DESCRIPTION

TECHNICAL
GUIDE

YORK Sunline PLUS II units are convertible single package


high efficiency rooftops. All models have independent dual
refrigerant circuits for efficient part load operation. Although
the units are primarily designed for curb mounting on a roof,
they can also be slab-mounted at ground level or set on steel
beams above a finished roof.

All units include:

Powder Paint finish that meets ASTM-B-117 750 hour


salt spray standards

Two-stage cooling provided by dual independent refrigeration circuits with expansion valves, filter-driers, high
and low pressure/loss of charge switches and freezestats
Hermetically sealed compressors with crankcase heaters
Two-stage heating provided by dual independent heat
exchangers with aluminized steel tubes, redundant gas
valves, spark ignition with induced draft logic
Permanently lubricated motors

SINGLE PACKAGE GAS/ELECTRIC UNITS


AND SINGLE PACKAGE AIR

CONDITIONERS

D1HG/D1HE 180 & 240

15 & 20 NOMINAL TONS

Bottom or side air discharge configuration capability


(field convertible)

Belt Drive Blower Motor


Manufactured under the quality standards of ISO9001

Twenty-four volt control circuit with compressor lock-out


Zero-25% fixed air damper with hood

Copper tube/aluminum fin coils

Easy access to all components


Rigging holes in base rails for lifting

Single point power connection


Complete factory package - tested, charged and wired

ETL & CGA agency approvals on all units


Factory Limited Parts Warranty

One-year parts warranty


A Five-years part warranty on the compressor and electric heat elements.
Ten-year Part Warranty on the gas-fired heat exchangers.

10.00 EER (15 TONS), 9.7 EER (20 TONS)

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

036-21035-002-D-0602

TABLE OF CONTENTS
pg.

pg.

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

8 COOLING CAP FOR DHE/DHG 180 AT 115F . 11

FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5

9 COOLING CAP FOR DHE/DHG 240 AT 85F . . 12

FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . . 6

10 COOLING CAP FOR DHE/DHG 240 AT 95F . . 13

LIST OF FIGURES

11 COOLING CAP FOR DHE/DHG 240 AT 105F . 14

pg.

12 COOLING CAP FOR DHE/DHG 240 AT 115F . 15

1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . 5

13 DHG 15 TON SUPPLY AIR BLOWER PERF . . 16

2 DHG/DHE FIELD WIRING DIAGRAM . . . . . . . . 23

14 DHG 20 TON SUPPLY AIR BLOWER PERF . . 17

3 UNIT DIMENSIONS FRONT VIEW . . . . . . . . . . 24


4 UNIT DIMENSIONS REAR VIEW . . . . . . . . . . . 25
5 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . 25

15 DHE 15 TON SUPPLY AIR BLOWER PERF . . 18


16 DHE 20 TON SUPPLY AIR BLOWER PERF . . 19

6 UNIT DIMENSIONS RAINHOOD . . . . . . . . . . . . 26

17 BLOWER MOTOR AND DRIVE DATA . . . . . . . 20

7 TYPICAL UNIT APPLICATIONS . . . . . . . . . . . . 26

18 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . 20

8 UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . 27

19 POWER EXHAUST PERFORMANCE . . . . . . . . 20

9 UNIT 6 POINT LOAD . . . . . . . . . . . . . . . . . . . . . 27


10 UNIT ROOF CURB DIMENSIONS . . . . . . . . . . . 28
11 ROOF CURB DUCT OPENINGS DIMENSION . 28

20 DHG ELECTRICAL DATA . . . . . . . . . . . . . . . . . 21


21 DHG VOLTAGE LIMITATIONS . . . . . . . . . . . . . 21

12 CUT AWAY OF ROOF CURB . . . . . . . . . . . . . . 28

22 DHE VOLTAGE LIMITATIONS . . . . . . . . . . . . . 21

13 TYPICAL ROOFTOP INSTALLATION . . . . . . . . 29

23 DHE ELECTRICAL DATA . . . . . . . . . . . . . . . . . 21

LIST OF TABLES

24 ELEC DATA UNITS WITH SUPPL ELEC HEAT 22

1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . 4

25 ELECTRIC HEAT CORRECTION FACTORS . . 22

2 SOUND POWER RATING . . . . . . . . . . . . . . . . . . 7

26 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . 23

3 CAPACITY RATINGS - (ARI 360) . . . . . . . . . . . . 7

27 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . 23

4 GAS HEAT RATIINGS . . . . . . . . . . . . . . . . . . . . . 7

28 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . 24

5 COOLING CAP FOR DHE/DHG 180 AT 85F . . . 8

29 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . 24

6 COOLING CAP FOR DHE/DHG 180 AT 95F . . . 9

30 4 POINT LOADS WEIGHT DISTRIBUTION . . . 27

7 COOLING CAP FOR DHE/DHG 180 AT 105F . 10

31 6 POINT LOADS WEIGHT DISTRIBUTION . . . 27

Unitary Products Group

036-21035-002-D-0602

D 1 HG 180 N 240 25 EC

TABLE 1: PRODUCT NOMENCLATURE


Model #

Model Number
Description

Product Category

Product Generation

1 = 1st Generation

HG

Product Identifier

HG = Gas/Electric

HE = Electric/Electric

180

Nominal Cooling Capacity

180 = 15 Tons

240 = 20 Tons

Factory Installed Heat

A = No Heat Installed
E = Electric Heat

N = Natural Gas

240

Nominal Heating Output


Capacity

25

Voltage Code

Options
D = Air Cond., Single Package

240 = 240 MBH

GAS

320 = 320 MBH

25 = 208/230-3-60

46 = 460-3-60

BG = Motorized Outdoor Air Damper


EC

Factory Installed
Option Code

CF = Dual Input Econo. w/ Pwr Exhaust


DK = Diff. Input Economizer

FD = Sing. Input Econo.er w/ Pwr Exhaust


EC = Single Input Economizer

All models are available with a wide variety of factorymounted options and field-installed accessories to make
them suitable for almost every application.

damper assembly should be mounted over the opening in the


return air panel. With horizontal ductwork, it should be
mounted on the return air duct.

All units are self-contained and assembled on full perimeter


base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at
the factory to simplify the field installation and to provide
years of dependable operation.

All supply air blowers are equipped with a belt drive that can
be adjusted to meet the exact requirements of the job. A high
speed drive accessory is available for applications with a
higher CFM and/or static pressure requirement.

All models (including those with an economizer) are suitable


for either bottom or horizontal duct connections. Models with
power exhaust are suitable for bottom duct connections only.
For bottom duct, you remove the sheet metal panels from the
supply and return air openings through the base of the unit.
For horizontal duct, you replace the supply and return air
panels on the rear of the unit with a side duct flange accessory.
All models are available with seven different outdoor air
damper options:

Single enthalpy economizer

Differential (dual) enthalpy economizer

Single enthalpy economizer with power exhaust

Differential (dual) enthalpy economizer with power


exhaust

Single Dry Bulb Economizer

Single Dry Bulb Economizer with power exhaust

Motorized outdoor air damper

A fixed outdoor air intake assembly will be shipped in the


return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10, 15
or 25% outdoor air. With bottom duct connections, the intake

Unitary Products Group

All compressors include crankcase heat and internal pressure relief. Every refrigerant circuit includes an expansion
valve, a liquid line filter-drier, a discharge line high pressure
switch and a suction line with a freezestat and low pressure/
loss of charge switch to protect all system components. The
unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with two compressor lockout
circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls.
All units have long lasting powder paint cabinets with 750
hour salt spray test approval under ASTM-B117 procedures.
All 208/230 and 460-volt models are ETL approved. All 208/
230 and 575-volt models are CGA approved.
All models include a one-year limited parts warranty on the
complete unit. Compressors and electric heater elements
carry a five-year warranty. Aluminized steel tubular heat
exchangers carry a 10-year parts warranty.
All gas heat units are built with two heating sections for two
equal stages of capacity control. Each section includes a
durable heat exchanger with aluminized steel tubes, a redundant gas valve, spark ignition, power venting, an ignition
module for 100% shut-off and all of the safety controls
required to meet the latest ANSI standards.

036-21035-002-D-0602

The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through
a knockout in the piping panel on the front of the unit.
All electric heat models are wired for a single power source
and include a bank of nickel chromium elements mounted at
the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.

Every element is fully protected against excessive current


and temperature by fuses and two thermal limit switches.
The power supply wiring can be routed into the control box
through a threaded pipe connection in the base pan of the
unit or through a knockout in the wiring panel on the front of
the unit.

ELECTRIC HEATER LOCATION


(OPTIONAL ELECTRIC/ELECTRIC UNITS)

LONG LASTING
POWDER PAINT FINISH

HIGH EFFICIENCY COMPRESSORS


WITH CRANKCASE HEATERS

20 GAUGE ALUMINIZED STEEL


TUBULAR HEAT EXCHANGERS

COPPER TUBE/ALUMINUM FIN


CONDENSER COILS
LOW VOLTAGE RELAY BOARD
AND TERMINAL STRIP

ECONOMIZER HOOD

ELECTRICAL DISCONNECT
MOUNTING LOCATION
(Field installed)
KNOCKOUT FOR
SIDE CONTROL WIRING ENTRY
KNOCKOUT FOR
SIDE POWER WIRING ENTRY SIDE

2" DISPOSABLE
FILTERS

TERMINAL BLOCK
(For Single Point Power Supply
with Electric Heat)
ELECTRIC\ELECTRIC UNITS

OUTDOOR AIR OPENING


FOR SLIDE-IN/PLUG-IN
INTERNAL ECONOMIZER(OPTION)

BOTTOM POWER & CONTROL


WIRING ENTRY
KNOCKOUTS FOR SIDE
GAS SUPPLY ENTRY

SIDE AND BOTTOM


SUPPLY & RETURN AIR
DUCT OPENINGS(SIDE X SIDE)
1" NPTI
CONDENSATE DRAIN

BELT-DRIVE
BLOWER MOTOR

FULL PERIMETER 14 GUAGE BASE


RAILS WITH LIFTING HOLES

HOLE FOR BOTTOM


GAS SUPPLY ENTRY
POWER VENTOR MOTOR
WITH POST PURGE CYCLE

GAS/ELECTRIC
UNIT SHOWN

FIGURE 1 : UNIT CUTAWAY

FACTORY-INSTALLED OPTIONS

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return monitor actuator
capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed option.

