PCC1301 MODBUS REGISTER MAP

Preliminary The 1301 genset control contains data that can be read using a remote device communicating with the 1301 via Modbus RTU protocol on a two-wire RS485 master/slave multi-drop bus. In this arrangement the remote device is the master and the 1301 is the slave. The 1301 is configured to communicate at a baud rate of 19,200, 8 data bits, even parity and 1 stop bit. Default slave address is 1. Parity, baud rate and slave address may be adjusted with InPower. For more information about the Modbus protocol, refer to Modbus Application Protocol v1.1a and Modbus Serial Line Implementation Guide v1.0, both available at www.modbus.org. Multi-Drop Network Mode PCC1301 Pins Lo (-) TB2-4

Hi(+) TB2-3

Shield TB2-1

Register Map
Description
Save adjustments

Address
40004

Read/ Write
Read and Write

Scale

Units

Type
Unsigned integer 0=No action

Notes

1=Save adjustments Save adjustments saves to non volital memory all the write parameters listed in this table

Genset control run/off/auto switch position Genset operating state

40010

Read

Switch position

Unsigned integer Unsigned integer

0=off 1=Run/Manual 2=Auto 0=Stopped 1=Start Pending 2=Warm-up at Idle 3=Running 4=Cool down at Rated 5=Cool down at Idle

40011

Read

Operating state

Fault Code

40012

Read

Event code

Unsigned integer

This register contains the fault code number of currently active fault. See service manual for list of supported fault codes.

Fault Type

40013

Read

Fault type

Unsigned integer

This register contains the fault type of currently active fault 0=Normal 1=Warning 2=Derate

3/14/2006

Page 1 of 8

PCC1301 MODBUS REGISTER MAP


Preliminary
Description Address Read/ Write Scale Units Type Notes
3=Shutdown with Cool down 4=Shutdown NFPA 110 fault register Extended Annunciation fault register Alternator output voltage line to neutral (a phase) Alternator output voltage line to neutral (b phase) Alternator output voltage line to neutral (c phase) Alternator output voltage line to line (a to b phase) Alternator output voltage line to line (b to c phase) Alternator output voltage line to line (c to a phase) Alternator output voltage (used for voltage regulation) Alternator output current (phase a) Alternator output current (phase b) Alternator output current (phase c) Alternator output average current Alternator output voltamperes (phase a) Alternator output voltamperes (phase b) Alternator output voltamperes (phase c) Alternator output voltamperes (total) Alternator frequency Alternator output current (phase a) Alternator output current (phase b) Alternator output current (phase c) Control battery voltage Engine oil pressure Engine coolant temperature 40061 40062 40064 Read Read Read 0.1 1.0 0.1 40060 Read 0.1 40059 Read 0.1 40044 40058 Read Read 0.1 0.1 Hz 40043 Read 0.1 kVA 40042 Read 0.1 kVA 40041 Read 0.1 kVA 40040 Read 0.1 kVA 40029 Read 0.1 AC Amps 40028 Read 0.1 AC Amps 40027 Read 0.1 AC Amps 40026 Read 0.1 AC Amps 40025 Read 1.0 AC Volts 40024 Read 1.0 AC Volts 40023 Read 1.0 AC Volts 40022 Read 1.0 AC Volts 40020 Read 1.0 AC Volts 40019 Read 1.0 AC Volts 40018 Read 1.0 AC Volts Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer 40016 40017 Read Read bitmap bitmap See NFPA110 bitmap See extended annunciation bitmap

Unsigned integer % of nominal Unsigned integer % of nominal Unsigned integer % of nominal Unsigned integer

