From the MassHighway Storm Water Handbook for Highways and Bridges
http://www.mass.gov/dep/water/wastewater/stormwat.htm
Description:
Subsurface recharge systems may include trenches, beds, galleys, or dry wells. Such systems have sucient storage capacity so as to permit the gradual inltration of runo. Pollutant removal is provided by ltration through the soil matrix. Pre-treatment is required to prevent failure of inltration systems due to sediment accumulation. Subsurface systems (other than leaching catch basins or leaching basins will rarely be used in the highway setting. These systems have historically had signicant failure rates, and site constraints often limit the eective use of inltration. Recharge BMPs should generally be designed as o-line systems. Separate Design Criteria tables follow this table, for Recharge Trenches and Beds and Recharge Dry Wells and Galleys.
GENERAL INFORMATION
Applicable DEP Stormwater Management Policy Performance Standards TSS Removal Standards #3 and #4. If sucient additional storage and appropriate outlet structures are provided, recharge basins may also be used to meet Standard #2. DEP Credit: Estimated Range from Literature: TSS Removal Construction: Maintenance: 80% >90% Moderate to high High
Depth to bedrock or other impermeable substratum Depth to groundwater Soils Slope Recharge systems can provide high levels of treatment of other pollutants, in addition to TSS removal High failure rates (particularly without sucient pre-treatment); replacement/rehabilitation (with a cost about equal to initial construction) may be required Frequent maintenance may be required Inspect at least twice annually Regular sediment removal from pre-treatment systems to prevent clogging Rehabilitation in the event of failure due to clogging Periodic removal of debris/trash from ow control structures MA-DEP Stormwater Technical Handbook: http://www.mass.gov/dep/brp/stormwtr/stormpub.htm Schueler, 1987 Young, et. al., 1996
Other Considerations
Maintenance Requirements
CRITERIA1
< 2.0 ha (5 acres) Varies with system. Recharge systems are sized for recharging an annual volume, not an event storm. Compute annual recharge volume using methodology specied in MA-DEP Stormwater Technical Handbook (see Primary Design References), or use an alternative method conforming to accepted engineering practice. Compute storage volume using methodology specied in MA-DEP Stormwater Technical Handbook. Determine recharge rate based on soil texture/hydrologic group as specied in MA-DEP Stormwater Technical Handbook, conrmed by on-site eld testing; or use an alternative method conforming to accepted engineering practice. A safety factor is recommended to allow for the potential clogging of underground systems. The system should be designed to drain the design storage volume in 48 hours or less, using the design recharge rate times the applicable safety factor. Depth of system shall be equal to or less than the depth permitting draw-down in the required time. When the void space in crushed stone is used for storage, the specied stone should be uniformly sized. A porosity (volume of voids divided by total volume of bed) of 0.39 or less should be used for design. The crushed stone material must be isolated from adjacent in-situ soils by a geotextile fabric designed to prevent the migration of ne soil particles into the void spaces in the stone. Geotextile materials must meet applicable standard specications, and must be selected based on an analysis of on-site soils conditions. An underground system should be designed as an o-line system, or otherwise provided with an overow or by-pass to safely convey ows that exceed the system capacity. Minimum 0.6 meters (2 feet) below bottom of system, unless engineering analysis demonstrates that lesser separation is feasible. Small systems: Minimum 0.6 meters (2 feet) below bottom of system. Large systems: Groundwater mounding analysis may be required. Pre-treatment system is required to provide TSS removal prior to discharge to an underground recharge system. Provide measures to dissipate velocity of ows into the device, to prevent erosion within the structure; generally, velocities < 0.61 meters/second (2 fps) are recommended.
