Low Voltage

Interpact
Switch-disconnectors INS/INV40 to 2500 A

Catalogue 2011

Interpact INS/INV

Contents

Presentation

Functions and characteristics

A-1

Installation recommendations

B-1

Dimensions and connection

C-1

Complementary technical information

D-1

Catalogue numbers

E-1

Presentation

Who else offers such from 40 to 2500 A?


0564a-7 0568_L5_SE

Switch-disconnectors with positive contact indication

Switch-disconnectors with visible break

05903_L5_SE

0590a-_SE

Emergency-off switch-disconnectors with positive contact indication

Emergency-off switch-disconnectors with visible break

The complete range Modular profile

40 A 63 A
INS40 INS63

80 A

100 A 125 A 160 A

056654_L5_SE

Interpact INV

05665_L5_SE

Interpact INS

056650_L6_SE

Interpact INV

056648_L6_SE

Interpact INS

200 A

250 A

INS80PV INS100 INS125 INS160

INS250-100

INS250-160 INS250-200 INS250

Mounting on backplate

INV100

INV160

INV200

INV250

... in a wide range


PB100016a-7_SE PB100020a-8_SE 059487_L0_SE

PB100017a-7_SE

320 A

400 A

500 A

630 A

PB100019a-7_SE

05949_L0_SE

PB100018a-7_SE

059489N_L0_SE

800 A

1000 A

1250 A

PB100021a-8_SE

059491_L0_SE

1600 A

2000 A

2500 A

INS320 INV320

INS400 INV400

INS500 INV500

INS630 INS630b INV630 INV630b

INS800 INV800

INS1000 INV1000

INS1250 INV1250

INS1600 INV1600

INS2000 INV2000

INS2500 INV2500

Presentation

Who else covers

678a-7

b Current ratings: up to 63 A for commercial and 630 A for industrial applications v Schneider Electric switch-disconnectors v NG125NA, Interpact INS40 to 160 and I modular switches v Interpact INS/INV v Schneider Electric switch-disconnectors b Vario 12 to 175 A.

Local isolation enclosures

E9069a-3_50dpi_SE

b Current ratings: up to 63/80 A b Schneider Electric switch-disconnectors: v Interpact INS b Schneider Electric switch-disconnectors v Vario.

Control panels

Local isolation Industrial or commercial Final distribution Sub-distribution Power distribution

DB068

E4506_3_SE

Sub-distribution boards

b Current ratings: up to 160 A b Schneider Electric switch-disconnectors: v Interpact INS/INV v NG125.

so many applications?

PD395007_L70_SE

b Current ratings: up to 400 A b Schneider Electric switch-disconnectors: v Interpact INS/INV.

Industrial switchboards and automatic control panels

E907_04_SE

b v v b v v

Main power distribution boards for commercial and industrial applications


Current ratings: 400 to 1000 A for commercial applications 400 to 1600 A for industrial applications Schneider Electric switch-disconnectors: Interpact INS/INV Masterpact NA/HA/HA10/HF.

Presentation

Who else offers such

INS/INV switch-disconnectors:
INS
056648_L8_SE

INS40 INS63 INS80 INS100 INS125

INV Ith at 60 C 40 63 690 8 80 690 8 00 750 8 5 750 8

Ui CA 50/60 Hz/CC (V) 690 Uimp (kV) 8

INS/INV switch-disconnectors:
INS
056650_L8_SE

INS40 INS63 INS80 INS100 INS125 40 40 3 63 63 40 80 7 40 00 00 00 00 63 5 5 5 5 80

Ue AC22A 380/415 V Ue AC22A 660/690 V Ue AC23A 380/415 V

DB068

Ue AC23A 500/525 V Ue AC23A 660/690 V

(1) 1600 A at 45 C and 1450 A at 60 C. (2) Ue AC22A / AC22B. (3) Ue AC22B.

Source changeover systems:

Standards and certifications:


The Interpact INS/INV range complies with international standards, as officially certified by an independent organisation. IEC 60 947-1, IEC 60 947-3 EN 60 947-1, EN 60 947-3 Conformity with UL and CSA standards Special versions of Interpact switch-disconnectors are available that comply with UL and CSA standards for moulded case switches. UL489 and CSA C22.2 No. 5-02
E95578

DB07389

high performances and safety?

... for high industrial performance


INS160 INS250- INS250- INS250- INS250 100 160 200 INV100 60 750 8 00 750 8 INV160 60 750 8 INV200 00 750 8 INV250 50 750 8 INS320 INV320 30 750 8 INS400 INV400 400 750 8 INS500 INV500 500 750 8 INS630 INV630 630 750 8 INS630b INS800 INV630b INV800 630 750  800 000  INS1000 INS1250 INS1600 INS2000 INS2500 INV1000 INV1250 INV1600 INV2000 INV2500 000 000  50 000  600 () 000  000 000  500 000 

... for maximum operational voltage


INS160 INS250- INS250- INS250- INS250 100 160 200 60 60 60 60 00 00 00 00 00 00 60 60 60 60 60 00 00 00 00 00 50 50 50 50 50 INS320 INS400 INS500 INS630 INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500 450/ 600 (2) 50/ 600 (2) 50 50 50 30 30 30 30 30 400 400 400 400 400 500 500 500 500 500 630 630 630 630 630 630 630 630 630 630 800 800 800 800 800 000 000 000 000 000 50 50 50 50 50 000 (3) 000 (3) 500 (3) 500 (3) -

Identical performance up to 500/690 V

... from 100 to 630 A, with identical performance

b The entire range has been fully certified IEC 60947-1, IEC 60947-3 and EN 60947-1, EN 60947-3. Certification was carried out within the framework of the LOVAG agreement by independent certification organisations b Marine certification is underway

b Certain ratings are UL listed (UL 489 listed for the switch part) for markets requiring such certification.

Presentation

Designed to work

INS for positive contact indication and INV for visible break
A mechanical system ensures that the position of the handle always reflects the position of the main contacts. With positive contact indication, Schneider Electric guarantees optimum safety for all users of the Interpact range. The physical separation of the main contacts is directly visible through a transparent cover. With this visible break function in addition to positive contact indication, the Interpact INV range offers double safety.
059487N_L36_SE 05949N_L36_SE 056660a-7_SE

Rotary, front and lateral handles... a very wide choice.


E9076a-34_SE 056650_L8_SE 056656a-4_SE

059487_L3_SE

Specially design handles for easy operation


The interruption of current flowing in high-power circuits is associated with high mechanical forces within small volumes. To facilitate the operation of the Interpact range of switch-disconnectors, Schneider Electric has paid particular attention to the design of the handles. As a result, the Interpact range offers both high performance and easy operation.
DB8004a_L47_SE

059495_SE_L3

the way you work

One-piece spreader
INS and INV devices may be equipped with a spreader corresponding to the pitch of the terminals of the next highest frame size, just like Compact NS devices. This one-piece spreader offers improved accessibility and ensures a uniform electrical installation. It may be fitted with all the connection and isolation accessories of the Compact NS device with the next highest frame size.
056384a-56 055994a-76_SE

Presentation

Manual sourcechangeover systems:

b Easy installation b Built-in safety b Automatic interlocking b Simple operating mechanism

0

solutions for continuous performance

The complete source-changeover assembly makes it possible to transfer between a normal source (N) and a replacement source (R) using a single operating handle



Presentation

A complete offering

DB7444



for all your needs

Power distribution incomers and coupling devices


PB06363A35_L49 PB0006b-47_SE E4579_43_SE

Masterpact NW25HA.

Interpact INS2000.

Compact NS1600NA.

Sub-distribution incomers
PB0486 PB0484 PB00840_L43_SE 056650_L30_SE 056908N_L8_SE

Compact NSX400NA.

Compact NS400NA.

Interpact INS630 complete sourcechangeover assembly.

Interpact INV400.

NG125.

Final distribution outgoers and local isolation and control devices


PB0485 PB0050b-7 E909b-9_SE PB0487 059489N_L5_SE 056908N_L8_SE 056738_L3_SE

Compact NSX250NA.

Compact NS250NA.

Interpact INV250.

NG125.

Interpact INS80.

Vario.

Multi 9.

3

TOOLS
schneider-electric.com The technical guide

This international site allows you to access all the Schneider Electric products in just  clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts

These technical guides help you comply with installation standards and rules i.e.: the electrical installation guide, the protection guide, the switchboard implementation guide, the technical booklets and the co-ordination tables all form genuine reference tools for the design of high performance electrical installations. For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.

Interpact INS/INV

Functions and characteristics

Presentation

General characteristics Specific application Switch-disconnector selection


Interpact INS40 to 60 Interpact INS50-00 to 630 Interpact INS630b to 500 Interpact INV00 to 630 Interpact INV630b to 500

A-2 A-5 A-6


A-6 A-0 A-4 A-8 A-3

Complete source-changeover assembly selection


Interpact INS50-00 to 630

A-26
A-6

Switch-disconnector selection
Interpact INS40 to 80 Interpact INS00 to 60 Interpact INS50-00 to 630 Interpact INV00 to 630 Interpact INS30 to 630 Interpact INV30 to 630 Interpact INS630b to 600 Interpact INV630b to 600 Interpact INS000 to 500 Interpact INV000 to 500

A-30
A-30 A-3 A-3 A-3 A-33 A-33 A-34 A-34 A-35 A-35

Electrical and mechanical accessories Manual source-changeover systems Connection accessories Installation
Installation recommendations Dimensions and connection Complementary technical information Catalogue numbers

A-36 A-40 A-42 A-52


B-1 C-1 D-1 E-1

A-

Functions and characteristics

General characteristics

Conformity with standards


INS 250-200A interpact

Ui 750V 50/60Hz IEC 947.3 Uimp 8kV CEI UTE Ith 200A/60C UNE VDE BS
AC22A AC23A DC23A

Ue (V) 690 Ie (A) 200

690 200

250 (4P) 200

Ith: Ui: Uimp: Ue: Ie:

conventional thermal current. rated insulation voltage. rated impulse-withstand voltage. rated operational voltage. rated operational current. suitable for isolation.

Interpact switch-disconnectors and auxiliaries comply with the following standards and international recommendations: b IEC 60947-: general rules b IEC 60947-3: switches, disconnectors, switch-disconnectors, etc. b IEC 60947-5. and following: control-circuit devices and switching elements; automatic-control components. In that these standards and recommendations are applied in most countries, Interpact switch-disconnectors and auxiliaries comply with European (EN 60947-, EN 60947-3, EN 60947-5-) and the corresponding national standards: b France NF b Germany VDE b United Kingdom BS b Australia AS b Italy CEI. Interpact switch-disconnectors are suitable for the control of machine-tools in that they comply with French standard NF C 79-30 and with the recommendations issued by the CNOMO organisation.

DB409

Installation in class II switchboards


All Interpact INS and INV switch-disconnectors are class II front-face devices. They may be installed through the door of class II switchboards (as per standard IEC 60664) without downgrading switchboard insulation. Installation requires no special operations even when the switch-disconnector is equipped with rotary handles.

Environmental withstand capacity (tropicalisation)


Interpact INS/INV switch-disconnectors meet the environmental requirements of the following standards: b IEC 60068-- - dry cold (-55 C) b IEC 60068-- - dry heat (+85 C) b IEC 60068--30 - damp heat (95 % relative humidity at +55 C) b IEC 68--5 (level ) - salt mist.

Degree of pollution
The Interpact range is certified for operation in pollution-degree 3 environments as defined by IEC standard 60947 for industrial environments.

Ambient temperature
Operating-temperature range b Interpact INS and INV switch-disconnectors may be used between -5 C and +70 C. b Switch-disconnectors should be put into service under the normal, ambient operating temperatures indicated above. Exceptionally, they may be put into service when the ambient temperature is between -35 C and -5 C. Storage-temperature range Interpact INS and INV switch-disconnectors may be stored in their original packing between -50 C and +85 C.

Environmental protection
Interpact INS and INV switch-disconnectors take into account important concerns for environmental protection. Most components are recyclable. Insulating parts making up the Interpact INS and INV switch-disconnectors are marked as specified in applicable environmental standards.

A-

Functions and characteristics

General characteristics

Altitude
Interpact INS and INV switch-disconnectors are designed to operate at their rated values at altitudes under 000 metres. Above 000 metres, the changes in the characteristics of the ambient air (electrical resistance, cooling capacity) result in a reduction of the characteristics below. Altitude (m)
Dielectric resistance voltage (V) Rated insulation voltage (V) Maximum utilisation voltage (V) Rated current (A) at 60 C

2000
3500 750 690  x In

3000
350 700 550 0.96 In

4000
500 600 480 0.93 In

5000
00 500 40 0.9 In

Vibrations
Interpact INS and INV switch-disconnectors are guaranteed against electromagnetic or mechanical vibrations. Tests are carried out in compliance with standard IEC 68--6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyds, etc.): b  to 3. Hz: amplitude  mm b 3. to 00 Hz: constant acceleration 0.7 g. Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts.

Electromagnetic compatibility
Interpact INS and INV switch-disconnectors are protected against: b overvoltages caused by devices that generate electromagnetic disturbances b overvoltages caused by atmospheric disturbances or by a distribution-system outage (e.g. failure of a lighting system) and devices emitting radio waves (radios, walkie-talkies, radar, etc.). Interpact INS and INV switch-disconnectors comply with the following electromagnetic-compatibility standards: b IEC/EN 6000-4- - electrostatic immunity discharge test b IEC/EN 6000-4-3 - electromagnetic-field immunity test b IEC/EN 6000-4-4 - electrical fast transient/burst immunity test b IEC/EN 6000-4-5 - surge immunity test b IEC/EN 6000-4-6 - immunity to conducted disturbances, induced by radiofrequency fields b CISPR  - radio-frequency conducted and radiated emission tests required for CE marking v EN 6000-6- - immunity standard for industrial environments v EN 5008-- - emissions in commercial and industrial environments.

Degree of protection
Interpact INS and INV switch-disconnectors offer the following protection characteristics depending on the installation conditions: b IP: degree of protection (standard IEC 6059) b IK: protection against external mechanical impacts (standard EN 500). IP40 IK07
DB05443 DB05444

IP40 IK07
DB05445

IP55 IK08

Bare switch-disconnector with terminal shields.

Switch-disconnector in cabinet or enclosure (direct handle).

Switch-disconnector in cabinet or enclosure (extended handle).

A-3

Functions and characteristics

General characteristics

Suitable for isolation with positive contact indication


059487N_SE_L49 DB05438

All Interpact switch-disconnectors are suitable for isolation as defined in IEC standards 60947- and 3: b the isolation position corresponds to the O (OFF) position b the operating handle cannot indicate the OFF position unless the contacts are actually open b padlocking in the OFF position is not possible unless the contacts are actually open. Installation of an extended handle does not alter the suitability for isolation. The isolation function is certified by tests guaranteeing: b the mechanical reliability of the position-indication system b the absence of leakage currents b overvoltage withstand capacity between upstream and downstream connections.

Suitable for isolation with positive contact indication.

05949N_SE_L49

Suitable for isolation with visible break


The physical separation of the main contacts is directly visible through a transparent cover. The Interpact INV range offers both positive contact indication and visible break.

Suitable for isolation with visible break.

Emergency-off switch disconnector


This switch-disconnector can be used as an emergency-off device. For this application, it must be easily visible, accessible and identifiable (see standards and rules concerning the safety of machines VDE 0660, VDE 03, CNOMO, etc.). For easy identification, the emergency-off switch-disconnector uses special colours stipulated by the standards and different from those of the standard version: b yellow for the front face of the device b red for the handle. The electrical and mechanical performance characteristics of Interpact emergencyoff switch-disconnector are the same as those of the standard version. The emergency-off switch-disconnectors are available in positive contact indication and visible-break versions.
05665_SE_L-47

INS250 emergency-off switch-disconnector.

056654_SE_L47

INV250 emergency-off switch-disconnector.

A-4

Functions and characteristics

Specific application
Photovoltaic

PB0485_50

No matter the size or scale of the project, Schneider Electric TM, has a photovoltaic solution to fit your needs. Fast ROI, high efficiency its all a part of our offer as the world leader in energy management. The INS PV- is a direct current switch disconnector dedicated to array isolation and control with Voc until 600 V DC.

Product used
Description Current INS PV- switch disconnector 40 A Reference 28907 Weight (kg) 0.657

Interpact INS PV-1.

PB04853

A-5

Functions and characteristics

Switch-disconnector selection
Interpact INS40 to 160

Interpact INS switch-disconnectors


0564b-38_SE

Number of poles

Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3


Conventional thermal current (A) Conventional thermal current in enclosure Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Interpact INS80 switch-disconnector. Ith Ithe Ui Uimp Ue at 60 C at 60 C AC 50/60 Hz AC 50/60 Hz DC AC 50/60 Hz Electrical AC 50/60 Hz 0-40 V 380-45 V 440-480 V (1) 500 V 660-690 V Electrical DC 5 V (P in series) 50 V (4P in series) Electrical AC 50/60 Hz 0-40 V 30 V (NEMA) 380-45 V 440 V 480 V (NEMA) 500-55 V 660-690 V Uninterrupted duty Intermittent duty Min. (switch-disconnector alone) Max. (with upstream protection circuit breaker) s 3s 0 s 30 s Mechanical Electrical AC 50/60 Hz 0-40 V 380-45 V 440 V 500 V 690 V Electrical DC 50 V

Rated operational voltage AC0 and DC0 (V) Rated operational current (A) Ie

05903_L45_SE

Rated operational power AC3 (kW)

Interpact INS40 emergency-off switch-disconnector.

Rated duties
0568_L50_SE

Short-circuit making capacity (kA peak)

Icm

Short-time withstand current (A rms)

Icw

Suitability for isolation Durability (O-C cycles)

Interpact INS160 switch-disconnector.

0590_L50_SE

Positive contact indication Visible break Emergency-off switch disconnector Degree of pollution

Upstream protection
See the Complementary technical information page D-. (1) Suitable for 480 V NEMA.

Interpact INS160 emergency-off switch-disconnector.

A-6

Functions and characteristics

Switch-disconnector selection
Interpact INS40 to 160

INS40
3-4

INS63
3-4

INS80
3-4

INS100
3-4

INS125
3-4

INS160
3-4

40 40 690 8 500 50 690 AC22A 40 40 40 40 DC22A 40 40

AC23A 40 40 40 3 DC23A 40 40

63 63 690 8 500 50 690 AC22A 63 63 63 63 DC22A 63 63

AC23A 63 63 63 40 DC23A 63 63

80 80 690 8 500 50 690 AC22A 80 80 80 80 DC22A 80 80

AC23A 80 7 63 40 DC23A 80 80

00 00 750 8 690 50 750 AC22A 00 00 00 00 00 DC22A 00 00

AC23A 00 00 00 00 63 DC23A 00 00

5 5 750 8 690 50 750 AC22A 5 5 5 5 5 DC22A 5 5

AC23A 5 5 5 5 80 DC23A 5 5

60 60 750 8 690 50 750 AC22A 60 60 60 60 60 DC22A 60 60

AC23A 60 60 60 60 00 DC23A 60 60

 7,5 0   8,5 b Class 0 - 60 % 5 75 3000 730 670 550 b 0000 AC22A 500 500 500 500 DC22A 500 b b 3 -

5 5 30 30 30  b Class 0 - 60 % 5 75 3000 730 670 550 b 0000 AC22A 500 500 500 500 DC22A 500 b b 3 -

 5 37 37 30  b Class 0 - 60 % 5 75 3000 730 670 550 b 0000 AC22A 500 500 500 500 DC22A 500 b b 3 -

  45 55 55 55 55 b Class 0 - 60 % 0 54 5500 375 30 000 b 5000 AC22A 500 500 500 500 500 DC22A 500 b b 3 -

37 37 55 55 75 75 75 b Class 0 - 60 % 0 54 5500 375 30 000 b 5000 AC22A 500 500 500 500 500 DC22A 500 b b 3 -

45 45 75 90 90 0 90 b Class 0 - 60 % 0 54 5500 375 30 000 b 5000 AC22A 500 500 500 500 500 DC22A 500 b b 3 -

AC23A 500 500 500 500 DC23A 500

AC23A 500 500 500 500 DC23A 500

AC23A 500 500 500 500 DC23A 500

AC23A 500 500 500 500 500 DC23A 500

AC23A 500 500 500 500 500 DC23A 500

AC23A 500 500 500 500 500 DC23A 500

A-7

Functions and characteristics

Switch-disconnector selection
Interpact INS40 to 160

Interpact INS switch-disconnectors


Installation
Fixed, front connection Fixed, rear connection On symmetrical rails On a backplate

Connection
By cables By cables with lugs To bare cable connectors Directly to terminals To spreaders To vertical-connection adapters via cable-lug adapters Directly to terminals To spreaders To vertical-connection adapters

Flat-facing bars Edgewise bars Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module

Indication and measurement auxiliaries

Control, locking and interlocking


Control Direct front rotary handle Extended front rotary handle Direct lateral rotary handle Extended lateral rotary handle By keylock By padlocks By keylock Mechanical

Locking Interlocking

Complete source-changeover assembly Operating torque (Nm) (typical value for 3-4 poles with front handle)

Installation and connection accessories


Bare cable connectors Rear connectors Terminal extensions Spreaders One-piece spreader Terminal shrouds Terminal shields Interphase-barrier Front panel escutcheons Coupling accessories Tightening torque for electrical connections (Nm)

Dimensions and weights


Overall dimensions H x W x D (mm) Approximate weight (kg) 3 poles 4 poles 3 poles 4 poles H x W x D (mm)
DB0543

Enclosure dimensions for Ithe

A-8

Functions and characteristics

Switch-disconnector selection
Interpact INS40 to 160

INS40
b b b b -

INS63
b b b b -

INS80
b b b b -

INS100
b b b b b b b b b b b b b .4 < Nm <  b b b b 8 00 x 35 x 6.5 00 x 35 x 6.5 0.8 0.9 60 x 60 x 55

INS125
b b b b b b b b b b b b b .4 < Nm <  b b b b 8 00 x 35 x 6.5 00 x 35 x 6.5 0.8 0.9 60 x 60 x 55

INS160
b b b b b b b b b b b b b .4 < Nm <  b b b b 8 00 x 35 x 6.5 00 x 35 x 6.5 0.8 0.9 60 x 60 x 55

b
b b b b b b b 0.7 < Nm < .3 b b b b 5 85 x 90 x 6.5 85 x 90 x 6.5 0.5 0.6 90 x 5 x 55

b
b b b b b b b 0.7 < Nm < .3 b b b b 5 85 x 90 x 6.5 85 x 90 x 6.5 0.5 0.6 90 x 5 x 55

b
b b b b b b b 0.7 < Nm < .3 b b b b 5 85 x 90 x 6.5 85 x 90 x 6.5 0.5 0.6 90 x 5 x 55

A-9

Functions and characteristics

Switch-disconnector selection
Interpact INS250-100 to 630

Interpact INS switch-disconnectors


056648_L38_SE

Number of poles

Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3


Conventional thermal current (A) Conventional thermal current in enclosure Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Ith Ithe Ui Uimp Ue at 60 C at 60 C AC 50/60 Hz AC 50/60 Hz DC AC 50/60 Hz Electrical AC 50/60 Hz 0-40 V 380-45 V 440-480 V (1) 500-55 V 660-690 V Electrical DC 5 V (P in series) 50 V (4P in series) Electrical AC 50/60 Hz 0-40 V 30 V (NEMA) 380-45 V 440 V 480 V (NEMA) 500-55 V 660-690 V Uninterrupted duty Intermittent duty Min. (switch-disconnector alone) Max. (with upstream protection circuit breaker) s 3s 0 s 30 s Mechanical Electrical AC 50/60 Hz 440 V 500 V 690 V Electrical DC 50 V

Rated operational voltage AC0 and DC0 (V) Rated operational current (A) Ie Interpact INS250 switch-disconnector.

05665_L4_SE

Rated operational power AC3 (kW)

Rated duties Interpact INS250 emergency-off switch-disconnector. Short-circuit making capacity (kA peak) Icm

059487_L54_SE

Short-time withstand current (A rms)

Icw

Suitability for isolation Durability (O-C cycles)

Positive contact indication Visible break Emergency-off switch disconnector Degree of pollution

Upstream protection
Interpact INS400 switch-disconnector. See the Complementary technical information page D-. (1) Suitable for 480 V NEMA. (2) 550 A (DC).

059488_L54_SE

Interpact INS400 emergency-off switch-disconnector.

