Foundation Repair for Housing Compound of SWCC Jubail by Micropiling ABSAR Specialized Projects Unit Mircopile Design and Construction by Federal Highway Administration US Department of Transportation (FHWA-SA-97-070)
Jan. 7, 12 Page |1
Design: GEOMETRY
Revision 00
The above figure shows the typical foundation details supported by micropiles. The dimensions are arrived from the drawings supplied and client information. In the above figure, Unit Weight Of The Backfill Soil Angle Of Shearing Resistance = = 17 35 kN/m3 Deg
Project: Client:
Foundation Repair for Housing Compound of SWCC Jubail by Micropiling ABSAR Specialized Projects Unit Mircopile Design and Construction by Federal Highway Administration US Department of Transportation (FHWA-SA-97-070)
Jan. 7, 12 Page |2
Design:
Revision 00
The ASBUILT drawings supplied shows a safe bearing pressure of 1.0 kg/cm2. Due to absence of live load and dead load coming from the superstructure details we back calculate the loading from the bearing pressure. Allowable bearing pressure = = However for the design considerations we take the SBC as = 1.0 100 200 kg/cm2 kPa kPa
This is for increasing the loading which is expected from the superstructure. So for the given dimension the column load And hence Dc Load from the column Dead Load from the soil covering the Foundation Ds = = = = Approximately = Total Design Load = (Ds + Dc) For this design we use Load Factor Design Method (LFD). The Group I factored loads as per AASHTO are calculated from the footing loads Since the foundation structure is symmetrical about the center of base of the footing the sum of all HORIZONTAL forces and MOMENTS gets nullified. But the vertical forces are considered Fy = (BDDc + BDDs) = 1.3 (1.0 x 50 + 1.0 x 53) = 133.9 kN 134 kN = 50 50 kN kN
Approximately =
The Group VII Seismic load as per AASHTO Division I-A are calculated from the footings loads
Project: Client:
Foundation Repair for Housing Compound of SWCC Jubail by Micropiling ABSAR Specialized Projects Unit Mircopile Design and Construction by Federal Highway Administration US Department of Transportation (FHWA-SA-97-070) = 50+53 =
Jan. 7, 12 Page |3
Design: Fy = Dc + Ds
Revision 00 103 kN
From the above figure the Centroid of the Pile Group (From Outer Pile)
1/1 1/1 2
x x
0.0 1.5
= =
Project: Client:
Foundation Repair for Housing Compound of SWCC Jubail by Micropiling ABSAR Specialized Projects Unit Mircopile Design and Construction by Federal Highway Administration US Department of Transportation (FHWA-SA-97-070)
Jan. 7, 12 Page |4
Design:
Revision 00
So the Centroid is at (1.5/2) = 0.75 m from the Outer Pile. Eccentricity e = (1.5/2) 0.75 = 0.0 m
And hence there is no Eccentricity in our design case. Due to the absence of the Eccentricity the vertical load are distributed equally to the outer and inner piles. That is, Outer Pile Vertical Load = Inner Pile Vertical Load = Fy/2=134/2 Inner pile Axial loading Determine Structural and Geotechnical Pile Design Strength Use Reinforcing Bar of 25 mm diameter of grade 520 steel Bar Area = 491 mm2 = Fybar = 520 MPa = 67 kN 71.3 kN
= 67/Cos (20o) =
Soil Condition and the method of pile installation can affect the resulting diameter of the pile bond length. For this example assume a drill-hole diameter of 50 mm greater that the drilled diameter of the pile. Therefore GROUTdia = GROUT Area = 150+50 31429 mm2 = 200 mm
Project: Client:
Foundation Repair for Housing Compound of SWCC Jubail by Micropiling ABSAR Specialized Projects Unit Mircopile Design and Construction by Federal Highway Administration US Department of Transportation (FHWA-SA-97-070)
Jan. 7, 12 Page |5
Revision 00
Fy-steel(Area-bar) =
= 230 kN
255 kN
Pt-design = t Pt-nominal
Compression Design Strength Pc-nominal = = [0.85 Fc-grout (Area-grout) + Fy-steel (Area-bar)] 1177 kN
Considering the design transfer load in full to the bond length area. P-transfer-design = 250 kN
Tension Design Strength P-t-design = 0.9x Fy-bar x Area-bar + P transfer design = 230 kN Compression Design Strength P-c-design =0.75 (0.85 x f-c-grout x Area-grout + Fy-bar x Area-bar) + PtransferDesign =883kN Grout to Grout Bond Strength = 335 kPa
Designing for AASHTO Loading calculated Maximum Axial Loading Calculation of Bond Length Bond Length = 72 / (-G x bond strength x 3.14 x DIAbond) 72 / (0.6x335 kpa x 3.14 x 0.200 ) = 0.57 m ~ 0.6 m = 71.3 ~ 72 kN
Project: Client:
Foundation Repair for Housing Compound of SWCC Jubail by Micropiling ABSAR Specialized Projects Unit Mircopile Design and Construction by Federal Highway Administration US Department of Transportation (FHWA-SA-97-070)
Jan. 7, 12 Page |6
Design:
Revision 00
Hence provide pile length of 5.5 m below the footing base. This shall cover the bond length in the hard strata. The spacing of inner and outer piles shall be 1.0 m c/c The reinforcing bars shall be curtailed and welded or jointed with the footing reinforcement.