ELEAD ASSOCIATES

AIR CONDITIONING HEAT LOAD CALCULATION


PROJECT PROPOSED A&A BODY CONTOURS (NAIL SPA AND BEAUTY SERVICES CONCESSION) AT BASEMENT
DESCRIPTION: 2 NORTH, TERMINAL 3, SINGAPORE CHANGI AIRPORT
PROJECT NO.: A 106
PREPARED BY: ZAW MOE
SENSIBLE HEAT LOAD
FACTORS (KWim2) COOLING
ITEMS DIRECTIONS AREA (m2)
WITH BLINDS LOAD (KVV)
N, NW - 0.3 -
S,E,NE,SE - 0.23 -
EXPOSED GLASS SW - 0.3 -
W - 0.4 -
SHADED - 0.05 -
MEDIUM
LIGHT HEAVY
CONSTRUCTI
CONSTRUCTION CONSTRUCTION
ON
N, NW - 7 x 10-3 6.42 x 10-3 4.08 x 10-3 -
EXPOSED WALLS S,E,NE,SE - 6.42 x 10-3 5.25 x 10-3 5.25 x 10-3 -
SW - 8.75 x 10 -3
7 x 10 -3
6.42 x 10 -3
-
W - 8.75 x 10-3 7.59 x 10-3 6.42 x 10-3 -
SHADED - 2.334x10-3 -
WITH
- 9.336 x 10 -3
5.84 x 10 -3
2.92 x 10 -3
-
CEILING
ROOF WITHOUT
- 2.51 x 10 -3
14.0 x 10 -3
5.84 x 10 -3
-
CEILING
GLASS - 1.75 x 10-3 -
PARTITION
WALL - 1.167 x 10- 3
-
INTERNAL SENSIBLE HEAT LOAD (DINING AREA)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 60 0.06 3.6


LIGHTS W/m 2 128.90 30 3.87
ELECT. APPLIANCES KW 6 0.5 3.00
OUTDOOR AIR 20CMH/PERSON 2.05
(1) TOTAL ROOM SENSIBLE HEAT : 12.52
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 5,364.43
TOTAL DESIGN CMH: 5,750.00
CAAS PROVIDE CMH 3,030.00
NEW ADDITIONAL AIR CON (DINING AREA) 2,720.00

INTERNAL SENSIBLE HEAT LOAD (BODY MASSAGE 1)


NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 2 0.06 0.12


LIGHTS W/m 2 7.43 30 0.22
ELECT. APPLIANCES W/m 2 7.43 27 0.20
OUTDOOR AIR 20CMH/PERSON 0.07
(1) TOTAL ROOM SENSIBLE HEAT : 0.61
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 262.22
DESIGN CMH: 270
INTERNAL SENSIBLE HEAT LOAD (BODY MASSAGE 2)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 2 0.06 0.12


LIGHTS W/m 2 8.20 30 0.25
ELECT. APPLIANCES W/m 2 8.20 27 0.22
OUTDOOR AIR 20CMH/PERSON 0.07
(1) TOTAL ROOM SENSIBLE HEAT : 0.66
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 281.03
DESIGN CMH: 320
INTERNAL SENSIBLE HEAT LOAD (FACIAL 1)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 2 0.06 0.12


LIGHTS W/m 2 5.50 30 0.17
ELECT. APPLIANCES W/m 2 5.50 27 0.15
OUTDOOR AIR 20CMH/PERSON 0.07
(1) TOTAL ROOM SENSIBLE HEAT : 0.50
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 215.07
DESIGN CMH: 220
INTERNAL SENSIBLE HEAT LOAD (FACIAL 2)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 2 0.06 0.12


LIGHTS W/m 2 5.55 30 0.17
ELECT. APPLIANCES W/m 2 5.55 27 0.15
OUTDOOR AIR 20CMH/PERSON 0.07
(1) TOTAL ROOM SENSIBLE HEAT : 0.50
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 216.29
DESIGN CMH: 220
INTERNAL SENSIBLE HEAT LOAD (OFFICE)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 2 0.06 0.12


LIGHTS W/m 2 5.50 30 0.17
ELECT. APPLIANCES W/m 2 5.50 27 0.15
OUTDOOR AIR 20CMH/PERSON 0.07
(1) TOTAL ROOM SENSIBLE HEAT : 0.50
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 215.07
DESIGN CMH: 220
INTERNAL SENSIBLE HEAT LOAD (SHOULDER MASSAGE )
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 8 0.06 0.48


LIGHTS W/m 2 10.90 30 0.33
ELECT. APPLIANCES W/m 2 10.90 27 0.29
OUTDOOR AIR 20CMH/PERSON 0.27
(1) TOTAL ROOM SENSIBLE HEAT : 1.37
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 589.13
DESIGN CMH: 600
INTERNAL SENSIBLE HEAT LOAD (FOOT SPA)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 24 0.06 1.44


LIGHTS W/m 2 35.40 30 1.06
ELECT. APPLIANCES W/m 2 35.40 27 0.96
OUTDOOR AIR 20CMH/PERSON 0.82
(1) TOTAL ROOM SENSIBLE HEAT : 4.28
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 1,833.34
DESIGN CMH: 1900
INTERNAL SENSIBLE HEAT LOAD (RECEPTION & MANICURE)
NO. OF
DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 8 0.06 0.48
LIGHTS W/m 2 23.80 30 0.71
ELECT. APPLIANCES W/m 2 23.80 27 0.64
OUTDOOR AIR 20CMH/PERSON 0.27
(1) TOTAL ROOM SENSIBLE HEAT : 2.11
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 904.26
DESIGN CMH: 970
INTERNAL SENSIBLE HEAT LOAD (CORRIDOR & MANICURE)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 6 0.06 0.36


LIGHTS W/m 2 15.80 30 0.47
ELECT. APPLIANCES W/m 2 15.80 27 0.43
OUTDOOR AIR 20CMH/PERSON 0.21
(1) TOTAL ROOM SENSIBLE HEAT : 1.47
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 628.11
DESIGN CMH: 710
INTERNAL SENSIBLE HEAT LOAD (PANTRY)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 4 0.06 0.24


LIGHTS W/m 2 6.50 30 0.2
ELECT. APPLIANCES W/m 2 6.50 27 0.18
OUTDOOR AIR 20CMH/PERSON 0.14
(1) TOTAL ROOM SENSIBLE HEAT : 0.75
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 320.21
DESIGN CMH: 320
TOTAL 5,464.74
TOTAL DESIGN CMH: 5750