Geotextile
CRITERIA1
3.0 meters (10 feet) 6.1 meters (20 feet) 4.6 meters (15 feet) (top edge of system to top of slope), or as required for impoundment stability. Distance may need to be greater where potential for break-out and resulting slope instability may be a problem. 7.6 meters (25 feet) (or greater, if required under 310 CMR 15.000 [Title 5]) 30.5 meters (100 feet) Zone I radius; additional setback may be required depending on hydro-geologic conditions Zone A, and 30.5 meters (100 feet) from tributaries The infiltration surface shall be constructed to preserve and enhance the capability of the soil to pass ows from the basin into the groundwater. Consider measures such as minimizing tracking by heavy construction equipment If structural chambers are used to construct the bed or trench, they should be designed for dead and live loads appropriate to their location. The minimum design load shall be H-20 loading. Underground systems should be provided with access ports, man-ways, or observation wells to enable inspection of water levels within the system. At a minimum, provide two (2) observation wells (152.40 mm (6-inch) diameter perforated PVC or HDPE risers) per trench or bed; for beds greater than 372.0 square meters (4,000 square feet) in area, provide one (1) well for each 186.0 square meters (2,000 square feet) (minimum of three wells). The inspection port should be accessible at-grade (i.e. not buried). Design shall consider accessibility to system, and capability to replace system components, to provide for eventual repair and rehabilitation of the system. Runoff from disturbed areas shall not be discharged to the recharge structure. The contributing site shall be completely stabilized, prior to placing the recharge structure in service. Recharge trenches and beds should be off-line devices, with provisions for the bypassing or overflow of storms exceeding the storage capacity of the trench or bed.
Setback from on-site sewage disposal system Setback from private well 30.5 meters (100 feet) Setback from surface water supply Construction of inltration surface
Other
Several of the design criteria regarding setbacks from slopes, foundations, and other site features have been adapted from the requirements for on-site sewage disposal systems described in Massachusetts Title 5 (310 CMR 15.000). However, storm water quantities and ow durations dier markedly from the hydraulic loadings to septic systems. The design engineer should be aware of these dierences, and may need to consider additional setbacks to provide for slope stability, protect structures, and provide for the satisfactory performance of the recharge system.
1
CRITERIA2
Contributing area will be limited by the size of well or galley used. These devices are typically used for discharging roof top runo, or small parking areas. Designer will need to relate size and number of units to the volume of runo to be treated. Varies with system. Recharge systems are sized for recharging an annual volume, not a storm event. Compute annual recharge volume using methodology specied in MA-DEP Stormwater Technical Handbook (see Primary Design References), or use an alternative method conforming to accepted engineering practice. Compute storage volume using methodology specied in MA-DEP
Geotextile
Depth to Bedrock or Impermeable Stratum Depth to seasonal high groundwater Pretreatment (roofs)
DESIGN CRITERIA
DESIGN PARAMETER
Velocity Dissipation at Inlet
CRITERIA2
Provide measures to dissipate velocity of ows into the device, to prevent erosion within the structure; generally, velocities < 0.61 meters/second (2 fps) are recommended. 3.0 meters (10 feet) 6.1 meters (20 feet) 50 feet (top edge of system to top of slope), or as required for impoundment stability. Distance may need to be greater where potential for break-out and resulting slope instability may be a problem. 7.6 meters (25 feet) (or greater, if required under 310 CMR 15.000 [Title 5]) 30.5 meters (100 feet) Zone I radius; additional setback may be required depending on hydro-geologic conditions Zone A, and 30.5 meters (100 feet) from tributaries Structural components should be designed for dead and live loads appropriate to their location. The minimum design load shall be H-20 loading. Each well or galley unit should be provided with an access port, man-way, or observation well to enable inspection of water levels within the system. The inspection port should be accessible at-grade (i.e. not buried). If inspection port does not provide access, additional manhole access should be provided to each well or galley chamber. Runo from disturbed areas shall not be discharged to the recharge structure. The contributing site shall be completely stabilized, prior to placing the recharge structure in service. Recharge dry wells and galleys should be o-line devices, with provisions for bypassing or overow of storms exceeding the design capacity of the devices.
Setback from slab foundation Setback from cellar foundation Setback from slope >15%
Setback from on-site sewage disposal system Setback from private well Setback from groundwater supply Setback from surface water supply Structural design loading
Inspection access
Other
Several of the design criteria regarding setbacks from slopes, foundations, and other site features have been adapted from the requirements for on-site sewage disposal systems described in Massachusetts Title 5 (310 CMR 15.000). However, storm water quantities and ow durations dier markedly from the hydraulic loadings to septic systems. The design engineer should be aware of these dierences, and may need to consider additional setbacks to provide for slope stability, protect structures, and provide for the satisfactory performance of the recharge system.
2