DC Volts kPa Degrees

Unsigned integer Unsigned integer Unsigned

3/14/2006

Page 2 of 8

PCC1301 MODBUS REGISTER MAP


Preliminary
Description Address Read/ Write
Read Read Read Read Read and Write 40302 43000 43001 43002 43003 43004 43005 43006 43007 Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Remote stop time delay Read and Write Engine starting - cycle crank 43008 attempts setting Engine starting - cycle crank 43009 time setting Engine starting - cycle crank 43010 rest time setting Fault bypass (battle short) feature enable Fault bypass (battle short) switch input assignment 43012 43011 Read and Write Read and Write Read and Write Read and Write Read and Write Feature enabled Switch assignment 1.0 Sec 1.0 1.0 Number of attempts Sec 1.0 Sec 1.0 # of phases Alternator connection Feature enabled Feature enabled Sec Hz 1.0 AC Volts

Scale

Units
Celsius

Type
integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer 0 =Inactive 1 = Active 0= None 0 = 60 1 = 50 0=1 1 =3 1=Wye 0= Delta 0 = No 1 = Yes 0 = No 1 = Yes

Notes

Engine speed Number of engine starts Engine runtime (high byte) Engine Runtime (Low byte) Genset start stop control via Modbus Genset E-stop switch via Modbus Nominal alternator voltage setting Nominal alternator frequency setting Alternator phase setting Alternator connection setting Glow plug driver feature enable Battery charging alternator fault enable Remote start time delay

40068 40069 40070 40071 40300

1.0 1.0 1.0 1.0

RPM Number of starts Sec Sec

0 Stop 1- Start 0 Estop not active 1 Estop active

1=Customer Input 1 2=Customer Input 2 3=Operator Panel

Automatic voltage regulator 43013 Enable Automatic voltage regulator 43014 volts per hertz roll off knee setting Automatic voltage regulator 43015 volts per hertz roll off slope

Read and Write Read and Write Read and Write 0.1

Feature enabled Hz

Unsigned integer Unsigned integer Unsigned integer

0 = No 1 = Yes

0.1

%V/Hz

3/14/2006

Page 3 of 8

PCC1301 MODBUS REGISTER MAP


Preliminary
Description
setting Automatic voltage regulator 43016 gain setting Automatic voltage regulator 43017 integral setting Automatic voltage regulator 43018 derivative setting Electronic governing enable 43019 Electronic governing initial duty cycle setting Electronic governing initial duty cycle time Electronic governing start ramp duty cycle setting Electronic governing maximum duty cycle setting Electronic governing gain setting Electronic governing integral setting Electronic governing derivative setting Electronic governing crank exit fuel duty cycle setting Electronic governing dither factor setting Electronic governing start ramp time setting Electronic governing enable 43030 engine speed Electronic governing minimum duty cycle setting Electronic governing maximum duty cycle setting Model number character #1 Model number character #2 Model number character #3 Model number character #4 Model number character #5 Model number character #6 43034 43035 43036 43037 43038 43033 43032 43031 43029 43028 43027 43026 43025 43024 Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Character Character Character Character Character 1.0 % 1.0 % 0.01 1.0 Sec RPM 1.0 % 1.0 0.1 % % 1.0 % 1.0 % Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Character 43023 43022 43021 43020 Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write 0.1 % 0.1 % 0.1 0.1 1.0 Feature enabled % Sec 1.0 1.0 % % 1.0 % Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer 0 = No 1 = Yes

Address

Read/ Write

Scale

Units

Type

Notes

3/14/2006

Page 4 of 8

PCC1301 MODBUS REGISTER MAP


Preliminary
Description Address Read/ Write
Write Model number character #7 Model number character #8 Model number character #9 Model number character #10 Model number character #11 Model number character #12 Model number character #13 Model number character #14 Model number character #15 Model number character #16 Serial number character #1 Serial number character #2 Serial number character #3 Serial number character #4 Serial number character #5 Serial number character #6 Serial number character #7 Serial number character #8 Serial number character #9 43049 43050 43051 43052 43053 43054 43055 43056 43057 43048 43047 43046 43045 43044 43043 43039 43040 43041 43042 Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Serial number character #10 43058 Serial number character #11 43059 Serial number character #12 43060 Serial number character #13 43061 Read and Write Read and Write Read and Write Read and Write Character Character Character Character Character Character Character Character Character Character Character Character Character Character Character Character Character Character Character Character Character Character Character