This enthalpy system contain one sensor that monitors


the outdoor air and one sensor that monitors the return
air. The logic module compares these two values and
modulates the dampers providing the maximum efficiency of economizer system.

DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with
fully modulating spring-return monitor actuator capable
of introducing up to 100% outdoor air with nominal 1%
leakage type dampers.

The rainhood is painted to match the basic unit and must


be field-assembled before installing.

POWER EXHAUST - Both the single and differential


economizer options are available with power exhaust.
Whenever the outdoor air intake dampers are opened for
free cooling, the exhaust fan will be energized to prevent
the conditioned space from being over-pressurized during economizer operation.
The exhaust fan, motor and controls are installed and
wired at the factory. The rain hood and the back-draft
damper need to be assembled and installed in the field.

Unitary Products Group

036-21035-002-D-0602

The power exhaust option can only be used on bottom


duct configurations.

operating and will drive fully closed when the blower unit
shuts down.

MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit
shuts down.

The rain hood is painted to match the basic unit and


must be field assembled before installing.
Power exhaust is not available as a field installed option.

ROOF CURBS - Fourteen-inch high roof curbs provide a


water-tight seal between the unit and the finished roof.
These full perimeter curbs meet the requirements of the
National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly. They're
designed to fit inside the base rails of the unit and
include both a wood nailing strip and duct hanger supports.

ANTI-RECYCLE TIMERS - Two solid state timers prevent the compressors from short-cycling. Once a compressor is de-energized, it will remain de-energized for
approximately five minutes.

HIGH ALTITUDE NATURAL GAS - Burner orifices and


pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.

PROPANE - Burner orifices, pilot orifices and gas valve


parts are provided to convert a natural gas furnace to
propane.

HIGH ALTITUDE PROPANE - Burner orifices and pilot


orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.

SIDE DUCT FLANGES - One-inch flanges replace the


supply and return air panels on the rear of the unit to
accommodate horizontal duct connections. These
flanges can also be used individually for bottom supply/
horizontal return or horizontal supply/bottom return. They
cannot be used on units with power exhaust.

BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.

HIGH SPEED DRIVE - A smaller blower pulley and a


shorter belt increase the speed of the supply air blower
for applications with a higher CFM and/or static pressure
requirements.

LOW AMBIENT CONTROLS TO 0F (15 Tons) - An


autotransformer and a thermostat maintain stable system operation by reducing the speed of the #1 condenser fan motor at low outdoor temperatures. The kit
also includes a 1-phase motor to replace the unit's standard 3-phase condenser fan motor. Standard units can
operate down to 25F.

The rain hood is painted to match the basic unit and


must be field assembled before installing.
Power exhaust is not available as a field installed option.

PHENOLIC COATED CONDENSER COIL - Special


coating process that utilizes Technicoat 10-1" processes.
Coating is applied by total immersion of the complete coil
for maximum protection.
ELECTRIC HEATERS (DHE UNITS ONLY) wired for
single point power supply. These nickel chromium heater
elements are provided with limit and automatic reset
capability to prevent operation at excessive temperatures.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return monitor actuator
capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed option.

DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with
fully modulating spring-return monitor actuator capable
of introducing up to 100% outdoor air with nominal 1%
leakage type dampers.
This enthalpy system contain one sensor that monitors
the outdoor air and one sensor that monitors the return
air. The logic module compares these two values and
modulates the dampers providing the maximum efficiency of economizer system.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
Power exhaust is not available as a field installed option.

MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is

Unitary Products Group

036-21035-002-D-0602

LOW AMBIENT CONTROLS TO 0F (20 TON) - An


electronic head pressure control is added to each refrigeration system to maintain stable system operation at
low outside temperatures. The kit also includes a single
phase motor to replace the units 3-phase condenser fan
motor. One kit is needed for each refrigerant system
standard unit can operate down to 45F.

TABLE 2: SOUND POWER RATING1

UNIT
SIZE

ESP

SOUND POWER (db 10-12 Watts)

BLOWER

Octave Band Centerline Frequency (Hz)

CFM
IWG

RPM

BHP

63

125

250

500

1,000

2,000

4,000

8,000

SWL
dB(A)

dB(A)
@
10Ft.2

180

8,000

1.00

1,080

4.60

99

99

89

82

84

77

72

67

89

56

240

8,000

1.00

1,120

6.65

102

102

92

85

87

80

75

70

92

59

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.

TABLE 4: GAS HEAT RATIINGS1

TABLE 3: CAPACITY RATINGS - (ARI 360)1


MODEL

MBH

EER2

IPLV3

MODEL

MBH INPUT

MBH OUTPUT

D1HG180N240

300

240

10.7

D1HG180N320

400

320

10.2

D1HG240N240

300

240

D1HG240N320

400

320

COOLING ONLY
D1HE180
D1HE240

177
223

10.0
9.7

COOLING WITH GAS HEAT


D1HG180N240

177

10.0

10.7

D1HG180N320

177

10.0

10.7

D1HG240N240

223

9.7

10.2

D1HG240N320

223

9.7

10.2

1. All units are two-stage heating. First stage is 50% of


total.

COOLING WITH ELECTRIC HEAT


D1HE180E018

177

10.0

10.7

D1HE180E036

177

9.9

10.6

D1HE180E054

175

9.7

9.9

D1HE180E072

175

9.7

9.9

D1HE240E018

223

9.6

10.1

D1HE240E036

223

9.6

10.1

D1HE240E054

221

9.5

9.7

D1HE240E072

219

9.5

9.7

1. 80/67F Indoor and 95F outdoor.


2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btus per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. IPLV = Integrated part load value.

Unitary Products Group

036-21035-002-D-0602

TABLE 5: COOLING CAPACITIES FOR DHE/DHG 180 AT 85F


Capacity (MBH) at Entering Dry Bulb (F)

Air On Evaporator
Coil
CFM

4500

5250

5765

6750

7200

86

83

80

77

74

71

68

WB F

Tot.1
Input
(kW)

TOT2

72

16.6

193.2

118.2

192.2

105.1

190.9

92.5

189.1

77.9

186.9

63.3

67

16.2

180.7

141.7

179.4

128.8

178.2

114.5

176.9

101.9

175.7

89.1

173.8

74.8

171.5

60.1

62

15.8

176.4

162.3

168.4

150.8

166.0

137.8

164.7

125.0

163.1

111.5

162.0

98.4

160.6

85.6

57

15.6

176.3

162.2

170.6

157.0

165.0

151.8

164.7

125.0

152.5

133.8

150.4

120.7

148.7

107.2

72

16.7

197.5

127.3

196.4

112.1

195.1

97.5

193.2

82.0

190.7

65.0

67

16.3

185.9

154.3

184.4

139.1

182.6

122.9

181.2

108.3

179.8

93.7

177.8

78.2

175.2

61.1

62

16.1

185.4

170.6

179.5

165.1

172.1

149.9

169.5

134.7

167.4

119.3

166.3

104.2

164.8

89.6

57

16.0

185.3

170.5

179.4

165.0

173.4

159.5

167.5

154.1

161.5

148.5

155.2

130.1

164.8

89.6

72

16.8

199.9

133.4

198.8

117.0

197.3

100.7

195.3

84.8

192.7

66.2

67

16.3

189.8

162.6

187.1

146.0

185.0

128.7

183.5

112.5

182.0

96.6

179.9

80.5

163.2

146.9

62

16.2

190.6

175.3

184.4

169.7

175.3

157.5

172.2

141.2

170.5

125.3

168.5

108.0

167.0

92.1

57

16.1

190.5

175.2

184.3

169.6

178.2

163.9

172.1

158.3

166.0

152.7

158.6

136.6

156.0

120.1

72

16.9

204.7

145.3

202.3

125.5

200.7

106.7

198.6

88.4

195.7

68.3

67

16.5

196.3

177.9

191.2

158.3

189.7

139.4

187.1

120.6

185.4

101.8

183.1

83.7

180.0

62.9

62

16.3

198.7

182.8

192.2

176.9

185.7

170.8

177.5

153.3

174.5

134.4

172.1

115.3

170.3

96.6

57

16.2

198.5

182.7

192.1

176.8

185.7

170.8

179.3

164.9

172.9

159.1

163.2

146.9

159.9

128.5

72

16.9

206.2

150.1

203.6

129.3

202.0

109.3

199.8

90.0

196.8

69.3

67

16.6

201.9

185.7

194.0

164.5

191.3

143.8

188.4

124.0

186.7

104.1

184.3

85.0

181.1

63.4

62

16.4

201.8

185.6

195.2

179.6

188.7

173.6

179.4

158.0

176.0

138.7

173.4

118.3

171.5

98.6

57

16.3

201.6

185.5

195.1

179.5

188.6

173.5

181.8

167.3

175.3

161.3

166.3

152.0

161.3

132.2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.

