Types K, R, N, and C
Catalog 8501CT0301R7/08
2008
Class 8501
CONTENTS Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Type R Miniature Plug-in Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 Type K Plug-in Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78 Type KA Alternating Relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .910 Type N Sockets and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 1113 Type C Power Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Options
None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator
Type
RS41* RS41M1* RS41P14* RS41M1P14* RSD41* RSD41M1* RSD41P14* RSD41M1P14*
These miniature plug-in relays have a 10 Ampere resistive rating (except for RS/RSD41), the same as the Type K plug-in relays, but are much smaller. The compact size of these relays makes them ideal for downsizing equipment. SPDT through 4PDT AC or DC Operated Horsepower rated UL Contact Ratings
Type
8501RS41 h 8501RSD41 h 8501RS42 8501RSD42 8501RS43 8501RSD43 8501RS44 8501RSD44
h
DC Pilot Light Silver Cadmium Oxide Contacts Manual Operator and Pilot Light
Input Voltage
DPDT AC 50/60 Hz
Options
None Manual Operator Pilot Light Manual Operator and Pilot Light None
Type
RS42* RS42M1* RS42P14* RS42M1P14* RSD42* RSD42M1* RSD42P14* RSD42M1P14*
Complete line of Sockets Manual Operator / Bidirectional Green LED Pilot Light Options
Voltage
120 VAC 240 VAC 28 VDC 120 VAC 240 VAC 30 VDC 120 VAC 250 VAC 28 VDC 120 VAC 250 VAC 28 VDC
Resistive Rating
15 12 15 10 10 10 10 10 10 10 10 10
Horsepower Rating
1/3 1/2 1/3 1/2 Silver Cadmium Oxide Contacts 3PDT Silver Cadmium Oxide Contacts
Input Voltage
AC 50/60 Hz
Options
None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator
Type
RS43* RS43M1* RS43P14* RS43M1P14* RSD43* RSD43M1* RSD43P14* RSD43M1P14*
DC
Stocked Relays
AC Voltage 50/60 Hz Type 6
Voltage Code RS41 RS41M1 RS41P14 RS41M1P14 RS42 RS42M1 RS42P14 RS42M1P14 RS43 RS43M1 RS43P14 RS43M1P14 RS44 RS44M1 RS44P14 RS44M1P14 S S S S S S S S S S S S S S S V35
DC Voltage Type 6
Voltage Code RSD41 RSD41M1 RSD41P14 RSD41M1P14 S RSD42 RSD42M1 RSD42P14 RSD42M1P14 RSD43 RSD43M1 RSD43P14 RSD43M1P14 RSD44 RSD44M1 RSD44P14 RSD44M1P14 S S S S S S S S S
Options
None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator
Type
RS44* RS44M1* RS44P14* RS44M1P14* RSD44* RSD44M1* RSD44P14* RSD44M1P14*
12
V36
24
V14 S S S S S
120 240
V20 S S S S S V24
12
V51 S
24
V53 S S S S
V50
DC
Voltage code must be specified to order this product. Refer to standard voltage codes listed in the Stocked Relay table to the left and insert as shown in How To Order.
How to Order:
To Order Specify:
Class Number Type Number Voltage Code (See Stocked Relay Table to left)
Catalog Number
Class 8501 Type RS42 Voltage Code V20
S Stocked Factory Order items require a minimum order quantity of 25 and have a lead time of 12 weeks.