A-0

Functions and characteristics

Switch-disconnector selection
Interpact INS250-100 to 630

INS250-100 INS250-160 INS250-200 INS250


3-4 3-4 3-4 3-4

INS320
3-4

INS400
3-4

INS500
3-4

INS630
3-4

00 00 750 8 690 50 750 AC22A 00 00 00 00 00 DC22A 00 00

60 60 750 8 690 50 750 AC23A AC22A 00 60 00 60 00 60 00 60 00 60 DC23A DC22A 00 60 00 60

00 00 750 8 690 50 750 AC23A AC22A 60 00 60 00 60 00 60 00 60 00 DC23A DC22A 60 00 60 00

50 50 750 8 690 50 750 AC23A AC22A 00 50 00 50 00 50 00 50 00 50 DC23A DC22A 00 50 00 50

30 30 750 8 690 50 750 AC23A AC22A 50 30 50 30 50 30 50 30 50 30 DC23A DC22A 50 30 50 30

400 400 750 8 690 50 750 AC23A AC22A 30 400 30 400 30 400 30 400 30 400 DC23A DC22A 30 400 30 400

500 500 750 8 690 50 750 AC23A AC22A 400 500 400 500 400 500 400 500 400 500 DC23A DC22A 400 500 400 500

630 630 (2) 750 8 690 50 750 AC23A AC22A 500 630 500 630 500 630 500 630 500 630 DC23A DC22A 500 550 500 550

AC23A 630 630 630 630 630 DC23A DC23B 550 630 550 630

  45 55 55 55 55 b Class 0 - 60 % 30 330 8500 4900 00 800 b 5000 AC22A 500 500 500 DC22A 500 b b 3 -

45 45 75 90 90 0 90 b Class 0 - 60 % 30 330

55 55 90 0 0 3 60 b Class 0 - 60 % 30 330

75 75 3 50 50 60 0 b Class 0 - 60 % 30 330

90 90 60 85 85 0 50 b Class 0 - 60 % 50 330

0 0 00 0 0 50 400 b Class 0 - 60 % 50 330

3 50 50 50 50 355 500 b Class 0 - 60 % 50 330

00 00 35 400 375 400 560 b Class 0 - 60 % 50 330

8500 4900 00 800 b 5000 AC23A AC22A 500 500 500 500 500 500 DC23A DC22A 500 500 b b 3 -

8500 4900 00 800 b 5000 AC23A AC22A 500 500 500 500 500 500 DC23A DC22A 500 500 b b 3 -

8500 4900 00 800 b 5000 AC23A AC22A 500 500 500 500 500 500 DC23A DC22A 500 500 b b 3 -

0000 500 4900 4000 b 0000 AC23A AC22A 500 500 500 500 500 500 DC23A DC23A 500 000 b b 3 -

0000 500 4900 4000 b 0000 AC23A AC22A 500 500 500 500 500 500 DC23B DC23A 000 b b 3 -

0000 500 4900 4000 b 0000 AC23A AC22A 500 500 500 500 500 500 DC23B DC23A 000 b b 3 -

0000 500 4900 4000 b 0000 AC23A AC22A 500 500 500 500 500 500 DC23B DC23A 000 b b 3 -

AC23A 500 500 500 DC23B 00

A-

Functions and characteristics

Switch-disconnector selection
Interpact INS250-100 to 630

Interpact INS switch-disconnectors


Installation
Fixed, front connection Fixed, rear connection On symmetrical rails On a backplate

Connection
By cables By cables with lugs To bare cable connectors Directly to terminals To spreaders To vertical-connection adapters via cable-lug adapters Directly to terminals To spreaders To vertical-connection adapters

Flat-facing bars

Edgewise bars Indication and measurement auxiliaries Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module Control, locking and interlocking Control Direct front rotary handle Extended front rotary handle Direct lateral rotary handle Extended lateral rotary handle Locking By keylock By padlocks Interlocking By keylock Mechanical Complete source-changeover assembly Operating torque (Nm) (typical value for 3-4 poles with front handle)

Installation and connection accessories


Bare cable connectors Rear connectors Terminal extensions Spreaders One-piece spreader Terminal shrouds Terminal shields Interphase-barrier Front panel escutcheons Coupling accessories Tightening torque for electrical connections (Nm)

Dimensions and weights


Overall dimensions H x W x D (mm) Approximate weight (kg) 3 poles 4 poles 3 poles 4 poles H x W x D (mm)
DB0543

Enclosure dimensions for Ithe

A-

Functions and characteristics

Switch-disconnector selection
Interpact INS250-100 to 630

INS250-100 INS250-160 INS250-200 INS250


b b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b b b b 5 36 x 40 x 96 36 x 40 x 96  . 400 x 300 x 00 b b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b b b b 5 36 x 40 x 96 36 x 40 x 96  . 400 x 300 x 00 b b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b b b b 5 36 x 40 x 96 36 x 40 x 96  . 400 x 300 x 00 b b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b b b b 5 36 x 40 x 96 36 x 40 x 96  . 400 x 300 x 00

INS320
b b b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b b b 50 05 x 85 x 30 05 x 85 x 30 4.6 4.9 600 x 400 x 00

INS400
b b b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b b b 50 05 x 85 x 30 05 x 85 x 30 4.6 4.9 600 x 400 x 00

INS500
b b b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b b b 50 05 x 85 x 30 05 x 85 x 30 4.6 4.9 600 x 400 x 00

INS630
b b b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b b b 50 05 x 85 x 30 05 x 85 x 30 4.6 4.9 600 x 400 x 00

A-3

Functions and characteristics

Switch-disconnector selection
Interpact INS630b to 2500

Interpact INS switch-disconnectors


PB0006b-55_SE

Number of poles

Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3


Conventional thermal current (A) Conventional thermal current in enclosure Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Ith Ithe Ui Uimp Ue at 60 C at 60 C AC 50/60 Hz AC 50/60 Hz DC AC 50/60 Hz Electrical AC 50/60 Hz 0-40 V Interpact INS1600 switch-disconnector. 380-45 V 440-480 V (1)

Rated operational voltage AC0 and DC0 (V) Rated operational current (A) Ie

PB0008b-55_SE

500-55 V 660-690 V Electrical DC 5 V (P in series) 50 V (4P in series) Electrical AC 50/60 Hz 0-40 V 380-400 V 45 V 500-55 V 660-690 V Uninterrupted duty Intermittent duty Min. (switch-disconnector alone) Max. (with upstream protection circuit breaker) 0.5 s 0.8 s s 3s 0 s 30 s Mechanical Electrical AC 50/60 Hz 0-40 V 380-45 V 440-480 V (1) 500-55 V 660-690 V Electrical DC 5 V (P) 50 V (4P) Interpact INS2500 switch-disconnector. Positive contact indication Visible break Emergency-off switch disconnector Degree of pollution

Rated operational power AC3 (kW)

Rated duties Interpact INS1600 emergency-off switch-disconnector. Short-circuit making capacity (kA peak) Icm

PB0000b-65_SE

Short-time withstand current (kA rms)

Icw

Suitability for isolation Durability (O-C cycles)

Upstream protection
See the "Complementary technical information" page D-. (1) Suitable for 480 V NEMA. (2) For vertical connection busbars only. For horizontal connection busbars, see derating charts in Installation recommendations see p. B-22.

A-4

Functions and characteristics

Switch-disconnector selection
Interpact INS630b to 2500

INS630b
3-4

INS800
3-4

INS1000
3-4

INS1250
3-4

INS1600
3-4

INS2000
3-4

INS2500
3-4

630 630 000  690 50 800

800 800 000  690 50 800

000 000 000  690 50 800

50 50 000  690 50 800

600 (2) 600 (2) 000  690 50 800

000 000 000  690 50 800

500 500 000  690 50 800

AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B AC21A AC22A

630 630 630 630 630

630 630 630 630 630

630 630 630 630 630

800 800 800 800 800

800 800 800 800 800

800 800 800 800 800

000 000 000 000 000

000 000 000 000 000

000 000 000 000 000

50 50 50 50 50

50 50 50 50 50

50 50 50 50 50

600 450 600 450 600 50 600 50 600 50

600 450 600 450 600 50 600 50 600 50

50 50 50 50 50

000 000 000 000 000

000 000 000 000 000

500 500 500 500 500

500 500 500 500 500

DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B

630/ 630/ 630/ 800/ 800/ 800/ 000/ 000/ 000/ 50/ 50/ 50/ 600/ 600/ 600/ 000/ 000/ 630/4 630/4 630/4 800/4 800/4 800/4 000/4 000/4 000/4 50/4 50/4 50/4 600/4 600/4 600/4 000/4 000/4 50 400 500 560 70 b Class 0 - 60 % 75 330 50 4 35 0 0 8 b 5000 50 400 500 560 70 b Class 0 - 60 % 75 330 50 4 35 0 0 8 b 3000 35 560 630 70 900 b Class 0 - 60 % 75 330 50 4 35 0 0 8 b 3000 400 70 800 900 b Class 0 - 60 % 75 330 50 4 35 0 0 8 b 3000 400 70 800 900 b Class 0 - 60 % 75 330 50 4 35 0 0 8 b 3000 b Class 0 - 60 % 05 330 50 50 50 30 3  b 3000

500/ 500/ 500/4 500/4 b Class 0 - 60 % 05 330 50 50 50 30 3  b 3000

AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B AC21A AC22A

000 000 000 000 000

000 000 000 000 000

000 000 000 000 000

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

00 500 00 500 00 500 00 500 00 500 500 500 b b 3 -

00 500 00 500 00 500 00 500 00 500 500 500

500 500 500 500 500

00 00 00 00 00

00 00 00 00 00

00 00 00 00 00

00 00 00 00 00

DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B

000 000 b b 3 -

000 000

000 000

500 500 b b 3 -

500 500

500 500

500 500 b b 3 -

500 500

500 500

500 500 b b 3 -

500 500

500 500

500 500

00 00 b 3 -

00 00

00 00 b 3 -

00 00

A-5

Functions and characteristics

Switch-disconnector selection
Interpact INS630b to 2500

Interpact INS switch-disconnectors


Installation
Fixed, front connection Fixed, rear connection On symmetrical rails On a backplate

Connection
By cables By cables with lugs To bare cable connectors Directly to terminals To spreaders To vertical-connection adapters via cable-lug adapters Directly to terminals To spreaders To vertical-connection adapters

Flat-facing bars Edgewise bars Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module

Indication and measurement auxiliaries

Control, locking and interlocking


Control Direct front rotary handle Extended front rotary handle Direct lateral rotary handle Extended lateral rotary handle By keylock By padlocks By keylock Mechanical

Locking Interlocking

Complete source-changeover assembly Operating torque (Nm) (typical value for 3-4 poles with front handle)

Installation and connection accessories


Bare cable connectors Rear connectors Terminal extensions Spreaders One-piece spreader Terminal shrouds Terminal shields Interphase-barrier Front panel escutcheons Coupling accessories Tightening torque for electrical connections (Nm)

Dimensions and weights


Overall dimensions H x W x D (mm) Approximate weight (kg) Enclosure dimensions for Ithe H x W x D (mm)
DB0543

3 poles 4 poles 3 poles 4 poles

A-6

Functions and characteristics

Switch-disconnector selection
Interpact INS630b to 2500

INS630b
b b b b b b b b b b b b b 30 b b b b b 50

INS800
b b b b b b b b b b b b b 30 b b b b b 50

INS1000
b b b b b b b b b b b b b 30 b b b b b 50

INS1250
b b b b b b b b b b b b b 30 b b b b b 50

INS1600
b b b b b b b b b b b b b 30 b b b b b 50

INS2000
b b b b b b b b b b b 60 b b b b b 50

INS2500
b b b b b b b b b b b 60 b b b b b 50

300 x 340 x 46.5 300 x 40 x 46.5 4 8 -

300 x 340 x 46.5 300 x 40 x 46.5 4 8 -

300 x 340 x 46.5 300 x 40 x 46.5 4 8 -

300 x 340 x 46.5 300 x 40 x 46.5 4 8 -

300 x 340 x 46.5 300 x 40 x 46.5 4 8 -

440 x 347.5 x 7.5 440 x 46.5 x 7.5 35 45 -

440 x 347.5 x 7.5 440 x 46.5 x 7.5 35 45 -

A-7

Functions and characteristics

Switch-disconnector selection
Interpact INV100 to 630

Interpact INV switch-disconnectors


056650_L4_SE

Number of poles

Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3


Conventional thermal current (A) Conventional thermal current in enclosure Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Ith Ithe Ui Uimp Ue at 60 C at 60 C AC 50/60 Hz AC 50/60 Hz DC AC 50/60 Hz Electrical AC 50/60 Hz 0-40 V 380-45 V 440-480 V (1) 500-55 V 660-690 V Electrical DC 5 V (P in series) 50 V (4P in series) Electrical AC 50/60 Hz 0-40 V 30 V (NEMA) 380-45 V 440 V 480 V (NEMA) 500-55 V 660-690 V Uninterrupted duty Intermittent duty Min. (switch-disconnector alone) Max. (with upstream protection circuit breaker) s 3s 0 s 30 s Mechanical Electrical AC 50/60 Hz 440 V 500 V 690 V Electrical DC 50 V Positive contact indication Visible break Emergency-off switch disconnector Degree of pollution Interpact INV400 Std.

Rated operational voltage AC0 and DC0 (V) Rated operational current (A) Ie Interpact INV250 switch-disconnector.

056654_L4_SE

Rated operational power AC3 (kW)

Interpact INV250 emergency-off switch-disconnector.

Rated duties Short-circuit making capacity (kA peak) Icm

05949_L54_SE

Short-time withstand current (A rms)

Icw

Suitability for isolation Durability (O-C cycles)

Upstream protection
See the Complementary technical information page D-. (1) Suitable for 480 V NEMA. (2) 550 A (DC).

059493_L5_SE

Interpact INV400 emergency-off switch-disconnector.

A-8

Functions and characteristics

Switch-disconnector selection
Interpact INV100 to 630

INV100
3-4

INV160
3-4

INV200
3-4

INV250
3-4

INV320
3-4

INV400
3-4

INV500
3-4

INV630
3-4

00 00 750 8 690 50 750 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00

60 60 750 8 690 50 750 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

00 00 750 8 690 50 750 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00

50 50 750 8 690 50 750 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 00 00 00 00

30 30 750 8 690 50 750 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30

400 400 750 8 690 50 750 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400

500 500 750 8 690 50 750 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500

630 630 (2) 750 8 690 50 750 630 630 630 630 630 550 550 630 630 630 630 550 550 550 630/630 630/630 630/630 500/630 500/630 550/630 550/630

AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/ AC23B

DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23B DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/ DC23B

  45 55 55 55 55 b Class 0 - 60 % 30 330 8500 4900 00 800 b 5000


AC22A AC23A

45 45 75 90 50 0 90 b Class 0 - 60 % 30 330 8500 4900 00 800 b 5000


AC22A AC23A

55 55 90 0 0 3 60 b Class 0 - 60 % 30 330 8500 4900 00 800 b 5000
AC22A AC23A

75 75 3 50 50 3 60 b Class 0 - 60 % 30 330 8500 4900 00 800 b 5000
AC22A AC23A

90 90 60 85 85 0 50 b Class 0 - 60 % 50 330 0000 500 4900 4000 b 0000

0 0 00 0 0 50 400 b Class 0 - 60 % 50 330 0000 500 4900 4000 b 0000

3 50 50 50 50 355 500 b Class 0 - 60 % 50 330 0000 500 4900 4000 b 0000

00 00 35 400 375 400 560 b Class 0 - 60 % 50 330 0000 500 4900 4000 b 0000

AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A/ AC23B

500 500 500


DC22A

500 500 500


DC23A

500 500 500


DC22A

500 500 500


DC23A

500 500 500


DC22A

500 500 500


DC23A

500 500 500


DC22A

500 500 500


DC23A

000 000 000 000 000 000 000 000 000 000 000 000 000 000 000 000 000 000 000 000 000 000 000 000/00 000 000 000 000 000 000 000 000 000 000 000 000/00
DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A/ DC23B

500 b b b 3 -

500

500 b b b 3 -

500

500 b b b 3 -

500

500 b b b 3 -

500

000 000 000 000 000 000 000 000 000 000 000 000/00 b b b b b b b b b b b b 3 3 3 3 -

A-9

Functions and characteristics

Switch-disconnector selection
Interpact INV100 to 630

Interpact INV switch-disconnectors


Installation
Fixed, front connection Fixed, rear connection On symmetrical rails On a backplate

Connection
By cables By cables with lugs To bare cable connectors Directly to terminals To spreaders To vertical-connection adapters via cable-lug adapters Directly to terminals To spreaders To vertical-connection adapters

Flat-facing bars Edgewise bars Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module

Indication and measurement auxiliaries

Control, locking and interlocking


Control Direct front rotary handle Extended front rotary handle Direct lateral rotary handle Extended lateral rotary handle By keylock By padlocks By keylock Mechanical

Locking Interlocking

Complete source-changeover assembly Operating torque (Nm) (typical value for 3-4 poles with front handle)

Installation and connection accessories


Bare cable connectors Rear connectors Terminal extensions Spreaders One-piece spreader Terminal shrouds Terminal shields Interphase-barrier Front panel escutcheons Coupling accessories Tightening torque for electrical connections (Nm)

Dimensions and weights


Overall dimensions H x W x D (mm) Approximate weight (kg) 3 poles 4 poles 3 poles 4 poles H x W x D (mm)
db0543

Enclosure dimensions for Ithe

A-0

Functions and characteristics

Switch-disconnector selection
Interpact INV100 to 630

INV100
b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b b b b 5 36 x 40 x 96 36 x 40 x 96  . 400 x 300 x 00

INV160
b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b b b b 5 36 x 40 x 96 36 x 40 x 96  . 400 x 300 x 00

INV200
b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b b b b 5 36 x 40 x 96 36 x 40 x 96  . 400 x 300 x 00

INV250
b b b b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b b b b 5 36 x 40 x 96 36 x 40 x 96  . 400 x 300 x 00

INV320
b b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b b b b 50 05 x 85 x 30 05 x 85 x 30 4.6 4.9 600 x 400 x 00

INV400
b b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b b b b 50 05 x 85 x 30 05 x 85 x 30 4.6 4.9 600 x 400 x 00

INV500
b b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b b b b 50 05 x 85 x 30 05 x 85 x 30 4.6 4.9 600 x 400 x 00

INV630
b b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b b b b 50 05 x 85 x 30 05 x 85 x 30 4.6 4.9 600 x 400 x 00

A-

Functions and characteristics

Switch-disconnector selection
Interpact INV630b to 2500

Interpact INV switch-disconnectors


PB0007b-55_SE

Number of poles

Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3


Conventional thermal current (A) Conventional thermal current in enclosure Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Ith Ithe Ui Uimp Ue at 60 C at 60 C AC 50/60 Hz AC 50/60 Hz DC AC 50/60 Hz Electrical AC 50/60 Hz 0-40 V Interpact INV1600 switch-disconnector. 380-45 V 440-480 V (1)

Rated operational voltage AC0 and DC0 (V) Rated operational current (A) Ie

PB0009b-55_SE

500-55 V 660-690 V Electrical DC 5 V (P in series) 50 V (4P in series) Electrical AC 50/60 Hz 0-40 V 380-400 V 45 V 500-55 V 660-690 V Uninterrupted duty Intermittent duty Min. (switch-disconnector alone) Max. (with upstream protection circuit breaker) 0.5 s 0.8 s s 3s 0 s 30 s Mechanical Electrical AC 50/60 Hz 0-40 V 380-45 V 440-480 V (1) 500-55 V 660-690 V Electrical DC 5 V (P) 50 V (4P) Interpact INV2500 switch-disconnector. Positive contact indication Visible break Emergency-off switch disconnector Degree of pollution

Rated operational power AC3 (kW)

Rated duties Interpact INV1600 emergency-off switch-disconnector. Short-circuit making capacity (kA peak) Icm

PB000b-65_SE

Short-time withstand current (kA rms)

Icw

Suitability for isolation Durability (O-C cycles)

Upstream protection
See the "Complementary technical information" page D-. (1) Suitable for 480 V NEMA. (2) For vertical connection busbars only. For horizontal connection busbars, see derating charts in Installation recommendations p. B-22.

A-

Functions and characteristics

Switch-disconnector selection
Interpact INV630b to 2500

INV630b
3-4

INV800
3-4

INV1000
3-4

INV1250
3-4

INV1600
3-4

INV2000
3-4

INV2500
3-4

630 630 000  690 50 800

800 800 000  690 50 800

000 000 000  690 50 800

50 50 000  690 50 800

600 (2) 600 (2) 000  690 50 800

000 000 000  690 50 800

500 500 000  690 50 800

AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B AC21A AC22A

630 630 630 630 630

630 630 630 630 630

630 630 630 630 630

800 800 800 800 800

800 800 800 800 800

800 800 800 800 800

000 000 000 000 000

000 000 000 000 000

000 000 000 000 000

50 50 50 50 50

50 50 50 50 50

50 50 50 50 50

600 450 600 450 600 50 600 50 600 50

600 450 600 450 600 50 600 50 600 50

50 50 50 50 50

000 000 000 000 000

000 000 000 000 000

500 500 500 500 500

500 500 500 500 500

DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21B DC22B DC23B DC21B DC22B DC23B

630/ 630/ 630/ 800/ 800/ 800/ 000/ 000/ 000/ 50/ 50/ 50/ 600/ 600/ 600/ 000/ 000/ 630/4 630/4 630/4 800/4 800/4 800/4 000/4 000/4 000/4 50/4 50/4 50/4 600/4 600/4 600/4 000/4 000/4 50 400 500 560 70 b Class 0 - 60 % 75 330 50 4 35 0 0 8 b 5000 50 400 500 560 70 b Class 0 - 60 % 75 330 50 4 35 0 0 8 b 3000 35 560 630 70 900 b Class 0 - 60 % 75 330 50 4 35 0 0 8 b 3000 400 70 800 900 b Class 0 - 60 % 75 330 50 4 35 0 0 8 b 3000 400 70 800 900 b Class 0 - 60 % 75 330 50 4 35 0 0 8 b 3000 b Class 0 - 60 % 05 330 50 50 50 30 3  b 3000

500/ 500/ 500/4 500/4 b Class 0 - 60 % 05 330 50 50 50 30 3  b 3000

AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21A AC22A AC23A AC21B AC22B AC23A AC21B AC22B AC23B AC21B AC22B AC23B AC21A AC22A

000 000 000 000 000

000 000 000 000 000

000 000 000 000 000

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

500 500 500 500 500

00 500 00 500 00 500 00 500 00 500 500 500 b b b 3 -

00 500 00 500 00 500 00 500 00 500 500 500

500 500 500 500 500

00 00 00 00 00

00 00 00 00 00

00 00 00 00 00

00 00 00 00 00

DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23A DC21A DC22A DC23B DC21B DC22B DC23B DC21B DC22B DC23B

000 000 b b b 3 -

000 000

000 000

500 500 b b b 3 -

500 500

500 500

500 500 b b b 3 -

500 500

500 500

500 500 b b b 3 -

500 500

500 500

500 500

00 00 b b 3 -

00 00

00 00 b b 3 -

00 00

A-3

Functions and characteristics

Switch-disconnector selection
Interpact INV630b to 2500

Interpact INV switch-disconnectors


Installation
Fixed, front connection Fixed, rear connection On symmetrical rails On a backplate

Connection
By cables By cables with lugs To bare cable connectors Directly to terminals To spreaders To vertical-connection adapters via cable-lug adapters Directly to terminals To spreaders To vertical-connection adapters

Flat-facing bars Edgewise bars Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module

Indication and measurement auxiliaries

Control, locking and interlocking


Control Direct front rotary handle Extended front rotary handle Direct lateral rotary handle Extended lateral rotary handle By keylock By padlocks By keylock Mechanical

Locking Interlocking

Complete source-changeover assembly Operating torque (Nm) (typical value for 3-4 poles with front handle)

Installation and connection accessories


Bare cable connectors Rear connectors Terminal extensions Spreaders One-piece spreader Terminal shrouds Terminal shields Interphase-barrier Front panel escutcheons Coupling accessories Tightening torque for electrical connections (Nm)

Dimensions and weights


Overall dimensions H x W x D (mm) Approximate weight (kg) Enclosure dimensions for Ithe H x W x D (mm)
DB0543

3 poles 4 poles 3 poles 4 poles

A-4

Functions and characteristics

Switch-disconnector selection
Interpact INV630b to 2500

INV630b
b b b b b b b b b b b b b 30 b b b b b 50

INV800
b b b b b b b b b b b b b 30 b b b b b 50

INV1000
b b b b b b b b b b b b b 30 b b b b b 50

INV1250
b b b b b b b b b b b b b 30 b b b b b 50

INV1600
b b b b b b b b b b b b b 30 b b b b b 50

INV2000
b b b b b b b b b b b 60 b b b b b 50

INV2500
b b b b b b b b b b b 60 b b b b b 50

300 x 340 x 46.5 300 x 40 x 46.5 4 8 -

300 x 340 x 46.5 300 x 40 x 46.5 4 8 -

300 x 340 x 46.5 300 x 40 x 46.5 4 8 -

300 x 340 x 46.5 300 x 40 x 46.5 4 8 -

300 x 340 x 46.5 300 x 40 x 46.5 4 8 -

440 x 347.5 x 7.5 440 x 46.5 x 7.5 35 45 -

440 x 347.5 x 7.5 440 x 46.5 x 7.5 35 45 -

A-5

Functions and characteristics

Complete source-changeover assembly selection


Interpact INS250-100 to 630
Interpact INS switch-disconnectors

PB00840_L67_SE

Number of poles

Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3


Conventional thermal current (A) Conventional thermal current in enclosure Rated insulation level (V) Impulse-withstand voltage (kV) Rated operational voltage (V) Ith Ithe Ui Uimp Ue at 60 C at 60 C AC 50/60 Hz AC 50/60 Hz DC AC 50/60 Hz Electrical AC 50/60 Hz 0-40 V 380-45 V 440-480 V (1) 500-55 V 660-690 V Electrical DC 5 V (P in series) 50 V (4P in series) Uninterrupted duty Intermittent duty Min. (switch-disconnector alone) Max. (with upstream protection circuit breaker) s 3s 0 s 30 s Mechanical Electrical AC 50/60 Hz 440 V 500 V 690 V Electrical DC 50 V

Rated operational voltage AC0 and DC0 (V) Rated operational current (A) Ie Complete source-changeover assembly.

