Escolar Documentos
Profissional Documentos
Cultura Documentos
AS/NZS 3004.1:2014
Electrical installations — Marinas and boats, Part 1:
Marinas
Committee: EL-057
Marine Queensland
2
All rights are reserved. No part of this work may be reproduced or copied in any
form or by any means, electronic or mechanical, including photocopying,
without the written permission of the publisher, unless otherwise permitted
under the Copyright Act 1968 (Australia) or the Copyright Act 1994 (New
Zealand).
Preface
It is not the intention of this Standard to limit the introduction and use of
emerging technologies. However, designers are reminded that it is essential
that the basic tenets of electrical and marine safety be addressed before any
other equipment and installation design elements are considered.
Any requirements that may be applicable in Australia only and New Zealand
only are indicated in the text and by a symbol in the right margin as follows:
A
3
‘In Australia…………’
NZ
The term ‘informative’ has been used in this Standard to define the application
of the appendix to which it applies. An ‘informative’ appendix is only for
information and guidance.
1.1 Scope
This Standard sets out requirements for electrical installations associated with
marinas supplied by low-voltage a.c. supply systems (i.e. exceeding 50 V a.c. but
not exceeding 1000 V a.c.).
NOTE The requirements for installations in boats are given in AS/NZS 3004.2 .
This Standard includes requirements for the periodic inspection and testing of
marinas.
1.2 Application
NOTE The relevant electrical safety authority might choose to apply this
Standard to other installations, e.g. mooring for facilities for commercial fishing
boats.
1.4 Definitions
For the purpose of this Standard, the definitions given in AS/NZS 3000 and
those below apply.
1.4.1
accessible, readily
capable of being reached quickly and without climbing over or removing
obstructions, mounting upon a chair, or using a movable ladder, and in any
case not more than 2.0 m above the ground, floor or platform
1.4.2
boats
any boat, yacht, motor launch, houseboat or other floating boat used
exclusively for sport or leisure
1.4.3
detachable connection
the electrical connection of a boat to the marina electrical installation by means
of a plug and socket-outlet, or socket and appliance inlet
1.4.4
direct connection
the connection of electrical equipment directly to the source conductors by
means of a terminal, stud or other such arrangements
1.4.5
5
galvanic isolator
device installed in series with the a.c. protective earthing conductor to block
low-voltage d.c. galvanic current flow, but permitting the passage of alternating
current normally associated with the protective earthing conductor
1.4.6
marina
any fixed wharf, jetty, pier or floating pontoon arrangement capable of berthing
or mooring one or more boats
Note 1 to entry: ‘Marina’ does not include buildings which are not associated
with the supply of electricity to boats.
1.4.7
service pillar
a specialized switchboard complete with its supporting structure, the
switchboard containing one or more socket-outlets for the purpose of
supplying power to boats
1.4.8
shall
indicates that a statement is mandatory
1.4.9
shore mounted
equipment not installed on a boat but installed as part of the marina
(see Clause 1.4.6)
1.4.10
should
indicates a recommendation
1.6.1 Scope
This Clause details specific variations to the requirements of AS/NZS 3000 and
the reasons for these variations.
NOTE 1 The order of alternative methods of connection given by (a), (b) and (c)
is not intended to indicate a preference for any particular method.
NOTE 2 Even with a galvanic isolator fitted, the supply arrangement shown
in Figure C3 of Appendix C can result in severe corrosion of metallic-hulled
(including ferro-concrete) boats because of galvanic action, caused by dissimilar
metals, occurring between boats.
NOTE 3 The supply arrangement shown in Figures C2 and C3 of Appendix C can
result in degradation of non-metallic-hulled boats where fittings of conductive
material in contact with the water pass through timber supports. This also
applies to wooden plugs in boats of reinforced plastic construction.
2.1.1 General
Electrical installations in marinas for boats’ berth supplies shall be carried out in
accordance with AS/NZS 3000 , and the additional requirements of this Section.
8
2.1.3.1 General
A protective earthing conductor or equipotential bonding conductor shall be
incorporated in each circuit and connected without interruption to each item of
electrical equipment as appropriate.
2.3.1 General
Isolating transformers shall comply with the appropriate requirements
of AS/NZS 61558.2.6 .
2.3.2 Protection
Isolating transformers shall have an enclosure that provides appropriate
protection against mechanical damage and a minimum degree of protection
IPX5 in accordance with AS 60529 .
Where mounted outdoors, an isolating transformer shall be effectively
protected from the weather, splashing, corrosion and mechanical damage.