3 08/2008
8501 RS4V14 Pilot Light Option An Internal green pilot light is available in both AC and DC versions for positive indication of power to the coil. The pilot lights are bidirectional LEDs. 8501 RSD14P14V53 Manual Operation Option To speed circuit testing, a manual operator can be provided. The relay can be manually switched to simulate normal operation. NOTE: All Type R relays with a manual operator must be used on circuits of same polarity. 8501 RS14M1V14
Type
RS14 RS14M1 RS14P14 RS14M1P14 RSD14 RSD14M1 RSD14P14 RSD14M1P14
AC 50/60 Hz
Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator
DC
3A
Input Voltage
Options
None
Type
RS4 RS4M1 RS4P14 RS4M1P14 RSD4 RSD4M1 RSD4P14 RSD4M1P14
Contact Ratings
Type
RS4 h RSD4
h
AC 50/60 Hz
Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator
Voltage
120/240 VAC 30 VDC 120/240 VAC 30 VDC 120/240 VAC 30 VDC 120/240 VAC 30 VDC
Horsepower Rating
1/ 10
1/ 6
DC
1/ 16 a
1A
Best for low level switching Bifurcated Silver Gold Plated Contacts
Input Voltage
AC 50/60 Hz DC
Type
RS24
h
RS34 RSD34
RSD24
RS4/RSD4, RS14/RSD14 have C300 pilot duty rating. a Horsepower rating at 120 VAC.
Hermetically Sealed
5 Ampere Resistive q Silver Cadmium Oxide Contacts Suitable for Class I Division 2 Locations
Input Voltage
AC 50/60 Hz DC
Type
RS34 RSD34
How to Order:
To Order Specify:
Class Number Type Number Voltage Code (See Stocked Relay Table on page 5)
Catalog Number
Class 8501 Type RS4 Voltage Code V20
Voltage code must be specified to order this product. Refer to standard voltage codes listed in the Stocked Relays table on page 5 and insert as shown in How To Order. Do not ground frame.
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6 Sockets and Holddown Clips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14
12
V36
24
V14 S
48
V17
120
V20 S S S S S S S S S S
6
V50
12
V51 S
24
V53 S
48
V56
110
V60
S Stocked Factory Order items require a minimum order quantity of 25 and have a lead time of 12 weeks. Class 8501 Type Pick-Up Time Operating Data Drop-Out Time Operating Temperature Range Duty Cycle Voltage Range Coil AC Coils 1.2 VA sealed 1.2 VA sealed 1.2 VA sealed 1.2 VA sealed RS4 RSD4 RS14 RSD14 RS24 RSD24 RS34 RSD34 RS41 RSD41 RS42 RSD42 RS43 RSD43 RS44 RSD44
13 ms Max. 6 ms Max. -45 C to +70 C (-49 F to +158 F) Continuous AC coils +10%, -15% of nominal DC coils +10%, -20% of nominal 1.5 VA inrush, 1.1 VA sealed 2.2 VA inrush, 1.3 VA sealed
0.9 watt
0.9 watt
0.9 watt
0.9 watt
1.0 watt
N/A
File CCN
N/A
File Class
N/A
211268 3211 07
Yes
File CCN
E78351 NLDX
E78351 NLDX
N/A
When
5 08/2008
1 5 9 13 14
1 3 5 7
RS42, RSD42
2 4 6 8
1 4 7 10
2 5 8
3 6 9 11
1 5 9 13
2 6 10
RS44, RSD44
3 7 11
4 8 12 14
1 5 9 13
2 6 10
3 7 11
4 8 12 14
RS41, RSD41
RS43, RSD43
.21 5
.04 1
.25 6
9 13
9 13
.52 13
.52 13
RS34, RSD34
1.10 27.9
0.55 14.0
1.100 27.94
1.42 36.1
0.870 22.10
(When Provided)
0.130 3.3
1
13 14
1 3
2 4
6 8
RS41, RSD41