Rated duties Short-circuit making capacity (kA peak) Icm

Short-time withstand current (A rms)

Icw

Suitability for isolation Durability (category A) (O - C-O cycles)

Positive contact indication Visible break Emergency-off switch disconnector Degree of pollution

Upstream protection
See the Complementary technical information page D-. (1) Suitable for 480 V NEMA.

A-6

Functions and characteristics

Complete source-changeover assembly selection


Interpact INS250-100 to 630

INS250-100 INS250-160 INS250-200 INS250


3-4 3-4 3-4 3-4

INS320
3-4

INS400
3-4

INS500
3-4

INS630
3-4

00 00 750 8 690 50 750 AC22A AC23A 00 00 00 00 00 00 00 00 00 00 DC22A DC23A 00 00 00 00 b Class 0 - 60 % 30 330 8500 4900 00 800 b 5000 AC22A 500 500 500 DC22A 500 b 3 -

60 60 750 8 690 50 750 AC22A AC23A 60 60 60 60 60 60 60 60 60 60 DC22A DC23A 60 60 60 60 b Class 0 - 60 % 30 330

00 00 750 8 690 50 750 AC22A AC23A 00 00 00 00 00 00 00 00 00 00 DC22A DC23A 00 00 00 00 b Class 0 - 60 % 30 330

50 50 750 8 690 50 750 AC22A AC23A 50 50 50 50 50 50 50 50 50 50 DC22A DC23A 50 50 50 50 b Class 0 - 60 % 30 330

30 30 750 8 690 50 750 AC22A AC23A 30 30 30 30 30 30 30 30 30 30 DC22A DC23A 30 30 30 30 b Class 0 - 60 % 50 330

400 400 750 8 690 50 750 AC22A AC23A 400 400 400 400 400 400 400 400 400 400 DC22A DC23A 400 400 400 400 b Class 0 - 60 % 50 330

500 500 750 8 690 50 750 AC22A AC23A 500 500 500 500 500 500 500 500 500 500 DC22A DC23A 500 500 500 500 b Class 0 - 60 % 50 330

630 630 750 8 690 50 750 AC22A AC23A 630 630 630 630 630 630 630 630 630 630 DC22A DC23A DC23B 550 550 630 550 550 630 b Class 0 - 60 % 50 330

8500 4900 00 800 b 5000 AC23A AC22A 500 500 500 500 500 500 DC23A DC22A 500 500 b 3 -

8500 4900 00 800 b 5000 AC23A AC22A 500 500 500 500 500 500 DC23A DC22A 500 500 b 3 -

8500 4900 00 800 b 5000 AC23A AC22A 500 500 500 500 500 500 DC23A DC22A 500 500 b 3 -

0000 500 4900 4000 b 0000 AC23A AC22A 500 500 500 500 500 500 DC23A DC23A 500 000 b 3 -

0000 500 4900 4000 b 0000 AC23A AC22A 500 500 500 500 500 500 DC23B DC23A 000 b 3 -

0000 500 4900 4000 b 0000 AC23A AC22A 500 500 500 500 500 500 DC23B DC23A 000 b 3 -

0000 500 4900 4000 b 0000 AC23A AC22A 500 500 500 500 500 500 DC23B DC23A 000 b 3 -

AC23A 500 500 500 DC23B 00

A-7

Functions and characteristics

Complete source-changeover assembly selection


Interpact INS250-100 to 630
Interpact INS switch-disconnectors
Installation
Fixed, front connection Fixed, rear connection On symmetrical rails On a backplate

Connection
By cables By cables with lugs To bare cable connectors Directly to terminals To spreaders To vertical-connection adapters via cable-lug adapters Directly to terminals To spreaders To vertical-connection adapters

Flat-facing bars Edgewise bars Auxiliary contacts Voltage-presence indicator Current-transformer module Ammeter module

Indication and measurement auxiliaries

Control, locking and interlocking


Control Direct front rotary handle Extended front rotary handle Direct lateral rotary handle Extended lateral rotary handle By keylock Mechanical

Interlocking

Complete source-changeover assembly Operating torque (Nm) (typical value for 3-4 poles with front handle)

Installation and connection accessories


Bare cable connectors Rear connectors Terminal extensions Spreaders One-piece spreader Terminal shrouds Terminal shields Interphase-barrier Front panel escutcheons Coupling accessories Tightening torque for electrical connections (Nm)

Dimensions and weights


Overall dimensions H x W x D (mm) Approximate weight (kg) 3 poles 4 poles 3 poles 4 poles

A-8

Functions and characteristics

Complete source-changeover assembly selection


Interpact INS250-100 to 630

INS250-100 INS250-160 INS250-200 INS250


b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b 5 36 x 95 x 3 36 x 95 x 3 6.4 6.4 b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b 5 36 x 95 x 3 36 x 95 x 3 6.4 6.4 b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b 5 36 x 95 x 3 36 x 95 x 3 6.4 6.4 b b b b b b b b b b b b b b b b b 5 < Nm < 6. b b b b b b 5 36 x 95 x 3 36 x 95 x 3 6.4 6.4

INS320
b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b 50 05 x 395 x 55 05 x 395 x 55 3.5 3.5

INS400
b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b 50 05 x 395 x 55 05 x 395 x 55 3.5 3.5

INS500
b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b 50 05 x 395 x 55 05 x 395 x 55 3.5 3.5

INS630
b b b b b b b b b b b b b b b b b b 3.5 < Nm < 6.5 b b b b b b 50 05 x 395 x 55 05 x 395 x 55 3.5 3.5

A-9

Functions and characteristics

Switch-disconnector selection
Interpact INS40 to 80

DB7753

A-30

Functions and characteristics

Switch-disconnector selection
Interpact INS100 to 160

DB775

A-3

Functions and characteristics

Switch-disconnector selection
Interpact INS250-100 to 630 Interpact INV100 to 630

DB7755

A-3

Functions and characteristics

Switch-disconnector selection
Interpact INS320 to 630 Interpact INV320 to 630

DB775

A-33

Functions and characteristics

Switch-disconnector selection
Interpact INS630b to 1600 Interpact INV630b to 1600

DB7754

A-34

Functions and characteristics

Switch-disconnector selection
Interpact INS2000 to 2500 Interpact INV2000 to 2500

DB7756

A-35

Functions and characteristics

Electrical and mechanical accessories

Indications and measurement


057357_L40_SE

Ammeter module
For Interpact INS50 to 630 and INV00 to 630. Function Measures and displays the current of each phase (phase selection by a threeposition switch on the front) on a dial-type ammeter. Installation b Connects directly to the downstream terminals of the switch-disconnector (except on a INS50 with a direct handle). b Ammeter clips into module in any of four 90 positions, i.e. can be installed of devices mounted both vertically and horizontally. b Degree of protection: IP40, IK04. b Class II insulation between front and power circuits. Electrical characteristics Accuracy: class 4.5.

Current-transformer module
For Interpact INS50 to 630 and INV00 to 630. Function The module enables direct connection of a measurement device such as an ammeter or a Digipact power meter (not supplied). Installation b Connects directly to the downstream terminals of the switch-disconnector. b Degree of protection: IP40, IK07. b Class II insulation between front and power circuits. b Connection via six built-in terminals for cables with a cross-sectional area of .5 mm. Electrical characteristics b Current transformer with 5 A secondary winding. b Class 3 for the following values of consumed output power. Accuracy: v 00 A rating - .6 VA v 50 A rating - 3 VA v 50 A rating - 5 VA v 400/630 A rating - 8 VA.

Interpact INV250 with ammeter module.

Current-transformer module with voltage measurement outputs


For direct connection of a digital power monitoring unit: Power Meter PM700, PM800, etc. (not supplied). Installation b Mounts directly on the downstream terminals of the circuit breaker. b Degree of protection: IP40, IK04. b Class II insulation of front with respect to the power circuits. b Built-in connectors for cables from .5 to .5 mm. Electrical characteristics b Rated operational voltage Ue: 530 V. b Frequencies of measured values: 50... 60 Hz. b Three CTs with 5 A secondary windings for the rated primary current IN. v class 0.5 to  for rated power consumption values at the output: - 5 A, 50 A and 50 A ratings: class  for . VA - 400/600 A rating: class 0.5 for  VA v use a cable of .5 mm section up to .5 m long. b Four voltage measurement outputs including protection with automatic reset v voltage measurement output impedance 3500 W 5 %, maximum current  mA.

Voltage presence indicator


The indicator detects and indicates that circuit breaker terminals are supplied with power. Installation b In the long or short terminal shields, via the knockouts. b Upstream or downstream of the circuit breaker. b Degree of protection, IP40, IK04. Electrical characteristics Operates on all networks with voltages ranging from 0 et 550 V AC.

A-36

Functions and characteristics

Electrical and mechanical accessories

Auxiliary contacts
04434d-8 DB9706

Interpact INS and INV


One or four common-point changeover contacts can be used to remote switchdisconnector status information for indications, electrical interlocking, relays, etc. Functions Each contact may be used for the following functions: b OF (ON/OFF): indicates the position of the switch-disconnector poles b CAM (early-make or early-break function): indicates the position of the handle. Used in particular for: v CAO early-break switch (auxiliary contacts open before the main contacts), used, for example, to automatically open a circuit breaker or a contactor before opening the Interpact INS v CAF early-make switch (auxiliary contacts close before the main contacts) b switching of very small loads. A low-level version of the auxiliary contacts exists for switching very small loads (for example, to control a PLC or electronic circuits). Standards The auxiliary contacts comply with international standard IEC 60947-5.. Installation They simply snap in under the auxiliaries cover (supplied as standard) of the switchdisconnector. Insulation Sealable auxiliary shield to protect against direct contact with power circuits. Electrical characteristics of auxiliary contacts for Interpact INS and INV Standard
6 0 mA at 4 V AC Utilisation category (IEC 60947-5-) AC AC5 6 6 Operational current (A) 4 V 48 V 6 6 0 V 6 5 00/40 V 6 4 50 V 380/440 V 6  480 V 6 .5 660/690 V 6 0. Interpact INS/INV320 to 630.

Auxiliary contacts for Interpact INS and INV


DB9707

Interpact INS40 to 160.

Interpact INS250 and INV100 to 250.

Low level
5  mA at 4 V DC AC DC DC4 AC AC5 6  5 3 .5 0. 5 3 0.6 0.05 5 .5 5  0.3 0.03 5 5 .5 5  DC DC 5 .5 0.6 0.3 -

DB9708

Rated thermal current (A) Minimum load

DC4  0. 0.05 0.03 -

Interpact INS40 to 2500, INV100 to 2500


Possible combinations
DB9709

Interpact
INS40 to 60 INS50 INS400 to 630 INS630b to 600 INS000 to 500

OF block
3 3 3 and and and

CAM block (CAO/CAF)


    

Interpact INS/INV800 to 1600.

DB970

Interpact INS/INV2000 to 2500.

A-37

Functions and characteristics

Electrical and mechanical accessories

Rotary handle
057c-40_SE

Interpact INS and INV


There are two types of rotary handle: b direct rotary handle b extended rotary handle. There are two models: b standard with a black handle b with a red handle and yellow front for machine-tool control, in accordance with VDE standard. INS40-160
Standard rotary handle Front direct Standard Lateral direct Standard

Interpact INS160 with lateral direct rotary handle.

INS250 INS/INV INV100-250 320-630

INS/INV 630b-1600

INS/INV 2000-2500

Interpact INS250 with lateral extended rotary handle.

Standard Standard Standard Standard With No No No conversion Front extended Optional Optional Optional Optional Optional Lateral extended Optional (1) Optional No No No Red and yellow rotary handle for emergency-off switch-disconnectors Front direct Standard Standard Standard Standard No (2) Lateral direct Standard With No No No conversion Front extended Optional Optional Optional Optional No (2) Lateral extended Optional (1) (3) Optional (3) No No No (1) Two models for universal enclosures and for Prisma G enclosures. (2) Emergency-off versions not available for INS/INV2000-2500. (3) The basic switch-disconnector must be the emergency-off (red and yellow) version.

056656c-68_SE

059495_L64_SE

Direct rotary handle b Degree of protection IP40.IK07. b The switch-disconnector may be locked in the OFF position by one to three padlocks, hasp diameter 5 to 8 mm (not supplied). Models b Standard switch-disconnector: with black handle. b Emergency-off version with red handle and yellow front for machine-tool control. Extended rotary handle Makes it possible to operate the switch-disconnector, installed inside a switchboard, from the front or side of the switchboard. The extended rotary handle may be installed on the front or the side of the switchdisconnector. Degree of protection IP55.IK08. Operation b Suitability for isolation is maintained. b Door opening is prevented when the switchdisconnector is in ON position (for front handle only). b The switch-disconnector may be locked in the OFF position by one to three padlocks, hasp diameter 5 to 8 mm (not supplied). Locking prevents opening of the switchboard door (for front handle only).
Interpact INS630 with front extended rotary handle.

DB06833

Direct rotary handle on INS40 to 160.

DB06834

Direct rotary handle on INS250 and INV100 to 250.

Models b Standard switch-disconnector: with black handle. b Emergency-off: with red handle and yellow front for machine-tool control. Installation The extended rotary handle is made up of: b An assembly that replaces the direct rotary handle on the Interpact switch-disconnector (secured by screws). b An assembly (handle and front plate) to be mounted on the door or the side of the switchboard. This assembly is always secured in the same position, whether the switch-disconnector is installed vertically or horizontally. b An adjustable extension shaft (see p. C-6 to p. C-9).
Direct rotary handle on INS/INV320 to 630.

05665_L40_SE

Interpact INS250 emergency-off version with front direct rotary handle.

DB0550

DB05509

Direct rotary handle on INS/INV800 to 1600.

A-38

Functions and characteristics

Electrical and mechanical accessories

Disabling device closing


056649d-56_SE

b INS40 to 500 A. b INV00 to 500 A. b Complete source-changeover assembly from 00 to 630 A. Switch-disconnectors may be locked in the OFF position The handle is designed for locking by up to three padlocks (not supplied). Locking in the OFF position guarantees isolation as defined by the IEC 60947-3 standard. The handle may also be lead-sealed in the OFF position.

Padlocking

DB055

Padlocked Interpact INS250 switch-disconnector.

b INS50-00 to 500 A. b INV00 to 500 A. b Complete source-changeover assembly from 00 to 630 A. INS50 to 630, INV00 to 630 or INV000 to 500 switch-disconnectors may be locked in the OFF position using a keylock (optional) that may be installed in the hole prepared for that purpose on the front of the devices. The key may not be removed when the switch-disconnector is in the ON position. Keylocks can also be fitted on switch-disconnectors equipped with extended rotary handles.

Keylocking

DB0554

INS/INV switch disconnectors INS40 to 80


OFF b b b ON v b b (2) v

INS80 to 160
OFF b b b ON v b b (2) v

INS250-100 to 250 INS320 to 630 INV100 to 250 INV320 to 630


OFF b b b b ON v v b b (2) v OFF b b b b ON v v b b (2) v

DB0555

DB0553

INS630b to 1600 INV630b to 1600


OFF b b b b ON v v b b (2) v

INV2000 to 2500 INS2000 to 2500


OFF b b b b ON v v b b (2) v

Locking by padlocks Locking by keylock Door locking (1) Door lock defeat (1) Door locking device padlocked (1) Lead-sealable handle

Complete source changeover assembly INS250-100 to 250


Locking by padlocks Locking by keylock Door locking (1) Door lock defeat (1) Door locking device padlocked (1) Lead-sealable handle Normal ON v b b (2) v OFF b b b b Replacement ON v b b (2) v

INS320 to 630
Normal ON v b b (2) v OFF b b b b Replacement ON v b b (2) v

b Standard. v By simple modification of the standard rotary handle. (1) Using a special tool. (2) With extended rotary control.

A-39

Functions and characteristics

Manual source-changeover systems

A source-changeover system is made up of two switchdisconnectors or circuit breakers that are mechanically interlocked. The mechanism prevents the simultaneous connection (even transient) of both sources. Switching from one source to the other can be achieved by: b a keylock-type interlocking system b a mechanical interlocking system b a complete source-changeover assembly.

Possible positions
Normal Replacement Sourcechangeover
By keylock Mechanical Complete assembly

 0 INS40160
b -

0 

0 0

INS250
b b b

INS320630 INS630b2500
b b b b -

INV100250 INV320630

DB0556

Interlocking of two devices using keylocks and a captive key


Interlocking is based on two identical keylocks with a single key and a keylock adapter (different for each device). This solution enables interlocking between two devices that are physically distant or that have very different characteristics.

DB077

Interlocking of two devices with rotary handles


The direct or extended rotary handles are padlocked with the devices in the OFF position. The mechanism prevents simultaneous closing of the devices, but allows them to be opened. Possible combinations of "Normal" and "Replacement" source INS40 to 160 switch-disconnectors "Normal N"
Interpact INS (1) INS40 Ratings 40 A INS63 Ratings 63 A INS80 Ratings 80 A INS100 Ratings 00 A INS125 Ratings 5 A INS160 Ratings 60 A

"Replacement" R
INS40 b b b b b b INS63 b b b b b b INS80 b b b b b b INS100 b b b b b b INS125 b b b b b b INS160 b b b b b b

(1) With extended rotary handles only.


DB0557

Possible combinations of "Normal" and "Replacement" source INS/INV100 to 250 switch-disconnectors "Normal N"
Interpact INS /INV (2) INS250-100/INV100 Ratings 00 A INS250-160/INV160 Ratings 60 A INS250-200/INV200 Ratings 00 A INS250-250/INV250 Ratings 50 A INS320/INV320 Ratings 30 A INS400/INV400 Ratings 400 A INS500/INV500 Ratings 500 A INS630/INV630 Ratings 630 A

"Replacement" R
INS250-100 INV100 b b b b v INS250-160 INV160 b b b b INS250-200 INV200 b b b b INS250-250 INV250 b b b b v

v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system. (2) Possible with INV, but visible-break function is significantly impaired.

A-40

Functions and characteristics

Manual source-changeover systems

Interlocking of two devices with rotary handles


DB0557

Possible combinations of "Normal" and "Replacement" source INS/INV320 to 630 switch-disconnectors "Normal N"
Interpact INS /INV (1) INS250-100/INV100 Ratings 00 A INS250-160/INV160 Ratings 60 A INS250-200/INV200 Ratings 00 A INS250-250/INV250 Ratings 50 A INS320/INV320 Ratings 30 A INS400/INV400 Ratings 400 A INS500/INV500 Ratings 500 A INS630/INV630 Ratings 630 A

"Replacement" R
INS320 INV320 v INS400 INV400 v INS500 INV500 v INS630 INV630

v b b b b b b b b b b b b

v b b b b

v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system. (1) Possible with INV, but visible-break function is significantly impaired.

DB0558

Complete source-changeover assembly for two switch-disconnectors


These assemblies provide an easy way to implement source changeover functions with:

b a single 3-position rotary handle that controls the two switch-disconnectors (Normal source ON, OFF, Replacement source ON) b a smaller size, taking up less room in the switchboard.
A complete source changeover assembly can be ordered with a single catalogue number.

Possible combinations of "Normal" and "Replacement" source switch-disconnectors "Normal N"


INS250-100 Ratings 00 A INS250-160 Ratings 60 A INS250-200 Ratings 00 A INS250-250 Ratings 50 A INS320 Ratings 30 A INS400 Ratings 400 A INS500 Ratings 500 A INS630 Ratings 630 A

"Replacement" R
INS250- INS250- INS250- INS250- INS320 INS400 INS500 INS630 100 160 200 250 b b b b b b b b

A-4

Functions and characteristics

Connection accessories

With Interpact INS/INV switch-disconnectors, it is easy to create a large number of series pole arrangements using prefabricated connections mounted on site during equipment installation.

Series connection of poles for direct current applications


Examples of series connection
Three-pole devices
DB594 DB595

DB04468

One type of connection per framesize, two catalogue numbers for all series connections.
DB596

Four-pole devices
DB597

b Indifferent connection of polarities, from left to right or right to left. b Indifferent connection of upstream and downstream cables to top or bottom terminals. b Series connection of poles is possible by upstream/ downstream connections. Creation of the connections is the responsibility of the panel builder or the installer.

Great flexibility for connections

DB598

Indifferent connection of polarities.

DB599

Upstream/downstream connections to top or bottom connectors.

DB600

Series connection of poles is possible by upstream/downstream connections (user made).

A-4

Functions and characteristics

Connection accessories

The exceptional performance levels of Interpact INS/ INV switch-disconnectors mean the poles can be parallel connected. This technique virtually doubles, triples or quadruples the current rating depending on the type of circuit breaker and thus reduces the cost of solutions.
DB60

Parallel connection of poles for direct current applications


Examples of parallel connection
Three-pole devices

DB04485

Parallel pole connection accessories are identical to those for series connections. The are equipped with heat sinks. Customer connections are made directly to the connection plates after removing the heat sinks.

DB04486

Four-pole devices (2 x 2 poles in parallel) Specific connections are required for parallel connection of three poles.
DB60

It is possible to mix series and parallel connections

DB605

Note: creation of the additional connection (1) is the responsibility of the panel builder or the installer.

Great flexibility for connections b Indifferent connection of polarities, from left to right or right to left. b Indifferent connection of upstream and downstream cables to top or bottom terminals.

A-43

Functions and characteristics

Connection accessories

Solutions depending on the distribution system and the voltage


Type of distribution system
Type Source Protected polarities Diagrams, connection method Earthed One polarity (negative here) connected to earth (or exposed conductive parts) Isolated

 (disconnection of P)
DB0864

 (disconnection of P)
DB0865

Mid-point connected to earth 


DB0866

Isolated polarities 
DB0867

Series connection of poles


Selection of switch-disconnectors and pole connection
Interpact INS/INV 24 V y Un y 125 V
DB0869 DB08589 DB08590 DB0859

Two-pole (1). 125 V < Un y 250 V


DB606

Three-pole.

Two-pole (1).

Four-pole. Not applicable

DB0859

Four-pole.

Four-pole.

Four-pole.

(1) A 3P switch-disconnectors can be used if a 2P version does not exist. In this case, the central pole is not connected.

Parallel connection of poles


Selection of switch-disconnectors and pole connection
Interpact INS/INV Un y 63 V
DB086 DB0863 DB0863 DB0863

Two, three-pole, 2, 3P in parallel, four-pole, 4P in parallel. 63 V < Un y 125 V


DB0865

Four-pole, 2 x 2P in parallel.

Four-pole, 2 x 2P in parallel.

DB0859

Four-pole, 2 x 2P in parallel.

Not applicable
DB0863

Not applicable

Four-pole, 2 x 2P in parallel, connected in series.

Four-pole, 2 x 2P in parallel.

A-44

Functions and characteristics

Connection accessories

One-piece spreader
Connection of large cables may require an increase in the distance between the switch-disconnector terminals. The one-piece spreader is an accessory that can also be fitted on Compact NSX/NS circuit breakers. It offers the following features: b increases the pitch of the switch-disconnector terminals to correspond to that of the upstream device b compatible with all the connection and insulation accessories available for the upstream device (connectors, terminal extensions, etc.) b enhances insulation between phases in comparison with standard spreaders. INS250 INS320 to 630 INV100 to 250 INV320 to 630
Pitch without spreaders (mm) Pitch with standard spreaders (mm) Pitch with one-piece spreader (mm) 35 45 45 45 5.5 or 70 056384b-56 DB05495

One-piece spreader.

Mounting
When equipped with a one-piece spreader, INS and INV switch-disconnectors may be installed either at the back of a switchboard or on the front panel with a front alignment base. b Devices with different frame sizes can thus be aligned in the switchboard. b The same mounting plate can be used for all devices (including Compact NSX/NS circuit breakers).
Connection and insulation accessories are identical to those for Compact NSX/NS.
DB05496 DB05497

Mounting at the back of a switchboard.

Mounting on the front panel with a front alignment base.

A-45

Functions and characteristics

Connection accessories

Multi-stage distribution block 125 A


PD39094Ra_SE

Electrical characteristics: b rated operating current: Ie (40 C) = 5 A b rated insulation voltage: Ui = 500 V b rated short-time withstand current: Icw = 3.5 kA rms/s b peak withstand current: Ipk = 0 k b rated impulse withstand voltage: Uimp = 8 kV. Mounting: b clipped onto Multifix or symmetrical rail b screwed on plain or slotted plate. Supplied with: b transparent, insulating cover b mounting hardware.

0453b-3

DB0735

Distribution block 125 to 160 A


PD390600Ra_SE DB0687

Distribloc 125 A.