Unitary Products Group

036-21035-002-D-0602

TABLE 6: COOLING CAPACITIES FOR DHE/DHG 180 AT 95F


Capacity (MBH) at Entering Dry Bulb (F)

Air On Evaporator
Coil
CFM

4500

5250

5765

6750

7200

86

80

83

77

74

71

68

WB F

Tot.1
Input
(kW)

TOT2

72

17.7

182.9

114.7

181.9

101.4

180.6

88.8

178.8

74.6

176.5

59.9

67

17.2

171.3

137.9

170.0

124.9

168.6

110.7

167.3

98.2

165.9

85.3

153.6

141.3

162.0

56.7

62

16.9

168.5

155.1

161.0

146.8

157.0

133.5

155.8

120.9

154.0

107.4

152.9

94.4

151.5

81.5

57

16.7

168.4

155.0

162.9

149.9

157.4

144.8

151.9

139.7

144.3

129.3

142.0

116.4

140.1

103.1

72

17.9

186.9

123.8

185.8

108.5

184.3

93.6

182.4

78.7

179.9

61.6

67

17.2

176.8

150.6

174.5

135.3

172.5

118.9

171.2

104.4

169.8

89.8

142.0

116.4

165.4

57.7

62

17.2

176.9

162.8

171.1

157.4

163.0

145.6

160.3

130.7

169.8

89.8

156.8

100.3

155.2

85.4

57

17.0

176.8

162.7

171.0

157.3

165.2

152.0

159.4

146.7

157.9

115.0

147.0

126.2

144.7

110.9

72

18.0

189.8

130.4

187.9

113.1

186.4

96.8

184.4

81.0

181.7

62.8

67

17.6

189.8

130.4

177.0

142.1

175.5

125.1

173.3

108.8

171.7

92.6

169.6

76.8

167.1

58.3

62

17.2

181.7

167.2

175.7

161.7

167.3

152.7

162.6

136.7

161.0

121.0

158.9

104.1

157.2

87.9

57

17.1

181.6

167.1

175.6

161.6

169.6

156.1

163.7

150.6

157.7

145.1

158.9

104.1

147.0

115.6

72

18.1

193.5

141.3

191.0

121.6

189.4

102.8

187.3

84.5

184.0

64.8

67

17.7

189.3

174.1

181.9

154.8

179.3

135.2

176.5

116.5

174.8

97.7

172.5

79.7

169.7

59.4

62

17.4

189.1

174.0

182.9

168.3

176.7

162.5

167.9

148.7

164.7

130.2

162.1

111.0

160.3

92.4

57

17.3

189.0

173.9

182.8

168.2

176.6

162.4

170.3

156.7

164.1

151.0

158.0

145.3

150.5

124.1

72

18.1

194.9

146.0

192.2

125.4

190.6

105.3

188.4

86.0

185.3

65.9

67

17.7

192.1

176.7

183.6

159.8

180.6

139.5

177.7

119.9

175.9

100.0

173.5

80.9

170.1

59.8

62

17.5

192.0

176.6

185.6

170.8

179.3

165.0

170.7

153.7

166.0

134.3

163.2

114.1

161.1

94.1

57

17.4

191.9

176.5

185.5

170.7

179.2

164.9

172.9

159.0

166.5

153.2

160.2

147.4

151.9

127.8

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.
Nominal Rating

Unitary Products Group

036-21035-002-D-0602

TABLE 7: COOLING CAPACITIES FOR DHE/DHG 180 AT 105F


Capacity (MBH) at Entering Dry Bulb (F)

Air On Evaporator
Coil
CFM

4500

5250

5765

6750

7200

86

83

80

77

74

71

68

WB F

Tot.1
Input
(kW)

TOT2

72

18.3

144.7

110.9

67

18.2

161.5

133.9

62

17.8

160.1

147.3

160.1

120.8

148.6

129.3

146.6

116.7

144.7

103.3

143.6

90.2

142.1

77.4

57

17.6

160.0

147.2

154.6

142.3

149.3

137.3

143.9

132.4

138.5

127.4

143.6

90.2

131.2

98.5

72

19.0

175.6

119.6

174.6

104.6

173.3

89.2

170.9

74.9

169.1

58.3

67

18.5

166.7

145.5

164.3

131.1

162.9

115.6

160.8

100.5

169.1

58.3

157.5

70.8

154.5

53.9

62

18.1

168.0

154.6

162.2

149.2

156.6

144.0

160.8

100.5

149.0

111.6

147.1

96.0

145.6

81.1

57

17.9

167.9

154.5

162.1

149.1

156.5

143.9

150.6

126.4

145.3

133.7

138.1

120.7

135.6

106.4

72

18.9

178.6

126.3

176.5

109.2

175.1

92.4

172.6

76.9

160.8

148.0

67

18.5

170.6

154.0

166.4

137.4

165.1

121.0

162.7

104.7

161.1

88.4

158.4

72.4

156.0

54.5

62

18.2

172.4

158.6

166.6

153.3

160.6

147.8

153.7

132.3

151.2

116.5

148.9

99.7

147.3

83.7

57

18.1

172.3

158.5

166.5

153.2

160.5

147.7

154.7

142.3

148.8

136.9

141.6

127.4

137.7

111.1

72

19.1

181.9

137.0

179.3

117.6

177.7

98.1

175.3

80.7

173.0

61.6

67

18.7

179.2

164.9

171.1

149.4

168.4

130.8

165.5

112.3

163.8

93.5

160.9

75.5

158.6

55.7

62

18.5

179.1

164.8

173.1

159.3

167.1

153.8

159.0

143.8

154.4

125.6

151.8

106.7

149.9

88.0

57

18.4

179.0

164.7

173.0

159.2

167.0

153.7

160.8

148.0

154.8

142.4

148.9

136.9

140.9

119.1

72

19.2

183.1

141.7

180.4

121.3

178.7

100.7

176.7

81.5

173.1

62.3

67

18.8

181.8

167.3

173.9

155.7

169.6

135.1

166.6

115.7

164.8

95.7

161.8

76.8

159.3

56.2

62

18.6

181.3

166.8

175.3

161.2

169.5

155.9

163.4

150.3

155.7

129.7

152.8

109.7

159.3

56.2

57

18.5

181.2

166.7

175.5

161.5

169.4

155.9

163.3

150.2

157.0

144.4

150.7

138.7

143.0

123.5

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

171.1

97.2

170.0

84.4

168.4

71.2

166.2

56.6

171.1

97.2

170.0

84.4

157.3

94.2

156.0

81.3

154.4

67.8

138.1

120.7

SEN

TOT2

SEN

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.

Unitary Products Group

036-21035-002-D-0602

TABLE 8: COOLING CAPACITIES FOR DHE/DHG 180 AT 115F


Capacity (MBH) at Entering Dry Bulb (F)

Air On Evaporator
Coil
CFM

4500

5250

5765

6750

7200

86

83

80

77

74

71

68

WB F

Tot.1
Input
(kW)

TOT2

72

19.9

161.0

67

19.4

151.8

62

18.8

151.4

139.3

146.2

134.5

139.3

124.8

57

18.6

151.4

139.3

146.2

134.5

141.2

129.9

72

20.1

164.8

115.7

163.0

100.1

161.7

85.2

160.0

70.8

157.4

54.7

67

19.4

157.3

142.4

153.5

126.6

152.2

110.7

150.1

96.3

148.6

81.0

146.7

66.7

143.9

50.3

62

19.1

158.4

145.7

153.0

140.7

147.6

135.8

141.4

121.6

139.0

106.5

137.1

91.8

143.9

50.3

57

18.9

158.3

145.7

152.9

140.7

147.5

135.7

142.2

130.9

136.8

125.8

129.9

116.9

126.2

101.2

72

20.2

166.7

121.4

164.6

104.5

163.3

88.3

161.4

72.6

158.8

55.9

67

19.7

162.6

149.6

156.4

133.6

163.3

88.3

151.7

100.4

150.2

83.7

148.0

67.8

144.2

50.5

62

19.3

162.3

149.3

156.8

144.2

163.3

88.3

143.8

127.5

140.9

111.4

138.6

94.8

137.1

78.7

57

19.1

162.2

149.3

156.7

144.2

151.1

139.0

145.5

133.9

140.1

128.9

134.5

123.7

128.1

105.7

72

20.3

169.6

132.0

167.8

113.6

165.6

94.0

163.7

75.9

160.5

57.9

67

19.7

168.7

155.2

161.2

145.3

157.1

126.2

154.8

108.1

152.6

88.7

148.9

70.9

145.4

51.4

62

19.5

168.4

154.9

162.7

149.7

156.9

144.4

151.3

139.2

144.6

121.0

141.8

102.1

139.4

82.9

57

19.4

168.3

154.8

162.6

149.6

156.8

144.3

151.1

139.1

145.3

133.7

139.5

128.4

131.9

114.2

72

20.3

170.6

136.6

168.8

117.2

166.5

96.5

164.5

77.4

160.5

58.7

67

19.9

170.9

157.3

165.2

151.9

158.9

130.7

164.5

77.4

160.5

58.7

149.6

72.1

143.6

51.0

62

19.6

170.7

157.0

165.1

151.9

159.2

146.5

153.4

141.1

145.9

124.6

142.9

105.0

140.2

84.8

57

19.5

170.6

156.9

165.0

151.8

159.2

146.4

153.3

141.0

147.3

135.5

141.4

130.1

133.2

118.2

TOT2

SEN

106.8

158.3

145.7

158.8

80.6

157.2

67.7

154.2

52.8

129.4

149.8

116.0

158.8

80.6

157.2

67.7

145.7

76.8

143.9

64.1

140.5

49.0

147.0

89.6

135.6

99.6

134.0

85.5

132.6

72.8

136.0

125.1

130.7

120.3

124.9

108.0

132.6

72.8

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.

