RISH Ducer I21 Transducer for AC current

Features / Benefits
RISH Ducer I21 RISH Ducer I21

Measuring input : AC current, sine or distorted wave forms, true RMS value measurement Narrow housing, 35 mm / Saves space and therefore costs Provision for either snapping the transducer onto top-hat rails or securing it with screws to a wall or panel Low power consumption / smaller CT's can be used

Two isolated Output (optional ) in E16 housing


Fig. 1 RISH Ducer I21 in housing E8 clipped onto a top - hat rail. Fig. 2 RISH Ducer I21 in housing E8 screw hole mounting brackets pulled out.

Electric isolation between Output 1 and Output 2 is 500V

Application
The RISH Ducer I21 measuring transducer (Figs. 1 and 2) is used to convert a sine - wave or distorted AC current into an impressed output signal. The output signal is proportional to the rootmean square value of the input current.

Mode of Operation
Input signal X is galvanically separated from the mains network using a transformer. The following mathematical expression is then formed using a root means quare value computer T2 1 x i dt Ieff = w T o Following filtration by means of an active filter, the transformation properties of the measuring transducer are determined in the succeeding characteristics circuit. The output amplifier transforms the impressed output signal Y. measuring signal into an

Symbols and their meaning


Symbols X X0 X2 Y Y0 Y2 H Hn T Tn Rext Meaning Measuring input / Input variable Start value of input current Final value of input current Measuring output / Output variable Start value of output variable Final value of output variable Power supply Rated value of power supply Setting time Rated value of setting time Min. output burden Rated value of output burden

The electronic components are supplied with voltage H from the mains supply unit.

T2 1 x i dt Ieff = w T o

Rn

Fig. 3 Block diagram


RISHABH INSTRUMENTS PVT.LTD. F-31, MIDC, Satpur, Nashik-422 007,India. Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064 E-mail : India :- marketing@rishabh.co.in International :- exp.marketing@rishabh.co.in Web-site : www.rishabh.co.in

Rishabh Instruments

Page 1 of 5

1 / 04 / XIX / 1107 / A

RISH Ducer I21 Transducer for AC current


Technical Data
General Measured quantity
: AC current Sine or distorted wave-forms True RMS value measurement Logarithmic 50, 60 or 400 Hz 1 A X 2 7.5 A Final value permanently set OR Final value can be adjusted in range 0.5 X2 X2 < 1 VA at X2 Residual ripple in output signal Setting time : : : for one output transducer 5% p.p. at setting time 50 ms 0.5% p.p. at setting time 300 ms 50 ms or 300 ms for one output 300 ms for two output for two output transducer : 3% p.p. at setting time 300 ms

Measuring principle

: : : :

Measuring input X Nominal frequency fN Final value of nominal input current X2 Re-calibration of X2

Accuracy (acc. to DIN/IEC 688-1) Reference value : Output end value Y2 Basic accuracy : Class 0.5
Reference condition

Own consumption

Overload Capacity :

Measured Number Duration quantity of appliof one cations application


2 X2 10 X2 50 X2
1 1

Interval between two successive applications


-----5 min. 1h

Ambient temperature Input variable Frequency Curve shape Shape factor Output burden

: : : : : :

23 C, 5 K Rated operating range fN 2% Sine-wave 1.1107 With DC current output signal: 7.5 V + 1 % for one output Y2 6V R= + 1 % for two output Y2 With DC voltage output signal : Rn = Rn = Y2 + 1 % for one output 1 mA

----5 1

continuously 3s 1s

but max. 250 A Measuring output Y Output variable Y OR DC voltage Load-independent DC current: Output burden with DC Current output signal

Load-independent DC current 1mA Y2 20 mA 15V for one output Y2 12V for two output Y2

Rn = 2 Rext.+ 1 % for one output Power supply Warm-up time : : Hn 1% 5 min.

Influence effects (maxima):


: 0R 0R Influence quantity Ambient temperature Curve shape of input signal Rated operating range
0 + 100C... 23 C...40 C0 0 0 0 C... 23 C...55 C0

Permitted effect as factor of precision class 1 2 1 1

DC Voltage Output burden with DC voltage output signal

: :

1 V Y2 10 V Y2 R one output for 2 mA Rext.[k ] > 10k /V for Two output

Current limit under overload Current limit under overload Voltage limit under R =

: : :

1.7 Y2 with current output approx. 20 mA with voltage O.P. 1.7 Y2 with current output approx. 20 mA with voltage O.P. < 40 V with current output < 1.7 Y2 with voltage output

Rectangle 1 : 1 40... 400 Hz Frequency of the > 400 .... 1000 Hz input variable Output burden with 15V 0R for one output DC Current Y2 12V 0R for two output Y2 DC Voltage Y2 R one output for 2 mA Rext.[k ] > 10k /V for Two O.P. Power Supply Conforms technical data

RISHABH INSTRUMENTS PVT.LTD. F-31, MIDC, Satpur, Nashik-422 007,India. Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064 E-mail : India :- marketing@rishabh.co.in International :- exp.marketing@rishabh.co.in Web-site : www.rishabh.co.in

Rishabh Instruments

Page 2 of 5

1 / 04 / XIX / 1107 / A

RISH Ducer I21 Transducer for AC current


Transformation characteristics
Electrical connection Screw - type terminals with indirect wire pressure, for max. 2 X 2.5 mm2or 1 X 6 mm 2 Approx. 0.5 kg for one output Approx. 0.7 kg for two outputs

Weight

Regulations
Fig. 4. Curve linear (X0 = 0; Y0 = 0). Fig. 5. Curve linear (X0 = 0; Y0 = 0.2 Y2).

