SACE Emax
Rated maximum voltage Rated voltage Rated continuous current Rated short-circuit current Rated short-time current 635 V 600 V 800 A - 5000 A 42 kA - 125 kA (480 V) 35 kA - 100 kA
ABB Control
GENERAL INDEX
Introduction
Technology and innovation for advanced plant engineering requirements 2 More efficient, safer installations Intelligent design Compact switchboards Optimal warehouse management A design dedicated to Quality and respect for the environment 4 6 7 8
Main characteristics
Electrical specifications 16 Construction characteristics 18 Identification of circuit-breakers Versions and connections SACE PR111 and PR112 microprocessor-based trip units Accessories 24 25
Overall dimensions
Fixed circuit-breaker Withdrawable circuit-breaker Mechanical interlock 70 74 82
Circuit-breaker accessories 83
26 30
10
Installation in switchboards
Installation in switchboards 32 Derating in altitude 36
Accessories
Circuit-breaker and fixed part accessories Spare parts 54 67
Introduction
Characteristics
Installation in switchboards
Trip units
Accessories
Overall dimensions
Circuit diagrams
The new series has been designed in accordance with the most modern ergonomical criteria, and the evidence for this can be seen in the prize awarded to the circuit-breakers at the Hanover Forum Design.
The constant increase in the technological and functional complexity of electrical installations makes it essential for every component - particularly those such as protection circuit-breakers which are crucial to safety - to offer the highest levels of continuity of service and reliability combined with minimal maintenance requirements. ABB SACE L.V. has designed the new generation of SACE Emax low voltage power circuit-breakers in line with these advanced plant engineering requirements, and featuring high resistance to mechanical, electrical and thermal stresses. SACE Emax circuit-breakers represent the logical functional complement to SACE Isomax S molded case circuit-breakers and have, like them, been designed for integration and perfect co-ordination with the different lines of ABB low voltage products.
The design and manufacture of the new circuit-breakers follow advanced ergonimical criteria, in line with the solutions adopted for selection and use of SACE Isomax S switchgear entirely to the benefit of all catagories of customers and users. Two aspects received particular attention during design: the modular versatility and physical dimensions of the different sizes, reduced from the six of the SACE Megamax series to four. SACE Emax circuit-breakers are available in five different models: E1, E2, E3, E4 and E6, each of which benefits from the interchangeability of the various different versions of moving parts (with different breaking and rated current capacities) for the same fixed part. The rated uninterrupted currents range from 800 to 5000 A. The breaking capacities, which have been improved in relation to the previous series, range from 42 kA to 125 kA (480 V a.c.).
The principal benefits of the new SACE Emax circuitbreakers are as follows:
Accessories
fitted without need for cabling, reducing stock levels and optimizing logistical costs from exposed conductive parts to be respected zero for withdrawable circuit-breakers construction of electrical switchboards.
Distances
Emax0459
Emax0460
Common
Simplified
Emax0476
Emax0346
Emax0397
SACE Emax circuit-breakers not only ensure the high level of reliability needed to achieve the necessary service continuity, but also offer a high level of safety for everyone operating on the installation, both during functional customization and during inspection and maintenance. The risk of carrying out incorrect and dangerous sequences of operations is prevented of suitable locks. Each sequence is only enabled if all the conditions which ensure it can be carried out safely and correctly followed. In any case, the state of the switchgear is automatically taken to the highest safety level for the operator performing the operation. Accessories are installed from the front of the circuit-breaker with cabling pre installed and the accessories section is separate from the power circuit.
Emax0309
Going into greater detail, the main solutions adopted to protect operators in the various different operating conditions are as follows:
Key locks or padlock devices, to control enabling of opening and closing operations and/or racking in and out
Anti-insertion
locks, to prevent moving parts from being inserted into fixed parts with different rated currents or when the circuit-breaker is closed.
Emax0454
Emax0393
Emax0408
SACE Emax circuit-breakers offer outstanding reliability in terms of both mechanical and electrical life. In the field of low voltage apparatus up to 5000 A, represent the maximum in
terms of performance, while with regard to their structural characteristics, their indices allow a high level of sturdiness to be achieved.
Emax0400
Intelligent design
Electrical installation designers choosing the new SACE Emax circuit-breakers can offer a vast range of solutions that enable them to satisfy the specific demands of every user without obliging them to adapt their needs to the switchgear available. When looking through the detailed SACE Emax catalogue of the complete and highly specialized range, the versatility and possibility of optimal sizing become immediately apparent. The rated current and breaking capacity levels have been studied to ensure optimal sizing in all plant configurations. The need to optimize the management of electrical installations is increasingly being recognized today, particularly where power consumption, control, monitoring, diagnostics and, consequently, maintenance operations are concerned. Benefiting from the know-how acquired with its other series of circuit-breakers, ABB SACE L.V. has specially designed and manufactured a family of microprocessor-based trip units, called SACE PR111 and PR112, that are able to provide a wide range of important dedicated functions for SACE Emax circuit-breakers. The SACE PR112 trip unit, in particular, features a 16 bit microprocessor and 12 bit analogue to digital converter, making its performance even more accurate.
Emax0466
As a result, the work of specifiers and designers is considerably simplified when it comes to choosing the technical characteristics and performance required. All this is thanks to the fact that the selection criteria are common to several families of circuit-breakers and use intuitive and easy-to-read codes and symbols. The new circuit-breakers build on the successful experience acquired with the SACE Isomax S family, continuing a tradition of switchgear designed and manufactured paying particular attention to use and user interface-related aspects, with obvious advantages in terms of ergonomics, clarity and speed of identification.
Emax0443
Compact switchboards
The need to build increasingly compact switchboards to satisfy the architectural and technical requirements of modern buildings while simultaneously rationalizing the related construction process is fully met by the new SACE Emax circuit-breakers which have a constant depth and height from 800 through to 5000 A. The new ABB SACE L.V. power circuitbreaker makes it possible to standardize the support structures for the circuitbreakers, considerably facilitating construction of the switchboards themselves. The reduced width of the circuit-breaker offers the benefit of more rational use of the space available and makes it possible to build compact switchboards. Moreover, the fact that a wide range of terminals is available for the entire series makes it possible to build switchboards mounted against walls or switchboards which can be accessed from behind with rear connections.
Emax0345
W W
E1 - E2 E3 E4 E6 Fixed 3 POL 296 mm / 11.65 inches 404 mm / 15.91 inches 566 mm / 22.28 inches 782 mm / 30.79 inches Withdrawable 3 POL 324 mm / 12.76 inches 432 mm / 17.01 inches 594 mm / 23.39 inches 810 mm / 31.89 inches
Withdrawable 461 mm 18.15 inches Fixed 418 mm 16.46 inches
Emax0405
Fixed Withdrawable
A single range of accessories serves the entire SACE Emax series of circuit-breakers. This standardization enables optimal warehouse management while simultaneously ensuring flexibility. Electrical distributors and every customer who has to manage maintenance and spare parts for large installations consequently benefits from simpler warehouse management. The ease with which accessories are installed makes modular fitting operations fast and safe, allowing even the end customer to carry out the customizing required in each different phase of the life of an installation. The designers job is made much easier since the switchgear can be chosen well in advance, preventing any overlapping with the phase for finalizing the construction details. The current transformers for the different rated currents of the trip units are very simple to change, meaning the end customer can also carry out this operation. SACE PR111 and PR112 microprocessor-based trip units are, likewise, easy to change and are also interchangeable. Moreover, conversion kits are available for the different terminal solutions and versions of the circuit-breaker, allowing a very high level of warehouse rationalization. The fixed parts for withdrawable circuitbreakers are common to each model, irrespective of the rated current and breaking capacity.
Emax0479
Emax0343
The new circuit-breakers have been developed in an environment where quality research has always been an overriding commitment. A commitment that involves every company function at ABB SACE L.V. and has made it possible to
obtain prestigious international marks of recognition. The Company Quality System has been certified by RINA (Registro Italiano Navale - Italian Naval Register), one of
Ema x036 1
the most prestigious international certification bodies, and conforms to the ISO 9001 Standard, while the ABB SACE L.V. test laboratory has been accredited by SINAL. Commitment to care for the environment is another priority at ABB, confirmed by the fact that the ABB SACE L.V. Frosinone factorys environmental management system has been certified by RINA. ABB SACE L.V., the first industrial company in the electro-mechanical sector in Italy to obtain this, thanks to an ecologycentred revision of its manufacturing process, has been able to reduce its raw material consumption and machining scrap by 20%.