NOTE A higher degree of protection than that specified may be required where
isolating transformers are exposed to extreme environmental conditions.
2.4.1 General
The low-voltage electrical supply to boats shall be via a supply lead or leads
originating from—
2.4.2.1 Introduction
Typically, each of these switchboards will be part of a free-standing structure,
referred to as a service pillar, situated close to the relevant berth.
Being switchboards, service pillars may contain electrical equipment other than
that specified in Clauses 2.4.2.4 and 2.4.2.5.
Subject to the requirements of AS/NZS 3000 , service pillars may also contain
other services.
2.4.2.2 Location
Each service pillar shall be located as close as practicable to the relevant
berth(s) and such that supply leads up to the maximum length, as specified
in Clause 3.1.1, can be installed to each applicable boat in accordance
with Clause 3.2.
2.4.2.3 Accessibility
Service pillars shall be readily accessible, as defined in AS/NZS 3000 .
2.4.2.4 Socket-outlets
2.4.2.4.1 Number
A maximum of six socket-outlets shall be grouped together in one service pillar.
A service pillar designated as the low-voltage electrical supply to a number of
berths shall have at least one socket-outlet for each berth.
NZ
(a) For New Zealand, comply with IEC 60309-2 (round pin) and be rated at
not less than 16 A. Socket-outlets rated at 32 A or more per phase shall be
arranged to prevent the removal of the plug when energized.
A
(b) For Australia, comply with AS/NZS 3112 (three pin, flat pin), be rated at
not less than 15 A and have an earthing contact.
A
11
(c) For Australia, comply with AS/NZS 3123 (round pin), be rated at not less
than 20 A and have an earthing contact.
NOTE 1 Two acceptable approaches to prevent the removal of the plug when
energized are the provision of a mechanical interlock or a clearly visible and
indelible notice adjacent to the outlet stating that the plug should not be
removed when the circuit is energized.
NOTE 2 The choice of the type and rating of the socket-outlets should be made
following consideration of local conditions including the types of plugs used
by typical or anticipated users of the socket-outlet. The requirements of any
relevant regulatory authority also need to be complied with.
NOTE This does not preclude protection of more than one socket-outlet by a
single RCD, however, it is recommended that one RCD be provided for each
socket-outlet to reduce both the possibility and consequences of nuisance
tripping.
12
2.4.2.4.6 Control
Each socket-outlet mounted on a service pillar shall be controlled by its own
individual switch which is—
2.4.2.6.1 General
Service pillars shall be of robust construction and of materials resistant to
corrosion and deterioration due to the relevant environmental influences, e.g.
UV, salt-laden atmosphere.
2.4.2.6.2 Height
Each socket-outlet and each associated circuit-breaker, RCD and operating
switch mounted on or in a service pillar shall be located not less than 300 mm
above the surface on which an operator would stand.
2.4.2.6.3 Weatherproofing
The choice of electrical equipment and means of construction of each service
pillar shall be such that all electrical components are provided with a degree of
protection not less than IPX5 in accordance with AS 60529 , both when
appropriate plugs are inserted and when no plug is inserted.
cover without the removal of, or damage to, any flexible cords or cables
attached to the connection facilities.
2.4.2.6.5 Identification
Where there is more than one service pillar in a marina, each service pillar shall
be legibly and indelibly identified with a set of numbers or letters, or both,
which uniquely identify that service pillar.
3.1.1 General
A supply lead for connection of boats to the low-voltage electrical supply of a
marina shall comply with AS/NZS 3004.2 . Maximum lengths of supply leads
shall be as set out in Table 3.1.
Table 3.1 — Maximum lengths of supply leads
(a) permit normal movement of a boat at its mooring without undue stress;
(b) prevent water flowing along the supply lead from reaching the appliance
inlet or the supply plug;
(c) minimize the likelihood of the plug or cord extension socket falling in the
water;
(d) minimize the possibility of accidental disconnection;
(e) not present a hazard to persons walking in the vicinity of the boat; and
(f) be either—
o (i) located where it will not be subject to mechanical damage or damage
by high temperatures; or
o (ii) provided with suitable protection against mechanical damage or
damage by high temperatures.
3.3 Earthing
3.3.1 General
For each of the three methods of connection addressed by this Standard
(see Clause 1.8), there are specific earthing requirements, as specified
in Clauses 3.3.2 to 3.3.4.
The protective earthing system of the boats shall be effectively connected to the
protective earthing system of the marina low-voltage electrical supply. A
galvanic isolator shall not be installed in a service pillar.