Scale

Units

Type

Notes

3/14/2006

Page 5 of 8

PCC1301 MODBUS REGISTER MAP


Preliminary
Description Address Read/ Write
Read and Write Read and Write Serial number character #16 43064 Configurable input #1 type: 43065 Read and Write Read and Write Configurable input #2 type: 43066 Read and Write Configurable output #1 event code number: Configurable output #2 fault 43068 event number: 60 Hz alternator output voltage adjust % 50 Hz alternator output voltage adjust % Alternator frequency adjustment % 60 Hz line 1 to neutral metering voltage calibration 60 Hz line 2 to neutral metering voltage calibration 60 Hz line 3 to neutral metering voltage calibration 50 Hz line 1 to neutral metering voltage calibration 50 Hz line 2 to neutral metering voltage calibration 50 Hz line 3 to neutral metering voltage calibration 60 Hz line 1 metering current calibration 60 Hz line 2 metering current calibration 60 Hz line 3 metering current calibration 50 Hz line 1 metering current calibration 50 Hz line 2 metering current calibration 50 Hz line 3 metering current calibration Annunciator configurable 43084 43083 43082 43081 43080 43079 43078 43077 43076 43075 43074 43073 43072 43071 43070 43069 43067 Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Write Read and Input type 0.001 % 0.001 0.001 % % 0.001 % 0.001 0.001 % % 0.0001 % 0.0001 0.0001 % % 0.0001 0.0001 % % 0.0001 % Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned 0 = Event 0.1 0.1 % % 0.1 % 1.0 1.0 Event code Event code Input type Input type Character Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Unsigned integer Integer 0 = Event 1 = Warning 2 = Shutdown 0 = Event 1 = Warning 2 = Shutdown

Scale

Units

Type
Character Character

Notes

Serial number character #14 43062 Serial number character #15 43063

3/14/2006

Page 6 of 8

PCC1301 MODBUS REGISTER MAP


Preliminary
Description
input #1 type: Annunciator configurable input #2 type: Annunciator configurable input #3 type: Annunciator configurable output #1 event code number: Annunciator configurable output #2 event code number: Annunciator configurable output #3 event code number Annunciator configurable output #4 event code number 43090 Read and Write 1.0 Event code Unsigned integer 43089 Read and Write 1.0 Event code Unsigned integer 43088 Read and Write 1.0 Event code Unsigned integer 43087 43086 43085

Address

Read/ Write
Write Read and Write Read and Write Read and Write .

Scale

Units

Type
integer 1 = Warning 2 = Shutdown 0 = Event 1 = Warning 2 = Shutdown 0 = Event 1 = Warning 2 = Shutdown

Notes

Input type

Unsigned integer Unsigned integer

Input type

1.0

Event code

Unsigned integer

NFPA110 bitmap (Register 40016)


NFPA 110 Description Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 (LSB) (MSB)

Common Alarm Genset Supplying Load Genset Running Not in Auto High Battery Voltage Low Battery Voltage Charger AC Failure Fail to Start Low Coolant Temperature PreHigh Engine Temperature High Engine Temperature PreLow Oil Pressure Low Oil Pressure Overspeed Low Coolant Level Low Fuel Level

3/14/2006

Page 7 of 8

PCC1301 MODBUS REGISTER MAP


Preliminary

Extended Annunciation Bitmap (Register 40017)


Description Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 (LSB) (MSB)

Check Genset Ground Fault High AC Voltage Low AC Voltage Under Frequency Overload Overcurrent Short Circuit Reverse KW Reverse KVAR Fail to Sync Fail to Close Load Demand Genset Circuit Breaker Tripped Utility Circuit Breaker Tripped Emergency Stop

3/14/2006

Page 8 of 8