10

Unitary Products Group

036-21035-002-D-0602

TABLE 9: COOLING CAPACITIES FOR DHE/DHG 240 AT 85F


Capacity (MBH) at Entering Dry Bulb (F)

Air On Evaporator
Coil

86

83

80

77

74

71

68

CFM

6000

7000

8000

9000

9400

WB F

Tot.
Input
(kW)

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

72

21.9

247.8

169.2

246.6

149.6

245.2

130.5

243.1

109.8

240.1

88.6

67

21.5

232.2

203.8

230.8

184.4

229.5

163.5

228.0

145.2

226.5

126.0

224.3

105.5

221.2

84.2

62

21.1

226.6

226.6

219.6

219.6

214.0

198.6

212.7

179.2

210.9

159.5

209.7

140.2

208.1

121.0

57

20.8

226.5

226.5

219.5

219.5

212.4

212.4

205.4

205.4

197.3

192.7

194.9

173.3

192.9

153.2

72

22.0

252.8

182.7

251.6

160.2

249.8

138.1

247.7

115.6

243.7

90.7

67

21.6

238.9

222.6

236.8

200.4

234.8

176.6

233.1

154.7

231.1

132.5

228.9

110.3

220.7

83.6

62

21.3

237.8

237.8

230.4

230.4

221.3

216.3

218.5

194.2

216.8

172.0

214.7

148.9

213.0

126.7

57

21.2

237.7

237.7

230.3

230.3

222.8

222.8

215.5

215.5

208.1

208.1

201.1

187.4

198.9

165.3

72

22.1

257.7

196.6

255.3

170.4

253.6

145.1

251.1

120.5

247.0

93.0

67

21.7

245.6

241.5

241.3

215.9

239.7

189.5

236.9

164.0

234.7

138.7

232.3

114.5

217.2

82.4

62

21.5

246.7

246.7

239.0

239.0

231.2

231.2

223.7

208.5

221.1

183.5

218.6

157.5

216.4

132.3

57

21.3

246.6

246.6

238.9

238.9

231.2

231.2

223.5

223.5

215.8

215.8

206.3

200.9

203.2

175.9

72

22.3

261.3

210.1

258.2

180.4

256.4

152.0

252.6

123.4

240.7

92.4

67

21.8

254.1

254.1

245.9

230.5

243.2

201.2

239.9

173.4

237.9

144.8

234.9

117.6

62

21.6

254.0

254.0

246.1

246.1

238.1

238.1

228.2

222.7

224.6

194.4

221.6

165.6

219.2

137.4

57

21.5

253.9

253.9

245.9

245.9

238.0

238.0

230.0

230.0

222.1

222.1

214.1

214.1

206.5

185.6

72

22.4

262.5

215.1

259.2

184.4

257.4

154.7

253.4

124.9

248.5

95.7

67

21.9

256.7

256.7

247.4

235.9

244.4

205.8

240.9

177.0

238.8

147.1

235.8

118.8

62

21.7

256.6

256.6

248.5

248.5

240.4

240.4

230.9

228.6

225.8

198.7

222.6

168.8

220.2

139.3

57

21.6

256.4

256.4

248.4

248.4

240.4

240.4

232.3

232.3

224.3

224.3

216.2

216.2

207.8

189.6

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.

Unitary Products Group

11

036-21035-002-D-0602

TABLE 10: COOLING CAPACITIES FOR DHE/DHG 240 AT 95F


Capacity (MBH) at Entering Dry Bulb (F)

Air On Evaporator
Coil

86

83

80

77

74

71

68

CFM

6000

7000

8000

9000

9400

WB F

Tot.
Input
(kW)

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

72

23.5

234.3

164.0

233.1

144.3

231.4

125.3

229.5

105.0

224.1

82.9

67

23.1

219.5

197.9

218.2

178.6

216.8

158.0

215.4

139.5

213.8

120.5

211.6

100.5

207.9

79.0

62

22.7

216.3

216.3

209.2

209.2

202.8

192.5

200.8

173.0

199.0

153.8

197.8

134.4

196.1

115.2

57

22.4

216.2

216.2

209.4

209.4

202.5

202.5

195.6

195.6

188.6

188.6

183.6

166.8

181.7

147.3

72

23.6

239.6

178.5

237.5

154.8

235.9

132.6

233.6

110.8

229.0

85.7

67

23.2

226.1

216.7

223.7

194.8

222.4

171.7

219.9

149.1

217.9

126.9

215.6

105.2

202.3

76.7

62

22.9

226.6

226.6

219.4

219.4

212.1

212.1

206.1

187.9

204.5

165.7

202.4

142.9

200.5

120.9

57

22.7

226.5

226.5

219.3

219.3

212.1

212.1

204.9

204.9

197.6

197.6

189.7

181.0

187.2

158.7

72

23.7

243.3

191.1

240.9

165.0

239.2

139.6

236.6

115.0

230.0

87.4

67

23.4

234.9

234.9

240.9

165.0

226.3

183.8

223.3

158.3

221.5

133.1

217.7

108.2

215.9

82.0

62

23.1

234.8

234.8

227.2

227.2

219.8

219.8

211.4

202.2

208.4

176.9

205.8

151.2

203.8

126.1

57

22.9

234.7

234.7

227.1

227.1

219.6

219.6

212.3

212.3

204.8

204.8

197.2

197.2

191.1

169.0

72

23.8

246.7

204.4

243.5

174.9

241.6

146.4

237.6

117.6

237.9

91.6

67

23.5

241.6

241.6

232.3

224.0

229.2

194.9

226.0

167.3

224.0

139.0

220.8

111.6

209.5

79.8

62

23.2

241.5

241.5

233.8

233.8

226.1

226.1

218.4

218.4

211.5

187.7

208.5

159.2

206.3

131.1

57

23.1

241.3

241.3

233.7

233.7

225.8

225.8

218.1

218.1

210.4

210.4

202.8

202.8

194.3

179.2

72

23.9

247.4

208.8

245.2

179.6

242.5

149.1

238.2

119.1

230.7

89.8

67

23.6

243.9

243.9

234.8

230.5

230.3

199.4

227.7

171.5

224.8

141.3

221.5

112.7

62

23.3

243.8

243.8

236.0

236.0

228.3

228.3

220.5

220.5

212.7

192.2

210.2

163.0

207.1

133.0

57

23.2

243.7

243.7

235.9

235.9

228.0

228.0

220.2

220.2

212.4

212.4

204.7

204.7

196.1

183.3

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.
Nominal Rating

12

Unitary Products Group

036-21035-002-D-0602

TABLE 11: COOLING CAPACITIES FOR DHE/DHG 240 AT 105F


Capacity (MBH) at Entering Dry Bulb (F)

Air On Evaporator
Coil

86

83

80

77

74

71

68

CFM

6000

7000

8000

9000

9400

WB F

Tot.
Input
(kW)

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

72

25.1

220.4

158.8

219.1

138.9

217.6

119.8

215.4

100.1

209.0

77.7

67

24.5

207.2

192.5

205.4

173.0

203.8

152.5

202.3

133.9

200.7

114.9

198.3

95.3

193.8

73.5

62

24.0

205.6

205.6

198.9

198.9

191.0

186.5

188.7

167.2

187.2

148.1

185.5

128.4

183.8

109.4

57

23.7

205.5

205.5

198.8

198.8

192.1

192.1

185.4

185.4

178.4

178.4

172.2

160.8

170.7

141.6

72

25.2

225.1

172.3

223.0

149.3

221.4

127.0

219.0

105.4

213.8

80.6

67

24.6

214.0

211.5

210.3

189.1

208.8

165.4

206.4

143.4

204.4

120.2

201.9

99.8

199.4

75.6

62

24.3

215.0

215.0

208.1

208.1

201.1

201.1

194.3

182.2

191.9

159.7

189.6

137.0

187.1

114.4

57

24.1

214.9

214.9

208.0

208.0

201.0

201.0

193.9

193.9

186.9

186.9

178.1

174.5

175.3

152.4

72

25.4

228.5

185.3

226.0

159.4

224.2

134.0

221.6

109.3

218.8

79.6

67

24.9

222.5

222.5

214.9

203.8

212.5

177.9

209.4

152.5

207.5

127.3

203.5

102.3

62

24.5

222.4

222.4

215.2

215.2

208.0

208.0

199.6

196.6

195.4

170.8

192.5

145.2

189.9

119.8

57

24.4

222.3

222.3

215.1

215.1

208.0

208.0

200.7

200.7

193.4

193.4

186.0

186.0

178.8

163.0

72

25.5

231.2

198.0

229.1

169.8

226.4

140.7

223.5

113.1

219.6

81.7

67

25.0

228.3

228.3

219.6

217.8

215.1

188.8

212.6

161.9

209.7

133.0

205.9

105.8

62

24.7

228.2

228.2

220.8

220.8

213.7

213.7

206.2

206.2

199.0

182.0

195.6

153.5

192.7

124.8

57

24.5

228.1

228.1

220.7

220.7

213.6

213.6

206.1

206.1

198.6

198.6

191.0

191.0

182.5

172.5

72

25.6

232.2

203.0

230.0

173.6

227.2

143.3

224.2

114.5

183.7

72.1

67

25.1

230.4

230.4

223.1

223.1

216.0

193.2

213.5

165.3

210.5

135.2

206.9

106.6

62

24.8

230.3

230.3

222.9

222.9

215.6

215.6

208.1

208.1

200.1

185.9

196.5

156.4

193.5

126.7

57

24.6

230.1

230.1

222.8

222.8

215.3

215.3

208.0

208.0

200.4

200.4

192.8

192.8

183.6

176.0

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.