NOTE 1 Extra sacrificial anodes and/or a galvanic isolator may need to be
installed on the boat.
NOTE 2 See also Clause 1.7 and Figure C3.
4.1 General
New installations, additions or alterations shall be verified in accordance
with AS/NZS 3000 .
A
4.2 Periodic verification—Australia
4.2.1 Testing
RCDs protecting final subcircuits constituting part of the low-voltage electrical
supply to a berth for boats should—
(a) be operated monthly by means of their in-built test facility (push button);
(b) be tested at least once every calendar year for correct response to a
leakage current (i.e. current imbalance/tripping time test) in accordance
with AS/NZS 3760 ; and
(c) be periodically inspected visually for damage, corrosion and excess wear
and tear.
NOTE 2 The test in Item (b) can be performed with an appropriate RCD
tester.
(a) the name of the person or company who performed the tests;
(b) the test or retest date;
(c) identification of each RCD tested; and
(d) identification of faulty RCDs and action taken to repair or replace the
faulty RCD.
16
NZ
4.3 Periodic verification—New Zealand
NOTE 2 Load leakage and stored energy can affect the result and increase
the meter trip time indication. In case of doubt, all loads on the circuit
should be disconnected.
Appendix A
(informative)
(a) The low-voltage electrical supply from the isolating transformer at your
berth is ∗ V, 50 Hz. The socket-outlet provided will accommodate a
standard ∗ plug. The maximum available current is ∗ A.
(b) Where a boat is provided with more than one low-voltage electrical
supply, the supplies must have the same method of connection, that is, by
connection through an isolating transformer with the hull and conductive
parts bonded.
(c) Precautions should be taken to prevent the supply lead from sagging or
falling into the water and, particularly, to prevent either end of the supply
lead falling into the water if it should become disengaged.
(d) Only one boat supply lead should be connected to any one socket-outlet.
(e) The supply lead should be in one length and should not be used while
coiled.
(f) The entry of moisture and salt into a boat’s appliance inlet may cause a
hazard. Examine carefully and clean before connecting to the marina low-
voltage electrical supply.
(g) It is dangerous for unskilled persons to attempt repairs or alterations. If
any difficulty arises, consult the marina management.
BEFORE LEAVING
(i) Ensure that the marina low-voltage electrical supply is switched off and
the supply lead is disconnected.
(ii) The supply lead should be disconnected first from the marina socket-
outlet and then from the boat appliance inlet. Any cover that may be
provided to protect the appliance inlet from the weather should be securely
replaced.
19
(iii) The supply lead should be coiled up and stored in a dry location where it
will not be damaged.’
Appendix B
(informative)
(c) Only one boat supply lead should be connected to any one socket-outlet.
(d) The supply lead should be in one length and should not be used while
coiled.
(e) The entry of moisture and salt into a boat’s appliance-inlet may cause a
hazard. Examine carefully and clean before connecting to the marina low-
voltage electrical supply.
(f) It is dangerous for unskilled persons to attempt repairs or alterations. If
any difficulty arises, consult the marina management.
BEFORE LEAVING
(i) Ensure that the marina low-voltage electrical supply is switched off and
the flexible cord is disconnected.
(ii) The supply lead should be disconnected first from the marina socket-
outlet and then from the boat appliance inlet. Any cover that may be
provided to protect the appliance inlet from the weather should be securely
replaced.
(iii) The supply lead should be coiled up and stored in a dry location where it
will not be damaged.’
21
Appendix C
(informative)
Appendix D
(informative)
(a) Calculation.
(b) Assessment.
(c) Measurement.
(d) Limitation.
D2.1 General
Where the maximum demand of mains and submains is to be determined by
calculation, the following values are provided as a guide to loads of a type
specific to marinas.
D2.2 Amenities
For a main or submain supplying amenities, 50% of the sum of the current
ratings of the circuit-breakers supplied by each active conductor of the main or
submain should be assumed to be the maximum demand on that conductor.
Examples
6A×(3215)=12.8A=13A(rounded)TOTAL=6×13=78A
10A×(3215)A=21.3Anearestwholenumber=21A(rounded)
o (b) The next 2 connection points would each be allocated the following
value:
Appendix E
(informative)
NZ
Sample certification of verification—
New Zealand only
CERTIFICATE OF VERIFICATION
Installation details
Client:
Address of marina (to which this certificate refers):
………………………………………………………………………………………
……………………………………………………………………………………….
This certificate covers verification of an existing electrical installation of the marina.
∗
Marina operator to fill in.
∗
Marina operator to fill in.