Emax0402
10
Emax0404
Emax0347
Emax0394
ABB SACE L.V.s commitment to protecting the environment can also be seen in the product Life Cycle Assessments (LCA) carried out in its Research Center. The materials, processes and packaging used are chosen with a view to optimizing the real environmental impact of each product, including its energy efficiency and recyclability.
Emax0348
11
SACE Emax Low Voltage power circuit-breakers are designed and tested in accordance with ANSI Standard C37.13, C37.16, C37.17 and C37.50 and are UL Listed in accordance with UL1066. SACE Emax power circuitbreakers UL Listed are also suitable for use in UL 1558 Low Voltage Switchgears, UL891 Low Voltage switchboards and CSA C22.2 no. 31 Switchgear Assemblies. All power circuit-breakers and their accessories are also available with a range in accordance with the International Standards IEC 947-2, EN 60947 (harmonized in the 17 CENELEC countries), CEI EN 60947, IEC 1000 and conform to the relevant CE directives: Low Voltage Directive (LVD) No. 73/23 EEC Electromagnetic Compatibility Directive (EMC) No. 89/336 EEC.
Emax0455
The apparatus complies with the specifications of the regulations for on-board installations and is approved by the following Naval Registers: RINA (Italian Naval Register) Det Norske Veritas Bureau Veritas Germanischer Lloyd Loyds Register of Shipping Polskj Reiestr Statkow The ABB SACE L.V. Quality System conforms to the International Standard ISO 9001 (quality assurance model for design, development, manufacture, installation and service) and the equivalent European Standard EN ISO 9001 and Italian Standard UNI EN ISO 9001. The third party certifying body is RINA-QUACER.
Em ax0 360
12
Emax0363
Emax0362
ISO 9001
13
14
Electrical specifications Construction characteristics Identification of circuit-breakers Versions and connections SACE PR111 and PR112 microprocessor-based trip units Accessories
16
18
24
25
26
30
Electrical specifications
Specifications common to the entire range
Voltages Rated maximum voltage Rated voltage Test voltage (1 min 50/60 Hz) Frequency Number of poles Versions 635 [V] 600 [V] 2,2 [kV] 50-60 [Hz] 3 Fixed - Withdrawable
Emax0422
Type of circuit-breaker
Performance level Currents Rated continuous current [A] [A] [A] [A] Rated short circuit current 240 V 480 V 600 V Rated short time current Trip units PR111/P-A PR112/P-A Operation times Make time (max) Break time (I< ST current) (max) Break time (I> ST current) (max) Overall dimensions Fixed: H= 418 mm / 16.46 in D= 302 mm / 11.89 in W (3 poles) Withdrawable: H= 461 mm /18.15 in D= 396,5 mm /15.61 in W (3 poles) Fixed 3 poles Withdrawable 3 poles [mm/in] [Kg/Ibs] [Kg/Ibs] [mm/in] [ms] [ms] [ms] [kA] [kA] [kA] [kA]
E1
B-A
Emax0426
E2
B-A N-A
800 1200
1600
1200 1600
42 42 35 35 80 70 30
42 42 42 42 80 70 30
65 50 50 50 80 70 30
296/11.65
296/11.65
Weights (CB fitted with releases, RH terminals and CTs, accessories excluded)
E1 B-A Rated continuous current Mechanical life Frequency Electrical life Frequency [A] [No. operations x 1000] [Operations/hour] [No. operations x 1000] [Operations/hour]
16
Emax0430
Emax0434
E3
N-A S-A H-A
E4
S-A H-A V-A
Emax0438
E6
H-A V-A
2000 2500
3200 3600
3200 3600
3200 3600
4000 5000
4000 5000
65 50 50 50 80 70 30
85 65 65 65 80 70 30
85 65 65 65 80 70 30
100 85 85 85 80 70 30
100 100 85 85 80 70 30
125 85 85 100 80 70 30
404/15.91
566/22.28
782/30.79
17
Construction characteristics
Structure
The structure of the circuit-breaker, which is made out of sheet steel, is extremely compact and allows the dimensions to be significantly reduced. Safety is increased by adopting double insulation for the live parts and total insulation between the phases. The dimensions are characterized by having the same height and depth for all the circuit-breakers in each version. The depth of the withdrawable version is suitable for installation in 500 mm /
18
Emax0417
19.68 inches deep switchboards. The width of 324 mm / 12.75 inches (up to 1600 A) for the withdrawable version allows the switchgear to be used in switchboard compartments 400 mm / 15.74 inches wide.
These compact dimensions also allow them to replace any models of power circuit-breakers from earlier series.
Emax0418
19
Construction characteristics
Selective circuit-breaker
S/H/V-A, H/V-A E1 B-A, E2 B/N-A, E3 N/S/H-A, E4 S/H/V-A, E6 H/V-A
9 8 7 6b 6a 5b 5a
10
2 4
11
1 2 3 4 5a 5b 6a 6b 7 8 9 10 11
Sheet steel supporting structure Current transformer for protection release Pole group insulating box Horizontal rear terminals Plates for fixed main contacts Plates for fixed arc-breaking contacts Plates for moving main contacts Plates for moving arc-breaking contacts Arcing chamber Terminal box for fixed version - Sliding contacts for withdrawable version Protection release Closing and opening control of circuit-breaker Closing springs
20
GSEM0098
7 6 8
3 4 2
1 2 Sheet steel supporting structure Single grounding pliers mounted on the left for E1, E2 and E3, double grounding pliers for E4 and E6. Safety shutters (degree of protection IP20) Terminal supporting insulating base Terminals Contacts signalling connected, isolated, isolated for test (to order) Sliding contacts Padlock device for safety shutters (to order) Fixing points (4 for E1, E2, E3 and 6 for E4, E6)
4 5
7
Emax0337
8 9
21
Construction characteristics
Operating mechanism
The operating mechanism is of the stored energy type, operated using pre-charged springs. The springs are charged manually by operating the front lever or using a motor operator, supplied on request. The opening springs are charged automatically during the closing operation. With the operating mechanism fitted with shunt closing and opening releases and the motor operator for charging the springs, the circuit-breaker can be operated by remote control and, if required, co-ordinated by a supervision and control system.
The following operating cycles are possible without recharging the springs: starting with the circuit-breaker open and the springs charged: closing-opening starting with the circuit-breaker closed and the springs charged: opening-closing-opening. The same operating mechanism is used for the entire series and is fitted with a mechanical and electrical anti-pumping device.
Emax0444
O I I O O
Emax0458 Emax0459
22
Fixed version
14
2 1 3 5 7 9 10 4 6 8
7 Mechanical signalling device for circuitbreaker open O and closed I 8 Signal for springs charged or discharged 9 Mechanical signal for protection release tripped 10 Operation counter
Emax0447
4 Pushbutton for manual closing operation 5 Lever for manual closing spring charging 6 Electrical rating plate
11 Key lock in open position 12 Key lock and padlock in isolatedwithdrawn position
Withdrawable version
13 Devices for the racking-in/racking-out operations 14 Terminal box (only for fixed version) 15 Sliding contacts (only for withdrawable version)
15
2 1 11 5 7 9
3 4 6 8 10 13
12
Emax0449
23
Identification of circuit-breakers
Where the dimensions of the circuit-breakers are concerned, they are divided into four sizes, each with the same external dimensions. There is one model in each size, with the exception of size 1, which has two models with different electrical specifications (E1 and E2). The circuit-breakers are identified using the following code:
Emax0459
Series
Model
08 B - A 42 kA N - A 50 kA S - A 65 kA H - A 85 kA V - A 100-125 kA 12 16 20 25 32 36 40
Gsem0005
50
24
Emax0412
All the circuit-breakers are available in fixed and withdrawable three-pole version. Each model of circuit-breaker has terminals made of silverplated copper bars which have the same dimensions irrespective of the rated currents of the circuit-breakers (except for E3). The fixed parts of each model of withdrawable circuit-breakers are the same for every rated current and breaking capacity of the related moving parts (except for E3).
The fact that different types of terminals are available makes it possible to build switchboards that can be mounted against walls or accessed from the rear with rear connections. The circuit-breakers can be fitted with different combinations of top and bottom terminals to meet special installation needs.
