U S T
R A IN H O O D
( o n R e tu r n A ir C o m p a r tm e n t)
E C O
M O T
D A M
R A IN
(o n O
N O M IZ E R
O R IZ E D
P E R
H O O D
u td o o r A ir C o m p a r tm e n t)
E C O N O M IZ E R / M O T O R IZ E D D A M P E R
A N D P O W E R E X H A U S T R A IN H O O D S
F IX E
O U T
IN T A
( lo c a
R e tu
C o m
3 4 -1 /4 "
D
D O O R A IR
K E H O O D
te d o n
r n A ir
p a rtm e n t)
1 " C O N D E N S T A T E
D R A IN
(M u s t b e tra p p e d )
1 6 -1 /8 "
5 "
3 6 "
6 6 -1 /2 "
R E A R
V IE W
2 "
9 2 "
3 6 -1 /4 "
D E T A IL "Y "
U N IT W IT H R A IN H O O D S
L H
V IE W
25
036-21035-002-D-0602
B
C
A
F R O N T
E
F
D
A
C
F R O N T
B
TOTAL
DHE180
2060
483
525
548
504
DHE240
2206
568
814
888
620
DHG180
2300
539
563
612
586
DHG240
2500
538
563
715
684
26
UNIT
TOTAL
DHE180
2060
322
336
350
365
351
336
DHE240
2260
325
368
412
431
385
339
DHG180
2300
351
367
392
416
399
375
DHG240
2500
334
350
426
502
481
407
036-21035-002-D-0602
NOTE: Ducts can be installed into the curb from the roof. All
27
036-21035-002-D-0602
28
036-21035-002-D-0602
NOTES
29
036-21035-002-D-0602
30
036-21035-002-D-0602
31
Supersedes: 035-21035-002-C-0500
5005
York
Drive
036-21035-002-D-0602