1.10 27.9
1.10 27.9
1.24 31.49
1.63 41.40
(When Provided)
(When Provided)
0.630 16.002
0.630 16.002
1.42 36.07
0.870 22.10
0.870 22.10
9 13 1 5
Dual Dimensions:
7 10 8 9 11
10
1 4 2 5 3 6
2 6 3 7 4 8
11 12 14
RS43, RSD43
RS44, RSD44
Inches Millimeters
Contact Arrangement
DPDT DPDT 3PDT 3PDT DPDT DPDT 3PDT 3PDT
Options
None Pilot Light None Pilot Light None Pilot Light None Pilot Light
Type
KP12 KP12P14 KP13 KP13P14 KPD12 KPD12P14 KPD13 KPD13P14
DC
Contact Arrangement
DPDT
Options
Options
None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator Pilot Light Manual Operator and Pilot Light
Type
KU12 KU12M1 KU12P14 KU12M1P14 KU13 KU13M1 KU13P14 KU13M1P14 KUD12 KUD12M1 KUD12P14 KUD12M1P14 KUD13 KUD13M1 KUD13P14 KUD13M1P14
None Available 3PDT DPDT KF13 KFD12 None Available 3PDT KFD13
DC
3PDT DPDT
Contact Arrangement
DPDT
Options
Type
DPDT DPDT
None Available
KL12 DC
DC
DPDT
None Available
KLD12
Stocked Relays
Type AC Voltage 50/60 Hz 6 12 24 120 240 Type 6 12 DC Voltage 24 48 110 125
Voltage V35 V36 V14 V20 V24 Voltage Codes V50 V51 V53 V56 V60 V63 Codes KP12 S S S S S KPD12 S S S S S S KP12P14 S S S S KPD12P14 S S S S KP13 S S S S KPD13 S S S S S KP13P14 S S S KPD13P14 S S KU12 S S S S KUD12 S S KU12M1 KUD12M1 S KU12P14 S S KUD12P14 KU12M1P14 S S S KUD12M1P14 S KU13 S S S S KUD13 S S S S KU13M1 KUD13M1 S KU13P14 S S KUD13P14 KU13M1P14 S S S KUD13M1P14 S S S KF12 S S S KFD12 S S KF13 S S KFD13 S KL12 S S S KLD12 S S S Stocked Factory Order items require a minimum order quantity of 25 and have a lead time of 12 weeks. Voltage code must be specified to order this product. Refer to standard voltage codes listed in the Stocked Relays table above and insert as shown in How To Order.
Pilot Light Option Available on Types KP and KU. Internal pilot lights are available in both ac and dc versions for positive indication of power to the coil. The pilot light will be a red bidirectional LED. Manual Operator Option Available on Type KU only. To speed circuit testing a manual operator can be provided. With this feature the relay can be manually switched to simulate normal operation. Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8 Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8 Sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14
How to Order:
To Order Specify:
Class Number Type Number Voltage Code (See Stocked Relay Table above)
Catalog Number
Class 8501 Type KP12 Voltage Code V20
7 08/2008
Wiring Diagrams
1 3 6 9 2 A B 1 8
A
4 3
5 6
1 4 7
3 6 9 8 RESET B LATCH
DC HP
1/ 3 1/ 2 1/ 3 1/ 2 1/ 3 1/ 2
DC Volts
28
Resistive Amperes
10
KP12, KPD12
6 5 7 8
COMMON
KL12
1 4 3 6 9
28
10
4 3 2 1 11
28
10
9
7
10
A B LATCH RESET +
8501 KP, KU, and KF relays have a B300 rating. 3 pole devices have a 20 A max. total (sum of currents in all 3 poles), continuous rating. q 3 pole devices have a 30 A max. total (sum of currents in all 3 poles), continuous rating.