FIXED CIRCUIT-BREAKERS
WITHDRAWABLE C.BREAKERS
GSEM0006
GSEM0007
GSEM0009
GSEM0010
25
The overcurrent protection for alternating current installations is provided by two types of microprocessor-based trip units in the SACE PR111 and PR112 series which can be installed as alternatives on SACE Emax circuit-breakers:
The protection units can be three-phase or three-phase with external neutral depending on the type of circuit-breaker used. The protection unit comprises:
an
opening solenoid which acts directly on the circuit-breaker operating mechanism (always supplied with the protection unit).
microprocessor
technology (8 bit for SACE PR111 and 16 bit for SACE PR112)
the setting for the phases, with the possibility of setting it to 100% (to order on E1, E2, E3). The main performances which distinguish the trip units are indicated in the following table.
26
SACE PR111
Protection functions
Overload protection with inverse long time-delay trip
Mini0466a Mini0465
SACE PR112
Residual Ground fault protection Source ground return Thermal memory for functions L and S
Measurements
Currents (in phases, in neutral, of ground fault)
Data storage
Counting of number of operations and contact wear
Self-test
Alarm and release due to trip units temperature rise Alarm due to microprocessor fault
User interface
Parameters set using DIP switches Parameters set using keys and liquid crystal display Alarm signals for functions L and S Complete management of pre-alarms and alarms for all protection and self-monitoring functions Enabling key for use in READ (consultation) or EDIT (consultation and setting) mode
Zone selectivity
Can be activated for protection functions S and G
27
Versions available
Trip unit SACE PR111 PR111/P-A
Mini0465
PR111/P-A
PR111/P-A
PR112/P-A
28
Emax0456
Type E1B-A
CURRENT TRANSFORMER SETTINGS (Rated current) R400 R800 R1000 R1200 R1600 R2000 R2500 R3200 R3600 R4000 R5000
E2B-A E2N-A
E3N-A
2000 A 2500 A
E3S-A
E3H-A
E4S-A
3200 A 3600 A
E4H-A
3200 A 3600 A
E4V-A
3200 A 3600 A
E6H-A
4000 A 5000 A
E6V-A
4000 A 5000 A
29
Accessories
E1 E6
Circuit-breaker
Emax0264a
Version Shunt opening/closing release SOR Test Unit Undervoltage release Delay device for undervoltage release Geared motor for automatic charging of closing springs Mechanical signal of overcurrent releases Mechanical and electrical signal of overcurrent releases tripped Electrical signal for circuit-breaker open/closed Electrical signal for circuit-breaker connected/isolated for test/isolated Contact for signalling closing springs charged Contact for signalling undervoltage release energised Current transformer for the circuit-breaker external neutral conductor Homopolar toroid for the earthing conductor of the main power supply Terminal box for fixed version circuit-breaker Sliding contacts for withdrawable version circuit-breaker Mechanical operation counter Key lock or padlock devices in open position Arrangement for key lock in open position with Kirk lock Circuit-breaker lock in connected / isolated for test / isolated position Anti-insertion lock for circuit-breakers of different models Padlock devices for fixed part shutters Compartment door mechanical lock Protection for opening and closing pushbuttons IP54 door protection (NEMA 3/3S/13) Interlock between circuit-breakers Lifting plate Racking out crank handle Flange for compartment door
Fixed
Emax0267a
Withdrawable
30
= optional
32
36
31
Installation in switchboards
Modular design
The circuit-breakers in the SACE Emax series have been made following modular design criteria to facilitate their installation and integration in L.V. electrical switchboards, giving them the same depth and height for every model while simultaneously achieving a significant reduction in their overall installation dimensions. Furthermore, the front metal shield of the circuit-breaker is identical for the entire series. This simplifies the construction of the switchboard doors since only one type of drilling is required and makes the front of the switchboard the same for all sizes.
32
Emax0457
tions in three phase installations depends on the type of electrical system (TN-S, TN-C, IT) and the type of user or, more generally, whether it features a distributed or non-distributed neutral.
THREE-POLE CIRCUIT-BREAKERS
PEN L1
L2
L3
L1
L2
L3
For TN-C systems (interruption of the neutral is not admissible because it also acts as the protection conductor). For users that do not use the neutral (e.g.: asynchronous motors) and, generally, for lines without neutral (non-distributed neutral).
PE
L1
L2
L3
Current transformers can be installed on the external neutral of five-wire systems (TN-S) with 3-pole circuitbreakers
SACE PR111-PR112
Fixed or withdrawable version The fixed version of the circuit-breaker has more compact dimensions than the withdrawable version. It is recommended for installations that can tolerate service interruptions in the event of faults or routine maintenance. The withdrawable version of the circuit-breaker is recommended for: applications that can only tolerate brief interruptions due to faults or routine maintenance: dual lines, one of which is a standby for the other, with a single circuit-breaker for each pair. 33
Emax0331a
SACE PR111-PR112
Installation in switchboards
The figures at the side show a number of indications for terminal selection.
Horizontal rear terminals - For switchboards with access from the rear
Vertical rear terminals - For switchboards with access from the rear
Degrees of protection
A number of solutions have been adopted on SACE Emax circuit-breakers to achieve degree of protection IP22 for fixed or withdrawable circuit-breakers excluding their terminals, and IP30 for their front parts using a flange. Automatic shutters have been designed for the fixed parts of withdrawable circuitbreakers which can be locked using padlock devices to allow maintenance of the load side or power-supply side of the fixed part. In addition, a transparent protective cover is available on request, which completely segregates the front part of the circuit-breaker, taking the degree of protection to IP54 (NEMA 3/3S/13) while still leaving the front panel and protection trip unit with its related indications fully visible. IP22 Fixed or withdrawable circuitbreaker, excluding terminals. IP30 Front parts of circuit-breakers (using flange). IP54 Fixed or withdrawable circuitbreaker fitted with transparent protective cover to be fixed on the front of the switchboard (on request).
34
Emax0453
Power loss
The following table gives information about power losses of fixed and withdrawable circuit-breakers. C.-breaker Rated current [A] E1 B-A E2 B-A E2 N-A E3 N-A E3 S-A 800 1200 1600 1200 1600 2000 2500 1200 1600 2000 2500 E3 H-A 1200 1600 2000 2500 E4 S-A E4 H-A E4 V-A E6 H-A E6 H-A 3200 3600 3200 3600 3200 3600
Emax0342
Power loss Fixed 3 Pole [W] 65 146 115 65 115 130 205 48 85 130 205 48 85 130 205 235 297 235 297 235 297 265 415 265 415 Withdrawable 3 Pole [W] 95 214 215 121 215 225 350 84 150 225 350 84 150 225 350 425 538 425 538 425 538 445 700 445 700
35
Altitude derating
Up to a height of 2000 metres, the SACE Emax air circuitbreakers do not undergo any changes in their rated performance. As the altitude increases their atmospheric properties alter in terms of composition, dielectric capacity, cooling power and pressure. The performance of the circuit-breakers therefore undergoes
derating which can basically be measured by means of the variation in significant parameters such as the maximum rated voltage of operation and the rated uninterrupted current. The table below shows the above-mentioned values in relation to the altitude.
<6600 (2000)
600 In
36
Overcurrent protection with SACE PR111 microprocessor-based trip units Trip curves of circuit-breakers with SACE PR111 trip units Overcurrent protection with SACE PR112 microprocessor-based trip units Trip curves of circuit-breaker with SACE PR112 trip units SACE PR010/T test and configuration unit
38
42
44
48
52
37
12
13
15
16
20
Emax0465
11
10
14
18
17
19
Caption 1 Alarm signal LED for protection function L 2 DIP switches for setting current threshold I1 3 Indication of the DIP switch positions for the values of current thresholds I1 4 DIP switches for setting trip time t1 (type of curve) 5 Indication of the DIP switch positions for the time settings 6 Alarm signal LED for protection function S 7 DIP switches for setting current threshold I2 8 Indication of the DIP switch positions for the values of current thresholds I2 9 DIP switches for setting trip time t2 (type of curve) 10 DIP switches for setting inverse time or definite time characteristic 11 Indication of DIP switch positions for time settings 12 DIP switches for setting current threshold I3 13 Indication of the DIP switch positions for the values of current thresholds I3 14 Rating plate showing the rated current of the neutral CT and the trip unit serial number 15 DIP switches for setting current threshold I4 16 Indication of the DIP switch positions for the values of current thresholds I4 17 DIP switches for setting trip time t4 (type of curve) 18 Indication of DIP switch positions for time settings 19 Symbol diagram showing operation of function G 20 Connection module with external units for testing the trip unit and socket for connection to the trip test (SACE TT1 unit and SACE PR010/T unit)
38
t=
K I2
t=K
GSEM0064
Power supply
The trip unit does not require an external power supply, being self-powered using the current transformers installed on the circuit-breaker. Operation requires at least one phase to be loaded at 20% of the rated current of the current transformers (In).
