Você está na página 1de 6

Applications and forms of differential

relays


ABB Residual Current Breaker with Overload Protection RCBo
ifferential relays take a variety oI Iorms, depending on the equipment they protect. The
deIinition oI such a relay is 'one that operates when the vector diIIerence oI two or more
similar electrical quantities exceeds a predetermined amount. It will be seen later that almost
any type oI relay, when connected in a certain way, can be made to operate as a diIIerential
relay. In other words, it is not so much the relay construction as the way the relay is
connected in a circuit that makes it a diIIerential relay.
Most diIIerential-relay applications are oI the 'current-diIIerential type. The simplest
example oI such an arrangement is shown in Fig. 14. The dashed portion oI the circuit oI Fig.
14 represents the system element that is protected by the diIIerential relay. This system
element might be a length oI circuit, a winding oI a generator, a portion oI a bus, etc.
A current transformer (CT) is shown in each connection to the system element. The
secondaries oI the CTs are interconnected, and the coil oI an overcurrent relay is connected
across the CT secondary circuit.
This relay could be any oI the a-c types that we have considered.

Fig. 14. A simple diIIerential-relay application

ow, suppose that current Ilows through the primary circuit either to a load or to a short
circuit located at X. The conditions will be as in Fig. 15. II the two current transformers
have the same ratio, and are properly connected, their secondary currents will merely
circulate between the two CT`s as shown by the arrows, and no current will Ilow through the
diIIerential relay.

Fig. 15. Conditions Ior an external load or Iault

But, should a short circuit develop anywhere between the two CT`s, the conditions oI Fig. 16
will then exist. II current Ilows to the short circuit Irom both sides as shown, the sum oI the
CT secondary currents will Ilow through the diIIerential relay. It is not necessary that short-
circuit current Ilow to the Iault Irom both sides to cause secondary current to Ilow through the
diIIerential relay. A Ilow on one side only, or even some current Ilowing out oI one side
while a larger current enters the other side, will cause a diIIerential current.
In other words, the diIIerential-relay current will be proportional to the vector diIIerence
between the currents entering and leaving the protected circuit; and, iI the diIIerential current
exceeds the relay`s pickup value, the relay will operate.

Fig. 16. Conditions Ior an internal Iault

It is a simple step to extend the principle to a system element having several connections.
Consider Fig. 17, Ior example, in which three connections are involved.

Fig. 17 A three-terminal current-diIIerential application
It is only necessary, as beIore, that all the CT`s have the same ratio, and that they be
connected so that the relay receives no current when the total current leaving the circuit
element is equal vectorially to the total current entering the circuit element.
The principle can still be applied where a power transIormer is involved, but, in this case, the
ratios and connections oI the CTs on opposite sides oI the power transIormer must be such
as to compensate Ior the magnitude and phase-angle change between the power transIormer
currents on either side. This subject will be treated in detail when we consider the subject oI
power-transIormer protection.
A most extensively used Iorm oI diIIerential relay is the 'percentage-diIIerential type. This
is essentially the same as the overcurrent type oI current-balance relay that was described
earlier, but it is connected in a diIIerential circuit, as shown in Fig. 18.

Fig. 18. A percentage-diIIerential relay in a two-terminal circuit

The diIIerential current required to operate this relay is a variable quantity, owing to the
eIIect oI the restraining coil. The diIIerential current in the operating coil is proportional to

, and the equivalent current in the restraining coil is proportional to

, since the
operating coil is connected to the midpoint oI the restraining coil; in other words, iI we let
be the number oI turns on the restraining coil, the total ampere-turns are

, which
is the same as iI

were to Ilow through the whole coil.


The operating characteristic oI such a relay is shown in Fig. 19. Thus, except Ior the slight
eIIect oI the control spring at low currents, the ratio oI the diIIerential operating current to the
average restraining current is a Iixed percentage, which explains the name oI this relay. The
term 'through current is oIten used to designate I2, which is the portion oI the total current
that Ilows through the circuit Irom one end to the other, and the operating characteristics may
be plotted using I2 instead oI (I1 I2)/2, to conIorm with the ASA deIinition Ior a percentage
diIIerential relay.
The advantage oI this relay is that it is less likely to operate incorrectly than a diIIerentially
connected overcurrent relay when a short circuit occurs external to the protected zone.

Fig. 19. Operating characteristic oI a percentage-diIIerential relay

Current transIormers oI the types normally used do not transIorm their primary currents so
accurately under transient conditions as Ior a short time aIter a short circuit occurs.
This is particularly true when the shortcircuit current is oIIset. Under such conditions,
supposedly identical current transIormers may not have identical secondary currents, owing
to slight diIIerences in magnetic properties or to their having diIIerent amounts oI residual
magnetism, and the diIIerence current may be greater, the larger the magnitude oI short-
circuit current. Even iI the short-circuit current to an external Iault is not oIIset, the CT
secondary currents may diIIer owing to diIIerences in the CT types or loadings, particularly
in power-transIormer protection. Since the percentage-diIIerential relay has a rising pickup
characteristic as the magnitude oI through current increases, the relay is restrained against
operating improperly.
Figure 20 shows the comparison oI a simple overcurrent relay with a percentage-diIIerential
relay under such conditions. An overcurrent relay having the same minimum pickup as a
percentage-diIIerential relay would operate undesirably when the diIIerential current barely
exceeded the value X, whereas there would be no tendency Ior the percentage-diIIerential
relay to operate.

Fig. 20. Illustrating the value oI the percentage-diIIerential characteristic

Percentage-diIIerential relays can be applied to system elements having more than two
terminals, as in the three-terminal application oI Fig. 21. Each oI the three restraining coils oI
Fig. 21 has the same number oI turns, and each coil produces restraining torque
independently oI the others, and their torques are added arithmetically.
The percent-slope characteristic Ior such a relay will vary with the distribution oI currents
between the three restraining coils.

Fig. 21. Three-terminal application oI a percentage-diIIerential relay

Percentage-diIIerential relays are usually instantaneous or high speed. Time delay is not
required Ior selectivity because the percentage-diIIerential characteristic and other
supplementary Ieatures to be described later make these relays virtually immune to the eIIects
oI transients when the relays are properly applied. The adjustments provided with some
percentage-diIIerential relay will be described in connection with their application.
Several other types oI diIIerential-relay arrangements could be mentioned. One oI these uses
a directional relay. Another has additional restraint obtained Irom harmonics and the d-c
component oI the diIIerential current. Another type uses an overvoltage relay instead oI an
overcurrent relay in the diIIerential circuit. Special current transIormers may be used having
little or no iron in their magnetic circuit to avoid errors in transIormation caused by the d-c
component oI oIIset current waves. All these types are extensions oI the Iundamental
principles that have been described, and they will be treated later in connection with their
speciIic applications.
There has been great activity in the development oI the diIIerential relay because this Iorm oI
relay is inherently the most selective oI all the conventional types. However, each kind oI
system element presents special problems that have thus Iar made it impossible to devise a
diIIerential-relaying equipment having universal application.
D 1he ArL Sclence Cf roLecLlve 8elaylng C 8ussel Mason

Você também pode gostar