General
Downstream circuits are connected from the front, to spring terminals. Contact pressure automatically adapts to the size of the conductor. It does not depend on the operator. Contacts are insensitive to vibrations and thermal variations. Only one cable (flexible or rigid, without a metal ferrule) can be inserted in a spring terminal. Degree of protection: IPxxB.
Cable connection.
DD38399

Advantages: b a reliable electrical connection, no maintenance required (tightness guaranteed over time) b very fast connection b easy phase balancing b rewiring is very easy if the switchboard is expanded or modified.

A-46

Functions and characteristics

Connection accessories

Distribution block 125 to 160 A


Made up of: b a fully insulated, one-piece distribution block complying with the degree of protection IPxxB (protection against direct contacts) b a modular cover. The design of the front (45 mm nose) blends perfectly into a row comprising modular devices. Electrical characteristics b Rated insulation level: Ui = 750 V. b Rated operational current Ie (40 C): v 5 A for the 5 A Distribloc v 60 A for the 60 A Distribloc with its prefabricated connection for INS60. b Short-circuit withstand current: the reinforced breaking capacity due to cascading in circuit-breaker combinations is maintained. The worst-case situations have been tested. b Complies with the low-voltage device standard IEC 60947.7. and/or IEC 60439.. b Impulse withstand voltage Uimp = 8 kV. Supply b Tunnel terminal on 5 A Distribloc 5 for 6 to 35v flexible cables (0 to 35v rigid cables). b The 60 A Distribloc is supplied with a prefabricated flexible connection. It is designed for an INS00/60 switch-disconnector, installed on the left or right. Distribution (5 and 60 A Distribloc) b Spring terminals: v  outgoers from  to 0v, flexible or rigid v 3 outgoers from  to 6v, flexible or rigid v 7 outgoers from  to 4v, flexible or rigid. b Tunnel terminals: v  outgoer from 4 to 6v, flexible (4 to 5v rigid). Supply b An identification label. b Adhesive labels for phase identification. b A prefabricated flexible connection for the INS60 (60 A Distribloc only).
PD39065R_L0_SE PD390657R_L7_SE

DB07343

Accessories
PD390658a

b Set of four flexible connections, 35v, L = 0 mm. To supply a 5 A Distribloc from an NG5 or an INS5.

A-47

Functions and characteristics

Connection accessories

250 A Polybloc distribution block


PD390549a

General
Downstream circuits are connected from the front, without screws, to spring terminals. Contact pressure automatically adapts to the size of the conductor (minimum size =  mm). Contacts are insensitive to vibrations and thermal variations. Only one cable (flexible or rigid, without a metal ferrule) can be inserted in a spring terminal. Degree of protection: IPxxB. Advantages of spring terminals b A reliable electrical connection, no maintenance required. b The fast connections make phase balancing very easy. b Rewiring is very easy if the switchboard is expanded or modified. Applications The Polybloc distribution block is designed for installation directly downstream of Compact circuit breakers and Interpact switch-disconnectors devices up to 50 A. It can be rapidly mounted in the horizontal position. Electrical connections are made directly to the device terminals. It has the same width as the devices and does not take up any additional space in the switchboard. The connection terminals are slanted to facilitate cable entry and not exceed the bending radius of the flexible and rigid cables. Electrical characteristics The electrical characteristics are perfectly compatible with the connected devices. Neither the temperature derating curves nor the performance levels of the circuit breakers and switch-disconnectors are altered. b Rated insulation level Ui = 750 V. b Short-circuit withstand current: the reinforced breaking capacity due to cascading in circuit-breaker combinations is maintained. The worst-case situations have been tested. b Impulse withstand voltage Uimp = 8 kV. Supply Directly to the terminals of the Compact NSX/NS and Interpact INS devices up to 50 A. Distribution Via cables, up to six 0 mm cables and three 6 mm cables per phase. Installation Directly on the mounting plates of horizontally mounted Compact NSX/NS00/50 and Interpact INS50 devices in the enclosures. It can also be mounted downstream of vertically mounted Compact NSX/NS00/50 and Interpact INS50 devices in the enclosures. In this case, the Polybloc is mounted on a depth-adjustable modular rail (0300 System G) or (0340 System P).

DB07345

DD38399

Vertically mounted Polybloc on a depth-adjustable modular rail (03402) in a cubicle (System G).

DB07347

b Special connection blocks can be added to Polybloc 50 A distribution blocks for connection of two 35 mm cables per phase via screw terminals.

Accessories

A-48

Functions and characteristics

Connection accessories

160 A Polybloc distribution block


The 60 A Polybloc is made up of individual elements that can be used alone or with others to make two-pole, three-pole or four-pole distribution blocks. Mounting is very fast. It clips onto a modular rail and is supplied by cables via a tunnel terminal. The connection spring terminals are slanted to facilitate cable entry and bending of the flexible and rigid cables. It is supplied with a cover that also guides the cables. Electrical characteristics b Rated insulation level Ui = 750 V. b Short-circuit withstand current: the reinforced breaking capacity due to cascading in circuit-breaker combinations is maintained. The worst-case situations were tested. The electrical characteristics are perfectly compatible with the connected devices. Neither the temperature derating curves nor the performance levels of the circuit breakers and switch-disconnectors are altered. b Impulse withstand voltage Uimp = 8 kV. Supply Direct to a tunnel terminal, for cables up to 70 mm. Distribution Via cables, up to six 6 mm cables. Installation The blocks clip onto a modular rail.
DD383493

Three 160 A Polybloc distribution blocks in the vertical position on a modular rail, supplied by an INS160.

DD3839

160 A Polybloc distribution block in a front plate cut-out.

A-49

Functions and characteristics

Connection accessories

Insulation of live parts


056063Rc-57_SE

Terminal shields for INS and INV switch-disconnectors


Lead-sealable insulation accessories used to protect against direct contact with power circuits. b Degree of protection: IP40, IK07. b Supplied with lead-sealing accessories. b Safety accessories providing maximum insulation between the phases of the power connection. b Easy installation by snapping into the case. b May be combined with all other connection accessories, except the terminal shields and terminal shrouds.

Interphase-barrier for INS/INV

DB05498

Terminal shields for Interpact INS and INV.

Terminal shrouds for INS40 to INS160


These insulation accessories are used for protection against direct contact with live connection screws. It is also possible to attach an insulating plate (not supplied) to the shrouds to avoid any contact with the power conductors.
DB05499

Spare viewport for Interpact INV switchdisconnectors


Viewports are darkened by the electrical arc. A new viewport may be installed to maintain the visible-break function. If 500 V y U y 690 V, interphase-barrier or long terminal shields are mandatory.
DB05500

Interphase-barrier for Interpact INS and INV.

Terminal shrouds for Interpact INS40 to 160 (with insulating plate to avoid contact with the conductors).

DB0550

Spare viewport for Interpact INV.

A-50

Functions and characteristics

Connection accessories

DB055

Coupling accessory for complete source-changeover assembly


This accessory simplifies connection of bars or cables with lugs when coupling two Compact NSX/NS00 to 630 circuit breakers or two Interpact INS/INV00 to 630 switch-disconnectors of the same size. Pitch between outgoing terminals: b Interpact INS50 and INV00 to 50: 35 mm b Interpact INS/INV30 to 630: 5.5 mm b Compact NSX/NS00 to 50: 35 mm b Compact NSX/NS400 to 630: 5.5 mm.

Connection and insulation accessories


The coupling accessory may be fitted with the same connection and insulation accessories as the coupled circuit breakers or switch-disconnectors.

Possible combinations
Manual source-changeover
INS50 (00 to 50 A) with rotary handle NSX/NS00/50 with rotary handle NSX/NS00/50 on mounting plate with toggle INS400/630 (30 to 630 A) with rotary handle NSX/NS400/630 with rotary handle NSX/NS400/630 on mounting plate with rotary handle

Downstream coupling
Possible
b b b b b b b b b b

Pitch of outgoing terminals (mm)


35 35 35 5.5 5.5 5.5 35 5.5 35 5.5

Complete source-changeover assembly


INS50 (00 to 50 A) complete assembly INS400/630 (30 to 630 A) complete assembly

Remote-operated source-changeover
NSX/NS00/50 NSX/NS400/630

A-5

Functions and characteristics

Installation

Interpact INS and INV switch-disconnectors offer a number of rational installation solutions to optimise available space inside enclosures. They may be installed in individual enclosures or as incomers in power distribution or control panels. b Interpact INS40 to 60 switch-disconnectors have a standard 45 mm high front and may be clipped onto a Multifix or symmetrical rail. They may be installed in all Multi 9 modular enclosures, including Pragma, Prisma, etc. b Interpact INS50 to 630 and INV00 to 630 switch-disconnectors may be installed on mounting plates or rails. Installation as incomers in Prisma power distribution cubicles is very flexible: b the mounting plates are the same as those used for Compact NSX/NS circuit breakers and are identical for direct and extended handles b installation in 300 mm ducts is possible for ratings up to 630 A.

05760b-39

Local isolation enclosure.

Individual enclosures

b Each individual enclosure includes: v a door with a cut-out v a mounting plate v accessories required for extended front or lateral rotary handle v removable plates (without holes) for cable entry. The Interpact INS switch-disconnector must be order separately.

PD390446_L65_SE

DB05446

Heavy-duty individual enclosure (sheet metal or plastic).

Pragma modular enclosures

b The enclosures in the Pragma range are: v made of self-extinguishing insulating material v supplied with all accessories (terminal blocks, blanking plates, etc.) v rated class .

DB05447

Interpact INS40 on a symmetrical rail.

Power distribution incomer in a Prisma cubicle.

Prisma metal cubicles and enclosures


PD395007_L60_SE

b The metal cubicles and enclosures in the Prisma range are highly adaptable to the type of installation: v basic cubicle or enclosure v multifix rail v modular front plates v distribution accessories v ducts for running cables or installing terminals v plain or transparent doors.

DB05448

Installation in a 300 mm duct.

Power distribution incomer in a Prisma Plus System G IP55 cubicle.

A-5

Functions and characteristics

Installation

Front-panel escutcheons
Escutcheons for switch-disconnectors and ammeter modules Mounted on switchboard panel from the front using four screws.

DB0559

Escutcheon for switch-disconnectors.

DB0550

Escutcheon for ammeter modules.

Identification labels
Interpact INS40 to 60 switch-disconnectors may receive Telemecanique prefabricated labels, catalogue number AB- (eight characters). Interpact INS50 to 630 and INV00 to 630 switch-disconnectors are supplied as standard with a clip-on label for handwritten indications. These devices also come with a nameplate into which a label can be inserted.

DB055

Individual enclosures
Interpact INS and INV switch-disconnectors equipped with a front handle may be installed in individual enclosures. All fixed, front connections are possible, except right-angle and edgewise terminal extensions. Spreaders may be installed in the enclosures intended for Interpact INS50 to 630 and INV00 to 630 switch-disconnectors. Heavy-duty metal individual enclosure for Interpact INS (IP55, IK08) b metal enclosure b door with keylock and cut-out for switch-disconnector rotary handle b extended rotary front handle b device mounting plate b removable plate (without holes) for cable entry through bottom. Heavy-duty insulating individual enclosure for Interpact INS and INV (IP55, IK08) b thermoplastic enclosure b transparent cover, screwed, lead sealable, with cut-out for switch-disconnector rotary handle b extended rotary front handle b device mounting plate b removable plates (without holes) for cable entry through bottom and/or top. Dimensions Metal enclosures
Interpact INS40 to 60 Interpact INS50 Interpact INV00 to 50 Interpact INS30 to 630 Interpact INV30 to 630
678b-35

HxWxD
350 x 350 x 60 450 x 350 x 60 650 x 350 x 60

Insulating enclosures
Interpact INS40 to 60 Interpact INS50 Interpact INV00 to 50 Interpact INS30 to 630 Interpact INV30 to 630

HxWxD
80 x 70 x 85 360 x 70 x 35 70 x 360 x 35

A-53

TOOLS
schneider-electric.com CAD software and tools

This international site allows you to access all the Schneider Electric products in just  clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts

The CAD software and tools enhance productivity and safety. They help you create your installations by simplifying product choice through easy browsing in the Schneider Electric offers. Last but not least, they optimise use of our products while also complying with standards and proper procedures.

Interpact INS/INV

Installation recommendations

Presentation Functions and characteristics

2 A-1

Operating principle Possible installation positions and mounting techniques Implementation Interpact INS40 to 80 Interpact INS100 to 160

B-2 B-4 B-5 B-6 B-7

Interpact INS250-100 to 250 Interpact INV100 to 250 Complete source-changeover assembly INS250-100 to 250 B-8 Interpact INS320 to 630 Interpact INV320 to 630 Complete source-changeover assembly INS320 to 630 Interpact INS630b to 1600 Interpact INV630b to 1600 Interpact INS2000 to 2500 Interpact INV2000 to 2500 Use at high temperatures
Dimensions and connection Complementary technical information Catalogue numbers

B-12 B-16 B-20 B-22


C-1 D-1 E-1

B-

Installation recommendations

Operating principle

INS40 to 250 - INV100 to 250


DB954

INS320 to 630 - INV320 to 630


DB05607

B-

Installation recommendations

Operating principle

INS630b to 2500 - INV630b to 2500


DB05608

B-3

Installation recommendations

Possible installation positions and mounting techniques

Possible installation positions


DB05609 DB0560 DB056 DB0563

DB056

Possible mounting
INS40 to 160

DB0564

DB0565

Symmetrical rail.

Plain mounting plate.

DB0566

Slotted mounting plate.

INS250-100 to 630 - INV100 to 630

DB0567

DB05609

Rails.

Plain mounting plate.

DB0568

Slotted mounting plate.

INS/INV630b to 2500

DB0569

Rails.

DB0560

Plain mounting plate.

B-4

Installation recommendations

Implementation

Reverse supply
DB056

Interpact switch-disconnectors may be supplied indifferently via the top or bottom terminals, without any reduction in performance.

Neutral pole position


On Merlin Gerin switch-disconnectors, the neutral pole is traditionally located on the left-hand side. On the INS and INV ranges, the four poles are identical and the neutral pole can therefore be located on the right-hand side simply by adding an appropriate label.

Conductor materials and electrodynamic forces


Interpact switch-disconnectors may be connected using either bare copper, tinned copper or tinned aluminium conductors (flexible or rigid bars, cables). In the event of a short-circuit, thermal and electrodynamic forces are exerted on the conductors. The conductors must therefore be adequately sized and suitably supported. Note that the terminals of electrical devices (switch-disconnectors, contactors, circuit breakers, etc.) should not be considered to contribute to the support of the conductors.
DB06835

Cables ties and flexible bars


The table below indicates the maximum distances between cable ties depending on the prospective short-circuit current. Care must be taken not to exceed a distance of 400 mm between ties mechanically secured to the switchboard frame. Type of tie "Panduit" type Width: 4.5 mm Max. load: 22 kg Colour: white
00 7

"Sarel" type Width: 9 mm Max. load: 90 kg Colour: black


00 35 70 45 50 (double ties) 00

00 50 350 Max. distance between 00 ties (mm) Short-circuit current 0 5 0 0 (kA rms) Note: for cables u 50 mm, 9 mm wide ties must be used.

B-5

Installation recommendations

Interpact INS40 to 80

Front connection of bare copper and aluminium cables


Interpact INS40 to INS80 switch-disconnectors are equipped as standard with connectors for bare copper or aluminium cables (.5 to 50 mm rigid cables, .5 to 35 mm flexible cables) Distribution connector This connector screws directly into the switch-disconnector terminals for connection of three cables of the following types: b  to 0 mm flexible cables (1) b .5 to 6 mm rigid cables.
DB06838 DB05450 DB0545

Pole pitch
8 mm

Standard device
Distribution connector.
DB0676

With distribution connector


3

Bars

e (mm) L (mm)

y 5 3

y 0 L (mm) y 0 S (mm) .5 to 50 rigid .5 to 6 rigid Cu / Al .5 to 35 flexible  to 0 flexible (1) Torque (Nm) 5  (1) Connection of 1.5 to 4 mm flexible cables requires crimped or auto-crimping ferrules. Lugs

If 500 V y U y 690 V, long terminal shields are mandatory.

Insulation of live parts


b With long terminal shields. b With terminal shrouds.

DB0545

Terminal shields.

DB0684

Terminal shrouds.

B-6

Installation recommendations

Interpact INS100 to 160

DB05453

DB05454

Front connection of insulated bars and cables with crimped lugs


Interpact INS00 to INS60 switch-disconnectors are equipped as standard with terminals comprising nuts with M6 screws for direct connection of insulated bars or cables with lugs. Lugs The special lugs for copper cables may be used for cables with cross-sectional areas up to 95 mm. Secure the lugs by hexagonal crimping or punching. Lugs are supplied with interphase-barrier and are compatible with the terminal shields.

DB06839

Pole pitch
30 mm Lug.
DB07386

Dimensions
Bars d (mm) e (mm) L (mm) L (mm) (mm) (Nm) y 0 6.4 y  5 u 6. 8

Lugs Torque

b -cable connectors snap directly onto the device terminals ( to 0 mm flexible cables (1)) b Distribution connectors for 4 flexible cables (.5 to 5 mm rigid cables or .5 to 6 mm flexible cables (1)) are screwed directly to the device terminals. These connectors are supplied with interphase-barrier (mandatory installation) which may be replaced by long terminal shields b Distribloc distribution block supplied via tunnel terminals. Provides  screwless spring type and  screw type outgoing terminals. 1-cable connector Distribution connector
5 .5 to 5 rigid .5 to 6 flexible (1) 3

Front connection of bare copper and aluminium cables

DB05456

DB05459

DB05459

DB05457

DB05630

Lugs

1-cable connector.

Distribution connector.

Torque Torque

L (mm) S (mm) Cu / Al (Nm) (Nm)

5 .5 to 35 rigid 50 to 95 rigid .5 to 35 flexible (1) 50 to 95 flexible 0 

Distribloc
Supply: 5 Nm Distribution: 3 Nm (1) Connection of 1.5 to 4 mm flexible cables requires crimped or auto-crimping ferrules.

100
DB603 DB07340

75

127

2 4

48

108

9 Multi-stage distribution block.

Distribloc 125 and 160 A.

If 500 V y U y 690 V, interphase-barrier or long terminal shields are mandatory.

b With long terminal shields. b With terminal shrouds. b Interphase-barrier: v distribution blocks, lugs, right-angle/straight/edgewise terminal extensions and spreaders are supplied with interphase-barrier v interphase-barrier may be positioned horizontally or vertically v they may be replaced by long terminal shields.

Insulation of live parts

DB0545

DB0684

Terminal shields.

Terminal shrouds.

DB06843

Interphasebarrier.

B-7

Installation recommendations

Interpact INS250-100 to 250 Interpact INV100 to 250 Complete source-changeover assembly INS250-100 to 250
Front connection of bare copper and aluminium cables
Bare-cable connectors for Interpact INS/INV switch-disconnectors may be used for both copper and aluminium cables. 1-cable connectors The connectors snap directly on to the device terminals or clip onto right-angle and straight terminal extensions as well as spreaders. These connectors are supplied with interphase-barrier. Material: steel I y 60 A and tinned aluminium I y 50 A. 6-cable distribution connectors These connectors are screwed directly to device terminals. These connectors are supplied with interphase-barrier (mandatory installation) which may be replaced by long terminal shields. Each connector can receive six cables with cross-sectional areas ranging from .5 to 35 mm each. Material: tinned aluminium. Polybloc distribution blocks, for 6 or 9 rigid or flexible cables The Polybloc connects directly to the device terminals and is used to connect up to six or nine flexible or rigid cables with cross-sectional areas not exceeding 0 mm, to each pole. Connection is made to spring terminals without screws. 1-cable connector
L (mm) S (mm) Cu / Al Torque (Nm)

DB05456

DB0569

DB0569

Steel y 160 A
0 .595 (1)  5 or 30 .56 (1) 4

Aluminium y 250 A
0 550 0 7095 6 085 6

DB05474

DB05477

Distribution connector, 6 cables Cu or Al


L (mm) S (mm) Cu / Al Torque (Nm) Distribution connector. 835 6

Polybloc distribution block, 6 or 9 cables


1-cable connector. L (mm)  S (mm) Cu / Al .50 (1) Connection of 1.5 to 4 mm flexible cables requires crimped or auto-crimping ferrules.

DB07346

Polybloc 250 A distribution block.

DB0563

Distribution connector, 6 cables


DB0735 DB05634

Polybloc 160 A.

B-8

DB05633

Dimensions -cable connector

Installation recommendations

Interpact INS250-100 to 250 Interpact INV100 to 250 Complete source-changeover assembly INS250-100 to 250
Front connection of insulated bars and cables with crimped lugs
Interpact INS50-00 to INS50 and INV00 to 50 switch-disconnectors are equipped as standard with terminals receiving snap-in nuts and M8 screws for direct connection of insulated bars or cables with lugs. Lugs b The small lugs for copper cables may be used for cables with the following crosssectional areas 0, 50 or 85 mm (secure the lugs by hexagonal crimping or punching). b The small lugs for aluminium cables may be used for cables with the following cross-sectional areas 50 or 85 mm (secure the lugs by hexagonal crimping). Pole pitch

DB05453

DB05635

DB0569

35 mm

Dimensions
Bars Small lugs for copper cables.
DB0567

Lugs
DB05477

Torque

d (mm) e (mm) L (mm) (mm) L (mm) (mm) (Nm)

y 0 y6 y 5 u 0 y 5 u 0 5

Small lugs for aluminium cables.


DB05636

Dimensions

DB0566

Bar.

If 500 V y U y 690 V, interphase-barrier or short or long terminal shields are mandatory.

Terminal shields.

b With short or long terminal shields. b Interphase-barrier: v distribution blocks, lugs, right-angle/straight/edgewise terminal extensions and spreaders are supplied with interphase-barrier v interphase-barrier may be positioned horizontally or vertically v they may be replaced by long terminal shields. b One-piece spreader: the one-piece spreader increases the pitch to correspond to that of the upstream device and provides protection against direct contact (see page A-45).

Insulation of live parts

DB05637

Interphase-barrier.

DB0547

DB0545

One-piece spreader.

B-9

Installation recommendations

Interpact INS250-100 to 250 Interpact INV100 to 250 Complete source-changeover assembly INS250-100 to 250
Front connection with accessories
DB0676

Straight terminal extensions Material: tinned copper.


DB05467

DB05453

DB05635

Right-angle extensions Material: tinned copper.

Connection of two cables with lugs.

Insulation stripping lengths and tightening torques for cables, bare bars and cables with lugs are identical to those for direct connection to devices. Spreader Material: tinned copper.
DB05470

DB0676

Separate parts.

Connection of two cables with lugs.

DB06763

DB05466

One-piece spreader.

Pole pitch
45 mm

Dimensions
Bars
DB0567

Lugs Torque

d (mm) e (mm) L (mm) (mm) L (mm) (mm) (Nm)

y 0 y6 y 5 8.5 y 5 8.5 5 (1)

(1) Tightening torque for spreader.

Spreaders, straight terminal extensions and right-angle terminal extensions are supplied with interphase-barrier. Dimensions Spreader and straight terminal extensions

Right-angle terminal extensions


DB06764 DB06765

One-piece spreader 3P/4P


DB06766

B-0

Installation recommendations

Interpact INS250-100 to 250 Interpact INV100 to 250 Complete source-changeover assembly INS250-100 to 250
Rear connection
The rear connections are simply fitted to the device connection terminals. All combinations of rear connection lengths and positions are possible on a given switch-disconnector. The switch-disconnector is mounted on a backplate. For the connection of cables without lugs, the -cable connectors for Interpact INS00-50 to INS50 and INV00 to 50 may be simply clipped onto the rear connections. Bars or cables with crimped lugs Interpact INS50-00 to INS50 and INV00 to 50 switch-disconnectors may be equipped with long or short rear connections, or a mix of the two. The connections may be positioned flat, on edge or at 45 angles, or any combination thereof. Material of rear connections: tinned copper. Pole pitch
35 mm
DB0567

DB05453

DB06769

DB06768

Connection of bars or cables with lugs.


DB0566

Dimensions
Bars d (mm) e (mm) L (mm) (mm) L (mm) (mm) (Nm) y 0 y6 y 5 u8 y 5 u8 5 (1)

Lugs Bar. Torque

DB05480

(1) Tightening torque for rear connections.

Dimensions
DB06836

Two lenghts.

DB06855

Four positions.

Bare cables (copper or aluminium) The rear connections may be equipped with -cable connectors secured by clips.
DB06773

1-cable connector Steel y 160 A


DB05630

Aluminium y 250 A
0 085 6

L (mm) S (mm) Cu / Al Torque (Nm)

0 .595 (1) 

Distribution connector, 6 cables Cu or Al


L (mm) 5 or 30 S (mm) Cu / Al .56 (1) 835 Torque (Nm) 4 6 (1) Connection of 1.5 to 4 mm flexible cables requires crimped or auto-crimping ferrules.

Insulation stripping lengths and tightening torques for cables, bare bars and cables with lugs are identical to those for direct connection to devices.
DB0677

Rear connection with bar.