GSEM0065
Protection functions
The SACE PR111 trip unit offers the following protection functions: overload (L) selective short-circuit (S) instantaneous short-circuit (I) ground fault (G). See the following section for the range of settings available.
Overload (L)
The inverse long time-delay trip overload protection L is of the type I2t = k. Eight current thresholds and 4 curves indicated by the letters A, B, C, D are available. Each curve is identified by the trip time in relation to the current I = 6 x I1 (I1 = threshold set).
Versions available
The versions available are as follows:
Setting neutral
Protection of the neutral is available at 50% in the standard version or at 100% (version which can be supplied on request for E1-E2-E3) of the rated current and of the phases.
Test function
The Test function is carried out by means of the pocketsized SACE TT1 Trip Test unit, fitted with a two-pole polarized connector housed on the bottom of the box, which allows the device to be connected to the TEST input socket on the front of SACE PR111 trip unit. The SACE TT1 unit allows the SACE PR111 trip unit to be checked and the opening solenoid trip test. The device is supplied by means of a 12V replaceable battery.
Emax0413 Emax0465
Emax0471
Emax0470
A complete test of the SACE PR111 microprocessorbased trip unit can be carried out using the special SACE PR010/T apparatus by applying it to the TEST connector. All the trip unit functions can be checked by means of this unit.
40
Protection functions and setting values of the SACE PR111/P-A trip unit
Function Current thresholds Trip time Can be excluded Relation t = f (I) t = k/I2
Overload protection
I1 =
0.4 x In 0.5 x In 0.6 x In 0.7 x In 0.8 x In 0.9 x In 0.95 x In 1 x In 1 x In 2 x In 3 x In 4 x In 6 x In 8 x In 10 x In 1 x In 2 x In 3 x In 4 x In 6 x In 8 x In 10 x In 1.5 x In 2 x In 4 x In 6 x In 8 x In 10 x In 12 x In 0.20 x In 0.25 x In 0.30 x In 0.35 x In 0.40 x In 0.45 x In 0.48 x In
NO
I2 =
With current I = 8 x In t2 = 0.05 s (curve A) 0.10 s (curve B) 0.25 s (curve C) 0.40 s (curve D)
YES
I2 =
With current I > I2 t2 = 0.05 s (curve A) 0.10 s (curve B) 0.25 s (curve C) 0.40 s (curve D)
YES
I3 =
Instantaneous trip
YES
t=k
I4 =
With current I = 4 x I4 t4 = 0.1 s (curve A) 0.2 s (curve B) 0.3 s (curve C) 0.4 s (curve D)
YES
t = k/I2
Mini0465
41
D C B
C B A
0.01 0.1
0.2
0.3
0.4
1.2
1.5
7 8 9 10 12
15
20
25
30 20 20 10 5 2 2 10 1
2
10
10
12
D C B A D D C C B A B A 1
t=K I2
I2t ON
GSEM0107b
42
0.01 0.1
0.2
0.3
0.4
1.2
1.5
7 8 9 10 12
15
20
25
30 20 20 10 5 2 2 1 102 60 40 A D 20 10 6 4 2 1 0.6 0.4 0.2 0.1 0.06 0.04 0.02 0.01 0.1 B A A C B D C B 1 0.95 103 0.4 6 0.5 4 0.6 0.7 0.8 0.9 1 1.5 2 4 6 8 10 12 2 3 4 6 8 10
t=K
I OFF
D C
GSEM00108b
0.2
0.3
0.4
1.2
1.5
7 8 9 10 12
15
20
25
0.2
0.25 0.3
0.35 0.4
0.45 0.48
D C
B A
0.01 0.1
0.2
0.3
0.4
1.2
1.5
7 8 9 10 12
15
20
25
43
10
11
12
13
Emax0466a
Caption 1 Programming keys (for selecting parameters) 2 Liquid crystal display 3 Rating plate indicating the rated current of the CT and neutral plus the trip unit serial number 4 Test pushbutton (TEST) 5 Magnetic signalling devices showing protection functions L, S, I, G tripped 6 Magnetic signalling device showing excessive trip unit case temperature rise (second threshold) 7 Key for resetting the magnetic signalling devices and protection device tripped signalling contact (RESET) 8 Key-operated selector switch for choosing read only mode (READ) or setting mode (EDIT) for the parameters 9 Microprocessor fault LED signalling device 10 Auxiliary power supply LED signalling device 11 Pre-alarm signalling device (dedicated message on display) 12 Alarm signalling device (dedicated message on display) 13 Connector for connecting to external units such as SACE PR110/B and SACE PR010/T (additional functions).
44
t=
K I2
t=
K I2
t=K
t=K
GSEM0073
Power supply
The SACE PR112 trip unit does not normally require any external power supplies, being self-powered from the current transformers (CT). For the protection and ammeter functions to operate, at least one phase to have a current load equivalent to 35% of the rated current of the CTs (20% in cases where two phases are powered). The unit ensures full operation with selfpowering, but by supplying 24 Vdc + 20% auxiliary power supply the unit can also be used with the circuit-breaker open or with the circuit-breaker closed, but with a single-phase current load of less than 35% of the rated current of the CTs. It is also possible to use an auxiliary power supply provided by the PR110/B portable battery unit (always supplied) which allows the protection functions to be set when the circuitbreaker is not self-powered. A wide range of setting options is available for the thresholds and trip times of all the functions. Functions S and G can operate with a time delay that is independent of the current (t = k) or with an inverse time delay (constant specific let-through energy: I2t = k), as required. Protection against ground faults can also be obtained by connecting the SACE PR112 to an external toroid located on the conductor which connects the transformer star centre to earth (homopolar toroid).
GSEM0074
I
All the thresholds and trip curve delays of the protection functions are stored in special memories which retain the information even if no power is supplied.
Protection functions
The SACE PR112 trip unit offers the following protection functions: overload (L) selective short-circuit (S) instantaneous short-circuit (I) ground fault (G). (Residual or Source ground return) by means of a toroid installed on the earthing connection of the main power supply. self-protection against excessive temperature rises.
Neutral adjustment
The external neutral protection is 50% of the value set for the phase protection in the standard version. A version with the neutral protection set to 100% is available on request (for E1, E2 and E3 only).
45
Protection functions and setting values of the SACE PR112/P-A trip unit
Function Limit values Threshold steps Trip time adjustment (s) Can be excluded Relation t = f (I) Thermal memory Zone selectivity
Overload protection
I1 = 0,41,0 x In
0,01xIn
NO
t = k/I2
YES (can be
excluded)
NO
I2 = 0,610 x In
0,1 x In
t2 = 0,0 et from 0,05 to 0,4 s with step 0,01 (With current I=10xIn) I = 10 x In t2 = from 0,05 to 0,4 s with step 0,01 Instantaneous trip
YES
t=k
NO
YES
(can be
excluded)
I2 = 0,610 x In
0,1 x In
YES
t = k/I2
YES (can be
excluded)
NO
I3 = 1,515,0 x In
0,1 x In
YES
t=k
NO
NO
0,02 x In
YES
t=k
NO
YES (can be
excluded)
0,02 x In
YES
t = k/I2
NO
NO
46
Mini0466a
In case of a temporary or continuous malfunction, the following two signals are activated: lighting up of the P Fault when there is auxiliary power supply, closure of the P Fault contact.
Test functions
Following enabling on the control menu, the TEST pushbutton on the front of the release (detail 4) allows correct operation of the chain consisting of the microprocessor, opening solenoid and circuit-breaker to be checked. Within the control menu there is also the possibility of testing correct operation of the display, signalling LEDs, magnetic signals and electrical contacts supplied in all the versions of the PR112 trip unit. By means of the front multi-pin connector (indicated by number 13), it is possible to apply a Test unit called SACE PR010/T which allows the functions of the SACE PR112 and PR111 trip units to be tested and checked.
Microprocessor self-diagnosis
The range of SACE PR112 trip units contains an electronic circuit which checks operation of the microprocessor of the protection unit in real time.