KP13, KPD13
KLD12
Operating Data
Type
KP
Approximate Dimensions
Comments
AC coil: approximately 12 ms DC coil: approximately 18 ms AC coil: approximately 8 ms DC coil: approximately 11 ms approximately 25 ms AC coil: approximately 12 ms DC coil: approximately 7 ms AC coil: approximately 8 ms DC coil: approximately 7 ms approximately 25 ms AC: 2 pole: -40C to +55C (-40F to +131F) 3 pole: -40C to +45C (-40F to +113F) DC: -40C to +70C (-40F to +158F) AC/DC: -45C to +70C (-49F to +158F) Type KU Type KP 2PDT or 3PDT (2 or 3 Form C) See contact ratings table above. KF, KU, and KLSilver cadmium oxide KPSilver nickel
1.42 MAX 36.1 .76 19.3 1.52 38.6
MAX
KF, KU KL KP
1.15 29.3
KF, KU KL
1.39 35.2
KF, KP, KU KL
1.39 35.2
Contacts
Configuration Ratings Material
1.90 48.4
MAX
1.79 45.5
MAX
2.61 66.3
MAX
Coils
Duty Available Voltages Operate
Continuous rated coils See Stocked Relays page 7. AC: +10, -15% of Nominal Voltage at 25C (77F) DC: +10, -25% of Nominal Voltage at 25C (77F) Types KP, KU, KF AC: 3.6 VA inrush, 2.5 VA sealed DC: 1.5 watts standard, 3 watts maximum AC: 2.0 VA latch, 0.8 VA unlatch DC: 1.2 watts
1.42 36.1
MAX
Typical Burden
Type KL
1.40 35.5
MAX
1.52 38.6
MAX
General Terminals: Solder/plug-in UL/CSA: For 8501 KP, KU, and KF:
File CCN E197072 NRNT2
Type KL
Type KF
Dual Dimensions:
Inches Millimeters
File Class
212845 3211 07
File Class
211269 3211 04
Options
LED, Toggle LED, Toggle, Duplex Pumping LED, Toggle LED, Toggle
Type
8501KA81 8501KA82 8501KA112 8501KA112A
Contact Ratings
AC Type DC HP
1/3 1/2
8501 KA alternating relays are designed to minimize pump and motor wear by equalizing run time between parallel components in a multi-pump system. These relays are controlled by an external control switch. This switch may be any type of contact closure; for example, the contacts of a timing relay or the closure of a float switch. The 8501 KA relays also have a toggle switch that allows the operator to lock one side of the duplex system, preventing alternation.
12 A Resistive Rating SPDT or DPDT Toggle switch for load control LED Load Indicators Horsepower Rated AC and DC Control UL Listed w/ SquareD Socket Rohs Compliant
Pilot Duty
B300
DC Volts
30
Resistive Amperes
12
Relay Availability
AC & DC Voltage Type 12
Voltage Code 8501KA 8501KA 8501KA 8501KA V36
AC Voltage 120
V20 S S S S
24
V14 S S S S
240
V24
AC Voltage = 50/60 Hz S Stocked. Stocked items do not require a minimum quantitiy and have a lead time of 2 weeks. All other part numbers require a minimum order quantity of 100 and have a lead time of 18 weeks.
Alternating Functions
Diagram Toggle Switch Position
Alternate A, C & D Lock 1 Lock 2 Alternate Lock 1 B Lock 2
Detail
S1 = Control Switch 1
S2 = Control Switch 2
LA = Load 1
LB = Load 2
Closing S1 alternates the loads between LA and LB. LA is ON and LB is OFF. S1 is not used in this mode. LA is OFF and LB is ON. S1 is not used in this mode. Closing S1 alternates the loads between LA and LB. S2 will only control LA. S1 will control LA and S2 will control LB. S1 will control LB and S2 will control LA.
The cross wired option allows extra system load capacity through simultaneous operation of both motors when needed (LA and LB energize simultaneously when both S1 and S2 are closed - relay contacts are not isolated). All Input voltage must be applied at all times for proper alternation. Use of a solid state control switch for S1 or S2 may not initiate alternation correctly. S1 or S2 voltage must be from the same supply as the units input voltage (see wiring diagrams). Loss of input voltage resets the unit; LA becomes the lead load for the next operation.
9 08/2008
S1
Approximate Dimensions
FILE CLASS
E78351 NLDX2
FILE CLASS
242675 3211 07
8501 NR51
8501 NR61
CSA
Std. Qty.