B-

Installation recommendations

Interpact INS320 to 630 Interpact INV320 to 630 Complete source-changeover assembly INS320 to 630
Front connection of bare copper and aluminium cables
Bare-cable connectors for Interpact INS/INV switch-disconnectors may be used for both copper and aluminium cables. 1-cable and 2-cable connectors -cable and -cable connectors, made of tinned aluminium for copper and aluminium cables, are screwed to the device terminals or to right-angle terminal extensions. These connectors are supplied with interphase-barrier. 1-cable connector
DB05630

DB05456

DB06774

2-cable connector
3

Torque (Nm)

3

DB05475

1-cable connector.

Dimensions
DB0686

DB05476

2-cable connector.

-cable connector
DB0774 DB06775

-cable connector
DB0775 DB06777

B-

Installation recommendations

Interpact INS320 to 630 Interpact INV320 to 630 Complete source-changeover assembly INS320 to 630
Front connection of insulated bars and cables with crimped lugs
Interpact INS30 to 630 and INV30 to 630 switch-disconnectors are equipped as standard with terminals receiving snap-in nuts and M0 screws for direct connection of bars or cables with lugs. Lugs b The small lugs for copper cables may be used for cables with the following crosssectional areas 40 or 300 mm (secure the lugs by hexagonal crimping or punching). b The small lugs for aluminium cables may be used for cables with the following cross-sectional areas 40 or 300 mm (secure the lugs by hexagonal crimping). Pole pitch
45 mm

DB05453

DB06779

Dimensions
Bars
DB0569 DB0567

Small lugs for copper cables.

Lugs Torque

d (mm) e (mm) L (mm) (mm) L (mm) (mm) (Nm)

y 5 3 y e y 0 y 3 u 0 y 3 u 0 50

DB05477

Small lugs for aluminium cables.


DB06780

Dimensions

DB0566

Bar.

If 500 V y U y 690 V, interphase-barrier or short or long terminal shields are mandatory.

b With short or long terminal shields. b Interphase-barrier: v distribution blocks, lugs, right-angle/straight/edgewise terminal extensions and spreaders are supplied with interphase-barrier v interphase-barrier may be positioned horizontally or vertically v they may be replaced by long terminal shields.

Insulation of live parts

DB05637

DB0545

Terminal shields.

Interphase-barrier.

B-3

Installation recommendations

Interpact INS320 to 630 Interpact INV320 to 630 Complete source-changeover assembly INS320 to 630
Front connection with accessories
Spreader Material: tinned copper. Edgewise terminal extensions Material: tinned copper. Right-angle extensions Material: tinned copper. Installation on upstream terminals.
DB06784

DB05453

DB06767

DB0678

Pole pitch
Without spreader With spreader 45 mm 5.5 or 70 mm

Dimensions
DB0566 DB0567

DB06783

With spreader
Bars d (mm) e (mm) L (mm) (mm) L (mm) (mm) (Nm) y 5 3 y e y 0 y 3 > 0.5 y 3 0.5 50 (1)

With edgewise terminal ext.


y 5 3 y e y 0 y 3 > 0.5 y 3 0.5 50 (1)

Bar. Lugs Torque

(1) Tightening torque for spreader.

Spreaders, straight terminal extensions and right-angle terminal extensions are supplied with interphase-barrier. Dimensions Edgewise terminal extensions
DB07387 DB06786

Right-angle terminal extensions

Spreader
DB55

Type
Spreader Width in mod. of 5.5 mm Width in mod. of 70 mm

K8
5.5 70

K9
87.5 40

K10
35 70

K11
39 5.5

K12
4.5 56

B-4

Installation recommendations

Interpact INS320 to 630 Interpact INV320 to 630 Complete source-changeover assembly INS320 to 630
Rear connection
The rear connections are simply fitted to the device connection terminals. All combinations of rear connection lengths and positions are possible on a given switch-disconnector. The switch-disconnector is mounted on a backplate. Bars or cables with crimped lugs Interpact INS30 to 630 and INV30 to 630 switch-disconnectors may be equipped with long or short rear connections, or a mix of the two. The connections may be positioned flat, on edge or at 45 angles, or any combination thereof. Material of rear connections: tinned copper. Dimensions
Bars d (mm) e (mm) L (mm) (mm) L (mm) (mm) (Nm) y 5 3 y e y 0 y 3 > 0.5 y 3 u 0.5 0 (1)

DB05453

DB06769

DB06768

Lugs
DB0567

Connection of bars or cables with lugs.


DB0566

Torque

(1) Tightening torque for rear connections. Bar.

Dimensions
DB06789 DB06837

Two lenghts.

DB06855

Four positions.

DB0677

DB0679

Bare cables (copper or aluminium) The rear connections may be equipped with -cable connectors secured by clips. Insulation stripping lengths and tightening torques for cables, bare bars and cables with lugs are identical to those for direct connection to devices.

Rear connection with bar.

B-5

Installation recommendations

Interpact INS630b to 1600 Interpact INV630b to 1600

Connections
There are many solutions to connect bars: b vertical connection adapters to connect edgewise bars, b spreaders with a 95 mm pole pitch to increase the clearance between bars. Spreaders Spreaders increase the pole pitch of a switch-disconnector for greater clearance between the bars. They are not compatible with terminal shields.
DB05488 DB05490 DB05483 DB05487

Spreaders.

Vertical connection adapters For connection of edgewise bars.


DB05489

Vertical connection adapters.

DB0549

Adapters for cables with crimped lugs Cable-lug adapters are used in conjunction with vertical connection adapters. They may be used to connect one to four cables (S y 300 mm) with crimped lugs. To ensure adequate mechanical strength, the cable-lug adapters must be secured together by spacers.

DB06793

Lugs for copper cables.

DB0549

Adapters for cables with crimped lugs.

2-cable connector.

Pole pitch
Without spreader With spreader 70 mm 95 mm

Dimensions

With spreader
Bars d (mm) e (mm) L (mm) (mm) L (mm) (mm) (Nm) .5 3 y e y 0 y 80  50 (1)

With vertical With cable connection lug adapters adapters


y .5 3 y e y 0 y 80 >  50 y 40 y  50 (1)

DB0567

Lugs Torque

(1) Tightening torque for spreader.

B-6

Installation recommendations

Interpact INS630b to 1600 Interpact INV630b to 1600

Front connection of insulated bars


Connection of bars Interpact switch-disconnectors are equipped with terminals for direct connection of bars.
DB05483 DB05484

If 500 V y U y 690 V, interphase-barrier or short or long terminal shields are mandatory.

DB06794

b b v v

Insulation of live parts


With terminal shields. Interphase-barrier: interphase-barrier may be positioned horizontally or vertically, they may be replaced by long terminal shields.

DB06796

Interphase-barrier.

DB06797

Terminal shield.

Compatibility of terminal shields + base for connections


Base Terminal shields Spreader Interphase-barrier Base YES NO NO Terminal shields YES NO NO Spreader YES NO YES Interphase-barrier NO NO YES -

B-7

Installation recommendations

Interpact INS630b to 1600 Interpact INV630b to 1600

Dimensions
Connection with spreaders
DB06798 DB06799 DB06800

Spreader details
DB0680 DB0680 DB06803 DB06804

For 3P switch-disconnectors.

For 4P switch-disconnectors.

Connection with vertical connection adapters


DB06805 DB06806 DB06807

Connector details
DB06808

Note: lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector. 2 connection possibilities on vertical connection adapters (21 mm between centres). Recommended connection screws: M10 class 8.8. Tightening torque: 50 Nm with contact washer.

B-8

Installation recommendations

Interpact INS630b to 1600 Interpact INV630b to 1600

Connection with vertical connection adapters


DB06809 DB0680 DB068

Cable lug adapter detail


DB068

B-9

Installation recommendations

Interpact INS2000 to 2500 Interpact INV2000 to 2500

Front connection of insulated bars


Connection of bars Interpact switch-disconnectors are equipped with terminals for direct connection of bars.
DB05483

DB05486

DB06795

Connector for connection of edgewise bars

DB06860

If 500 V y U y 690 V, interphase-barrier are mandatory.

Insulation of live parts


Interphase-barrier

B-0

DB0683

DB0686

DB06859

Installation recommendations

Interpact INS2000 to 2500 Interpact INV2000 to 2500

Dimensions
Connection with spreaders
DB0684 DB0685 DB0686

Spreader details
DB755 DB756

For 3P and 4P switch-disconnectors.

Connection with spreaders


DB757 DB07380 DB758 DB753 DB753

DB759

DB7530

Note: lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

DB7533

B-

Installation recommendations

Use at high temperatures

Power dissipated and resistance per pole


Interpact INS
Rating (A) Resistance per pole (mW) Power dissipated per pole (W)

40
40 0.3 0.5

63
63 0.3 .

80
80 0.3 .9

100
00 0. 

125
5 0. 3.

160
60 0. 5.

Interpact INS/INV
Rating (A) Resistance per pole (mW) Power dissipated per pole (W)

100
00 0.5 .5

160
60 0.5 4

200
00 0.5 6

250
50 0.5 9.5

320
30 0.06 6.

400
400 0.06 9.6

500
500 0.06 5

630
630 0.06 4

Interpact INS/INV
Rating (A) Resistance per pole (mW) Power dissipated per pole (W)

800
800 0.04 6

1000
000 0.04 4

1250
50 0.04 38

1600
600 0.04 6

2000
000 0.0 48

2500
500 0.0 75

Temperature derating
Interpact INS 40 63 80
80 80 80

100
00 00 00

125
5 5 5

160
60 60 50

Front connection with bare-cable connectors or lugs Thermal current Ith at 60 C 40 63 65 C 40 63 70 C 40 63

Interpact INS/INV

100

160

200

250
50 50 50 50 50 50 40 50 50 50 40 30 0

320
30 30 30 30 30 30 30 30 30 30 30 30 30

400
400 400 400 400 400 400 400 400 400 400 400 400 400

500
500 500 500 500 500 500 500 500 500 500 500 480 450

630
630 590 550 630 590 550 50 600 575 540 505 480 450

Front connection / rear connection Thermal current Ith at 60 C 00 60 00 65 C 00 60 00 70 C 00 60 00 Front connection with right-angle terminal extension + bare-cable connectors Thermal current Ith at 55 C 00 60 00 60 C 00 60 00 65 C 00 60 00 70 C 00 60 00 Front connection / rear connection with ammeter or CT module Thermal current Ith at 40 C 00 60 00 50 C 00 60 00 55 C 00 60 00 60 C 00 60 00 65 C 00 60 00 70 C 00 60 00

Interpact INS/INV

630b

800 with or without term. shield

1000 with or without term. shield

1250 with term. shield

without term. shield

1600 with term. shield

without term. shield

2000 with term. shield

2500 without term. shield

(1) Direct connection by flat-facing bars Thermal current Ith at 40 C 630 800 000 50 50 600 600 000 45 C 630 800 000 50 50 570 600 000 50 C 630 800 000 50 50 500 550 000 55 C 630 800 000 50 50 40 470 000 60 C 630 800 000 50 50 340 390 000 65 C 630 800 000 50 50 50 300 000 70 C 630 800 000 060 0 060 0 000 (2) Connection by flat-facing bars via spreaders, without terminal shields Thermal current Ith at 40 C 630 800 000 50 600 45 C 630 800 000 50 600 50 C 630 800 000 50 580 55 C 630 800 000 50 500 60 C 630 800 000 50 40 65 C 630 800 000 50 330 70 C 630 800 000 40 40 Connection of edgewise bars via vertical connection adapters or cables via vertical connection adapters with cable-lug adapters Thermal current Ith at 40 C 630 800 000 50 600 600 45 C 630 800 000 50 600 600 50 C 630 800 000 50 600 600 55 C 630 800 000 50 600 600 60 C 630 800 000 50 600 600 65 C 630 800 000 50 50 560 70 C 630 800 000 50 40 450 (1) INS/INV1600: 4 bars 50 x 5. (2) INS/INV1600: 3 bars 80 x 5. Note: thermal current Ith in Amps (QA).

500 500 500 500 500 500 400 -

B-

B-3

TOOLS
schneider-electric.com Training

This international site allows you to access all the Schneider Electric products in just  clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts

Training allows you to acquire the Schneider Electric expertise (installation design, work with power on, etc.) for increased efficiency and a guarantee of improved customer service. The training catalogue includes beginners courses in electrical distribution, knowledge of MV and LV switchgear, operation and maintenance of installations, design of LV installations to give but a few examples.

Interpact INS/INV

Dimensions and connection

Presentation Functions and characteristics Installation recommendations

2 A-1 B-1

Interpact INS40 to 160 Interpact INS250-100 to 630 Interpact INV100 to 630 Interpact INS250-100 to 630 Interpact INV100 to 630 Interpact INS630b to 1600 Interpact INV630b to 1600 Interpact INS2000 to 2500 Interpact INV2000 to 2500 Mechanical interlocks for direct and extended handles
INS40 to 630, INV00 to 630

C-2 C-5 C-6 C-10 C-12 C-14


C-4

Complete source changeover assembly


INS50-00 to 630, INV00 to 630

C-15
C-5

Installation of downstream coupling


INS50-00 to 630, INV00 to 630

C-16
C-6

Front-panel accessories
INS50-00 to 500, INV00 to 500

C-17
C-7

Parallel or series connection accessories for direct current


Interpact INS50-00 to 50 Interpact INV00 to 50 Interpact INS30 to 630 Interpact INV30 to 630 Complementary technical information Catalogue numbers

C-18
C-8 C-9 D-1 E-1

C-

Dimensions and connection

Interpact INS40 to 160

Dimensions
Front handle
DB0684 DB0685 DB0686

(a) Terminal shields INS40/63/80. (b) Terminal shields INS100/125/160.

Dimensions (mm)

Type
INS40/63/80 INS00/5/60

H
.5 .5

H1
45 45

H2
40.5 50

H3
8 00

H4
4.5 50

H5
85 00

H6
73.5 0

H7
47 0

K
 7.5

K1
8 30

L
46 67.5

L1
73 9

L2
90 35

P
3.3 .5

P1
43 45

P2
47 47

P3
6.5 6.5

P4
79 79

P5
5 5

Extended front handle


Dimensions (mm) Type A (on back plate) Min. Max. INS40/63/80 8 59 INS00/5/60 8 59 Type e K  7.5 B (on rail) Min. Max. 3 54 3 54 Length of shaft A - 69 A - 69
DB0565 DB05650

INS40/63/80 3 INS00/5/60 3

Door or front panel cutout for front handle Direct


DB0565 DB05653

Extended
Dimensions (mm) Type C INS40/63/80 47 INS00/5/60 47 R 9 37 K  7.5

Note: lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

C-

Dimensions and connection

Interpact INS40 to 160

Dimensions
Lateral handle
DB0564 DB0564 DB05643

Dimensions (mm)
Type INS40/63/80 INS00/5/60 L3 09 54 P6 40 4.5 P7 66. 69.3

Extended lateral handle


DB05644 DB05645

Dimensions (mm)
Type With shaft INS40/63/80 INS00/5/60 Without shaft INS40/63/80 INS00/5/60 B Min. 55 00 B 0 47 e Max. 396 44 3 3 e 3 3 P6 40 4.5 P6 40 4.5 Length of shaft B - 95 B - 40

Lateral handle for functional enclosure


DB05644 DB05646

Dimensions (mm)
Type INS40/63/80 INS00/5/60 Enclosure length 550 mm 600 mm 550 mm 600 mm Type of shaft Short Long Short Long B 49 74 94 9 e 3 3 3 3 P6 4.5 4.5 4.5 4.5

C-3

Dimensions and connection

Interpact INS40 to 160

Dimensions
Front panel cutout for extended handle
Dimensions (mm) Type INS40/63/80 INS00/5/60 P6 40 4.5
DB05644

Installation
On a backplate
DB05639 DB05640

On rail

Dimensions (mm) Type INS40/63/80 INS00/5/60

C1 40 37.5

C2 80 75

R1 0 .5

R2 36 60

T 4.5 4.5

U 35 35

C-4

Dimensions and connection

Interpact INS250-100 to 630 Interpact INV100 to 630

Dimensions
Front handle
DB05654 DB05655 DB05656

(a) Terminal shields. (b) Interphase-barrier. (c) Long terminal shields.

Dimensions (mm) Type INS50 INV00/50 INS30/630 INV30/630 H 40 6.5 H1 80 3 H2 68 H3 36 H4 8 8 H5 64 36 H6 48 5 H7 96 430 H8 66 H9 33 H10 5 77 K 7.5 .5 K1 35 45 L 70 9.5 L1 40 85 P .5 6 P1 86 0 P2 96 30 P3 3 P4 38

0.5 05

.5 45

60.4 6

Extended front handle


INS250-100 to 250 and INV100 to 250

DB05657

DB05658

(1) Length of shaft = A - 101. INS320 to 630 and INV320 to 630

DB55

(1) Length of shaft = A - 124. Note: Lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

DB0566

DB800

DB4554

C-5

Dimensions and connection

Interpact INS250-100 to 630 Interpact INV100 to 630

Door or front panel cutout for front handle


Without escutcheon
DB05663 DB05664 DB05665

With escutcheon

Dimensions (mm) Type INS/INV00 to 50 INS/INV30 to 630 C6 5.5 76.5 C7 03 53 H9 8 7 L3 66 86 L4 3 7 P5 86 0 P6 88  R6 8 0 R7 6 0

Installation
On panel fixed/FC
DB09 DB093

On panel fixed/RC
DB094

On rail

Dimensions (mm) Type INS/INV00 to 50 INS/INV30 to 630 G 50 75 G1 00 50 G2 5 77 G3 57.5 88.5 K 7.5 .5 K1 35 45 K2 70 90 T 6 6

Front panel cutout


Switch-disconnector equipped with a voltage-presence indicator
DB0863 DB0864

Dimensions (mm) Type INS/INV00 to 50 INS/INV30 to 630 P43 87.  R14 65 86 R15 30 7 C22 80 5.7 C23 40 6.85 C30 58.5 97 T8 3 3 K3 8 .7

C-6

Dimensions and connection

Interpact INS250-100 to 630 Interpact INV100 to 630

Dimensions
Lateral handle (only for INS250-100 to 250 and INV100 to 250)
DB05669 DB05670

Extended lateral handle (only for INS250-100 to 250 and INV100 to 250)
DB0865 DB0567

Door or front panel cutout for lateral handle (only for INS250-100 to 250 and INV100 to 250)
DB05673

C-7

Dimensions and connection

Interpact INS250-100 to 630 Interpact INV100 to 630

Dimensions
Switch-disconnector with ammeter module
Direct handle (INS250/INV100 to 250)
DB05674 DB05675

Switch-disconnector equipped with current transformer

Extended handle
DB05676

(1) To front of direct handle. (2) To front of key.

Front panel cutout


Switch-disconnector with ammeter module
Direct handle (INS250/INV100 to 250)
DB05677 DB05678

Extended handle
DB05679

(1) Only for INS250/INV100 to 250 with direct handle and ammeter module.

C-8

Dimensions and connection

Interpact INS250-100 to 630 Interpact INV100 to 630

Installation (for INS250 direct rotary handle equipped with ammeter module or current transformer)
On a backplate
Fixed front connection
DB095 DB096

On rails
Fixed rear connection
DB097

Installation (for extended rotary handle equipped with ammeter module)


On a backplate
Fixed front connection
DB098 DB099

On rails
Fixed rear connection
DB0930

Dimensions (mm) Type INS/INV00 to 50 INS/INV30 to 630 Type INS/INV00 to 50 INS/INV30 to 630 Type INS/INV00 to 50 INS/INV30 to 630 C22 4 63.5 H8 6 K 7.5 .5 C23 8 7 H9 8 K1 35 45 C27 56.5 56.5 H10 79.5 K2 70 90 C28 87 6 H11 40 P1 8 95.5 C29 95 H12 97.5 P2 86 0 G 50 75 H13 446 P3 3 60.4 G1 00 50 H14 4 0.5 P4 38 6 G6 5 75 H15 07 305 P43 89  G7 75 50 H16 05 30.5 P47 37 6 G8 3.5 88.5 H17 334 5.5 R14 48.5 64.5 G9 90 77 H18 3 7.5 R15 97 9 G10 00 75 H19 370 530 R16 46.5 64.5 R17 93 93 T 6 6 T4  3 U(e) y 3 y 3 G11 50 50 G12 07.5 88.5 G13 65 77

C-9

Dimensions and connection

Interpact INS630b to 1600 Interpact INV630b to 1600

Dimensions
Direct front handle
3 poles
DB05686 DB588 DB05688

4 poles

(a) Terminal shields. (b) Interphase-barrier.

Door or front panel cutout for extended handle Cutout for switch-disconnector cover (mm)
Type 3P 4P A 07 07 D 99 369 E 03 73 F 08 08 G 6 6
DB05689 DB05690

Cutout for switch-disconnector front (mm)


Type 3P 4P B 4 4 D 74 344 E 90,5 60,5 F 95.5 95.5 G 9 9

Cutout for escutcheon (mm)


Type 3P 4P C 3 3 D 330 400 E 0 90 F 3 3 G 46 46

Note: Lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

C-0

Dimensions and connection

Interpact INS630b to 1600 Interpact INV630b to 1600

Extended front handle


DB589 DB0897 DB0896

(1) Length of shaft = A - 151.

Installation
On backplate
DB05694 DB05695

On rail

C-

Dimensions and connection

Interpact INS2000 to 2500 Interpact INV2000 to 2500

Dimensions
Direct front handle
3 poles
DB05696 DB05697 DB05698

4 poles

DB08569

A : 50 min. / 72 max.

Door or front panel cutout for front handle Cutout for switch-disconnector cover (mm)
Type 3P 4P A 88 88 D 99 369 E 03 73 F 08 08 G 6 6
DB08570 DB05700

Cutout without escutcheon (mm)


Type 3P 4P B 3 3 D 74 344 E 90,5 60,5 F 95.5 95.5 G 9 9

Cutout with escutcheon (mm)


Type 3P 4P C 3 3 D 37 397 E 0 80 F ,5 ,5 G 43 43

Note: Lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

C-

Dimensions and connection

Interpact INS2000 to 2500 Interpact INV2000 to 2500

Extended front handle


DB590 DB7768 DB0896

(1) Length of shaft = A - 232.

Installation
On backplate
DB05704

C-3

Dimensions and connection

Mechanical interlocks for direct and extended handles


INS40 to 630, INV100 to 630

Dimensions for direct handle (INS250-100 to 630 and INV100 to 630)


DB05705 DB05706

Door cutout
DB05707

Dimensions (mm) Type INS50 INV00/50 INS30/630 INV30/630 A B 35 90 C D E 87.5 75 70 F G H K L M N 56 06 7.5 95 75.5 50 75 P 68 Q 36

46 5 00 00 9.5 0 30 .5 386 00 75 74.5 0.5 05

Dimensions for extended handle (INS250-100 to 630 and INV100 to 630)

DB05708

DB05709

Door cutout
DB06737

Dimensions (mm) Type INS40/80 INS00/60 INS50 INV00/50 INS30/630 INV30/630 A 35 46 B 90 5 C 87.5 00 D 75 00 E 46 70 70 9.5 F 56 56 56 0 G min. 55 8 85 04 H max. 396 59 600 7.5 600 .5 P 45 50 68 Q 90 00 36

0.5 05

Note: Lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

C-4

Dimensions and connection

Complete source changeover assembly


INS250-100 to 630, INV100 to 630

Dimensions of the complete source-changeover assembly with a direct handle


DB06738 DB06739

Front cutout
DB06740

Dimensions (mm) Type INS50 INS30/630 A 60.4 8.5 B C 30.4 95 75 395 D E 68 36 0.5 05 F 3 55 G 6.8 87 H J 79.3 84 383.7 8 K 56 0 L 4 64

Dimensions of the complete source-changeover assembly with an extended handle

DB0674

DB0674

Door cutout
DB06743

Dimensions (mm) Type INS50 INV00/50 INS30/630 INV30/630 A 60.4 8.5 B 30.4 75 C 95 395 E 36 05 K 56 0 L 38.5 6.5 M 63 658 N 50 75 P 00 50

Note: Lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

C-5

Dimensions and connection

Installation of downstream coupling

INS250-100 to 630, INV100 to 630


Dimensions
DB06744 DB06745

Dimensions
DB06746 DB06748 DB06747

Connection

Dimensions (mm) Type INS50 INV00/50 INS30/630 INV30/630 Type INS50 INV00/50 INS30/630 INV30/630 G2 05.5 4 L28 30 40 G3 69 40.7 L29 8. 05. G28 5. 35 L30 300 400 G29 83.5 8.4 L31 7. 95. G30 7.5 63.4 L32 6.4 . G52 43.5 0.5 L33 3 87.5 K1 35 45 L34 39.5 84.7 K2 35 5.5 L35 74.5 96.5 K3 5 75 L36 9.5 4 K4 56 0 L37 70 9.5 K8 57.5 88.5 L38 .5 6 K9 57.5 5.7 L39 4.9 .4 K16 5.4 6. L40 40 0

Note: Lines X and Y indicate the axes of symme try of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

C-6

Dimensions and connection

Front-panel accessories

INS250-100 to 2500, INV100 to 2500

Front-panel escutcheon
For switch-disconnectors
DB06750 DB06749 DB0675

Dimensions (mm) Type INS50 INV00/50 INS30/630 INV30/630 INS630b/500 INV630b/500 A2 74 5.5 3P 4P 346 46 D1 3.5 3.5 3.5 3.5 D2 6.5 6.5 .5 .5 M6 4 64 57.5 57.5 M7 0 5 4 x 36.5 4 x 396.5

For ammeter module


DB0675 DB06753 DB06754

Connection

Front alignment (only for INS/INV250-100)


DB06755 DB06756

Note: Lines X and Y indicate the axes of symme try of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

C-7

Dimensions and connection

Parallel or series connection accessories for direct current


Interpact INS250-100 to 250 Interpact INV100 to 250

With series connections


3P
DB4678

4P
DB4680

With parallel connections


3P
DB4679 DB468

4P

C-8

Dimensions and connection

Parallel or series connection accessories for direct current


Interpact INS320 to 630 Interpact INV320 to 630

With series connections


3P
DB468

4P
DB4683

With parallel connections


4P
DB4684

3P (1)

(1) Connection to be made by customer.