Emax0354x
13
47
0.4
0.6
1.5
7 8
10
10
6 4 1.5 2
10 12
15
t=k/I
0.01 0.1
0.2
0.3
0.4
1.2
1.5
7 8 9 10 12
15
20
0.4
1 0.6 1.5 2 3 4 5 6 7 8 10
6 4 1.5 2
10 12
15
t=k
0.1 0.06 0.04 0.02
GSEM0111b
48
0.01 0.1
0.2
0.3
0.4
1.2
1.5
7 8 9 10 12
15
20
0.2 0.2
0.3 0.3
0.4 0.4
0.5 0.5
0.7 0.7
1 1
t=k/I
t=k
0.02
GSEM00112b
0.01 0.1
0.2
0.3
0.4
1.2
1.5
7 8 9 10 12
15
20
49
User interface
Four pushbuttons and an enabling key with two positions (READ and EDIT) are used to consult the information available and the parameters set in the memory of the SACE PR112 (READ mode) or to program and configure the unit (EDIT mode) - all the choices are made using step-by-step menus.
A further two LEDs (9, 10) signal the following: P Fault: indicates that the protection unit microprocessor has a temporary (lit for a limited time) or permanent (lit for an unlimited time) fault Vaux: indicates there is an auxiliary power supply
10
Emax0350
7
50
Measuring function
The current measuring function (ammeter) is present on all versions of the SACE PR112 unit. The display shows the currents of the three phases, of the neutral and of the earth fault. The latter current value takes on two different meanings depending on whether the external toroidal transformer for the Source Ground Return function or the internal transformer (residual type) is connected. The ammeter can operate either with self-supply or with auxiliary power supply voltage. Accuracy of the ammeter measuring chain (current transformer plus ammeter) in the 30% - 120% current is + 5%.
Versions available
PR112/P-A (LSI)
Emax0375
PR112/P-A (LSIG)
51
The SACE PR010/T unit is an instrument able to carry out the Test, programming and parameter readout functions for the protection units which are fitted with SACE Emax low voltage power circuit-breakers. In particular, the Test function regards the following units: SACE PR112 (in all versions) SACE PR111 (in all versions) whereas the programming and parameter readout functions regard the SACE PR112 range of trip units. All the functions mentioned can be carried out ON BOARD by connecting the SACE PR010/T unit to the front multi-pin connector on the various protection units. Connection is ensured by special interfacing cables supplied as standard with the unit. The man-machine interface is ensured by the use of a membrane keyboard and a multi-line alphanumerical display. There are also two LEDs on the unit which signal the following respectively: POWER-ON and STAND BY situation state of battery charge Two different types of Test are provided: automatic and manual. By means of connection to a PC (with diskette supplied by ABB SACE), it is also possible to up-grade the SACE PR010/T unit software to adapt the Test unit as new products evolve. It is also possible to memorize the most important results of the test in the unit itself and to send them to the Personal Computer on a specific request for issue of report. In automatic mode (operation allowed with the SACE PR112 range), the SACE PR010/T unit can test the following: L, S, I protection functions; G protection function with internal transformer; G protection function with the toroid placed on the star centre of the transformer; monitoring of correct microprocessor operation. The same tests can be repeated manually for both the SACE PR111 and SACE PR112 ranges of trip units.
Emax0377
The SACE PR010/T unit is portable, operates with rechargeable batteries and/or with an external feeder (always provided) with 100-240 Vac / 12 Vdc rated voltage The SACE PR010/T unit includes the following in the standard supply: SACE PR010/T Test unit complete with rechargeable batteries SACE TT1 Test unit external 100 240 Vac/12 Vdc feeder connection cables between the unit and the multi-pin connector on the range of trip units which equip the SACE Emax series connection cable between the unit and the PC (RS232 serial) power supply cable instruction manual and diskette with application software plastic container.
52
CONTENTS Accessories
54
67
53
The table below shows some functions which can be obtained by making a suitable selection of the accessories provided. Several of the functions listed may be needed at the same
time depending on the use of the circuit-breaker. See the related section for a detailed description of the individual accessories.
Function
Remote control
Components
Shunt opening release Shunt closing release Geared motor for automatic charging of closing springs Auxiliary contacts of circuit-breaker open / closed Auxiliary contacts of circuit-breaker connected, isolated for test (for withdrawable circuit-breakers only) Contact for electrical signalling of overcurrent trip units tripped Contact for signalling undervoltage de-energised Contact for signalling springs charged Shunt opening or undervoltage release
Remote signalling or actuation of automatic functions depending on the state (open / closed) or isolated, or on the position (connected / isolated) of the circuit-breaker
Remote opening for various needs, including: manual emergency operation opening interlocked with operation of other switchgear or with plant automation requirements. Examples circuit-breakers on L.V. side of transformers in parallel that must open automatically when the M.V. side device opens automatic opening controlled by external relay (undervoltage, residual-current, etc.) Automatic opening of circuit-breaker due to undervoltage (as in the case, for example, of operation of asynchronous motors)
Instantaneous or time delay voltage release N.B. The time-delay device is recommended when unwarranted operation due to temporary voltage drops, is to be avoided (for functional or safety reasons). Contact for signalling undervoltage energised IP54 protective cover for door Key lock in open position Padlock device in open position Key lock and padlock device in connected, isolated for test, isolated position Mechanical interlock between two or three circuit-breakers
Increase in degree of protection Mechanical safety locks for maintenance or functional requirements for interlocking two or more circuit-breakers
54
Emax0450
Fixed circuit-breakers:
flange for switchboard compartment door (IP30) support for service releases four auxiliary contacts for electrical signalling of circuitbreaker open/closed (for circuit-breakers only) terminal box for connecting outgoing auxiliaries horizontal rear terminals lifting plate
Emax0448
Withdrawable circuit-breakers:
flange for switchboard compartment door support for service releases four auxiliary contacts for electrical signalling of circuitbreaker open/closed (for circuit-breakers only) sliding contacts for connecting outgoing auxiliaries horizontal rear terminals anti-insertion lock for circuit-breakers with different rated currents racking-out crank handle lifting plate device against racking-out with charged springs (Fail Safe)
55
Circuit-breaker version 1a) 1b) 2a) 2b) 3) 4a) 4b) 5a) 5b) 5c) 5d) 6a) 6b) 7) 8a) 8b) 8c) 8d) 8e) (*) For automatic circuit-breakers four auxiliary contacts for electrical signalling of circuitbreaker open/closed is included in the supply as standard. 56 9a) 9b) 10) Shunt opening/closing release (YO/YC) SOR Test Unit Undervoltage rerlease (YU) Time-delay device for undervoltage release (D) Geared motor for automatic charging of closing springs (M) Mechanical signalling of overcurrent trip units tripped Electrical and mechanical signalling of overcurrent trip units tripped Electrical signalling of circuit-breaker open/closed(*) Electrical signalling of circuit-breaker connected/ isolated for test/isolated Contact signalling closing springs charged Contact signalling undervoltage release energised (C.aux YU) Current transformer for neutral conductor outside circuit-breaker Homopolar toroid for main power supply earthing conductor (star centre of the transformer) Mechanical operation counter Lock in open position Circuit-breaker lock in connected/ isolated for test position / isolated Accessories for lock in isolated/ isolated for test position Accessorie for shutter padlock device Mechanical lock for compartment door Protection for opening and closing pushbuttons IP54 door protection Circuit-breaker interlock
Emax0295a
Fixed
Withdrawable
CAPTION: = Accessory on request on fixed or on moving part = accessory on request for fixed part = accessory on request for moving part
Electrical accessories
Power supply (Un): 24 V 30 V 48 V 60 V 110-120 V 125-127 V 220-240 V 250 V
Emax0369
380-400 V 440-480 V
Operating limits:
DC = 200 W AC = 200 VA DC = 5 W AC = 5 VA
(max) 60 ms (max) 80 ms
Emax0374
Maintenance of all functions of this accessory is a necessary condition to guarantee a high level of safety in the installation. This bring about the need to have a device available which cyclically checks correct operation of the release, signalling any malfunctions. The SACE SOR Test Unit allows continuity of the shunt opening release with a rated operating voltage between 24 V and 250 V (a.c. and d.c.) to be checked. Checking of continuity is carried out cyclically with an interval of 20s between one test and the next. The unit has visual signals by means of LEDs. The following information in particular is indicated:
Emax0370
POWER ON: power supply present YO TESTING: version of the test TEST FAILED: signal following a failed test or lack of auxiliary power supply
The circuit-breaker is opened with release power supply voltages equal to 30-60% Un. The circuit-breaker can be closed with a release power supply voltage equal to 85% Un.
