MIC-2 Multi-instrument DATA SHEET

Measurements
All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters

Display
5 display rows 96 x 96 mm White backlight

Intelligent
Suitable for 2 and 3-phase network topologies

Communication
RS-485 Modbus RTU protocol TCP/IP Modbus (optional) Profibus DP (optional)

Installation
Compact dimensions Simple wiring

I/O modules optional


Analogue Input/Output Digital Input/Output Relay

Utility software
Data logging Remote reading Easy setting up

Accuracy
U, I and f class 0.2 Other values class 0.5

Alarms
Up to 16 configurable alarms

Document no.: 4921210130B

Data sheet
Application
The MIC-2 multi-instrument is a microprocessor-based measuring unit providing measurement of most electrical quantities on a 2- or 3-phase electric energy distribution network. The measurements are shown on the built-in display. MIC-2 can be used as a data logging device for an intelligent Power Distribution System or Plant Automation System. All measurements are monitored and data is available via the RS-485 Modbus port. Other communication types as Ethernet (Web page, TCP/IP Modbus and emails transfer) and Profibus DP are available options. True RMS values are measured with/without neutral and with both balanced and unbalanced load. A large number of standard analogue instruments can be replaced by the MIC-2 in all electrical measuring applications. The MIC-2 contains all necessary measuring circuits and presents all values on a display with white backlight. The display has 4-digits resolution for all measurements. The backlight duration is selectable. Operating the MIC-2 is very easy. It is a flexible and logical measuring unit that enables the user to easily adapt the instrument to individual applications. Password protection of KWh counter reset and change of settings is possible.

MIC-2
Energy counter Import and export of energy, inductive and capacitive of reactive energy. Apparent energy Energy pulse output (optional) Two ports of pulse output (assign to any energy (P, Q and S) counter. Statistics Max/min of voltage, current, Power (P, Q, S) total, PF total, Frequency, Unbalance factor and THD values with time stamps. Running hour indication. Unbalance factor Voltage and current. Based on the positive and the negative sequence

Connection
The MIC-2 can be used in 2- and 3-phase network topologies with/without neutral and with both balanced and unbalanced load, including the US split phase system. The voltage and current input wiring modes are set separately in the parameter setting process. The voltage wiring mode can be: 3LN 2LN 2LL* 3LL 3-phase 4-line Y and 3-line (split phase) 3-phase 4-line Y with 2 VT 3-phase 3-line open delta 3-phase 3-line delta

Measured and calculated values


Voltage True RMS each phase, line-to-line voltage and average. Current Each phase, average and neutral. Active power (P) Each phase, total power. Reactive power (Q) Each phase, total power. Apparent power (S) Each phase total power. Power factor Each phase and total power factor. Frequency Actual frequency Load nature Inductive/Capacitive/Resistive. THD (up to 31st harmonics) Voltage THD of each phase, current THD of each phase. Maximum Demand Demand of Active (P), Reactive (Q) and Apparent (S) power.

*Preferred on an IT network e.g. ships. Notice max. 400 V phase-to-phase voltage using coupling 2LL. The current input wiring mode can be: 3CT 2CT 1CT Unbalance system (split phase) Unbalance system without N Balance system

Any voltage mode can be grouped with any of the current modes.

Options
Communication Ethernet - TCP/IP Modbus Profibus DP/VO Input/Output Analogue input (AI) Analogue output (AO) Digital input/output (DI/DO) Relay output (RO) I/O Module
AXM-IO1 AXM-IO2 AXM-IO3 DI 6 4 4 DO RO 2 2 2 2 2 AI AO

AXM-IO1 has a 24V DC power supply for DI. A maximum of 1 communication and 2 input/output modules can be used for each MIC-2.
Page 2 of 6

DEIF A/S

Data sheet
Technical specifications
Voltage inputs Nominal voltage UN Measuring range Overload capacity VT primary VT secondary Fuse Current inputs Nominal current IN Measuring range Overload capacity CT primary CT secondary Load Frequency Nominal frequency fN Measuring range Measuring point Accuracy Voltage Current Power Power factor Frequency Energy Harmonic Standard L-N 400V AC L-L 690V AC 0 to 1.2 x UN 1500 V continuous 3250 V for 1min 220 V500 kV 100 V400 V 1 A slow blow 5A AC 0 to 10 A 20 A continuous 100 A for 1 s 5 A50 kA 1 A5 A 0.5 VA 50/60 Hz 45 Hz to 65 Hz V1 phase voltage 0.2% 0.2% 0.5% 0.5% 0.2% 0.5% 2.0% IEC 60051 Environmental conditions Operation temperature Storage temperature Humidity, relative Standard Connections Measuring inputs Screw torque Other Wire max. Screw torque Mounting Panel mounted Panel cutout

MIC-2
-2570C -4085C 5-95% non-condensing IEC 60068-2 Current input fixed block, Wire max. 5mm 0.5 Nm/5.5 lb-inch Pluggable block 1.5 mm 0.25 Nm/2.5 lb-inch Max. 6 mm thick 92 x 92 mm +0.8 mm (3.62 x 3.62) or 4 round IP52 (EN 60529) IP30 (EN 60529) IEC 61010-1, UL 61010-1 350 g (0.8 lbs) IEC 61000-4/-2-3-4-5-6-8-11 CISPR 16