8501 NR52
8501 NR62
8501 NR82
KP12 KPD12
10 A 600 V 10 A 15 A 300 V 300 V 5A 600 V 10 A 16 A 300 V 300 V 5 A 10 600 V 300A V 15 A q 300 V 5 A 10 600 V 300A V 16 A q 300 V 15 A 300 V j 15 A 300 V j 10 A 300 V 10 A 300 V q 10 A 300 V q
NR51 NR51B
1 10
NR52 NR52B
1 10
8501 NR45
8501 NR41
8501 NR42
KP13 KPD13
NR61 NR61B
1 10
NR62 NR62B NR82 NR82B NR41 NR41B NR42 NR42B NR43 NR43B NR34 NR34B
1 10 1 10 1 10 1 10 1 10 1 10 8501NR52
KL KU RS41 RSD41 RS42 RSD42 RS43 RSD43 RS44 RSD44 RS4 RSD4 RS14 RSD14 RS24 RSD24 RS34 RSD34
8501 NH7
8501 NR43
8501 NR34
Socket Accessories
Socket
8501NR51
Description
Hold Down Clip Restraining Strap Restraining Strap Hold Down Clip Restraining Strap Restraining Strap Hold Down Clip Restraining Strap Hold Down Clip Restraining Strap Hold Down Clip Restraining Strap Hold Down Clip Hold Down Clip Hold Down Clip Hold Down Clip
Catalog Number
Not Available 8501NH7 8501NH7 8501NH52 8501NH7 8501NH7 Not Available 8501NH7 8501NH52 8501NH7 8501NH82 8501NH7 Supplied with socket as standard 8501NH42 8501NH42 8501NH42
Std. Pack
1 1 10 1 1 1 10 1 10 1 10 10 10
10 A 300 V
NR45 NR45B
1 10 8501NR61
Must be ordered in multiples of the quantity listed. Units provided in standard quantity of one are individually packaged; devices with B suffix have a standard quantity of 10 per bulk pack. Rated for use with Class 8430 Type MPS at 480 Volts. q 20 A maximum total load (CSA)
8501NR62
NOTE: For DIN 3 mounting track and end clamps refer to the NEMA type terminal block section 9080CT9601 or the IEC type terminal block section 9080CT9901R5/02.
UL/CSA:
8501NR82
8501NR41 8501NR42
8501RS41, RSD41 8501RS42, RSD42 8501RS43, RSD43 8501RS44, RSD44 8501RS4, RSD4 8501RS14, RSD14 8501RS24, RSD24 8501RS34, RSD34
File CCN
E66924 SW1V2
File Class
LR84913 3211 07
8501NR43 8501NR34
Catalog Number
Class Type NR51B 8501
8501NR45
8501NH45
10
11 08/2008
Type NR52
Terminal Location
6 5 4 3
0.14 4
Terminal Location
2.86 73 2.04 52 0.88 22 3.06 78
1 4
1.57 40
1.30 33 1.60 41
0.77 20 0.97 25
Top View
1.09 28 1.42 36
0.71 18 1.11 28
Top View
Type NR61
Terminal screws 6-32 x 5/16" 0.17 dia. 4 1.30 33 0.96 24 2.04 52 2.16 55
1.07 (27)
TERMINAL LOCATION
8 7 6 5 4
Type NR62
1.03 26 0.62 16
8 11
0.38 10 0.76 19
TERMINAL LOCATION 7 6 5 4 1 3
1.79 46
2.06 52
0.77 20 0.97 25
9 10 11 1 2 3
1.88 48
2.33 59
TOP VIEW
1.44 37
0.71 18
10 TOP VIEW
Type NR82
6 5 4
Type NR45
TERMINAL LOCATION
6 5 2 4 1
MADE
IN
CHINA
1.210 30.73
5 6 7 8
1.52 38.70
B 9 8
A 7
1 4 1 3
TOP VIEW
1 2
TERMINAL LOCATION 7 3 6 5 2 1
0.070 1.18
2.750 69.85
14
13
1.265 32.13
2.530 64.29
12 11 10 9 TOP VIEW
1 1
1 0
Type NR42
Terminal Screws 6-32 x 5/16"
4 3
TERMINAL LOCATION 5
2.67 REF 67.81
TERMINAL LOCATION
0.170 4.32 DIA. TYP. 1.250 31.75 0.080 2.03 2.720 69.09
4 2 3 1
11
14
12
A2
13
1.560 39.62
0.165 4.19
1.820 46.22
2.598 65.99
14
13
8 6
7 5
1.299 32.99
9 TOP VIEW
1.390 35.30 2.875 73.02
TOP VIEW
1.178 29.92 0.653 16.59 0.995 25.27
2.637 66.97
Type NR43
Terminal Screws 6-32 x 5.16"
6 5 4
6
Type NR34
Terminal Screws 6-32 x 5.16"
TERMINAL LOCATION
5 2 4
TERMINAL LOCATION 8 4 7 3 6 5 2 1
1
3 1
2.74 69.6
2.74 69.6
1.85 47.0
0.16 4.11
2.58 65.5
1 1
1.45 36.8
1 0
1.45 36.8
11 9 8 10 7
1 4 1 2 1 1 1 0
1 3
14
13
TOP VIEW
12 11 10 9
1.44 36.6
1.09 27.7
0.653 16.59
TOP VIEW
1.09 27.7
0.653 16.59
13 08/2008
8501CDO6V51
Contact Arrangement
N.C.