Inrush power (Ps): DC = 200 W AC = 200 VA Continuous power (Pc) DC = 5 W AC = 5 VA Opening time (YU): 30 ms
250V AC
It can be fitted with a contact for signalling the undervoltage release is energised (C.aux YU) (see accessory 5d) Reference figure in circuit diagrams: YU (6)
Note: the use of an undervoltage release is not suitable when a Fail Safe device is present.
58
Emax0381
Emax0382
Reference figure in circuit diagrams: YU+D (7) It is always supplied with a limit contact and microswitch for signalling that the closing springs are charged (see accessory 5d). Reference figure in circuit diagrams: M (1)
59
5) Auxiliary contacts
Auxiliary contacts, installed on the circuit-breaker are available, which enable the state of the circuit-breaker to be signalled.
Un 125 Vdc 250 Vdc In max 0.3 A 0.15 A t 10 ms
Un 250 Vac
In max 5A
cos 0.3
5a) Electrical signalling of circuit-breaker open/closed It is possible to have electrical signalling of the state (open/ closed) of the circuit-breaker using 4, 10 or 15 auxiliary contacts. The auxiliary contacts have the following configurations:
4a) Mechanical signalling of overcurrent trip units tripped Where the circuit-breaker is open following operation of the overcurrent trip units, this can be signalled visually on the operating mechanism, moving the release tripped pushbutton out. The circuit-breaker can only be closed again by resetting the pushbutton to its normal position.
Emax0384
10 open/closed contacts (5 normally open + 5 normally closed); not available when the SACE PR112 overcurrent trip unit is required.
Emax0387
4b) Electrical and mechanical signalling of overcurrent trip units tripped Allows visual signalling on the operating mechanism (mechanical) and remote signalling (electrical using change-over contact) that the circuit-breaker is open following operation of the overcurrent trip units. The mechanical signalling pushbutton must be rearmed to reset the circuit-breaker. The SACE PR112 trip unit is already supplied with an internal overcurrent signalling contact. 60 Reference figure in circuit diagrams: S51 (12)
15 additional open/closed contacts for installation outside the circuit-breaker. The basic configuration described above may be modified by the user for normally open or normally closed indication by repositioning the faston connector on the microswitch. Reference figure in circuit diagrams: Q/110 (21-22)
Emax0380
Emax0389
5b) Electrical signalling of circuit-breaker connected/ isolated for test/isolated In addition to mechanical signalling of the circuit-breaker position, it is also possible to obtain electrical signalling using 5 or 10 auxiliary contacts which are installed on the fixed part. Only available for withdrawable circuit-breakers - for installation on the fixed part. The auxiliary contacts take on the following configurations: 5 contacts; set comprising 2 contacts for signalling connected, 2 contacts for signalling withdrawn and 1 contact for signalling test position (main pliers isolated, but sliding contacts inserted). 10 contacts; set comprising 4 contacts for signalling connected, 4 contacts for signalling withdrawn and 2 contacts for signalling test position (main pliers isolated, but sliding contacts inserted).
Emax0388
5c) Contact for signalling closing springs loaded Comprises a microswitch which allows remote indication of the state of the circuit-breaker operating mechanism closing springs. (Supplied as standard with spring-charging geared motor). Reference figure in circuit diagrams S33 M/2 (11)
5d) Contact signalling undervoltage release energised (C.aux YU) The undervoltage releases can be fitted with a contact (normally closed or open as preferred) for signalling undervoltage energised to provide remote signalling of the state of the undervoltage release. Reference figure in circuit diagrams: (12)
61
Mechanical accessories
Emax0386
6a) Current transformer for the neutral conductor outside the circuit-breaker
Only for three-pole circuit-breakers. Allows protection of the neutral by means of connection to the overcurrent release. (Can be supplied on request). Reference figure in circuit diagrams:TI/N-UI/N (51-52)
Emax0406
8) Mechanical locks
Emax0377
Emax0416
6b) Homopolar toroid for the main power supply grounding conductor (star centre of the transformer)
The range of SACE PR112 microprocessor-based electronic releases can be used combined with an external toroid located on the conductor which connects the start centre of the MV/LV transformer to earth (homopolar transformer). In this case, the protection to earth is defined as Source Ground Return. The homopolar transformer is proposed in four different versions in terms of rated current (but keeping the same overall dimensions in any case). Rated current 100 A, 250 A, 400 A, 800 A
8a) Lock in open position Several different mechanisms are available which allow the circuit-breaker to be locked in the open position. These devices can be controlled by: Key: a special circular lock with different keys (for a single circuit-breaker) or the same keys (for several circuit-breakers). In the latter case, up to four different key numbers are available. Padlocks: up to 3 padlocks (not supplied): 4 mm. Key with Kirk lock (arrangement only).
Emax0372
Emax0373
8b) Circuit-breaker lock in connected-isolated for test isolated This device can be controlled by a special circular lock with different keys (for a single circuit-breaker) or the same keys (for several circuit-breakers - up to four different key numbers available) and padlocks (up to 3 padlocks, not supplied - 4 mm). Only available for withdrawable circuit-breakers - for installation on the moving part.
8d) Accessory for shutter padlock device Allow the shutters (installed on the fixed part) to be padlocked in their closed position. Only available for withdrawable circuit-breakers - for installation on the fixed part.
Emax0415
8c) Accessories for locking in isolated - isolated for test position In addition to the circuit-breaker lock in the connected - isolated for test - isolated position, allows the circuit-breaker to be locked only in the isolated or isolated for test positions. Only available for withdrawable circuit-breakers - for installation on the moving part.
Emax0383
8e) Mechanical lock for compartment door Stops the compartment door from being opened when the circuit-breaker is closed (and circuit-breaker connected for withdrawable circuit-breakers) and locks closing of the circuitbreaker when the compartment door is open. 8f) Fail Safe device (against racking-out operations with springs charged) This prevents the moving part of the withdrawable circuitbreaker from being racked out of the fixed part when the closing springs are charged.
Note: the use of a Fail Safe device is not suitable when an undervoltage release is present.
63
9) Transparent protections
Emax0472
9a) Opening and closing pushbutton protection These protections are fitted over the opening and closing pushbuttons, preventing the relative circuit-breaker operations unless a special tool is used.
Emax0371
Emax0407
9b) IP54 door protection (NEMA 3/3S/13) This is a transparent plastic protective cover which completely protects the front panel of the circuit-breaker, and allows degree of protection IP54 to be achieved. Mounted on hinges, it is fitted with a key lock. 64
Interlocks
The mechanical interlocks possible are shown below linked to whether 2 or 3 circuit-breakers (any model in any version) are used in the switching system (also see chapter on Accessories).
Typical circuit
Interlocks possible
Circuit-breaker 1 can only be closed if 2 is open and vice versa
1 O I O
2 O O I
Type A
Between three circuit-breakers
O = Circuit-breaker open I = Circuit-breaker closed Circuit-breakers 1 and 3 can only be closed if 2 is open. Circuit-breaker 2 can only be closed when 1 and 3 are open.
1 O I O I O
2 O O O O I
3 O O I I O
Type B
Between three circuit-breakers
O = Circuit-breaker open I = Circuit-breaker closed One or two circuit-breakers out of three can be closed at the same time.
1 2 3
The two half-busbars can be powered by a single transformer (bus-tie closed) or by both at the same time (bus-tie open)
1 O I O O O I I
2 O O I O I I O
3 O O O I I O I
Type C
Between three circuit-breakers
O = Circuit-breaker open I = Circuit-breaker closed Only one of three circuitbreakers can be closed.