Unitary Products Group

13

036-21035-002-D-0602

TABLE 12: COOLING CAPACITIES FOR DHE/DHG 240 AT 115F


Capacity (MBH) at Entering Dry Bulb (F)

Air On Evaporator
Coil

86

83

80

77

74

71

68

CFM

6000

7000

8000

9000

9400

WB F

Tot.
Input
(kW)

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

TOT2

SEN

72

26.5

206.3

153.2

204.4

132.6

203.2

114.2

199.3

94.3

192.0

71.9

67

25.8

194.2

186.8

192.1

167.5

190.9

147.2

188.9

128.2

187.2

109.1

184.6

90.1

178.8

178.8

62

25.4

194.1

194.1

187.6

187.6

181.4

181.4

176.2

161.3

187.2

109.1

172.9

122.4

171.1

103.4

57

24.9

194.0

194.0

187.6

187.6

181.1

181.1

174.5

174.5

167.9

167.9

161.1

154.8

158.9

135.4

72

26.6

210.3

166.6

207.7

142.9

205.6

120.4

203.9

99.6

203.6

77.1

67

26.1

202.9

202.9

197.0

183.2

195.0

159.4

192.4

137.5

190.6

115.3

187.6

93.6

62

25.6

202.8

202.8

196.1

196.1

189.2

189.2

181.6

175.7

178.9

153.5

176.5

130.8

173.6

108.1

57

25.4

202.7

202.7

196.0

196.0

189.3

189.3

182.5

182.5

175.7

175.7

168.5

168.5

163.0

146.0

72

26.7

213.4

179.5

211.3

154.3

208.9

128.1

206.0

103.0

202.7

77.4

67

26.3

209.5

209.5

201.7

198.1

198.1

171.2

195.8

147.1

193.1

121.2

187.9

96.1

147.9

57.4

62

25.9

209.4

209.4

202.6

202.6

195.5

195.5

195.8

147.1

182.1

164.4

179.9

139.4

176.9

113.6

57

25.7

209.3

209.3

202.5

202.5

195.6

195.6

188.6

188.6

181.5

181.5

174.2

174.2

166.9

156.4

72

26.8

216.3

192.6

213.6

163.7

210.8

134.7

207.5

106.3

203.7

77.6

67

26.5

214.7

214.7

207.8

207.8

201.3

183.1

198.1

155.6

195.0

126.8

190.2

98.8

62

26.1

214.6

214.6

207.7

207.7

200.6

200.6

193.5

193.5

185.5

175.4

182.2

146.9

178.8

118.3

57

26.0

214.5

214.5

207.6

207.6

200.6

200.6

193.4

193.4

186.2

186.2

178.8

178.8

170.6

166.6

72

26.9

217.7

198.2

214.4

167.4

211.4

137.3

207.9

107.6

204.6

77.8

67

26.6

216.6

216.6

209.6

209.6

202.3

187.2

198.9

158.9

195.7

128.9

187.8

96.9

62

26.2

216.4

216.4

209.5

209.5

202.4

202.4

195.2

195.2

186.6

178.8

183.0

149.8

179.5

120.1

57

26.1

216.4

216.4

209.4

209.4

202.3

202.3

195.1

195.1

187.8

187.8

180.4

180.4

171.9

170.6

1. The ratings include the condenser fan motors (Total 1.7 kW) and the compressor motors but not the supply air blower motor.
2. These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x kW. Refer to
the appropriate Blower Performance Table for the kW of the supply air blower motor.

14

Unitary Products Group

036-21035-002-D-0602

TABLE 13: DHG 15 TON SUPPLY AIR BLOWER PERFORMANCE


DHG180 - BOTTOM DUCT CONNECTIONS1, 2
BLOWER
SPEED,
(RPM)

CFM

MOTOR
PULLEY
(TURNS
OPEN)3

4500
4

ESP

BHP

5250
KW

ESP

6000
3

6750

BHP

KW

ESP

BHP

KW

ESP

7200
3

BHP

KW

ESP

BHP

KW

208 VOLT AND STANDARD DRIVE


850

6.05

0.9

2.4

2.1

0.6

2.9

2.6

0.3

3.4

3.0

870

5.5

1.0

2.5

2.2

0.7

3.0

2.7

0.4

3.5

3.1

915

4.5

1.1

2.6

2.4

0.8

3.1

2.8

0.5

3.6

3.2

0.2

4.1

3.7

965

3.5

1.2

2.7

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.9

0.2

5.0

4.5

980

3.0

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1010

2.0

1.4

3.0

2.7

1.1

3.6

3.2

0.8

4.0

3.6

0.6

4.7

4.2

0.4

5.4

4.8

1040

1.0

1.6

3.2

2.9

1.3

3.8

3.4

1.0

4.4

3.9

0.8

5.0

4.5

0.6

5.6

5.0

208 VOLT AND HIGH SPEED DRIVE ACCESSORY


965

6.0

1.2

2.7

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.9

0.2

5.0

4.5

980

5.5

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1025

4.5

1.4

3.1

2.8

1.2

3.6

3.2

0.9

4.1

3.7

0.7

4.8

4.3

0.4

5.5

4.9

1065

3.5

1.6

3.4

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

1125

2.0

1.9

3.6

3.2

1.7

4.4

3.9

1.4

5.0

4.5

1.2

5.8

5.2

1170

1.0

2.1

3.9

3.5

1.9

4.7

4.2

1.6

5.5

4.9

230/460 VOLT AND STANDARD DRIVE


870

6.04

1.0

2.5

2.2

0.7

3.0

2.7

0.4

3.5

3.1

915

5.0

1.1

2.6

2.4

0.8

3.1

2.8

0.5

3.6

3.2

0.2

4.1

3.7

965

4.0

1.2

2.7

2.5

0.9

3.2

2.9

0.6

3.7

3.3

0.4

4.4

3.9

0.2

5.0

4.5

980

3.5

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1015

2.5

1.4

3.0

2.7

1.1

3.6

3.2

0.8

4.0

3.6

0.6

4.7

4.2

0.4

5.4

4.8

1050

1.5

1.5

3.1

2.8

1.2

3.7

3.3

0.9

4.2

3.8

0.7

4.9

4.4

0.5

5.7

5.1

1065

1.0

1.6

3.4

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

230/460 VOLT AND HIGH SPEED DRIVE ACCESSORY


980

6.0

1.3

2.9

2.6

1.0

3.4

3.0

0.7

3.8

3.4

0.5

4.5

4.0

0.3

5.1

4.6

1045

4.5

1.6

3.2

2.9

1.3

3.8

3.4

1.0

4.4

3.9

0.8

5.0

4.5

0.6

5.6

5.0

1065

4.0

1.7

3.4

3.0

1.4

3.9

3.5

1.1

4.5

4.0

0.9

5.1

4.6

1125

2.5

1.9

3.6

3.2

1.7

4.4

3.9

1.4

5.0

4.5

1.2

5.8

5.2

1170

1.5

2.1

3.9

3.5

1.8

4.7

4.2

1.6

5.5

4.9

1190

1.0

2.2

4.0

3.6

1.9

4.8

4.3

1.7

5.6

5.0

1.
2.
3.
4.

Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2 T/A filters and a dry evaporator coil.
Refer to the Static Resistance table.
DO NOT close the pulley below one turn open.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been
deducted from the total static pressure of the blower.
5. The factory setting.

Unitary Products Group

15

036-21035-002-D-0602

TABLE 14: DHG 20 TON SUPPLY AIR BLOWER PERFORMANCE


DHG240 - BOTTOM DUCT CONNECTIONS1, 2
BLOWER
SPEED,
(RPM)