0 0 1 1 2
AC DC Operated Operated Maximum Resistive Ampere Rating 75% Power Factor Coil Coil Contact Open Type Open Type Voltage Type Type 300V 600V
CO6 CO7 CO8 CO15 CO16 CDO6 CDO7 CDO8 CDO15 CDO16 600 600 600 600 600 30 30 30 30 30 10 5 10 5 5
230V
2 11/2 2 11/2 11/2
600V
1 2
0 2
CO21 CO22
CDO21 CDO22
Voltage code must be specified to order this product. Refer to standard voltage codes listed in the Stocked Relays table below and insert as shown in How to Order.
Enclosure: Separately packed NEMA Type 1 sheet steel enclosure for Types CO & CDO relays order Class 9991 Type UE1 Operating Data
Operating Voltages/ Voltage Range Coil Inrush (VAC Coil) Coils Operating Temp. Range
AC 6 through 480 volts, + 10/-15% of nominal at 25C DC 6 through 110 volts, + 10/-20% of nominal at 25C 15VA Duty: Continuous rated coils. (Non-replaceable) AC: -22F to +122F (-30C to +50C) DC: -22F to +140F (-30C to +60C)
Dimensions
Catalog Number 8501 A B C D E F IN mm IN mm IN mm IN mm IN mm IN mm
8.0 8.0 8.0 8.0 0.81 20.6 2.25 57.2 0.38 0.81 20.6 2.18 55.4 0.38 1.5 1.5 38.1 2.31 58.7 0.38 38.1 2.53 64.3 0.38 9.5 9.5 9.5 9.5
CO6, CO7, CO8, CDO6, CDO7, 2.43 61.7 2.50 63.5 0.31 CDO8 CO15, CO21, CDO15, CDO21 CO16,CDO16 CO22, CDO22 2.43 61.7 2.50 63.5 0.31 3.12 79.2 2.50 63.5 0.31 3.12 79.2 2.50 63.5 0.31
Stocked Relays
Class 8501 Type AC Voltage 50/60 Hz 6 12 24 120 208 240 277 480 Class 8501 Type Voltage Code CDO6 CDO7 CDO8 CDO15 CDO16 CDO21 CDO22 S DC Voltage 6 12 24 110
UL/CSA:
File CCN E78351 NLDX
File Class 04
209683 3211
Voltage V35 V36 V14 V20 V08 V24 V04 V29 Code CO6 CO7 CO8 CO15 CO16 CO21 CO22 S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S
Approximate Dimensions
S Stocked Factory Order items require a minimum order quantity of 25 and have a lead time of 12 weeks.
How to Order:
To Order Specify:
Class Number Type Number Voltage Code (See Stocked Relay Table above)
Catalog Number
Class 8501 Type CO6 Voltage Code V20
14 08/2008
15 08/2008
8501CT0301R7/08 2003-2008 Schneider Electric All Rights Reserved Replaces 8501CT0301, December 2003 08/2008