Three power supplies (generators or transformers) on the same busbar, so operation in parallel is not allowed
1 O I O O
2 O O I O
3 O O O I
Type D
ASEM0057
The emergency power supply is usually installed to take over from the normal power supply in two cases: to power health and safety services (e.g. hospital installations); to power parts of installations which are essential for requirements other than safety (e.g. continuous cycle industrial plants). The range of accessories for SACE Emax circuit-breakers includes solutions for a wide variety of different plant engineering requirements. Where devices for protection against overcurrents and direct and indirect contacts and the provisions aiming to improve reliability and safety of emergency circuits are concerned, see the relative standards. Switching from the normal to the emergency power supply can be carried out manually (locally or by remote control) or automatically. To this end, the circuit-breakers used for switching must be fitted with the accessories required to allow electric remote control and provide the electrical and mechanical interlocks required by the switching logic. These include: the shunt opening release the shunt closing release the motor operator the auxiliary contacts. The switching function can be automated using a suitable electronicallycontrolled relay circuit, to be installed by the customer (circuit diagram supplied by ABB SACE L.V.). The mechanical interlocks between two or three circuit-breakers are created using cables which are suitable both for horizontally and vertically installed circuit-breakers.
66
Spare parts
Spare parts
Front metal shields and escutcheon plate Opening solenoid for SACE PR111 - PR112 overcurrent trip unit Arcing chamber Closing springs Plier isolating contact for fixed part of withdrawable circuitbreaker Sliding grounding contact (for withdrawable version) Shutters for fixed part Complete pole Control device Cables for connecting trip units and current transformers to each other Transparent guard for trip units SACE PR110/B power supply unit.
67
68
70
74
82
83
69
Overall dimensions
Fixed circuit-breaker
Version with horizontal rear terminals
E1
E2 E3
Caption 1 Insulating wall or insulated metal wall
E4 E6
A E1-A E2-A E3-A E4-A E6-A 296/11.65'' 296/11.65'' 404/15.91'' 566/22.28'' 782/30.79''
70
Fixed circuit-breaker
Version with horizontal rear terminals
E1/E2
E4
E3
E6
Caption 1 Inside edge of compartment door 2 Segregation (when provided) 3 M10 mounting holes for circuit-breaker (use M10 screws) 4 1 x M12 screw for grounding (supplied as standard)
71
Overall dimensions
Fixed circuit-breaker
Version with vertical rear terminals
E1
E2 E3 (1200...2000A)
E1
E2
72
Fixed circuit-breaker
Version with vertical rear terminals
E3 (2500A)
E4 E6
E3 (2500A)
E4
E6
73
Overall dimensions
Withdrawable circuit-breaker
Version with horizontal rear terminals
E1
E2 E3 E4 E6
Caption 1 Travel from test connected to disconnected
A E1-A E2-A E3-A E4-A E6-A 324/12.76'' 324/12.76'' 432/17.01'' 594/23.39'' 810/39.89''
74
Withdrawable circuit-breaker
Version with horizontal rear terminals
E1 E2
E3
Vista A - View A
E4
E6
Caption 1 Inside edge of compartment door 2 Segregation (where provided) 3 M8 mounting holes for circuit-breaker (use M8 screw) 4 1 x M12 screw for grounding (supplied as standard)
75
Overall dimensions
Withdrawable circuit-breaker
Version with vertical rear terminals
E1 E2
E3
E4 - E6
A E1-A E2-A E3-A E4-A E6-A 324/12.76'' 324/12.76'' 432/17.01'' 594/23.39'' 810/39.89''
76
Withdrawable circuit-breaker
Version with vertical rear terminals
E1 E2
E1 E2
Caption 1 Inside edge of compartment door 2 Segregation (when provided) 3 M8 mounting holes for circuit-breaker (use M8 screws) 4 2 x M12 screw for grounding (supplied as standard) 5 Travel from test connected to disconnected
77
Overall dimensions
Withdrawable circuit-breaker
Version with vertical rear terminals
E3 (2500 A)
E4
E3 (2500 A)
Caption 1 Inside edge of compartment door 2 Segregation (when provided) 3 M8 mounting holes for circuit-breaker (use M8 screws) 4 2 x M12 screw for grounding (supplied as standard) 5 Travel from test connected to disconnected
E4
78
Withdrawable circuit-breaker
Version with vertical rear terminals
E6
Caption 1 Inside edge of compartment door 2 Segregation (when provided) 3 M8 mounting holes for circuit-breaker (use M8 screws) 4 2 x M12 screw for grounding (supplied as standard) 5 Travel from test connected to disconnected
79
Overall dimensions
Dimensions of compartment
Copper bars
Insulating support
A E1-A E2-A E3-A E4-A E6-A 400/15.7'' 400/15.7'' 500/19.7'' 700/25.7' 1000/39.3''
Suitable for continuos operation at 100% rating in a minimum cubicle space (see the table), with a ventilation of 48 (12x4) sq. in. side bottom and side top. Refer to shop drawings for verification.
80
Withdrawable version
Fixed version
81
Overall dimensions
5 6 6 5 6
Type A
Horizontal Vertical
Type B
(emergency interlock underneath) Horizontal Vertical
Type B
(emergency interlock in middle) Horizontal Vertical
Type B
(emergency interlock above) Horizontal Vertical
Type C
Horizontal Vertical
Horizontal interlocks
5 6
Notes
When fitting interlocks between two circuitbreakers one has to make suitable holes (through the switchboard) in the mounting surface for fixed circuit-breakers or for the fixed part of withdrawable circuit-breakers in order to pass through the flexible cables, respecting the measurements shown in the figures on page 81. For vertical interlocks, align the right-hand sides vertically and reduce the bends in the flexible cables to a minimum (radius R. 70 mm). All the angle values of the bends which the cable passes through added together must not exceed 720.
Maximum distance between two interlocks 1200 mm from one interlock to the other. The cables pass under the fixed parts, following the same connection layout shown for vertical circuitbreakers.
Take up the excess cable by making it go through one complete turn only or an omega as shown in the figure.
Type D
Horizontal Vertical
82
Circuit-breaker accessories
Compartment door mechanical interlock
Holes in compartment door Minimum distance between circuit-breaker and switchboard wall
31,5/1.24
X
20/0.79
180 7.09
6/0.24
73.5/2.89
35/1.38
Fixed version
Withdrawable version
Homopolar toroid
E1 - E2 - E4
E3 - E6
83
Overall dimensions
A flexible cable 600 mm (26.3 in) long is available from point "A" to point "B"
250 9.84
250 9.84
50,5/1.99
50,5/1.99
Fixed version
Withdrawable version
84
86
87
88
85
Versions
The circuit diagrams show withdrawable circuit-breakers but are also valid for fixed circuit-breakers.
Fixed version
The control circuits are between terminals XV (connector X is not supplied). With this version, the applications indicated in figures (31, 32, 51) cannot be provided.
Withdrawable version
The control circuits are between the poles of connector X (terminal box XV is not supplied). With this version, the application indicated in figure (52) cannot be provided.