CFM

MOTOR
PULLEY
(TURNS
OPEN)3

6000
4

ESP

BHP

7000
KW

8000

ESP

BHP

KW

ESP

9000

BHP

KW

ESP

9400

BHP

KW

ESP

BHP

KW

208 VOLT AND STANDARED DRIVE


870

6.05

1.3

3.6

3.0

0.7

4.3

3.7

0.2

5.1

4.3

900

5.0

1.4

3.8

3.2

0.9

4.7

4.0

0.4

5.6

4.7

930

4.0

1.6

4.1

3.4

1.1

5.0

4.2

0.6

5.9

5.0

0.1

6.7

5.7

950

3.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

980

2.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

1.5

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1015

1.0

2.2

4.8

4.0

1.7

5.7

4.8

1.2

6.6

5.6

0.7

7.8

6.6

208 VOLT AND HIGH SPEED DRIVE ACCESSORY


950

6.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

980

5.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

4.5

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1025

3.5

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

1050

2.5

2.5

5.1

4.3

2.0

6.1

5.1

1.4

7.1

6.0

0.9

8.4

7.0

1065

2.0

2.6

5.3

4.4

2.1

6.3

5.3

1.5

7.3

6.2

1.0

8.6

7.2

1100

1.0

2.9

5.6

4.7

2.3

6.8

5.7

1.8

7.9

6.6

230/460 VOLT AND STANDARD DRIVE


870

6.05

1.3

3.6

3.0

0.7

4.3

3.7

0.2

5.1

4.3

900

5.0

1.4

3.8

3.2

0.9

4.7

4.0

0.4

5.6

4.7

930

4.0

1.6

4.1

3.4

1.1

5.0

4.2

0.6

5.9

5.0

0.1

6.7

5.7

950

3.5

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

965

2.5

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

2.0

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1015

1.5

2.2

4.8

4.0

1.7

5.7

4.8

1.2

6.6

5.6

0.6

7.8

6.6

1025

1.0

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

230/460 VOLT AND HIGH SPEED DRIVE ACCESSORY


950

6.0

1.7

4.2

3.6

1.3

5.1

4.3

0.8

6.0

5.1

0.2

6.9

5.8

980

5.0

1.9

4.5

3.8

1.5

5.4

4.5

1.0

6.3

5.3

0.4

7.2

6.1

0.1

8.5

7.1

995

4.5

2.1

4.6

3.9

1.6

5.5

4.7

1.1

6.4

5.4

0.5

7.5

6.3

0.2

8.6

7.3

1015

4.0

2.2

4.8

4.0

1.7

5.7

4.8

1.2

6.6

5.6

0.6

7.8

6.6

1025

3.5

2.3

4.9

4.1

1.8

5.8

4.9

1.3

6.7

5.7

0.7

8.0

6.7

1050

3.0

2.5

5.1

4.3

2.0

6.1

5.1

1.4

7.1

6.0

0.9

8.4

7.0

1065

2.5

2.6

5.3

4.4

2.1

6.3

5.3

1.5

7.3

6.2

1.0

8.6

7.2

1100

1.5

2.9

5.6

4.7

2.3

6.8

5.7

1.8

7.9

6.6

1120

1.0

3.1

5.8

4.9

2.5

7.0

5.9

1.9

8.3

6.9

1.
2.
3.
4.

Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2 T/A filters and a dry evaporator coil.
Refer to the Static Resistance table.
DO NOT close the pulley below one turn open.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have
been deducted from the total static pressure of the blower.
5. The Factory Setting.

16

Unitary Products Group

036-21035-002-D-0602

TABLE 15: DHE 15 TON SUPPLY AIR BLOWER PERFORMANCE


DHE180 - BOTTOM DUCT CONNECTIONS1, 2
BLOWER
SPEED,
(RPM)

CFM

MOTOR
PULLEY
(TURNS
OPEN)3

4500
ESP

BHP

5250
4

KW

ESP

BHP

6000
KW

ESP

BHP

6750
KW

ESP

BHP

7200
KW

ESP

BHP

KW

208 VOLT AND STANDARD DRIVE


850

6.05

0.9

2.4

2.2

0.7

3.0

2.7

0.5

3.2

2.9

870

5.5

1.0

2.5

2.3

0.8

3.1

2.8

0.6

3.5

3.1

0.2

4.1

3.7

915

4.5

1.1

2.6

2.4

0.9

3.4

3.0

0.7

3.7

3.3

0.3

4.4

3.9

0.2

4.5

4.0

965

3.5

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

4.9

4.4

980

3.0

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1010

2.0

1.4

3.1

2.8

1.2

3.8

3.4

1.0

4.2

3.8

0.7

5.0

4.5

0.6

5.4

4.8

1040

1.0

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.2

4.7

0.7

5.7

5.1

208 VOLT AND HIGH SPEED DRIVE ACCESSORY


965

6.0

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

5.0

4.4

980

5.5

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1025

4.5

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.8

5.1

4.6

0.7

5.6

5.0

1065

3.5

1.6

3.4

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

1095

3.0

1.7

3.5

3.1

1.5

4.2

3.8

1.3

4.9

4.4

1.2

5.7

5.1

1130

2.0

1.9

3.7

3.3

1.7

4.5

4.0

1.5

5.1

4.6

1170

1.0

2.1

3.9

3.5

2.0

4.7

4.2

1.8

5.5

4.9

230/460/575 VOLT AND STANDARD DRIVE


870

6.05

1.0

2.4

2.2

0.8

3.1

2.8

0.6

3.5

3.1

0.2

4.1

3.7

915

5.0

1.1

2.6

2.4

0.9

3.3

3.0

0.7

3.7

3.3

0.3

4.4

3.9

0.2

4.5

4.0

965

4.0

1.2

2.9

2.6

1.0

3.6

3.2

0.8

4.0

3.6

0.5

4.7

4.2

0.4

5.0

4.4

980

3.5

1.3

3.0

2.7

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1040

2.0

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.3

4.7

0.7

5.7

5.1

1065

1.0

1.6

3.3

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

230/460/575 VOLT AND HIGH SPEED DRIVE ACCESSORY


980

6.0

1.3

2.9

2.6

1.1

3.7

3.3

0.9

4.1

3.7

0.6

4.8

4.3

0.5

5.1

4.6

1040

4.5

1.5

3.2

2.9

1.3

3.9

3.5

1.1

4.5

4.0

0.9

5.3

4.7

0.7

5.7

5.1

1065

4.0

1.6

3.4

3.0

1.4

4.0

3.6

1.2

4.7

4.2

1.0

5.5

4.9

1095

3.5

1.7

3.5

3.1

1.5

4.2

3.8

1.3

4.9

4.4

1.2

5.7

5.1

1130

2.5

1.9

3.7

3.3

1.7

4.5

4.0

1.5

5.1

4.6

1170

1.5

2.1

3.9

3.5

2.0

4.7

4.2

1.8

5.5

4.9

1190

1.0

2.2

4.0

3.6

2.1

4.8

4.3

2.0

5.7

5.1

1.
2.
3.
4.

Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2 T/A filters and a dry evaporator coil.
Refer to the Static Resistance table.
DO NOT close the pulley below one turn open.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been
deducted from the total static pressure of the blower.
5. The Factory Setting.

Unitary Products Group

17

036-21035-002-D-0602

TABLE 16: DHE 20 TON SUPPLY AIR BLOWER PERFORMANCE


DHE240 - BOTTOM DUCT CONNECTIONS1, 2
BLOWER
SPEED,
(RPM)

CFM

MOTOR
PULLEY
(TURNS
OPEN)3

600
ESP

BHP

7000
KW

ESP

8000

BHP

KW

ESP

BHP

9000
4

9400

KW

ESP

BHP

KW

ESP

BHP

KW

208 VOLT AND STANDARD DRIVE


870

6.05

0.4

2.1

1.8

0.1

2.3

2.0

900

5.0

0.8

3.2

2.7

0.5

3.5

2.9

0.2

3.8

3.2

930

4.0

1.1

4.1

3.4

0.9

4.5

3.8

0.6

4.9

4.1

0.1

5.1

4.3

950

3.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

980

2.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

1.0

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

208 VOLT AND HIGH SPEED DRIVE ACCESSORY


950

6.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

980

5.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1010

4.0

1.8

5.8

4.9

1.7

6.3

5.3

1.5

6.9

5.8

1.0

7.5

6.3

0.5

7.9

6.7

1020

3.5

1.9

6.1

5.1

1.8

6.5

5.5

1.6

7.1

6.0

1.1

7.8

6.6

0.6

8.3

7.0

1035

3.0

2.0

6.2

5.2

1.9

6.8

5.7

1.7

7.4

6.2

1.2

8.1

6.8

0.7

8.6

7.3

1050

2.5

2.1

6.4

5.4

2.0

7.0

5.9

1.8

7.6

6.4

1.3

8.3

7.0

1075

2.0

2.3

6.6

5.5

2.1

7.2

6.0

1.9

7.8

6.6

1.5

8.6

7.2

1100

1.0

2.4

6.7

5.6

2.2

7.3

6.1

2.1

7.9

6.7

230/460/575 VOLT AND STANDARD DRIVE


870

6.05

0.4

2.1

1.8

0.1

2.3

2.0

900

5.0

0.8

3.2

2.7

0.5

3.5

2.9

0.2

3.8

3.2

930

4.0

1.1

4.1

3.4

0.9

4.5

3.8

0.6

4.9

4.1

0.1

5.1

4.3

950

3.5

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

980

2.5

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

1.5

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

1025

1.0

2.0

6.1

5.1

1.8

6.6

5.6

1.6

7.3

6.1

1.1

7.9

6.7

0.7

8.6

7.3

230/460/575 VOLT AND HIGH SPEED DRIVE ACCESSORY


950

6.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

980

5.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

4.0

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

1035

3.5

2.0

6.2

5.2

1.9

6.8

5.7

1.7

7.4

6.2

1.2

8.1

6.8

0.7

8.6

7.3

1050

3.0

2.1

6.4

5.4

2.0

7.0

5.9

1.8

7.6

6.4

1.3

8.3

7.0

1080

2.0

2.3

6.6

5.5

2.1

7.2

6.0

1.9

7.8

6.6

1.5

8.6

7.2

1100

1.5

2.4

6.7

5.6

2.2

7.3

6.1

2.1

7.9

6.7

1120

1.0

2.5

6.8

5.7

2.3

7.4

6.2

2.2

8.1

6.8

1.
2.
3.
4.

Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2 T/A filters and a dry evaporator coil.
Refer to the Static Resistance table.
DO NOT close the pulley below one turn open.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been
deducted from the total static pressure of the blower.
5. The Factory Setting.

18

Unitary Products Group

036-21035-002-D-0602

TABLE 17: BLOWER MOTOR AND DRIVE DATA (DHG/DHE MODELS)


MODEL
DRIVE
SIZE

Std.
15 Ton

HP FRAME

ADJ. MOTOR PULLEY


EFF. DESIGN(%) NATION

O/D
(in.)

PITCH
BORE DESIGNDIA
(in.)
NATION
(in.)

965/1190

Std.

870/1025
950/1120

184T

7.5

213T

89.5

91

1VP56

1VP68

5.35

6.75

4.3-

5.5-

1-3/8

6.52

PITCH
PITCH
BORE DESIGDIA
LNGTH. QTY.
(in.) NATION
(in.)
(in.)

O/D
(in.)