C-9

TOOLS
schneider-electric.com The electrical installation guide
According to IEC 60364 This guide, part of the Schneider Electric offer, is the essential tool to "guide" you any time in your business: p design office, consultant p contractor, panelbuilder p teacher, trainer. Comprehensive and concrete information on: p all the new technical solutions p all the components p of an installation from a global point of view p all the IEC standards modifications p all the fundamental electrotechnical knowledge p all the design stages, from medium to low voltage.

This international site allows you to access all the Schneider Electric products in just  clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts

Interpact INS/INV

Complementary technical information


Presentation Functions and characteristics Installation recommendations Dimensions and connection 2 A-1 B-1 C-1

Protection of switch-disconnectors
INS40 to INS60 by Compact NSX circuit breaker INS/INV00 to INS/INV630 by Compact NSX circuit breaker INS40 to INS60 by Compact NS circuit breaker INS/INV00 to INS/INV630 by Compact NS circuit breaker INS/INV630b to INS/INV500 by Compact NS circuit breaker INS/INV630b to INS/INV500 by Masterpact NT and NW circuit breakers INS40 to 500 and INV00 to 500 by fuses

D-2
D- D-8 D- D-4 D-6 D-8 D-0

Characteristics of switch-disconnectors
INS40 to 500 and INV00 to 500 for direct current Catalogue numbers

D-22
D- E-1

D-

Complementary technical information

Protection of switchdisconnectors

INS40 to INS160 by Compact NSX circuit breaker


DB40454

Interpact INS switch-disconnectors Upstream protection


By Compact NSX By circuit breaker 380/415 V Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

D-

Complementary technical information

Protection of switchdisconnectors

INS40 to INS160 by Compact NSX circuit breaker


INS40 INS63 INS80 INS100
NSX00B/00 5 5 NSX00F/00 36 75 NSX00N/00 36 75 NSX00H/S/L/00 36 75 NSX60B/00 5 5 NSX60F/00 36 75 NSX60N/00 50 05 NSX60H/S/L/00 70 54 NSX50B/00 5 5 NSX50F/00 36 75 NSX50N/00 50 05 NSX50H/S/L/00 70 54 NSC00N/00 8 37 NG5N/00 5 5 -

INS125
-

INS160
-

NSX00B/40 5 5 NSX00F/40 36 75 NSX00N/40 36 75 NSX00H/S/L/40 36 75 NSX60B/40 5 5 NSX60F/40 5 5 NSX60N/40 5 5 NSX60H/S/L/40 5 5 -

NSX00B/63 5 5 NSX00F/63 36 75 NSX00N/63 36 75 NSX00H/S/L/63 36 75 NSX60B/63 5 5 NSX60F/63 5 5 NSX60N/63 5 5 NSX60H/S/L/63 5 5 -

NSX00B/80 5 5 NSX00F/80 36 75 NSX00N/80 36 75 NSX00H/S/L/80 36 75 NSX60B/80 5 5 NSX60F/80 5 5 NSX60N/80 5 5 NSX60H/S/L/80 5 5 -

NSC00N/40 8 37 NG5N/40 5 5 NG5H/40 36 75 NG5L/40 50 05 NG60N/40 5 5

NSC00N/63 8 37 NG5N/63 5 5 NG5H/63 36 75 NG5L/63 50 05 NG60N/63 5 5

NSC00N/80 8 37 NG5N/80 5 5 NG5H/80 36 75 NG5L/80 50 05 NG60N/80 5 5

NSX60B/5 5 5 NSX60F/5 36 75 NSX60N/5 50 05 NSX60H/S/L/5 70 54 NSX50B/5 5 5 NSX50F/5 36 75 NSX50N/5 50 05 NSX50H/S/L/5 70 54 -

NSX60B/60 5 5 NSX60F/60 36 75 NSX60N/60 50 05 NSX60H/S/L/60 70 54 NSX50B/60 5 5 NSX50F/60 36 75 NSX50N/60 50 05 NSX50H/S/L/60 70 54 -

NG5N/5 5 5 -

NG60N/00 5 5

NG60N/5 5 5

NG60N/60 5 5

D-3

Complementary technical information

Protection of switchdisconnectors

INS40 to INS160 by Compact NSX circuit breaker


DB40454

Interpact INS switch-disconnectors Upstream protection


By Compact NSX By circuit breaker 440/480 V (1) Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

By circuit breaker 500/525 V

(1) Applicable for 480 NEMA.

D-4

Complementary technical information

Protection of switchdisconnectors

INS40 to INS160 by Compact NSX circuit breaker


INS40
NSX00B/40 0 40 NSX00F/40 35 73 NSX00N/40 35 73 NSX00H/S/L/40 35 73 NSX60B/40 0 40 NSX60F/40 5 5 NSX60N/40 5 5 NSX60H/S/L/40 5 5 -

INS63
NSX00B/63 0 40 NSX00F/63 35 73 NSX00N/63 35 73 NSX00H/S/L/63 35 73 NSX60B/63 0 40 NSX60F/63 5 5 NSX60N/63 5 5 NSX60H/S/L/63 5 5 -

INS80
NSX00B/80 0 40 NSX00F/80 35 73 NSX00N/80 35 73 NSX00H/S/L/80 35 73 NSX60B/80 0 40 NSX60F/80 5 5 NSX60N/80 5 5 NSX60H/S/L/80 5 5 -

INS100
NSX00B/00 0 40 NSX00F/00 35 73 NSX00N/00 35 73 NSX00H/S/L/00 65 43 NSX60B/00 0 40 NSX60F/00 35 73 NSX60N/00 35 73 NSX60H/S/L/00 65 43 NSX50B/00 0 40 NSX50F/00 35 73 NSX50N/00 35 73 NSX50H/S/L/00 65 43 NSC00N/00 8 37 NSX00B/00 5 30 NSX00F/00 8 36 NSX00N/00 8 36 NSX00H/S/L/00 5 53 NSX60B/00 5 30 NSX60F/00 5 30 NSX60N/00 5 30 NSX60H/S/L/00  46 NSX50B/00 5 30 NSX50F/00 5 30 NSX50N/00 5 30 NSX50H/S/L/00  46 NSC00N/00 8 37

INS125
-

INS160
-

NSC00N/40 8 37 NSX00B/40 5 30 NSX00F/40 8 36 NSX00N/40 8 36 NSX00H/S/L/40 5 53 NSX60B/40 5 30 NSX60F/40 5 30 NSX60N/40 5 30 NSX60H/S/L/40 5 30 -

NSC00N/63 8 37 NSX00B/63 5 30 NSX00F/63 8 36 NSX00N/63 8 36 NSX00H/S/L/63 5 53 NSX60B/63 5 30 NSX60F/63 5 30 NSX60N/63 5 30 NSX60H/S/L/63 5 30 -

NSC00N/80 8 37 NSX00B/80 5 30 NSX00F/80 8 36 NSX00N/80 8 36 NSX00H/S/L/80 5 53 NSX60B/80 5 30 NSX60F/80 5 30 NSX60N/80 5 30 NSX60H/S/L/80 5 30 -

NSX60B/5 0 40 NSX60F/5 35 73 NSX60N/5 35 73 NSX60H/S/L/5 65 43 NSX50B/5 0 40 NSX50F/5 35 73 NSX50N/5 35 73 NSX50H/S/L/5 65 43 -

NSX60B/60 0 40 NSX60F/60 35 73 NSX60N/60 35 73 NSX60H/S/L/60 65 43 NSX50B/60 0 40 NSX50F/60 35 73 NSX50N/60 35 73 NSX50H/S/L/60 65 43 -

NSC00N/40 8 37

NSC00N/63 8 37

NSC00N/80 8 37

NSX60B/5 5 30 NSX60F/5  46 NSX60N/5  46 NSX60H/S/L/5  46 NSX50B/5 5 30 NSX50F/5  46 NSX50N/5  46 NSX50H/S/L/5  46 -

NSX60B/60 5 30 NSX60F/60  46 NSX60N/60  46 NSX60H/S/L/60  46 NSX50B/60 5 30 NSX50F/60  46 NSX50N/60  46 NSX50H/S/L/60  46 -

D-5

Complementary technical information

Protection of switchdisconnectors

INS40 to INS160 by Compact NSX circuit breaker


DB40454

Interpact INS switch-disconnectors Upstream protection


By Compact NSX By circuit breaker 690 V Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

Upstream protection by fuse


By 500 V fuse Type aM (2)/maximum rating (A) Isc max. Making capacity Type gG (3)/maximum rating (A) Isc max. Making capacity Type gG (2)/maximum rating (A) Isc max. Making capacity Type BS (3)/maximum rating (A) Isc max. Making capacity Type BS (2)/maximum rating (A) Isc max. Making capacity By 690 V fuse Type aM (2)/maximum rating (A) Isc max. Making capacity Type gG (3)/maximum rating (A) Isc max. Making capacity Type gG (2)/maximum rating (A) Isc max. Making capacity (2) Protection by external thermal relay obligatory. (3) Without external thermal relay. kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

D-6

Complementary technical information

Protection of switchdisconnectors

INS40 to INS160 by Compact NSX circuit breaker


INS40
-

INS63
-

INS80
-

INS100
NSX00B/00 6 9 NSX00F/00 8 4 NSX00N/00 0 7 NSX00H/S/L/00 0 7 NSX60B/00 6 9 NSX60F/00 8 4 NSX60N/00 0 7 NSX60H/S/L/00 0 7 NSX50B/00 6 9 NSX50F/00 8 4 NSX50N/00 0 7 NSX50H/S/L/00 0 7 NSC00N/00 8 37 00 00 0 80 00 0 5/60 00/50 0/05 80 and 63M80 80 76 60 and 00M60 80 76 5 00 0 80 00 0 5 00 0

INS125
-

INS160
-

NSC00N/40 8 37 5 00 0 3 00 0 00 00 0 3 80 76 5 and 00M5 80 76 -

NSC00N/63 8 37 5 00 0 50 00 0 00 00 0 50 and 3M50 80 76 5 and 00M5 80 76 -

NSC00N/80 8 37 5 00 0 50 00 0 00 00 0 63 and 3M63 80 76 5 and 00M5 80 76 -

NSX60B/5 6 9 NSX60F/5 8 4 NSX60N/5 0 7 NSX60H/S/L/5 0 7 NSX50B/5 6 9 NSX50F/5 8 4 NSX50N/5 0 7 NSX50H/S/L/5 0 7 -

NSX60B/60 6 9 NSX60F/60 8 4 NSX60N/60 0 7 NSX60H/S/L/60 0 7 NSX50B/60 6 9 NSX50F/60 8 4 NSX50N/60 0 7 NSX50H/S/L/60 0 7 -

00 00 0 00 00 0 5/60 00/50 0/05 00 and 63M00 80 76 60 and 00M60 80 76 5 00 0 00 00 0 5 00 0

00 00 0 5 00 0 5/60 00/50 0/05 5 and 00M5 80 76 60 and 00M60 80 76 5 00 0 5 00 0 5 00 0

D-7

Complementary technical information

Protection of switchdisconnectors

INS/INV100 to INS/INV630 by Compact NSX circuit breaker


DB40456

Interpact INS switch-disconnectors Upstream protection


By Compact NSX By circuit breaker 380/415 V Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

INS250-100 / INV100 INS250-160 / INV160

By circuit breaker 440/480 V (1)

By circuit breaker 500 V

NSX00-60-50B/00 5 5 NSX00-60-50F/00 36 75 NSX00-60-50N/00 50 05 NSX00-60-50H/00 70 54 NSX00-60-50S/00 00 0 NSX00-60-50L/00 50 330 NSX00-60-50B/00 0 40 NSX00-60-50F/00 35 73 NSX00-60-50N/00 50 05 NSX00-60-50H/00 65 43 NSX00-60-50S/00 90 98 NSX00-60-50L/00 30 86 NSX00-60-50B/00 5 30 NSX00F/00 5 5 NSX60-50F/00 30 63 NSX00-60-50N/00 36 75 NSX00-60-50H/00 50 05 NSX00-60-50S/00 65 43 NSX00-60-50L/00 70 54

NSX60-50B/60 5 5 NSX60-50F/60 36 75 NSX60-50N/60 50 05 NSX60-50H/60 70 54 NSX60-50S/60 00 0 NSX60-50L/60 50 330 NSX60-50B/60 0 40 NSX60-50F/60 35 73 NSX60-50N/60 50 05 NSX60-50H/60 65 43 NSX60-50S/60 90 98 NSX60-50L/60 30 86 NSX60-50B/60 5 30 -

NSX60-50H/60 30 63 NSX60-50N/60 36 75 NSX60-50H/60 50 05 NSX60-50S/60 65 43 NSX60-50L/60 70 54

(1) Applicable for 480 NEMA.

D-8

Complementary technical information

Protection of switchdisconnectors

INS/INV100 to INS/INV630 by Compact NSX circuit breaker


INS250-200 / INV200
NSX50B/00 5 5 NSX50F/00 36 75 NSX50N/00 50 05 NSX50H/00 70 54 NSX50S/00 00 0 NSX50L/00 50 330 NSX50B/00 0 40 NSX50F/00 35 73 NSX50N/00 50 05 NSX50H/00 65 43 NSX50S/00 90 98 NSX50L/00 30 86 NSX50B/00 5 30 -

INS/INV250

INS/INV320

INS/INV400

INS/INV500

INS/INV630

NSX50N/50 5 5 NSX50F/50 36 75 NSX50N/50 50 05 NSX50H/50 70 54 NSX50S/50 00 0 NSX50L/50 50 330 NSX50B/50 0 40 NSX50F/50 35 73 NSX50N/50 50 05 NSX50H/50 65 43 NSX50S/50 90 98 NSX50L/50 30 86 NSX50B/50 5 30 -

NSX400-630F/30 36 75 NSX400-630N/30 50 05 NSX400-630H/30 70 54 NSX400-630S/30 00 0 NSX400-630L/30 50 330 -

NSX400-630F/400 36 75 NSX400-630N/400 50 05 NSX400-630H/400 70 54 NSX400-630S/400 00 0 NSX400-630L/400 50 330 -

NSX630F/500 36 75 NSX630N/500 50 05 NSX630H/500 70 54 NSX630S/500 00 0 NSX630L/500 50 330 -

NSX630F/630 36 75 NSX630N/630 50 05 NSX630H/630 70 54 NSX630S/630 00 0 NSX630L/630 50 330 -

NSX400-630F/30 35 73 NSX400-630N/30 50 05 NSX400-630H/30 65 43 NSX400-630S/30 90 98 NSX400-630L/30 30 86 -

NSX400-630F/400 35 73 NSX400-630N/400 50 05 NSX400-630H/400 65 43 NSX400-630S/400 90 98 NSX400-630L/400 30 86 -

NSX630F/500 35 73 NSX630N/500 50 05 NSX630H/500 65 43 NSX630S/500 90 98 NSX630L/500 30 86 -

NSX630F/630 35 73 NSX630N/630 50 05 NSX630H/630 65 43 NSX630S/630 90 98 NSX630L/630 30 86 -

NSX50F/00 30 63 NSX50N/00 36 75 NSX50H/00 50 05 NSX50S/00 65 43 NSX50L/00 70 54

NSX50F/50 30 63 NSX50N/50 36 75 NSX50H/50 50 05 NSX50S/50 65 43 NSX50L/50 70 54

NSX400-630F/30 5 5 NSX400-630N/30 30 63 NSX400-630H/30 50 05 NSX400-630S/30 65 43 NSX400-630L/30 70 54

NSX400-630F/400 5 5 NSX400-630N/400 30 63 NSX400-630H/400 50 05 NSX400-630S/400 65 43 NSX400-630L/400 70 54

NSX630F/500 5 5 NSX630N/500 30 63 NSX630H/500 50 05 NSX630S/500 65 43 NSX630L/500 70 54

NSX630F/630 5 5 NSX630N/630 30 63 NSX630H/630 50 05 NSX630S/630 65 43 NSX630L/630 70 54

D-9

Complementary technical information

Protection of switchdisconnectors

INS/INV100 to INS/INV630 by Compact NSX circuit breaker


DB40456

Interpact INS switch-disconnectors Upstream protection


By Compact NSX By circuit breaker 525 V Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

INS250-100 / INV100 INS250-160 / INV160

By circuit breaker 690 V

NSX00-60-50B/00  4 NSX00-60-50F/00  47 NSX00-60-50N/00 35 73 NSX00-60-50H/00 35 73 NSX00-60-50S/00 40 8 NSX00-60-50L/00 50 05 NSX00-60-50B/00 6 9 NSX00-60-50F/00 8 4 NSX00-60-50N/00 0 7 NSX00-60-50H/00 0 7 NSX00-60-50S/00 5 30 NSX00-60-50L/00 0 40 35 00 0 80 00 0 5/355 00/50 0/05 80 and 63M80 80 76 50 and 00M50 80 76 50 00 0 80 00 0 00 00 0

NSX60-50B/60  4 NSX60-50F/60  47 NSX60-50N/60 35 73 NSX60-50H/60 35 73 NSX60-50S/60 40 8 NSX60-50L/60 50 05 NSX60-50B/60 6 9 NSX60-50F/60 8 4 NSX60-50N/60 0 7 NSX60-50H/60 0 7 NSX60-50S/60 5 30 NSX60-50L/60 0 40 35 00 0 5 00 0 5/355 00/50 0/05 5 and 00M5 80 76 50 and 00M50 80 76 50 00 0 5 00 0 00 00 0

Upstream protection by fuse


By 500 V fuse Type aM (2)/maximum rating (A) Isc max. Making capacity Type gG (3)/maximum rating (A) Isc max. Making capacity Type gG (2)/maximum rating (A) Isc max. Making capacity Type BS (3)/maximum rating (A) Isc max. Making capacity Type BS (2)/maximum rating (A) Isc max. Making capacity By 690 V fuse Type aM (2)/maximum rating (A) Isc max. Making capacity Type gG (3)/maximum rating (A) Isc max. Making capacity Type gG (2)/maximum rating (A) Isc max. Making capacity (2) Protection by external thermal relay obligatory. (3) Without external thermal relay. kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

D-0

Complementary technical information

Protection of switchdisconnectors

INS/INV100 to INS/INV630 by Compact NSX circuit breaker


INS250-200 / INV200
NSX50B/00  4 NSX50F/00  47 NSX50N/00 35 73 NSX50H/00 35 73 NSX50S/00 40 8 NSX50L/00 50 05 NSX50B/00 6 9 NSX50F/00 8 4 NSX50N/00 0 7 NSX50H/00 0 7 NSX50S/00 5 30 NSX50L/00 0 40 35 00 0 60 00 0 5/355 00/50 0/05 60 and 00M60 80 76 50 and 00M50 80 76 50 00 0 60 00 0 00 00 0

INS/INV250

INS/INV320

INS/INV400

INS/INV500

INS/INV630

NSX50B/50  4 NSX50F/50  47 NSX50N/50 35 73 NSX50H/50 35 73 NSX50S/50 40 8 NSX50L/50 50 05 NSX50B/50 6 9 NSX50F/50 8 4 NSX50N/50 0 7 NSX50H/50 0 7 NSX50S/50 5 30 NSX50L/50 0 40 35 00 0 00 00 0 5/355 00/50 0/05 00 and 00M00 80 76 50 and 00M50 80 76 50 00 0 00 00 0 00 00 0

NSX400-630F/30  47 NSX400-630N/30  47 NSX400-630H/30 35 73 NSX400-630S/30 40 8 NSX400-630L/30 50 05 -

NSX400-630F/400  47 NSX400-630N/400  47 NSX400-630H/400 35 73 NSX400-630S/400 40 8 NSX400-630L/400 50 05 -

NSX630F/500  47 NSX630N/500  47 NSX630H/500 35 73 NSX630S/500 40 8 NSX630L/500 50 05 -

NSX630F/630  47 NSX630N/630  47 NSX630H/630 35 73 NSX630S/630 40 8 NSX630L/630 50 05 -

NSX400-630F/30 8 4 NSX400-630N/30 0 7 NSX400-630H/30 0 7 NSX400-630S/30 5 30 NSX400-630L/30 0 40 630 50 05 50 00 0 630 50 05 50 and 00M50 80 76 355 and 35M355 80 76 630 50 05 50 00 0 630 50 05

NSX400-630F/400 8 4 NSX400-630N/400 0 7 NSX400-630H/400 0 7 NSX400-630S/400 5 30 NSX400-630L/400 0 40 630 50 05 35 00 0 630 50 05 35 and 00M50 80 76 355 and 35M355 80 76 630 50 05 35 00 0 630 50 05

NSX630F/500 8 4 NSX630N/500 0 7 NSX630H/500 0 7 NSX630S/500 5 30 NSX630L/500 0 40 630 50 05 400 00 0 630 50 05 400 80 76 450 and 400M450 80 76 630 50 05 400 00 0 630 50 05

NSX630F/630 8 4 NSX630N/630 0 7 NSX630H/630 0 7 NSX630S/630 5 30 NSX630L/630 0 40 630 50 05 500 00 0 500/630 00/50 0/05 450 and 400M450 80 76 450 and 400M450 80 76 630 50 05 500 00 0 500/630 00/50 0/05

D-

Complementary technical information

Protection of switchdisconnectors

INS40 to INS160 by Compact NS circuit breaker


DB40454

Interpact INS switch-disconnectors Upstream protection


By Compact NS circuit breaker By circuit breaker 380/415 V Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker Type/maximum rating (A) 440/480 V (1) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker Type/maximum rating (A) 500 V (INS40 to INS80) Isc max. 500/525 V (INS100 to INS160) Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker 690 V Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity (1) Applicable for 480 NEMA. kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

D-

Complementary technical information

Protection of switchdisconnectors

INS40 to INS160 by Compact NS circuit breaker


INS40
NS00N/40 36 75 NS00SX-H-L/40 36 75 NS60N-SX/40 5 5 NS60H-L/40 5 5 NSC00N/40 8 37 NG5N/40 5 5 NG5H/40 36 75 NG5L/40 50 05 NS00N/40 35 73 NS00SX-H-L/40 35 73 NS60N/40 5 5 NS60H-L/40 5 5 NSC00N/40 8 37 NS00N/40 8 36 NS00SX-H-L/40 8-5 36-53 NS60N/40 5 30 NS60SX-H-L/40 5 30 NSC00N/40 0 7 -

INS63
NS00N/63 36 75 NS00SX-H-L/63 36 75 NS60N-SX/63 5 5 NS60H-L/63 5 5 NSC00N/63 8 37 NG5N/63 5 5 NG5H/63 36 75 NG5L/63 50 05 NS00N/63 35 73 NS00SX-H-L/63 35 73 NS60N/63 5 5 NS60H-L/63 5 5 NSC00N/63 8 37 NS00N/63 8 36 NS00SX-H-L/63 8-5 36-53 NS60N/63 5 30 NS60SX-H-L/63 5 30 NSC00N/63 0 7 -

INS80
NS00N/80 36 75 NS00SX-H-L/80 36 75 NS60N-SX/80 5 5 NS60H-L/80 5 5 NSC00N/80 8 37 NG5N/80 5 5 NG5H/80 36 75 NG5L/80 50 05 NS00N/80 35 73 NS00SX-H-L/80 35 73 NS60N/80 5 5 NS60H-L/80 5 5 NSC00N/80 8 37 NS00N/80 8 36 NS00SX-H-L/80 8-5 36-53 NS60N/80 5 30 NS60SX-H-L/80 5 30 NSC00N/80 0 7 -

INS100
NS00N/00 36 75 NS00SX-H-L/00 50/70 05/54 NS60-50N/00 36 75 NS60-50SX-H-L/00 50/70 05/54 NSC00N/00 8 37 NG5N/00 5 5 -

INS125
-

INS160
-

NS60-50N/5 36 75 NS60-50SX-H-L/5 50/70 05/54 -

NS60-50N/60 36 75 NS60-50SX-H-L/60 50/70 05/54 -

NG5N/5 5 5 -

NS00N/00 35 73 NS00SX-H-L/00 35/65 73/43 NS60-50N/00 35 73 NS60-50SX-H-L/00 35/65 73/43 NSC00N/00 8 37 NS00N/00 8 36 NS00SX-H-L/00 35-00 73-0 NS60-50N/00  46 NS60-50SX-H-L/00  46 NSC00N/00 0 7 NS00N/00 8 4 NS00SX-H-L/00 0-75 7-65 NS60-50N/00 8 4 NS60-50SX-H-L/00 0-0 7-40