86
Emax0341
Mechanical connection
Switch-disconnector
M
IEC 617 02-13-01 IEC 617 06-04-01 IEC 617 07-13-08
Current transformer
Pushbutton control
Equipotential
Make contact
Galvanicallyseparated converter
IEC 617 02-17-06/02-17-07
Break contact
Conductor connections
Current sensor
87
L1
L2
L3
PE
L1
L2
L3
Q
T11
K51 XK1
T11 T12 T21 T22 T31 T32 T41 T42 T12 T21 T22 T31 T32 T41 T42
XO
1 1 4 3 2 1
Y01 XO
2 2
TI/O
XK
T13 T13 T14 T23 T24 T33 T34 T43 T44 PR111
(*G)
XK1
T5 T6
GSEM0077x
XV
T5 T6 T5 T6
X
T5 T6
PR112/P
88
(*B)
(*B)
Control circuits
External circuit
Closing release
Opening release
SC
SC
S43
SO
SO
S43
SO
SO
U1 U1
C1
C1 C1
C1
C1 C1
C3
C3 C3
C11
C11 C11
C11
C11 C11
C13
C13 C13
D1
D1 D1
D1
D1 D1
XK3 K51 YC
28
14
Internal circuit
XK3 X1 1 X3 1 X3 1
26
16 X5 1 X5 1
2 3 1 4 5 6 7
S33M/1
M
X1
U2
YC
2 X3
C2
YC
2 X3
C2
YO
2 X4
C12
YO
2 X4
C12
YU
X5
D2
YU
2 X5
D2
GSEM0078
U2 U2
C2 C2
C2 C2
C12 C12
C12 C12
D2 D2
D2 D2
External circuit
(*B)
13
21
22
Signalling contacts
External circuit
Signalling circuitFirst set of circuitbreaker open due to breaker auxiliary overcurrent release contacts trip
37 37
D13
D13 D13
96
96 96
98
98 98
13
13 13
11
11 11
23
23 23
21
21 21
33
33 33
31
31 31
43
43 43
41
41 41
53
53 53
51
51 51
21 22
Internal circuit
X2
X6
X7
11 13
S33M/2
YU
S51
Q/1
Q/2
Q/3
Q/4
Q/5
Q/6
Q/7
Q/8
Q/9
Q/10
X2
GSEM0078
X6
X7
D14
95
14
12
24
22
34
32
44
42
54
38
52
12
38 38
D14 D14
95 95
14 14
12 12
24 24
22 22
34 34
32 32
44 44
42 42
54 54
52 52
External circuit
89
(*) See note indicated by the letter on page 93
31
32
Signalling contacts
External circuit
104
104 112
112
124
124
134
134
142
142
154
154
162
162
174
174
184
184
192
192
31 32
4 2 S75I/1 S75I/2 1
4 2 S75I/4 1
Fixed part
2 4
GSEM0079
101
111
121
131
141
151
161
171
181
101
111
121
131
141
151
161
171
181
191
191
External circuit
(*F)
Protection unit
External circuit
(*F)
Uaux. 24V
K1 K1
K1 K2
K2 K2
K3
K3 K3
K5
K5 K5
K7
K7 K7
K9
K9 K9
K10
K10 K10
XK2
XK2
XK3
22
XK3
18
XK3
XK2
16
XK2
15
41
Internal circuit
K51 P
K51 pL
K51 YO1
K51 Zin
K51
XK3
GSEM0079
24
XK3
20
XK3
30
XK2
XK2
10
XK2
19
XK2
K4 K4
K6 K6
K8 K8
K11 K11
W3 W3
W4 W4
CC2
K11
W3
W4
K4
K6
K8
CC2 CC2
External circuit
( A ) ( B )( )
90
(*) See note indicated by the letter on page 93
W2
Three-pole circuit-breaker with SACE PR111 or PR112/P release and current transformer on external neutral conductor
51
52
(*C
PE N
104 TI/N
104 112
112
124
124
134
134
142
142
4 2 UI/N S75I/1
101
4 2 S75I/2
111
2 4 S75E/2
121
2 4 S75R/1
131
2 4 S75R/2
141
L1
L2
L3
1 101
1 111
1 121
1 131
1 141
K51
PE L1 L2 L3 N
Q TI/L1 TI/L2 T11 T12 T21 T22 T31 T32 T13 T14 T23 T24 T33 T34
TI/O
4 3 2 1
TI/L3
XK1 T11 T12 T21 T22 T31 T32 XK1 T13 T14 T23 T24 T33 T34 PR111
T1
T2
T1
T2 T1
T42
T2
XO 1
T2
T43
X XV XK1 T5 T T5 T5 T5 T5 T T6 T6 T6
T3 T3 PR112/P
T3 T4 T3 T4
T44
T4
T4
(*G)
GSEM0081x
External circuit Fixed part terminal box Fixed part circuit Connector Internal circuit Terminal
91
Caption
D K51 = Electronic time-delay device for undervoltage release, outside circuit-breaker = PR111 or PR112/P microprocessor-based overcurrent release with the following protection functions(see note on page 93) S75E/14 = Contacts for electrical signalling of circuit-breaker in withdrawn position (for withdrawable circuit-breakers only) S75R/14 = Contacts for electrical signalling of circuit-breaker in racked-out position (for withdrawable circuit-breakers only) SC SO short-circuit protection with inverse or defi nite short time-delay trip - setting I2 short-circuit protection with instantaneous time-delay trip - setting I3 ground-fault protection with inverse short timedelay trip - setting I4 TI/L1 TI/L2 TI/L3 TI/N TI/O = Pushbutton or contact for closing the circuit-breaker = Pushbutton or contact for opening the circuit-breaker = Current transformer located on phase L1 = Current transformer located on phase L2 = Current transformer located on phase L3 = Current transformer located on neutral = Homopolar current transformer, located on the conductor connecting the star centre of the MV/LV tranformer to earth (see note G) = Current sensor (Rogowski coil) located on phase L1 = Current sensor (Rogowski coil) located on phase L2 = Current sensor (Rogowski coil) located on phase L3 = Current sensor (Rogowski coil) located on neutral = Auxiliary power supply (see note F) = Serial interface with the control system (external bus): EIA RS485 interface (see note E) = Serial interface with the accessories of the PR112/P release (internal bus) = Delivery connector for auxiliary circuits of withdrawable version circuit-breaker = Connectors for circuit-breaker applications = Delivery terminal board for the position contact of the withdrawable circuit-breaker (applied to the fixed part of the circuit-breaker) = Connector for the power circuits of PR111 and PR112/ P releases
L S I G
K51/YO1 K51/Zin
= Electrical signalling of alarm due to tripping of release YO1 (for PR112/P release only) = Zone selectivity: input (with Uaux and PR112/P releases only)
K51/Zout = Zone selectivity: output (with Uaux and PR112/P release only) K51/pL K51/P M Q Q/110 S33M/1 S33M/2 S43 S51 = Electrical signalling of protection function L in prealarm zone (with Uaux and PR112/P release only) = Electrical signalling of alarm due to microprocessor operating faults (with Uaux and PR112/P releases) = Motor for charging the closing springs = Circuit-breaker = Auxiliary contacts of the circuit-breaker = Limit contact of spring-charging motor = Contact for electrical signalling of springs charged = Change-over contact for setting remote/local control = Contact for electrical signalling of circuit-breaker open due to tripping of the overcurrent release. The circuitbreaker can only be closed after the reset pushbutton has been pressed
XK1
XK2, XK3 = Connector for the auxiliary circuits of PR112/P release XO XV YC YO YO1 YU = Connector for release YO1 = Delivery terminal board for auxiliary circuits of fixed version circuit-breaker = Shunt closing release = Shunt opening release = Overcurrent shunt opening release = Undervoltage release (see note B)
S75I/14 = Contacts for electrical signalling of circuit-breaker in connected position (for withdrawable circuit-breakers only)
92
Incompatibility
The circuits shown in the following figures cannot be provided on the same circuit-breaker at the same time: (2 - 3) (4 - 5) (6 - 7) (22 - 41 - 42) (31 - 51) (51 - 52) Notes A) The circuit-breaker is only fitted with the applications specified in the ABB order acknowledgement. B) The undervoltage release is supplied for operation using a power supply branched on the supply side of the circuit-breaker or from an independent source. The circuit-breaker can only close when the release is energized (there is a mechanical lock on closing). If the same power supply is used for the closing and undervoltage releases and one wants automatic closing of the circuit-breaker on return of the auxiliary power supply, it is necessary to insert a 30 millisecond delay between the undervoltage release accept signal and energisation of the closing release. This can be obtained using a circuit outside the circuitbreaker which comprises a permanently closed contact, the contact indicated in figure (12) and a time-delay relay. C) For fixed circuit-breakers with current transformers on the neutral conductors outside the circuit-breakers, the terminals of transformer TI/N must be short-circuited when one wants to remove the circuit-breaker. D) Connect contact S33M/2 shown in Fig. (11), one of the make contacts and one of the break contacts of the circuit-breaker shown in Fig. (21) and one of the S75I contacts shown in Fig. (31) or (51) as shown in Fig. (42). On fixed circuit-breakers, connect terminal XV-K14 directly to terminal XV-K16 (contact S75I does not exist). E) See the following documents on how to connect the EIA RS485 serial line: examples of EIA RS485 serial communication distribution = 401517 prescriptions for laying EIA RS485 serial communication cable = 601823. F) Auxiliary voltage Uaux. is necessary to guarantee that the following functions of SACE PR112/P releases will operate correctly even without self-supply (primary currents lower than 0.35 In): current measurement protection against earth fault and relative signals K51/p and K51/pL signals The presence of a primary current > 0.35 In on at least one phase fitted with current transformer guarantees the correct operation of all protection and measurement functions. G) Ground fault protection is available with the PR112/P release by means of a current transformer located on the conductor connecting the star centre of the MV/LV transformer. The connection between terminals 1 and 2 of the TI/O current transformer and poles T5 and T6 of connector X must be made with a two-pole shielded and corded ABB SACE L.V. type T54602 cable with a length not exceeding 5 m. The shield must be grounded on the circuitbreaker side.
93
Due to the continuous development of Standards and materials, the specifications and dimensions in this catalogue may only be considered binding on confirmation by ABB Control. 94