BK90

8.75

8.4

BX70

71.8

BK80

7.75

7.4

BX68

69.8

BK120

11.75

11.4

1-3/16

BX83

84.8

BK110

10.75

10.4

1-3/16

BX80

81.8

1-1/8

5.32

BELT
(NOTCHED)

FIXED BLOWER PULLEY

850/1065

High
Spd.
Acs.
High
Spd.
Acs.

20 Ton

MOTOR1

BLWR
RANGE
(RPM)

1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base.
2. DO NOT close this pulley below 1 turn.

TABLE 18: STATIC RESISTANCES1


RESISTANCE, IWG
CFM
DESCRIPTION
15 TON
4500

5765

7200

6000

7000

9400

0.1

0.1

0.1

0.1

0.1

0.1

18kW

0.1

0.1

0.1

0.1

0.1

0.1

36kW

0.1

0.2

0.3

0.1

0.2

0.3

54kW

0.2

0.3

0.4

0.2

0.3

0.4

72kW

0.2

0.4

0.6

0.2

0.4

0.6

0.1

0.1

0.1

0.1

0.1

0.1

0.2

0.3

0.5

0.2

0.3

0.5

WET COIL

ELECTRIC HEAT
OPTIONS
(DHE models only)

EXONOMIZER OPTION
HORIZONTAL DUCT

20 TON

CONN.2

1. Deduct theses resistance values from the available unit ESP values listed in the respective blower performance table except for Horizontal Duct Connections.
2. Add these values due to less airflow resistance.

TABLE 19: POWER EXHAUST PERFORMANCE


STATIC RESISTANCE OF RETRUN DUCTWORK, IWG

MOTOR
SPEED

0.2

0.3

0.4

0.5

0.6

CFM

kW

CFM

kW

CFM

kW

CFM

kW

CFM

kW

HIGH2

5250

0.83

4500

0.85

4200

0.88

3750

0.93

3000

0.99

MEDIUM

4900

0.77

3900

0.79

3500

0.82

2900

0.85

LOW

4400

0.72

3700

0.74

3000

0.78

1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
2. The factory setting.

Unitary Products Group

19

036-21035-002-D-0602

TABLE 20: DHG ELECTRICAL DATA


COMPRESSORS
MODEL

DHG180
DHG240

COND. FAN
MOTORS
(#1 & #2)

SUPPLY AIR
BLOWER
MOTOR

RLA

LRA

RLA

LRA

HP
(ea.)

FLA
(ea.)

HP

FLA

MIN.
CIRCUIT
AMPACITY
(AMPS)

208/230-3-60

28.6

274

14.3

137

4.1/4.2

11.8

77.8/77.0

POWER
SUPPLY

#1

#2

MIN. WIRE

MAX. TIME
DELAY FUSE
SIZE (AMPS)
90

4
8

SIZE1
75C

460-3-60

14.4

138

7.2

69

2.1

5.9

42.7

50

208/230-3-60

28.6

274

28.6

274

4.1/4.2

7.5

18.6

98.6/96.8

110

460-3-60

14.4

138

14.4

138

11

2.1

7.5

9.3

52.2

60

1. Although these sizes are based on copper conductors aluminum wire can be use3d. Refer to the National Electric Code to determine the proper size

TABLE 21: DHG VOLTAGE LIMITATIONS1

TABLE 22: DHE VOLTAGE LIMITATIONS1

VOLTAGE

POWER SUPPLY

VOLTAGE

POWER SUPPLY

MIN.

MAX.

208/230-3-60

187

253

460-3-60

414

506

1. Utilization Range A in accordance with ARI Standard


110.

MIN.

MAX.

208/230-3-60

187

253

460-3-60

414

506

575-3-60

518

506

1. Utilization Range A in accordance with ARI Standard


110.

TABLE 23: DHE ELECTRICAL DATA


COMPRESSORS
MODEL

POWER
SUPPLY

#1
RLA

DHE180

DHE240

#2
LRA

RLA

LRA

COND. FAN
MOTORS
(#1 & #2)

SUPPLY AIR
BLOWER
MOTOR

HP
(ea.)

FLA
(ea.)

HP

MIN. WIRE
MAX. TIME
DELAY FUSE
SIZE (AMPS)

FLA

MIN.
CIRCUIT
AMPACITY
(AMPS)

SIZE1
75C

208/230-3-60

28.6

274

14.3

137

3.6

11.8

77.0

90

460-3-60

14.4

138

7.2

69

2.0

5.9

42.7

50

575-3-60

11.4

116

5.7

58

1.4

5.2

30.7

35

208/230-3-60

28.6

274

28.6

274

3.6

7.5

18.6

98.6

110

460-3-60

14.4

138

14.4

138

2.0

7.5

9.3

52.2

60

575-3-60

11.4

116

11.4

116

1.4

7.5

7.5

40.2

45

1. Although these sizes are based on copper conductors aluminum wire can be used. Refer to the National Electric Code to determine the proper size.

20

Unitary Products Group

036-21035-002-D-0602

TABLE 24: ELECTRICAL DATA UNITS WITH SUPPLEMENTAL ELECTRIC HEAT


MODEL
D1HE

POWER
SUPPLY

208-3-60

180A25
230-3-60

180A46

460-3-60

180A58

575-3-60

208-3-60

240A25
230-3-60

240A46

460-3-60

240A58

575-3-60

HEATER OPTION
1

MIN. CIRCUIT
AMPACITY
(AMPS)

MAX. TIME
DELAY FUSE
SIZE (AMPS)

77.0

90
125

STAGES

AMPS

13.5

37.5

E036

27.0

75.1

111.8

E054

40.6

112.6

158.7

175

E072

54.1

150.1

168.1

200

E018

18.0

43.3

77.0

90

E036

36.0

86.6

126.3

150

E054

54.0

129.9

147.9

175

E072

72.0

173.2

191.2

225

E018

18.0

21.7

42.7

50

E036

36.0

43.3

63.1

70

E054

54.0

65.0

74.0

90

E072

72.0

86.6

95.6

110

E018

18.0

17.3

30.7

35

E036

36.0

34.6

50.7

60

E054

54.0

52.0

59.3

70

E072

72.0

69.3

76.7

90

E018

13.5

37.5

96.8

110

E036

27.0

75.1

118.1

125

E054

40.6

112.6

165.0

175

E072

54.1

150.1

174.4

200

E018

18.0

43.3

96.8

110

E036

36.0

86.6

132.5

150

E054

54.0

129.9

154.2

175

E072

72.0

173.2

197.5

225

E018

18.0

21.7

52.2

60

E036

36.0

43.3

66.3

70

E054

54.0

65.0

77.1

90

E072

72.0

86.6

98.7

110

E018

18.0

17.3

40.2

45

E036

36.0

34.6

53.1

60

E054

54.0

52.0

61.7

70

E072

72.0

69.3

79.0

90

MODEL

kW

E018

1. See Table 25 for electric heat correction factors.

TABLE 25: ELECTRIC HEAT CORRECTION FACTORS


NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTIPLIER

208

208

1.00

240

230

0.92

480

460

0.92

600

575

0.92

Unitary Products Group

21

036-21035-002-D-0602

CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT1
UNIT TERMINAL
TERMINALS
BLOCK 1TB2

COOLING ONLY (24 VOLT THERMOSTAT)


THERMOSTAT1
TERMINALS
UNIT TERMINAL
RC
BLOCK 1 TB2
RH
R
Y1
Y1
ADD
Y2
Y2
JUMPER
W1
W1
G
B
LED1
LED2
ADD
JUMPER

NOT USED

COM
A1
A2
T

Y1

ADD
JUMPER

Y2
W1
W2

W2
G
B
X

W2

R
Y1
Y2
W1
W2
G
B
X
A1
A2
Y3

RH
RC

24 VOLT
TRANSFORMER

24 Volt Thermostat 2TH04701024 or 2TH04701524


(with Subbase 2TB04700324).
Terminal strip 1TB - located on relay board in 24-volt section
of the unit control box.
3Second stage heating is not required on units with a single stage
electric heater.
1

24 VOLT
A1 TRANSFORMER
A2

POWER WIRING

L1
LINE VOLTAGE
TERMINAL
L2
BLOCK 2TB
L3
IN CONTROL BOX

TO REMOTE SENSOR
2THO4702224 IF USED
1Electronic programmable thermostat 2ET04700224 (includes subbase).
2Terminal block 1TB- located on relay board in 24-volt section of the unit control box.
3Second stage heating is not required on units with a single stage electric heater.
4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers
when the thermostat switches to the set-back position.
NOTE: Fans switch must be in "ON" position for minimum ventilation during heater operation.

Refer to the
ELECTRICAL DATA
tables to size the
power wiring, the
fuses and the
disconnect switch.

GROUND LUG

FIGURE 2 : DHG/DHE FIELD WIRING DIAGRAM

TABLE 26: PHYSICAL DATA

TABLE 27: OPERATING WEIGHTS (LBS.)


DHG/DHE

MODELS
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
(Two Per Unit)
CONDENSER
COILS
(Two Per Unit)
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS

CHARGE

MODEL SIZE

15 TON

20 TON

180

240

Centrifugal Blower (Dia. x Wd. in.)

15 x 15

18 x 15

Fan Motor HP

7.5

Rows Deep

Economizer

160

Economizer with
Power Exhaust

245

Motorized Damper

150

Fins Per Inch

13.5

13.5

Face Area (Sq. Ft.