NS60-50N/5 35 73 NS60-50SX-H-L/5 35/65 73/43 -

NS60-50N/60 35 73 NS60-50SX-H-L/60 35/65 73/43 -

NS60-50N/5  46 NS60-50SX-H-L/5  46 -

NS60-50N/60  46 NS60-50SX-H-L/60  46 -

NS60-50N/5 8 4 NS60-50SX-H-L/5 0-0 7-40

NS60-50N/60 8 4 NS60-50SX-H-L/60 0-0 7-40

D-3

Complementary technical information

Protection of switchdisconnectors

INS/INV100 to INS/INV630 by Compact NS circuit breaker


DB40456

Interpact INS switch-disconnectors Upstream protection


By Compact NS circuit breaker By circuit breaker 380/415 V Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker Type/maximum rating (A) Isc max. 440/480 V (1) Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker 500 V Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker 525 V Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker 690 V Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity (1) Applicable for 480 NEMA. kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

INS250-100 / INV100 INS250-160 / INV160

NS00-60-50N/00 36 75 NS00-60-50SX/00 50 05 NS00-60-50H/00 70 54 NS00-60-50L/00 50 330 NS00-60-50N/00 35 73 NS00-60-50SX 50 05 NS00-60-50H/00 65 43 NS00-60-50L/00 30 86 NS00-60-50N/00 5-30-30 53-63-63 NS00-60-50SX/00 36 75 NS00-60-50H/00 50 05 NS00-60-50L/00 00-70-70 0-54-54 NS00-60-50N/00  46 NS00-60-50SX/00 35 73 NS00-60-50H/00 35 73 NS00-60-50L/00 00-50-50 0-05-05 NS00-60-50N/00 8 4 NS00-60-50SX/00 0 7 NS00-60-50H/00 0 7 NS00-60-50L/00 75-0-0 65-40-40

NS60-50N/60 36 75 NS60-50SX/60 50 05 NS60-50H/60 70 54 NS60-50L/60 50 330 NS60-50N/60 35 73 NS60-50SX 50 05 NS60-50H/60 65 43 NS60-50L/60 30 86 NS60-50N/60 30 63 NS60-50SX/60 36 75 NS60-50H/60 50 05 NS60-50L/60 70 54 NS60-50N/60  46 NS60-50SX/60 35 73 NS60-50H/60 35 73 NS60-50L/60 50 05 NS60-50N/60 8 4 NS60-50SX/60 0 7 NS60-50H/60 0 7 NS60-50L/60 0 40

D-4

Complementary technical information

Protection of switchdisconnectors

INS/INV100 to INS/INV630 by Compact NS circuit breaker


INS250-200 / INV200
NS50N/00 36 75 NS50SX/00 50 05 NS50H/00 70 54 NS50L/00 50 330 NS50N/00 35 73 NS50SX/00 50 05 NS50H/00 65 43 NS50L/00 30 86 NS50N/00 30 63 NS50SX/00 36 75 NS50H/00 50 05 NS50L/00 70 54 NS50N/00  46 NS50SX/00 35 73 NS50H/00 35 73 NS50L/00 50 05 NS50N/00 8 4 NS50SX/00 0 7 NS50H/00 0 7 NS50L/00 0 40

INS/INV250

INS/INV320

INS/INV400

INS/INV500

INS/INV630

NS50N/50 36 75 NS50SX/50 50 05 NS50H/50 70 54 NS50L/50 50 330 NS50N/50 35 73 NS50SX/50 50 05 NS50H/50 65 43 NS50L/50 30 86 NS50N/50 30 63 NS50SX/50 36 75 NS50H/50 50 05 NS50L/50 70 54 NS50N/50  46 NS50SX/50 35 73 NS50H/50 35 73 NS50L/50 50 05 NS50N/50 8 4 NS50SX/50 0 7 NS50H/50 0 7 NS50L/50 0 40

NS400-630N/30 50 05 -

NS400-630N/400 50 05 -

NS630N/500 50 05 -

NS630N/630 50 05 -

NS400-630H/30 70 54 NS400-630L/30 50 330 NS400-630N/30 4 88 -

NS400-630H/400 70 54 NS400-630L/400 50 330 NS400-630N/400 4 88 -

NS630H/500 70 54 NS630L/500 50 330 NS630N/500 4 88 -

NS630H/630 70 54 NS630L/630 50 330 NS630N/630 4 88 -

NS400-630H/30 65 43 NS400-630L/30 30 86 NS400-630N/30 30 63 -

NS400-630H/400 65 43 NS400-630L/400 30 86 NS400-630N/400 30 63 -

NS630H/500 65 43 NS630L/500 30 86 NS630N/500 30 63 -

NS630H/630 65 43 NS630L/630 30 86 NS630N/630 30 63 -

NS400-630H/30 50 05 NS400-630L/30 00-70 0-54 NS400-630N/30  46 -

NS400-630H/400 50 05 NS400-630L/400 00-70 0-54 NS400-630N/400  46 -

NS630H/500 50 05 NS630L/500 70 54 NS630N/500  46 -

NS630H/630 50 05 NS630L/630 70 54 NS630N/630  46 -

NS400-630H/30 35 73 NS400-630L/30 00-50 0-05 NS400-630N/30 0 7 -

NS400-630H/400 35 73 NS400-630L/400 00-50 0-05 NS400-630N/400 0 7 -

NS630H/500 35 73 NS630L/500 50 05 NS630N/500 0 7 -

NS630H/630 35 73 NS630L/630 50 05 NS630N/630 0 7 -

NS400-630H/30 0 40 NS400-630L/30 75-35 65-73

NS400-630H/400 0 40 NS400-630L/400 75-35 65-73

NS630H/500 0 4 NS630L/500 35 73

NS630H/630 0 4 NS630L/630 35 73

D-5

Complementary technical information

Protection of switchdisconnectors

INS/INV630b to INS/INV2500 by Compact NS circuit breaker


DB40457

Interpact INS switch-disconnectors Upstream protection


By Compact NS circuit breaker By circuit breaker 380/415 V Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker Type/maximum rating (A) 440/480 V (1) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker Type/maximum rating (A) 500/525 V Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker Type/maximum rating (A) 690 V Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By Masterpact NT H1 circuit breaker By circuit breaker Type/maximum rating (A) 220/690 V Isc max. Making capacity By Masterpact NT H2 circuit breaker By circuit breaker Type/maximum rating (A) 220/690 V Isc max. Making capacity By Masterpact NT L1 circuit breaker By circuit breaker Type/maximum rating (A) 220/525 V Isc max. Making capacity By circuit breaker Type/maximum rating (A) 690 V Isc max. Making capacity (1) Applicable for 480 NEMA. kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

kA rms kA peak

kA rms kA peak

kA rms kA peak kA rms kA peak

D-6

Complementary technical information

Protection of switchdisconnectors

INS/INV630b to INS/INV2500 by Compact NS circuit breaker


INS/INV630b INS/INV800 INS/INV1000 INS/INV1250 INS/INV1600 INS/INV2000 INS/INV2500

NS630bN/630 35 75 NS630bH/630 35 75 NS630bL/630 50 330 NS630bN/630 35 75 NS630bH/630 35 75 NS630bL/630 30 86 NS630bN/630 35 75 NS630bH/630 35 75 NS630bL/630 00 0 NS630bN/630 30 63 NS630bH/630 35 75 NS630bL/630 5 53 NT06H/630 35 75 NT06H/630 35 75 NT06L/630 00 0 NT06L/630 5 53

NS800N/800 35 75 NS800H/800 35 75 NS800L/800 50 330 NS800N/800 35 75 NS800H/800 35 75 NS800L/800 30 86 NS800N/800 35 75 NS800H/800 35 75 NS800L/800 00 0 NS800N/800 30 63 NS800H/800 35 75 NS800L/800 5 53 NT08H/800 35 75 NT08H/800 35 75 NT08L/800 00 0 NT08L/800 5 53

NS000N/000 35 75 NS000H/000 35 75 NS000L/000 50 330 NS000N/000 35 75 NS000H/000 35 75 NS000L/000 30 86 NS000N/000 35 75 NS000H/000 35 75 NS000L/000 00 0 NS000N/000 30 63 NS000H/000 35 75 NS000L/000 5 53 NT0H/000 35 75 NT0H/000 35 75 NT0L/000 00 0 NT0L/000 5 53

NS50N/50 35 75 NS50H/50 35 75 -

NS600N - NS600bN/600 35 75 NS600H - NS600bH/600 35 75 -

NS000N/000 50 05 NS000H/000 50 05 -

NS500N/500 50 05 NS500H/500 50 05 -

NS50N/50 35 75 NS50H/50 35 75 -

NS600N - NS600bN/600 35 75 NS600H - NS600bH/600 35 75 -

NS000N/000 50 05 NS000H/000 50 05 -

NS500N/500 50 05 NS500H/500 50 05 -

NS50N/50 35 75 NS50H/50 35 75 -

NS600N - NS600bN/600 35 75 NS600H - NS600bH/600 35 75 -

NS000N/000 50 05 NS000H/000 50 05 -

NS500N/500 50 05 NS500H/500 50 05 -

NS50N/50 30 63 NS50H/50 35 75 -

NS600bN/600 30 63 NS600bH/600 35 75 -

NS000N/000 50 05 NS000H/000 50 05 -

NS500N/500 50 05 NS500H/500 50 05 -

NTH/50 35 75 NTH/50 35 75 NTL/50 00 0 NTL/50 5 53

NT6H/600 35 75 NT6H/600 35 75 NT6L/600 00 0 NT6L/600 5 53

D-7

Complementary technical information

Protection of switchdisconnectors

INS/INV630b to INS/INV2500 by Masterpact NW circuit breakers


DB40458

Interpact INS switch-disconnectors Upstream protection


By Masterpact NW N1- H1- H2- H3 circuit breaker By circuit breaker Type/maximum rating (A) 220/440-480 V (1) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker Type/maximum rating (A) 500/525 V Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By circuit breaker Type/maximum rating (A) 690 V Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity Type/maximum rating (A) Isc max. Making capacity By Masterpact NW L1 By circuit breaker Type/maximum rating (A) 220/690 V Isc max. Making capacity By fuse By fuse 500 V Type aM (2) / max. rating (A) Isc max. Making capacity Type gG (3) / max. rating (A) Isc max. Making capacity Type gG (2) / max. rating (A) Isc max. Making capacity Type BS (3) / max. rating (A) Isc max. Making capacity Type BS (2) / max. rating (A) Isc max. Making capacity By fuse 690 V Type aM (2) / max. rating (A) Isc max. Making capacity Type gG (3) / max. rating (A) Isc max. Making capacity Type gG (2) / max. rating (A) Isc max. Making capacity (1) Applicable for 480 NEMA. (2) Mandatory protection by an external thermal relay. (3) No external thermal relay. kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak DIN OFF / DIN ON DIN OFF / DIN ON DIN OFF / DIN ON DIN OFF / DIN ON DIN OFF / DIN ON DIN OFF / DIN ON

kA rms kA peak

kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak kA rms kA peak

D-8

Complementary technical information

Protection of switchdisconnectors

INS/INV630b to INS/INV2500 by Masterpact NW circuit breakers


INS/INV630b INS/INV800 INS/INV1000 INS/INV1250 INS/INV1600 INS/INV2000 INS/INV2500

NW08N/630 35 75 NW08H/630 35 75 NW08H/630 35 75 -

NW08N/800 35 75 NW08H/800 35 75 NW08H/800 35 75 -

NW0N/000 35 75 NW0H/000 35 75 NW0H/000 35 75 -

NWN/50 35 75 NWH/50 35 75 NWH/50 35 75 -

NW6N/600 35 75 NW6H/600 35 75 NW6H/600 35 75 -

NW08N/630 35 75 NW08H/630 35 75 NW08H/630 35 75 -

NW08N/800 35 75 NW08H/800 35 75 NW08H/800 35 75 -

NW0N/000 35 75 NW0H/000 35 75 NW0H/000 35 75 -

NWN/50 35 75 NWH/50 35 75 NWH/50 35 75 -

NW6N/600 35 75 NW6H/600 35 75 NW6H/600 35 75 -

NW0H/000 50 05 NW0H/000 50 05 NW0H3/000 50 05 -

NW5H/500 50 05 NW5H/500 50 05 NW5H3/500 50 05 -

NW08N/630 35 75 NW08H/630 35 75 NW08H/630 35 75 -

NW08N/800 35 75 NW08H/800 35 75 NW08H/800 35 75 -

NW0N/000 35 75 NW0H/000 35 75 NW0H/000 35 75 -

NWN/50 35 75 NWH/50 35 75 NWH/50 35 75 -

NW6N/600 35 75 NW6H/600 35 75 NW6H/600 35 75 -

NW0H/000 50 05 NW0H/000 50 05 NW0H3/000 50 05 -

NW5H/500 50 05 NW5H/500 50 05 NW5H3/500 50 05 -

NW0H/000 50 05 NW0H/000 50 05 NW0H3/000 50 05 NW0L/000 50 05 -

NW5H/500 50 05 NW5H/500 50 05 NW5H3/500 50 05 -

NW08L/630 35 75 000/50 00 0 500 00 0 000/50 80/50 76/05 500 80 76 000/50 80/50 76/05 000/50 00 0 500 00 0 000/50 80/50 76/05

NW08L/800 35 75 000/50 00 0 630 00 0 000/50 80/50 76/05 630 80 76 000/50 80/50 76/05 000/50 00 0 630 00 0 000/50 80/50 76/05

NW0L/000 35 75 000/50 00 0 800 00 0 000/50 80/50 76/05 800 80 76 000/50 80/50 76/05 000/50 00 0 800 00 0 000/50 80/50 76/05

NWL/50 35 75 000/50 00 0 000 80 76 000/50 80/50 76/05 000 80 76 000/50 80/50 76/05 000/50 00 0 000 80 76 000/50 80/50 76/05

NW6L/600 35 75 000/50 00 0 000/50 80/50 76/05 000/50 80/50 76/05 000/50 80/50 76/05 000/50 80/50 76/05 000/50 00 0 000/50 80/50 76/05 000/50 80/50 76/05

D-9

Complementary technical information

Protection of switchdisconnectors

INS40 to 2500 and INV100 to 2500 by fuses


DB40458

Interpact INS switch-disconnectors Upstream protection


By fuse 500 V Type aM (1) / max. rating (A) Isc max. kA rms Making capacity kA peak Type gG (2) / max. rating (A) Isc max. kA rms Making capacity kA peak Type gG (1) / max. rating (A) Isc max. kA rms Making capacity kA peak Type BS (2) / max. rating (A) Isc max. kA rms Making capacity kA peak Type BS (1) / max. rating (A) Isc max. kA rms Making capacity kA peak (1) Mandatory protection by an external thermal relay. (2) No external thermal relay.

INS40
5 00 0 3 00 0 00 00 0 3 80 76 5 & 00M5 80 76

INS63
5 00 0 50 00 0 00 00 0 50 & 3M50 80 76 5 & 00M5 80 76

INS80
5 00 0 63 00 0 00 00 0 63 & 3M63 80 76 5 & 00M5 80 76

Interpact INS switch-disconnectors Upstream protection


By fuse 500 V Type aM (1) / max. rating (A) Isc max. kA rms Making capacity kA peak Type gG (2) / max. rating (A) Isc max. kA rms Making capacity kA peak Type gG (1) / max. rating (A) Isc max. kA rms Making capacity kA peak Type BS (2) / max. rating (A) Isc max. kA rms Making capacity kA peak (1) Type BS / max. rating (A) Isc max. kA rms Making capacity kA peak By fuse 690 V Type aM (1) / max. rating (A) Isc max. kA rms Making capacity kA peak Type gG (2) / max. rating (A) Isc max. kA rms Making capacity kA peak Type gG (1) / max. rating (A) Isc max. kA rms Making capacity kA peak (1) Mandatory protection by an external thermal relay. (2) No external thermal relay.

INS/INV400
800 00 0 35 00 0 630 50 05 35 & 00M35 80 76 355 & 35M355 80 76 800 00 0 35 00 0 630 50 05

INS/INV500
800 00 0 400 00 0 630 50 05 400 80 76 450 & 400M450 80 76 800 00 0 400 00 0 630 50 05

INS/INV630
800 00 0 500 00 0 500/630 00/50 0/05 500 80 76 450 & 400M450 80 76 800 00 0 500 00 0 500/630 00/50 0/05

D-0

Complementary technical information

Protection of switchdisconnectors

INS40 to 2500 and INV100 to 2500 by fuses


INS100
00 00 0 80 00 0 5/60 00/50 0/05 80 & 63M80 80 76 60 & 00M60 80 76

INS125
00 00 0 00 00 0 5/60 00/50 0/05 00 & 63M00 80 76 60 & 00M60 80 76

INS160
00 00 0 5 00 0 5/60 00/50 0/05 5 & 00M5 80 76 60 & 00M60 80 76

INS250-100 INV100
35 00 0 80 00 0 5/355 00/50 0/05 80 & 63M80 80 76 50 & 00M50 80 76

INS250-160 INV160
35 00 0 5 00 0 5/355 00/50 0/05 5 & 00M5 80 76 50 & 00M50 80 76

INS250-200 INV200
35 00 0 60 00 0 5/355 00/50 0/05 60 & 00M60 80 76 50 & 00M50 80 76

INS/INV250
35 00 0 00 00 0 5/355 00/50 0/05 00 & 00M00 80 76 50 & 00M50 80 76

INS/INV320
800 00 0 50 00 0 630 50 05 50 & 00M50 80 76 355 & 35M355 80 76

INS/INV630b
000/50 00 0 500 00 0 000/50 80/50 76/05 500 80 76 000/50 80/50 76/05 000/50 00 0 500 00 0 000/50 80/50 76/05

INS/INV800
000/50 00 0 630 00 0 000/50 80/50 76/05 630 80 76 000/50 80/50 76/05 000/50 00 0 630 00 0 000/50 80/50 76/05

INS/INV1000
000/50 00 0 800 00 0 000/50 80/50 76/05 800 80 76 000/50 80/50 76/05 000/50 00 0 800 00 0 000/50 80/50 76/05

INS/INV1250
000/50 00 0 000 80 76 000/50 80/50 76/05 000 80 76 000/50 80/50 76/05 000/50 00 0 000 80 76 000/50 80/50 76/05

INS/INV1600
000/50 00 0 000/50 80/50 76/05 000/50 80/50 76/05 000/50 80/50 76/05 000/50 80/50 76/05 000/50 00 0 000/50 80/50 76/05 000/50 80/50 76/05

INS/INV2000
-

INS/INV2500
-

D-

Additional characteristics

Characteristics of switch-disconnectors

INS40 to 2500 and INV100 to 2500 for direct current


Parallel connection of poles
Maximum permissible current at 60 C
INS Rating (A) 40 63 80 00 5 60 00 50 30 400 500 630 800 000 50 600 000 500 In max 3P parallel 96 5 9 40 300 384 480 600 768 960 00 5 90 400 3000 3840 4800 6000 In max 4P parallel 8 0 56 30 400 5 640 800 04 80 600 06 560 300 4000 50 6400 8000

INS/INV

D-

D-3

TOOLS
schneider-electric.com The technical guide

This international site allows you to access all the Schneider Electric products in just  clicks via comprehensive range datasheets, with direct links to: p complete library: technical documents, catalogs, FAQs, brochures p selection guides from the e-catalog. p product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, the list of country contacts

These technical guides help you comply with installation standards and rules i.e.: the electrical installation guide, the protection guide, the switchboard implementation guide, the technical booklets and the co-ordination tables all form genuine reference tools for the design of high performance electrical installations. For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.

Interpact INS/INV

Catalogue numbers

Presentation Functions and characteristics Installation recommendations Dimensions and connection Complementary technical information

2 A-1 B-1 C-1 D-1

INS40 to 160
Complete fixed/FC device and accessories Accessories

E-2
E- E-3

INS250-100 to 630
Complete fixed/FC device and accessories

E-5
E-5

INV100 to 630
Complete fixed/FC device and specific accessories

E-6
E-6

INS250-100 to 250 and INV100 to 250


Accessories

E-7
E-7

INS320 to 630 and INV320 to 630


Accessories

E-10
E-0

INS630b to 2500
Complete fixed/FC device and accessories

E-12
E-

INS630b to 2500 and INV630b to 2500


Accessories

E-14
E-4

INSE80 (40 to 80 A) molded case switch UL489/ CSA C22-2 N 5.2


Complete fixed/FC device and accessories

E-16
E-6

INSJ400 (250 to 400 A) molded case switch UL489/ CSA C22-2 N 5.2
Complete fixed/FC device and accessories

E-18
E-8

E-

Catalogue numbers

INS40 to 160

Complete fixed/FC device and accessories

Interpact INS40 to 160 standard version with black handle


Interpact INS40 Interpact INS63 Interpact INS80 Interpact INS80PV - Photovoltaic 3P 28900 28902 28904 3P 28908 28910 28912 4P 28901 28903 28905 28907 4P 28909 28911 28913
DB56
.4 .2 .2 .1

Interpact INS00 Interpact INS5 Interpact INS60

DB56

Interpact INS40 to 160 with red handle and yellow front


Interpact INS40 Interpact INS63 Interpact INS80 3P 28916 28918 28920 3P 28924 28926 28928 4P 28917 28919 28921 4P 28925 28927 28929
DB56
.4 .1

Interpact INS00 Interpact INS5 Interpact INS60

DB56

Individual enclosures
IP55 heavy-duty sheetmetal enclosure
E9049

For INS40 to INS60 with extended standard rotary handle For INS40 to INS60 with extended red handle on yellow front

31208 31209

IP55 heavy-duty insulating enclosure


DB7566

For INS40 to INS60 with extended standard rotary handle For INS40 to INS60 with extended red handle on yellow front
N

28967 28968

Connection accessories
Distribloc distribution block (for bare cables)
INS40 to 5
E33404

INS00 to 60

5 A,  outgoing spring terminals (7 x 4 mm + 3 x 6 mm +  x 0 mm) +  outgoing tunnel terminal (35 mm) (1) 4 prefabricated connections 5 A, 35 mm, l = 0 mm (1) 60 A,  outgoing spring terminals (7 x 4 mm + 3 x 6 mm +  x 0 mm) +  outgoing tunnel terminal (35 mm) with 4 prefabricated connections (1) 40 A, 4 x 3 holes ( x 0 mm +  x 6 mm) (1) 00 A, 4 x 7 holes (3 x 0 mm + 3 x 6 mm +  x 5 mm) (1) 5 A, 4 x 3 holes (5 x 0 mm + 5 x 6 mm +  x 5 mm +  x 35 mm) (1) 5 A, 4 x 7 holes (7 x 0 mm + 7 x 6 mm +  x 5 mm +  x 35 mm) (1) Additional neutral bar 40 A, L = 89 mm (1) 00 A, L = 6 mm (1) 5 A, L = 07 mm (1) 5 A, L = 34 mm (1)

04045 04047 04046

Multi-stage distribution block (for bare cables)


INS40 to 5
DB7534

13508 13510 13512 13514 13516 13515 13517 13518

(1) Product sold by MGA.

E-

Catalogue numbers

INS40 to 160
Accessories

Connection accessories (cont.)


Connectors for bare Cu or Al cables
DB7559

Snap-in

INS00 to 60 S y 95 mm

Set of 3 Set of 4

28947 28948

DB7560

Distribution connector for 3 rigid cables up to 6 mm or 3 flexible cables up to 0 mm

INS40 to 80

Set of 3 Set of 4

19096 19091

DB756

Distribution connector for 4 rigid cables up to 5 mm or 4 flexible cables up to 6 mm

INS00 to 60

Set of 3 Set of 4

28949 28950

DB756

Crimp lugs for copper cables


For 95 mm cables with interphase barriers INS00 to 60 Set of 3 Set of 4 28951 28952

Terminal shrouds
DB759

INS40 to 80 INS00 to 60

3P/4P 3P/4P

Set of  Set of 

28955 28956

Terminal shields
DB7593

INS40 to 80 INS00 to 60

3P/4P 3P/4P

Set of  Set of 

28957 28958

Interphase barriers
INS00 to 60
E88893

3P/4P

Set of 6

28959

Electrical auxiliaries
Auxiliary contacts
DB7563

 OF / CAF / CAO (standard)  OF / CAF / CAO (low level)

INS40 to 60 INS40 to 60

29450 29452

Rotary handles
Accessories for conversion to extended rotary handles
E33405

Front control

Black handle Red handle on yellow front

INS40 to 60 INS40 to 60

28941 28942

DB563

Lateral control Lateral control on PRAGMA F functional enclosure

Black handle Red handle on yellow front Black handle Red handle on yellow front

INS40 to 60 INS40 to 60 (1) INS40 to 60 INS40 to 60 (1)

28943 28944 28945 (2) 28946

(1) For red/yellow switch versions only. (2) Not available with Prisma Plus.

E-3

Catalogue numbers

INS40 to 160 (cont.)


Accessories (cont.)

Locking and interlocking


Handle locking
By  to 3 padlocks (OFF position), hasp dia. 5 to 8 mm, or by lead seals

Built-in

DB7564

Interlocking for extended rotary handles


Mechanical
DB0770

Spare parts
DB7565

(1) For red/yellow switch versions only.

