Name of the work: Minor Capital Work at FSD Sevur for the year 2011-12 Supplying, Installation, Testing

and Commissioning of Solar Power Plant and LED streetlights Schedule of Work

5L' Yo. I

Quantity

Description
I

Rate

Unit

Amount
6

1 Set

Providing, installing, testing and commissioning MNRE approved solar panels conforming to IEC 61715, IEC61646, IEC 62108 or IS 13286 and having RFlD tag (mandatory) of 7400 Wp capacity (minimum capacity of one modute : 200 Wp) including designing the plant , integrate with the existing wiring system with the following components. Supplying, installation testing and commissioning of appropriate hybrid pure sine wave solar inverter capable of supplying out put loads up to at least 150% of the panel capacity with the following speciticat ions Inverter should be stand alone using microcontroller based hybrid design. A C input range: Voltage : 130V to 280 V Frequency: 50 Hz +/- 3 Hz Phase :single phase.3 wire Should have reverse battery protection Solar PV charging efficiency : minimum 90% Change over time : Mains to SPV A Battery : less than 100 m.s. SPV Battery to mains ; less than I00 m.s. Low battery cut off: DC bus voltage-20% Should include battery over voltage and over charging protection . Battery charging: 1" priority : SPV power only at 10-15% of battery AH 2ndpriority : Shared with input mains if SPV doesn't provide sufficient power. Out put characteristics: Voltage at no load. 220V -1-5%, 50 Hz +!-0.5% Out put waveform : pure sine wave THD : less than 3% at resistive load. Surge current capacity : up to 300% for one cycle Over load : Auto start 6 times at 110% -125% Efficiency at battery mode : Grater than 85 %

rp ~ e t

-[Should include overload. low battery and short circuit protections. , Display to have indicators for mains status, / overload, low battery, short circuit, mains MCB trip, I 1 nutpur frequency.
I

1 I I
I

I
I

I I
I
-2

( Providing ,installing, connecting to the system, (

---

testing and commissioning of a battery bank comprising of sealed maintenance free (SMF) deep ( cycle gel VR1.A batteries of 96 V and 360 Ah. Supplying and erection of mechanical structure 1 ( with suitable size angle/ channel iron including ainting for mounting solar panel of 2400 W I No l)providme and erecting floor mounted B a t t k rack made of suitable sizeangle iron frame work and sheet metal paneling with locking arrangement etc as required. Wiring for circuit sub main wiring alng with earth i 30.00 mtr wire with the following sizes of PVC insulated i copper conductor singld core cable in surface or / recessed PVC conduit as required( as per the site 1 conditions for inter connections etc as required)

,
1'

I
!

I 11
( Set

I
, Set

1
1

( ]

1
II

1
,

I I 1

1 approved 1 including

24 watts LED street light fittings of MNRE make on the existing point' bracket making connections with 3 core copper wire o f suitable rating and length from the existing point / cable junction box. (MNRE Test Certificate is to be provided ) (Approved rnake of LED: CREE/ PHILIPS/ OSRAM) Total against Subsidy o f m R E