15.5

20.0

Propeller Dia. (in.) (Each)

30

30

Fan Motor Hp (Each)


Nom. CFM (Each)
Rows Deep (Each)
Fins Per Inch (Each)
Face Area (Sq. Ft.) (Total)

1
5765
3
13
36.0

DHG
(Gas/Electric)

1900

2100

240Mbh

2100

2300

320Mbh

2140

OPTIONS

1
Electric Heater
(DHE only)

7000
3
43.3

11

5-Ton Hermetic Recip.

Quantity Per Unit (16 X 20 X 2)

Quantity Per Unit (16 X 25 X 2)

Quantity Per Unit (18 X 24 X 2)

Total Face Area (sq. ft.)

15.0

20.0

System #1

29/9

23

System #2

14/8

23/12

ACCY.

2340

18kW

25

36kW

30

54kW

35

72kW

15

10-Ton Tandem Hermetic Recip.

Refrigerant 22
(lbs./oz.)

BASIC
UNIT

DHE (Cooling Only)

40

Roof Curb

175

Barometric Damper

45

185
45

Wood Skid

220

220

1. This compressor will be energized first.

22

Unitary Products Group

036-21035-002-D-0602

BLOWER
ACCESS
BLOWER MOTOR
ACCESS
BLOWER
COMPARTMENT
ACCESS
(Auxiliary)

ECONOMIZER / MOTORIZED DAMPER,


FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")
COMPRESSOR
ACCESS
(See detail "X")

FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION

OPTIONAL COIL
GUARD KIT

DOT PLUG
(For pressure
Drop Reading)

48-5/8" (15 Ton)


52-5/8" (20 Ton)

GAS HEAT
ACCESS
VENT AIR
OUTLET
HOODS
COMBUSTION
AIR INLET
HOOD
(C)
GAS SUPPLY
ENTRY

)
Ton n)
(15 To
/4" " (20
1
4
6-3/8"
12536-1/
1

7-1/8"

9-3/4"
5-7/8"

n)
To n)
(15 20 To
"
4 (
-1/ 4"
24 5-1/
3

33"

BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)

RETURN
AIR

2-3/4"

(B)
POWER WIRING
ENTRY

RETURN AIR
3-3/4"

SUPPLY AIR

SUPPLY
AIR
21-1/2"

OUTDOOR AIR
OUTDOOR AIR
(Economizer)
(B)
POWER WIRING
ENTRY

(D)
GAS SUPPLY
ENTRY

NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.

(A)
CONTROL WIRING
ENTRY

11-1/2"

11-1/8"

UNIT BASE WITH RAILS


Shown separately to illustrate
Bottom Duct openings, Power
and Gas Piping Connection
locations

92"

46-5/8"

CONTROL BOX
35"
ACCESS

FRONT
VIEW

CONDENSER
COILS

21"
5"

8-1/8"
46-5/8"

9-1/4"
12-1/2"

All dimensions are in inches. They are


subject to change without notice. Certified dimensions will be provided upon
request.

(A)
CONTROL WIRING
ENTRY

9-3/4"

FIGURE 3 : UNIT DIMENSIONS DHE/DHG180 & 240 (FRONT VIEW)


TABLE 28: MINIMUM CLEARANCES

TABLE 29: UTILITIES ENTRY

LOCATION

CLEARNANCE

Front

36

Back

24 (Less Economizer)
49 (With Economizer

Left Side (Filter Access)

24 (Less Economizer)
36 (With Economizer)

Right Side (Cond. Coil)

36

Below Unit1

Above Unit2

72 With 36 Maximum
Horizontal Overhang (For
Condenser Air Discharge)

1. Units may be installed on combustible floors made


from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
NOTE: A 1 clearance must be provided between any com-

bustible material and the supply air ductwork for a distance of


3 feet from the unit.
NOTE: The products of combustion must not be allowed to

accumulate within a confined space and recirculate.

HOLE
A

OPENING SIZE (DIA.)


1-1/8 KO

USED FOR
Control Wiring

3/4 NPS (Fem.)

3-5/8 KO
3 NPS (Fem.)

Front
Bottom

Power Wiring

Front
Bottom

2-3/8 KO

Gas Piping (Front)1

1-11/16 Hole

Gas Pipping (Bottom)1,2

1. One-inch Gas Piping MPT Required.


2. Opening in the bottom to the unit can be located by the
side in the insulation.
NOTE: Locate unit so that the vent air outlet hood is at least:

Three (3) feet above any force air inlet located within 10
horizontal feet (excluding those integral to the unit).

Four (4) feet below, 4 horizontal feet from, or 1 foot


above any door or gravity air inlet into the building.

Four (4) feet from electric and gas meters, regulators


and relief equipment

NOTE: All entry holes should be field sealed to prevent rain

water entry into building.

Unitary Products Group

23

036-21035-002-D-0602

C O N D E N S E R S E C T IO N
G A U G E L IN E
A C C E S S

E V A P O R A T O R
S E C T IO N

D O T P L U G
(F o r p re s s u re
d r o p r e a d in g )
4 0 -3 /8 "

F IL T E R
A C C E S S
S U P P L Y
A IR
R E T U R N
A IR

5 -1 /2 "

C O M P R E S S O R
A C C E S S

1 " N P T F E M A L E
C O N D . D R A IN
C O N N E C T IO N

O U T D O O R
A IR

S U P P L Y A IR
A C C E S S

4 0 -1 /2 "

OUTDOOR AIR PANEL SIZES

1 8 -5 /8 "

R E A R
V IE W

15 TON UNITS 21-1/2 X 43


20 TON UNITS 32-1/2 X 43

2 7 -3 /4 "

R E T U R N A IR
A C C E S S

O U T D O O R A IR
C O M P A R T M E N T
A C C E S S

5 -1 /8 "

2 8 -5 /8 " (1 5 T o n s )
3 9 -5 /8 " (2 0 T o n s )

FIGURE 4 : UNIT DIMENSIONS DHE/DHG180 & 240 (REAR VIEW)


NOTE: Units are shipped with the bottom duct openings ocov-

ered. An accessory flange kit is available for connecting side


ducts.
For bottom duct applications:
1.

Remove the side panels from the supply and return air
compartments to gain access to the bottom supply and
return air duct covers.
2.Remove and discard the bottom duct covers. Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.
3.Replace the side supply and return air compartment
panels.
For side duct application:
1.

24

Replace the side panels on the supply and return air


compartments with the accessory flange kit panels.
2.Connect ductwork to the duct flanges on the rear of
the unit.

FIGURE 5 : UNIT CENTER OF GRAVITY

Unitary Products Group

036-21035-002-D-0602

S U P P L Y A IR
C O M P A R T M E N T

P O W E R E X H A U S T
R A IN H O O D
( o n R e tu r n A ir C o m p a r tm e n t)

E C O
M O T
D A M
R A IN
(o n O

N O M IZ E R
O R IZ E D
P E R
H O O D
u td o o r A ir C o m p a r tm e n t)

E C O N O M IZ E R / M O T O R IZ E D D A M P E R
A N D P O W E R E X H A U S T R A IN H O O D S

F IX E
O U T
IN T A
( lo c a
R e tu
C o m

3 4 -1 /4 "

D
D O O R A IR
K E H O O D
te d o n
r n A ir
p a rtm e n t)

1 " C O N D E N S T A T E
D R A IN
(M u s t b e tra p p e d )

1 6 -1 /8 "

5 "
3 6 "
6 6 -1 /2 "

R E A R

V IE W

2 "

9 2 "

3 6 -1 /4 "

D E T A IL "Y "
U N IT W IT H R A IN H O O D S

L H

V IE W

FIGURE 6 : UNIT DIMENSIONS DHE/DHG180 & 240 (RAINHOOD)

FIGURE 7 : TYPICAL UNIT APPLICATIONS

Unitary Products Group

25

036-21035-002-D-0602

B
C
A

F R O N T

FIGURE 8 : UNIT 4 POINT LOAD

E
F

D
A
C
F R O N T
B

FIGURE 9 : UNIT 6 POINT LOAD


TABLE 3: DHE/DHG 4 POINT LOADS WEIGHT DISTRIBUTION
UNIT

TOTAL

DHE180

2060

483

525

548

504

DHE240

2206

568

814

888

620

DHG180

2300

539

563

612

586

DHG240

2500

538

563

715

684

TABLE 4: DHE/DHG 6 POINT LOADS WEIGHT DISTRIBUTION

26

UNIT

TOTAL

DHE180

2060

322

336

350

365

351

336

DHE240

2260

325

368

412

431

385

339

DHG180

2300

351

367

392

416

399

375

DHG240

2500

334

350

426

502

481

407

Unitary Products Group

036-21035-002-D-0602

FIGURE 10 : UNIT ROOF CURB DIMENSIONS

FIGURE 12 : CUT AWAY OF ROOF CURB


FIGURE 11 : ROOF CURB DUCT OPENINGS
DIMENSION
1.

The 2 space between the ducts allows for jumping an


existing roof joist.
2.The 58-1/2 overall dimension of the ducts allows
ductwork penetration between roof joists that are
spaced on 72 centers.

NOTE: Ducts can be installed into the curb from the roof. All

electrical and gas line connections can be made inside the


curb.

Unitary Products Group

27

036-21035-002-D-0602

FIGURE 13 : TYPICAL ROOFTOP INSTALLATION

28

Unitary Products Group

036-21035-002-D-0602

NOTES

Unitary Products Group

29

036-21035-002-D-0602

30

Unitary Products Group

036-21035-002-D-0602

Unitary Products Group

31

Subject to change without notice. Printed in U.S.A.


Copyright by Unitary Products 2002. All rights reserved.
Unitary
Products
Group

Supersedes: 035-21035-002-C-0500
5005
York
Drive

036-21035-002-D-0602
Norman
OK