E-4

2 .

.4

1 .

.2

.1

28953

Black handle Red handle

(1)

28962 28963

Catalogue numbers

INS250-100 to 630

Complete fixed/FC device and accessories

Interpact INS250 to 630 standard version with black handle


Interpact INS50-00A Interpact INS50-60A Interpact INS50-00A Interpact INS50 3P 31100 31104 31102 31106 4P 31101 31105 31103 31107
E50995

Interpact INS30 Interpact INS400 Interpact INS500 Interpact INS630

3P 31108 31110 31112 31114

4P 31109 31111 31113 31115

E50996

Interpact INS250 to 630 with red handle and yellow front


Interpact INS50-00A Interpact INS50-60A Interpact INS50-00A Interpact INS50 3P 31120 31124 31122 31126 4P 31121 31125 31123 31127
E50995

Interpact INS30 Interpact INS400 Interpact INS500 Interpact INS630

3P 31128 31130 31132 31134

4P 31129 31131 31133 31135

E50996

Source changeover systems


Complete assembly
With Interpact INS50-00A With Interpact INS50-60A With Interpact INS50-00A With Interpact INS50 With Interpact INS30 With Interpact INS400 With Interpact INS500 With Interpact INS630 3P 31140 31144 31142 31146 31148 31150 31152 31154 3P 29358 32619 4P 31141 31145 31143 31147 31149 31151 31153 31155 4P 29359 29324 32620 32583
E89638

Downstream coupling accessories


For Interpact INS50 Long downstream 3P/4P terminal shields (set of ) For Interpact INS30 to 630 Long downstream 3P/4P terminal shields (set of )
E50998

Individual enclosures
IP55 heavy-duty sheetmetal enclosure
For INS50-00 to 50 with extended standard rotary handle For INS50-00 to 50 with extended red rotary handle on yellow front For INS30 to 630 with extended standard rotary handle For INS30 to 630 with extended red rotary handle on yellow front 31210 31211 31212 31213
E9049

IP55 heavy-duty insulating enclosure


For INS50-00 to 50 with extended standard rotary handle For INS50-00 to 50 with extended red rotary handle on yellow front For INS30 to 630 with extended standard rotary handle For INS30 to 630 with extended red rotary handle on yellow front 31204 31205 31206 31207
E349

E-5

Catalogue numbers

INV100 to 630

Complete fixed/FC device and specific accessories

Interpact INV100 to 630 standard version with black handle


Interpact INV00 Interpact INV60 Interpact INV00 Interpact INV50 3P 31160 31164 31162 31166 4P 31161 31165 31163 31167
DB569

Interpact INV30 Interpact INV400 Interpact INV500 Interpact INV630

3P 31168 31170 31172 31174

4P 31169 31171 31173 31175

DB5630

Interpact INV100 to 630 with red handle and yellow front


Interpact INV00 Interpact INV60 Interpact INV00 Interpact INV50 3P 31180 31184 31182 31186 4P 31181 31185 31183 31187
DB569

Interpact INV30 Interpact INV400 Interpact INV500 Interpact INV630

3P 31188 31190 31192 31194

4P 31189 31191 31193 31195

DB5630

Individual enclosures
IP55 heavy-duty insulating enclosure
For INV00 to 50 with extended standard rotary handle For INV00 to 50 with extended red rotary handle on yellow front For INV30 to 630 with extended standard rotary handle For INV30 to 630 with extended red rotary handle on yellow front 31204 31205 31206 31207
DB7566

Combination with Compact NS devices for "tarif jaune / tarif vert"


INV00 to 50 combination with NS50 INV30 to 630 combination with NS50 Front alignment base for INV30 to 630 combination with NS50 INV30 to 630 combination with NS400/630
5...8

E8964

E8964

(1) Product sold by MGA and valid for new Prisma Plus only.

E-6

31066 31067 31064 31068

Flexible connection assembly for vertical INV00 to 50 with horizontal NS50 (1) Flexible connection assembly for vertical INV00 to 50 with horizontal Vigi NS50 (1) Flexible connection assembly for vertical INV30 to 630 with horizontal NS50/400/630 (1) Flexible connection assembly for vertical INV30 to 630 with horizontal Vigi NS50/400/630 (1) Flexible connection assembly for vertical INV00 to 50 with vertical NS50 beside Flexible connection assembly for vertical INV30 to 630 with vertical NS400/630 beside Flexible connection assembly for vertical INV30 to 630 with vertical NS50 beside

04443 04444 04445 04446 31071 31072 31093

Catalogue numbers

INS250-100 to 250 and INV100 to 250


Accessories

Connection accessories
Rear connections
DB7567

Short ( pair) Long ( pair)

29235 29236

Cable connectors
DB7568

Snap-on, for cables:

Steel: .5 to 95 mm ; y 60 A Aluminium: 5 to 95 mm ; y 50 A Aluminium: 0 to 85 mm ; y 50 A

DB7569

Tab connector for voltage tap on 85 mm cable connector Clip for cable connector Distribution connector for six .5 to 35 mm cables with interphase barriers

Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4 Set of  Set of 0 Set of 3 Set of 4

29242 29243 29227 29228 29259 29260 29348 29241 29248 29249

Polybloc distribution block (for bare cables)


DB0744 DB07443

60 A 50 A

For 6 cables (0 mm) per pole For 9 cables (6 x 0 mm + 3 x 6 mm) per pole Additives blocks of  x 35 mm per pole

P 3P 4P 3P 4P Set of 3 Set of 4 Set of 3 Set of 4

04031 04033 04034 04155 04156 29261 29262 29263 29264

Terminal extensions (supplied with 2 or 3 interphase barriers)


DB7570

Right-angle terminal extensions

DB757

Straight terminal extensions

Spreaders (for upstream or downstream connection)


DB757

Separate for each pole

3P 4P 3/4P 3/4P

LV431563 LV431564 31061 31064

E5006

One-piece Front alignment base for one-piece spreader

Crimp lugs for copper cables (supplied with 2 or 3 interphase barriers)


DB7573

For 0 mm cables For 50 mm cables For cable 85 mm cables

Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4

LV429252 LV429256 LV429253 LV429257 LV429254 LV429258 LV429504 LV429505 LV429506 LV429507

Crimp lugs for aluminium cables (supplied with 2 or 3 interphase barriers)


DB7574

For 50 mm cables For 85 mm cables

Terminal shields
DB07444 DB07445

Short Long

3/4 P 3/4 P

Set of  Set of 

29322 29324

Interphase barriers
Set of 6
DB094

LV429329

E-7

Catalogue numbers

INS250-100 to 250 and INV100 to 250 (cont.)


Accessories (cont.)

Special connection accessories for INS250-100 to 250DC and INV100 to 250DC


Terminal extensions for series or parallel connection of two poles (*)  terminal ext. (*) Series connection of: 2 poles = 1 terminal extension 3 poles = 2 terminal extensions 4 poles = 3 terminal extensions Parallel connection of: 2 poles = 2 terminal extensions 3 poles = set of 2 terminal extensions (29499) 4 poles = 4 terminal extensions Terminal extensions for parallel connection of three poles Set of  terminal extensions 4P terminal shields for series connection of poles Set of  4P terminal shields for parallel connection of poles (P/4P) Set of  29498
DB08556

29499 29496 29497

DB08557

Electrical auxiliaries
Auxiliary contacts (changeover type)
DB7563

OF or CAM (early make or break) Low level OF or CAM (early make or break)

29450 29452

Indication and measurement modules


Ammeter module (4P)
Rating (A)
E5008
A
8 4 0
160/5

16 12

00 50 50

LV429456 LV430556 LV431566

Current transformer module and voltage output (4P)


E5009

Rating (A)

00 50 50

LV429462 LV430562 LV431570

Current transformer module (4P)


Rating (A)
E5009

00 50 50

LV429458 LV430558 LV431568

Voltage presence indicator


DB0570

Rating (A)

50

LV429325

Rotary handles
Extended front control
E33405

For INS50 with standard rotary handle For INS50 with red handle on yellow front For complete source changeover assembly

(1)

31050 31051 31055

Lateral control
Direct lateral control for INS and INV250 Lateral support + standard lateral control assembly or + red and yellow lateral control assembly Extended lateral control for INS and INV250 Standard lateral control assembly Red and yellow lateral control assembly (1) For red/yellow switch versions only. 31054 31057 31058 31057 31058
DB564

(1)

(1)

E-8

Catalogue numbers

INS250-100 to 250 and INV100 to 250 (cont.)


Accessories (cont.)

Locking and interlocking for INS/INV and source changeover systems


Locking for INS/INV

Handle locking by  to 3 padlocks (in OFF position) By keylock Keylocking device + Ronis 35B.500 keylock or + Profalux KS5 B4 D4Z keylock

Built-in 31087 41940 42888

DB565

Locking for INS complete source changeover assembly


Handle locking by  to 3 padlocks (in OFF position) By keylock Keylocking device + Ronis 35B.500 keylock or + Profalux KS5 B4 D4Z keylock Built-in 31097 41940 42888
DB077

Interlocking with key (2 keylocks / 1 key)


By  keylocks
DB0549

INS50 keylocking device INS30-600 keylocking device + Ronis 35B.500 keylock or + Profalux KS5 B4 D4Z keylock

 x 31087  x 31088 41950 42878

Interlocking for INS/INV with direct or extended rotary handle


Mechanical interlocking for INS50
DB7585
5...8 5...8

31073

5...8

Installation accessories
Front panel escutcheons
DB7586

For INS/INV For ammeter module, IP40

31079 29318

Lead seal accessories


29375

Spare parts
 snap-in nuts for fixed/FC(M8) 00 identification labels Bag of screws Black handle Red handle Viewport for INV00/60/50 (1) For red/yellow switch versions only. 30554 29314 29312 31082 31083 31089

(1)

E-9

Catalogue numbers

INS320 to 630 and INV320 to 630


Accessories

Connection accessories
Rear connections
DB7567

Short ( pair) Long ( pair)

32475 32476

Cable connectors
E040

For  cable, 35 mm to 300 mm For  cables, 35 mm to 40 mm

E04

Tab connector for voltage tap on cable connector

Set of 3 Set of 4 Set of 3 Set of 4 Set of 

32479 32480 32481 32482 29348

Terminal extensions (supplied with 2 or 3 interphase barriers)


DB7570

Right-angle terminal extensions

Set of 3 Set of 4 Set of 3 Set of 4

32484 32485 32486 32487

Edgewise terminal extensions


E76

Spreaders (for upstream or downstream connection)


DB757

One-piece

5.5 mm 70 mm

3P 4P 3P 4P Set of 3 Set of 4 Set of 3 Set of 4

32490 32491 32492 32493 32500 32501 32502 32503

Crimp lugs for copper cables (supplied with 2 or 3 interphase barriers)


DB7573

For 40 mm cables For 300 mm cables

Crimp lugs for aluminium cables (supplied with 2 or 3 interphase barriers)


DB7574

For 40 mm cables For 300 mm cables

Set of 3 Set of 4 Set of 3 Set of 4

32504 32505 32506 32507

Terminal shields
DB566

Short Long Long for 5.5 mm spreader (supplied with insulating plate)

3/4P 3/4P 3/4P

Set of  Set of  Set of 

32563 32565 32583

Interphase barriers
Set of 6
E896

32570

Special connection accessories for INS/INV320 to 630DC


Terminal extensions for series or parallel connection of two poles (*) (*) Series connection of: 2 poles = 1 terminal extension 3 poles = 2 terminal extensions 4 poles = 3 terminal extensions Parallel connection of: 2 poles = 2 terminal extensions 4 poles = 4 terminal extensions 4P terminal shields for series connection of poles 4P terminal shields for parallel connection of poles  terminal ext. 32868
DB08566

Set of  Set of 

32866 32867

E-0

Catalogue numbers

INS320 to 630 and INV320 to 630 (cont.)


Accessories (cont.)

Electrical auxiliaries
Auxiliary contacts (changeover type)
DB7563

OF or CAM (early make or break) OF or CAM low level (early make or break)

29450 29452

Indication and measurement modules


Ammeter module (4P)
Rating (A)
E5008
A
8 4 0
160/5

400 600

LV432656 LV432856

16 12

Current transformer module (4P)


Rating (A)
E5009

400 600

LV432658 LV432858

Voltage presence indicator


DB0570

Rating (A)

630

LV432566

Rotary handles
Extended front control
E8967

For INS30/400/630 with standard rotary handle For INS30/400/630 with red handle on yellow front For complete source changeover assembly

(1)

31052 31053 31055

Locking and interlocking for INS/INV and source changeover systems


Locking for INS/INV
Handle locking by  to 3 padlocks (in OFF position) By keylock Keylocking device + Ronis 35B.500 keylock or + Profalux KS5 B4 D4Z keylock Built-in 31088 41940 42888
E8968

Locking for INS complete source changeover assembly


Handle locking by  to 3 padlocks (in OFF position) By keylock Keylocking device + Ronis 35B.500 keylock or + Profalux KS5 B4 D4Z keylock Built-in 31097 41940 42888
DB077

Interlocking with key (2 keylocks / 1 key)


By  keylocks
DB0549

INS50 keylocking device INS30-600 keylocking device + Ronis 35B.500 keylock or + Profalux KS5 B4 D4Z keylock

 x 31087  x 31088 41950 42878

Interlocking for INS/INV with direct or extended rotary handle


Mechanical interlocking for INS30/400/630
E8964

31074

5...8

Installation accessories
Front panel escutcheons
E859

For INS/INV For ammeter module, IP40

31080 29318

Lead seal accessories


29375

Spare parts
00 labels Bag of screws Black handle Red handle Viewport for INV30/400/630 (1) For red/yellow switch versions only. 29314 32552 31084 31085 31090

(1)

E-

Catalogue numbers

INS630b to 2500

Complete fixed/FC device and accessories

Interpact INS630b to 2500 standard version with black handle


Interpact INS630b Interpact INS800 Interpact INS000 Interpact INS50 Interpact INS600 3P 31342 31330 31332 31334 31336 4P 31343 31331 31333 31335 31337
E88699

DB563

Interpact INS000 Interpact INS500

31338 31340

31339 31341

Interpact INS800 to 1600 with red handle and yellow front


Interpact INS800 Interpact INS000 Interpact INS50 Interpact INS600 3P 31344 31346 31348 31350 4P 31345 31347 31349 31351
E88699

E-

Catalogue numbers

INV630b to 2500

Complete fixed/FC device and specific accessories

Interpact INV630b to 2500 standard version with black handle


Interpact INV630b Interpact INV800 Interpact INV000 Interpact INV50 Interpact INV600 3P 31370 31358 31360 31362 31364 4P 31371 31359 31361 31363 31365
E89639

DB563

Interpact INV000 Interpact INV500

31366 31368

31367 31369

Interpact INV800 to 1600 with red handle and yellow front


Interpact INV800 Interpact INV000 Interpact INV50 Interpact INV600 3P 31372 31374 31376 31378 4P 31373 31375 31377 31379
E89639

Combination with Compact NS devices (for "tarif vert")


DB5633

INV630b/000/50 combination with NS800/000/50

3P 31385

4P 31386

E-3

Catalogue numbers

INS630b to 2500 and INV630b to 2500


Accessories

Connection accessories
Vertical connection adapters
INS/INV630b-600
E8870

3P 4P

Set of 3 Set of 4

31301 31302

Cable lug adapters


INS/INV630b-600
E8870

3P 4P

Set of 3 Set of 4

33644 33645

Spreaders
INS/INV630b-600
E88703

3P 4P

Set of 3 Set of 4

31305 31306 31310

Connector for direct connection (edgewise or flat) to INS000/500


DB08558

Insulation accessories
Base for terminal shield (not compatible with interphase barriers)
INS/INV630b-600
E88704

3P 4P

31307 31308

Terminal shield
INS/INV630b-600
E88705

3P 4P

33628 33629

Interphase barriers (not compatible with terminal shield and base)


E8965

INS/INV630b-600 INS/INV000/500

4P 4P

Set of 6 Set of 6

31315 31319

Electrical auxiliaries
Auxiliary contacts (changeover type) INS/INV630b-2500
DB7563

OF or CAM (early make or break) OF or CAM low level (early make or break)

29450 29452

Extended front control


E88708

INS/INV630b-500 INS/INV630b-600

For standard rotary handle For red handle on yellow front

(1)

31288 31289

(1) For red/yellow switch versions only.

E-4

Catalogue numbers

INS630b to 2500 and INV630b to 2500 (cont.)


Accessories (cont.)

Locking and interlocking


Locking for INS/INV630b to 2500
Handle locking by  to 3 padlocks (in OFF position) By keylock Keylocking device + Ronis 35B.500 keylock or + Profalux KS5 B4 D4Z keylock Built-in 31291 41940 42888
E8960

Interlocking for INS/INV630b to 2500


By keylock
E8966

Keylocking device + Ronis 35B.500 keylock ( keylocks /  key) or + Profalux KS5 B4 D4Z keylock ( keylocks /  key)

 x 31291 41950 42878

Installation accessories
Escutcheon
INS630b-500
E88707

3P/4P

31295

Lead seal accessories


31316

Spare parts
INS/INV630b-600
E88709

INS/INV000-500 Viewport for INV630b/500

Black handle Red handle Black handle 3P 4P

(1)

31296 31297 31298 31293 31294

E88700

(1) For red/yellow switch versions only.

E-5

Catalogue numbers

INSE80 (40 to 80 A) molded case switch UL489/CSA C22-2 N 5.2


Complete fixed/FC device and accessories

Interpact INSE80 (40 to 80 A) standard version with black handle


DB4737

Interpact INSE80

40 A 60 A 80 A

3P 28994 28996 28998

4P 28995 28997 28999

Individual enclosures
IP55 heavy-duty sheetmetal enclosure (1)
E9049

For INSE80-40 A to INSE80-80 A with extended standard rotary handle For INSE80-40 A to INSE80-80 A with extended red handle on yellow front

31208 31209

IP55 heavy-duty insulating enclosure (1)


E349

For INSE80-40 A to INSE80-80 A with extended standard rotary handle For INSE80-40 A to INSE80-80 A with extended red handle on yellow front
N

28967 28968

Connection accessories
Distribloc distribution block (for bare cables)
E33404

INSE80-40 A to INSE80-80 A (1)

60 A,  outgoing spring terminals (7 x 4 mm + 3 x 6 mm +  x 0 mm) +  outgoing tunnel terminal (5 mm) with prefabricated connections

(2)

07106

Multi-stage distribution block (for bare cables)


DB7534

INSE80-40 A to INSE80-80 A (1)

5 A, 4 x 0 holes (5 x 0 mm + 4 x 6 mm +  x 35 mm) 5 A, 4 x 7 holes (8 x 0 mm + 8 x 6 mm +  x 35 mm)

(2) (2)

13512 13514

Connectors for bare Cu or Al cables


Snap-on
DB7559

INSE80-40 A to INSE80-80 A .5 to 95 mm  AWG to 3/0 AWG C4/AL INSE80-40 A to INSE80-80 A (1)

Set of 3 Set of 4

28947 28948

DB756

Distribution connector for 4 rigid cables up to 5 mm or 4 flexible cables up to 6 mm

Set of 3 Set of 4

28949 28950

Crimp lugs for copper cables (1)


DB756

For 95 mm cables with interphase barriers

INSE80-40 A to INSE80-80 A

Set of 3 Set of 4

28951 28952

Terminal shrouds
INSE80-40 A to INSE80-80 A
DB759

3P/4P

Set of 

28956

Terminal shields
INSE80-40 A to INSE80-80 A
DB7593

3P/4P

Set of 

28958

(1) Not UL Listed. (2) Product sold by MGA.

E-6

Catalogue numbers

INSE80 (40 to 80 A) molded case switch UL489/CSA C22-2 N 5.2


Complete fixed/FC device and accessories (cont.)

Connection accessories (cont.)


Interphase barriers
INSE80-40 A to INSE80-80 A
E88893

3P/4P

Set of 6

28959

Electrical auxiliaries
Auxiliary contacts
DB7563

 OF / CAF / CAO (standard)  OF / CAF / CAO (low level)

INSE80-40 A to INSE80-80 A INSE80-40 A to INSE80-80 A

29450 29452

Rotary handles
Accessories for conversion to extended rotary handles
Front control
E33405

Lateral control

Black handle Red handle on yellow front Black handle

INSE80-40 A to INSE80-80 A INSE80-40 A to INSE80-80 A INSE80-40 A to INSE80-80 A INSE80-40 A to INSE80-80 A INSE80-40 A to INSE80-80 A INSE80-40 A to INSE80-80 A

28941 28942 28943 28944 28963 28945 28946

Red handle on yellow front + red handle (2) Lateral control on G, GX or Black handle PRAGMA F functional enclosure Red handle on yellow front (2)

DB4738

Locking and interlocking


Handle locking
By  to 3 padlocks (OFF position), hasp dia. 5 to 8 mm, or by lead seals

Built-in

DB7564

Interlocking for extended rotary handles


Mechanical (1)
DB0770

Spare parts
DB7565

(1) Not UL listed. (2) For red/yellow switch versions only.

2 .

4 .

1 .

2 .

1 .

28953

Black handle Red handle (2)

28962 28963

E-7

Catalogue numbers

INSJ400 (250 to 400 A) molded case switch UL489/ CSA C22-2 N 5.2

Complete fixed/FC device and accessories


Interpact INSJ400 (250 A to 400 A) standard version with black handle
DB4739

Interpact INSJ400-50 A Interpact INSJ400-400 A

3P 31118 31136

4P 31119 31137

Individual enclosures
IP55 heavy-duty sheetmetal enclosure (1)
E9049

For INSJ400-50 to 400 A with extended standard rotary handle For INSJ400-50 to 400 A with extended red rotary handle on yellow front

31212 31213

IP55 heavy-duty insulating enclosure (1)


DB7566

For INSJ400-50 to 400 A with extended standard rotary handle For INSJ400-50 to 400 A with extended red rotary handle on yellow front
N

31206 31207

Connection accessories
Rear connections
DB7567

Short ( pair) Long ( pair)

32475 32476

Bare cable connectors


DB7587

For  cable, 35 mm to 300 mm For  cables, 35 mm to 40 mm Tab connector for voltage tap on bare cable connector

DB7588

Set of 3 Set of 4 Set of 3 Set of 4 Set of 

32479 32480 32481 32482 29348

Terminal extensions (supplied with 2 or 3 interphase barriers)


DB7570

Right-angle terminal extensions Edgewise terminal extensions

DB7589

Set of 3 Set of 4 Set of 3 Set of 4

32484 32485 32486 32487

Spreaders (for upstream or downstream connection)


DB757

One-piece

5.5 mm 70 mm

3P 4P 3P 4P Set of 3 Set of 4 Set of 3 Set of 4

32490 32491 32492 32493 32500 32501 32502 32503

Crimp lugs for copper cables (supplied with 2 or 3 interphase barriers) (1)
DB7573

For 40 mm cables For 300 mm cables

Crimp lugs for aluminium cables (supplied with 2 or 3 interphase barriers) (1)
DB7574

For 40 mm cables For 300 mm cables

Set of 3 Set of 4 Set of 3 Set of 4

32504 32505 32506 32507

(1) Not UL Listed.

E-8

Catalogue numbers

INSJ400 (250 to 400 A) molded case switch UL489/ CSA C22-2 N 5.2

Complete fixed/FC device and accessories


Connection accessories (cont.)
Terminal shields
DB07444 DB07445

Short Long Long for 5.5 mm spreader (supplied with insulating plate)

3/4P 3/4P 3/4P

Set of  Set of  Set of 

32563 32565 32583

Interphase barriers
Set of 6
E896

32570

Electrical auxiliaries
Auxiliary contacts (changeover type)
DB7563

OF or CAM (early make or break) OF or CAM low level (early make or break)

29450 29452

Rotary handles
Extended front control
E8967

For INSJ400-50 to 400 A with standard rotary handle For INSJ400-50 to 400 A with red handle on yellow front + red handle (1)

31052 31053 31085

Locking and interlocking and source changeover systems


Locking
Handle locking by  to 3 padlocks (in OFF position) By keylock Keylocking device + Ronis 35B.500 keylock or + Profalux KS5 B4 D4Z keylock Built-in 31088 41940 42888
E8968

Interlocking with key (2 keylocks / 1 key)


By  keylocks
DB0549

INSJ400-50 to 400 A keylocking device + Ronis 35B.500 keylock or + Profalux KS5 B4 D4Z keylock

 x 31088 41950 42878

Interlocking with direct or extended rotary handle


Mechanical interlocking for INSJ400-50 to 400 A
E8964

31074

5...8

Installation accessories
Front panel escutcheons
31080
DB4740

Lead seal accessories


29375

Spare parts
00 labels Bag of screws Black handle Red handle (1) For red/yellow switch versions only. 29314 32552 31084 31085

E-9

Notes

E-0

Schneider Electric Industries SAS


35, rue Joseph Monier CS 30323 F- 92506 Rueil Malmaison Cedex RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper . Design: Schneider Electric Photos: Schneider Electric Printed: Altavia Connexion - made in France

LVPED208015EN

11-2010

ART.836823 2010 - Schneider Electric - All rights reserved