Electrical standards Housing protection

: :

Power Supply

Rated Value Hn AC AC AC AC AC 24 V 110 V 120 V 230 V 380 V*

Rated Operating voltage 22 .... 26 V 99 .... 121 V 108 .... 132 V 207 .... 253 V 360 .... 440 V

Rated insulation voltage :

Contamination level Overvoltage category Protection class Safe isolation:

: : : :

* for one output transducer only

Acc. to IEC 1010 IP 40 acc. to EN 60 529 Terminals IP 20 Measuring input AC 300 V Power supply AC 300 V, DC 230 V Measuring output DC 40 V 2 III II Acc. to IEC 1010 and DIN/VDE 106, part 101 5 kV, 1.2/50 ms, 0.5 Ws Common-mode and differentialmode between any terminals 3.7 kV / 50 Hz / 1 min. between electrically isolated circuits Measuring output versus housing 0.5 kV / 50 Hz / 1 min. measuring 2 : 0.5kV / 50 Hz / 1 min. Measuring output 1 versus

Rated operating range of frequency Power consumption

: :

Version with AC/DC power pack DC and 45 ... 400Hz

45 50 60 65 Hz 4 VA at H = Hn for one output transducer 7 VA at H = Hn for two output transducer Rated voltages and permissible variations Rated Voltage UN 24 .... 60 V DC / AC 85 .... 230 V DC / AC Permissible variation DC - 15 ... + 33% AC + 15%

Impulse withstand voltage acc. to IEC 255-4 Cl. III :

Test voltage

Environmental conditions
Climatic rating Operating temperature Storage temperature Relative humidity of annual mean : : : : Climate class 3Z acc. to VDI/VDE 3540 25 to + 55 C 40 to +70 C 75%

Power consumption

1.4W or 2.7VA for one output 3 W or 5 VA for two output

Installation Data
Mechanical design : Housing E8 / E16 Dimensions see Section Dimensional drawings Lexan 940 (polycarbonate), flammability Class V - 0 acc. to UL 94, self - extinguishing, non-dripping, free of halogen For snapping onto top-hat rail (35 mm or 35 mm) acc. to 15 7.5 EN 50 022 OR directly onto a wall or panel using the pull-out screw hole brackets Any

Electrical Connections
Connection Measuring input Measuring output 1 Measuring output 2 Power Supply Terminals R R + + R, + R, One output 5 6 1 2 ..... ..... ..... ..... Two output 9 10 1 2 11 12 3 4

Material of housing

Mounting

Mounting position

RISHABH INSTRUMENTS PVT.LTD. F-31, MIDC, Satpur, Nashik-422 007,India. Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064 E-mail : India :- marketing@rishabh.co.in International :- exp.marketing@rishabh.co.in Web-site : www.rishabh.co.in

Rishabh Instruments

Page 3 of 5

1 / 04 / XIX / 1107 / A

RISH Ducer I21 Transducer for AC current


Dimensional Drawings

5 6 77 6

8 8

10

11

12

13

14

15

16

125

125

1 2 33 2

4 4

35

130

E8 Housing

70

126

E16 Housing Fig. 6. RISH Ducer I 21 in housing E8 / E16 clipped onto a top-hat rail (35 mm or 35 7.5 mm, acc. to EN 50 022). 15
19

19
5 6 7 8

6.5
14 15 16

10

11

12

13

140

125

125

140

35

154

E8 Housing

12

70

4.5

6.5

125

E16 Housing Fig. 7. RISH Ducer I 21 in housing E8 / E16 with the screw hole brackets pulled out for wall mounting.

RISHABH INSTRUMENTS PVT.LTD. F-31, MIDC, Satpur, Nashik-422 007,India. Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064 E-mail : India :- marketing@rishabh.co.in International :- exp.marketing@rishabh.co.in Web-site : www.rishabh.co.in

Rishabh Instruments

Page 4 of 5

1 / 04 / XIX / 1107 / A

RISH Ducer I21 Transducer for AC current


Ordering Information
ITEM Measuring transducer for AC current (root - mean-sqare value measurement) Frequency of input current Fn = 50 Hz Fn = 60 Hz Fn = 400 Hz Final value of input current 1 A 2 2.5 A X 2.5 A < X 2 A 7.5 Final value of output signal (output 1) 1 mA 20 mA Y2 1 V V Y2 10 Curve Liner X0 = 0 Y0 = 0 X0 = 0 Y0 = 0.2 Y2 Re-calibration of X2 Final value permanently set Final value can be adjusting in range 0.5 X2 X2 Setting time 50 ms * 0.3 s * for one output transducer only AC 22 V ... 26 V AC 99 V ... 121 V AC 108 V ... 132 V AC 207 V ... 253 V AC 360 V ... 440 V * DC/AC 24 V ... 60 V DC/AC 85 V ... 230 V D0 D1 T1 T2 C91 C92 A91 A92 K01 K02 F1 F2 F3 MARKING I21

Power Supply

H1 H2 H3 H4 H5 H7 H8

* > 1) 300 V; phase - to - phase connection to a three - phase supply only. 2) for one output transducer only Extra text on name plate Without With Test report Without With Final value of output signal (output 2) 1 mA Y2 20 mA 1 V Y2 10 V A91 A92 P0 P1 Z0 Z9

RISHABH INSTRUMENTS PVT.LTD. F-31, MIDC, Satpur, Nashik-422 007,India. Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064 E-mail : India :- marketing@rishabh.co.in International :- exp.marketing@rishabh.co.in Web-site : www.rishabh.co.in