Protection Front Rear Safety Weight EMC

Auxiliary power supply Universal AC/DC power supply Supply voltage 100415V AC +/-10% 50/60 Hz/ 100300V DC +/-10% Consumption 5 VA Fuse 1 A slow blow Communication RS 485 Modbus RTU Number of devices Cable type Maximum cable length Data rate Vibration Max. 32 units Belden 3105 A or equivalent (twisted pair and shielded) up to 1000 m 1200 to 38400 bits/s 313.2 Hz: 2 mmpp 13.2100 Hz: 0.7 g To IEC 60068-2-6 To IACS UR E10

DEIF A/S

Page 3 of 6

Data sheet
Unit dimensions in mm (inches)

MIC-2

Panel cutout: H x W = 92 x 92 mm (3.622 x 3.622)

DEIF A/S

Page 4 of 6

Data sheet
Technical specifications optional modules Communication modules
Ethernet TCP/IP module AXM-NET 10 M/100 M self-adaptable, RJ45 Jack TCP/IP Modbus Protocol, HTTP Web page browse E-mail sending on time interval or on event. Profibus module AXM-PROFI Profibus-DP/V0 Input Byte (typical): 32 bytes Output Byte (typical): 32 bytes EN50170 vol.2 compliance Profibus slave mode, baud rate self-adaptable up to 12M Analogue Input (AI) Input range, 0~20 mA/4~20 mA Accuracy 0.2% Temperature drift 50ppm/C typical Isolation voltage 500 V Impedance: 100 Analogue Output (AO) Output range, 0~20 mA/4~20 mA Accuracy 0.5% Response time 300 ms The max load resistance is 500 Temperature drift 50ppm/C typical Isolation voltage 500 V

MIC-2

I/O modules
AXM-IO1 AXM-IO2 AXM-IO3 6 digital inputs (DI), 2 relay output (RO), 24V DC isolated voltage output 4 digital inputs (DI), 2 digital outputs (DO), 2 analogue output (AO) 4 digital inputs (DI), 2 relay output (RO), 2 analogue input (AI)

Note: Predefined output, see Description of options, I/O modules users manual, document no. 4189320032, for more information. Consumption AXM-NET: 1 W AXM-PROFI: 1 W AXM-IO1: 1 W AXM-IO2: 1.3 W AXM-IO3: 0.8 W Environmental conditions Operation temperature Storage temperature Humidity, relative Standard Safety -2570C -4085C 5-95% non-condensing IEC 60068-2 IEC 61010-1, UL 61010-1 AXM-NET: 65 g AXM-PROFI: 65 g AXM-IO1: 90 g AXM-IO2: 80 g AXM-IO3: 85 g IEC 61000-4/-2-3-4-5-6-8-11 CISPR 16

Digital Input (DI) Input voltage range 20~250V AC/DC Input current (max) 2 mA 1 voltage level 15 V 0 voltage level 5 V Switch response time <1 ms Pulse frequency (max) 100 Hz, 50% duty ratio (5 ms ON and 5 ms OFF) Power supply for digital Input (DI) Output voltage 24V DC Output current 42 mA Load (max) 21 DI Digital Output (DO) (Photo-MOS) Voltage range 0~250V AC/DC Load current 100 mA (Max) Output frequency 25 Hz, 50% Duty Ratio (20 ms ON, 20 ms OFF) Isolation voltage 2500 V Relay Output (RO) Switching voltage (Max) 250V AC, 30V DC Load current 3 A Set time 10ms (Max) Contact resistance 100 m (Max) Isolation voltage 2500 V 7 Mechanical life 1.5x10

Weight

EMC

DEIF A/S

Page 5 of 6

Data sheet

MIC-2

Order specifications

Optional modules:

MIC-2

Communication module
AXM-NET TCP/IP Modbus com. DEIF no. 1211020016 EAN no. 5703727109746

I/O module 1

I/O module 2

MIC-2
690V AC (L-L) 5 A RS485 Modbus RTU com. Aux. supply: 100415V AC 100300V DC DEIF no. 1211020012 EAN no. 5703727109739

AXM-IO1 DEIF no. 1211020013 EAN no. 5703727109760 AXM-IO2 DEIF no. 1211020014 EAN no. 5703727109777 AXM-IO3 DEIF no. 1211020015 EAN no. 5703727109784

AXM-IO1 (2) DEIF no. 1211020018 EAN no. 5703727110001 AXM-IO2 (2) DEIF no. 1211020019 EAN no. 5703727110018 AXM-IO3 (2) DEIF no. 1211020020 EAN no. 5703727110025

AXM-PROFI PROFI-BUS DP/VO DEIF no. 1211020017 EAN no. 5703727109753

A maximum of 1 communication and 2 input/output modules can be used for each MIC-2.

Due to our continuous development we reserve the right to supply equipment which may vary from the described.
DEIF A/S

DEIF A/S, Frisenborgvej 33 DK-7800 Skive, Denmark Tel.: 9614 9614, Fax: 9614 9615 E-mail: deif@deif.com, URL: www.deif.com

Page 6 of 6