General Purpose Relays

Types K, R, N, and C
Catalog 8501CT0301R7/08

2008

Class 8501

CONTENTS Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Type R Miniature Plug-in Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 Type K Plug-in Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78 Type KA Alternating Relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .910 Type N Sockets and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 1113 Type C Power Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

2 08/2008 2003-2008 Schneider Electric All Rights Reserved

Type R Miniature Plug-in Relay


General and Order Information
Input Voltage
SPDT AC 50/60 Hz

Options
None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator

Type
RS41* RS41M1* RS41P14* RS41M1P14* RSD41* RSD41M1* RSD41P14* RSD41M1P14*

These miniature plug-in relays have a 10 Ampere resistive rating (except for RS/RSD41), the same as the Type K plug-in relays, but are much smaller. The compact size of these relays makes them ideal for downsizing equipment. SPDT through 4PDT AC or DC Operated Horsepower rated UL Contact Ratings
Type
8501RS41 h 8501RSD41 h 8501RS42 8501RSD42 8501RS43 8501RSD43 8501RS44 8501RSD44
h

DC Pilot Light Silver Cadmium Oxide Contacts Manual Operator and Pilot Light

Input Voltage
DPDT AC 50/60 Hz

Options
None Manual Operator Pilot Light Manual Operator and Pilot Light None

Type
RS42* RS42M1* RS42P14* RS42M1P14* RSD42* RSD42M1* RSD42P14* RSD42M1P14*

Complete line of Sockets Manual Operator / Bidirectional Green LED Pilot Light Options

Voltage
120 VAC 240 VAC 28 VDC 120 VAC 240 VAC 30 VDC 120 VAC 250 VAC 28 VDC 120 VAC 250 VAC 28 VDC

Resistive Rating
15 12 15 10 10 10 10 10 10 10 10 10

General Use Rating


10 10 15 10 10 10 10 10 10 10 10 10

Horsepower Rating
1/3 1/2 1/3 1/2 Silver Cadmium Oxide Contacts 3PDT Silver Cadmium Oxide Contacts

Manual Operator DC Pilot Light Manual Operator and Pilot Light

Input Voltage
AC 50/60 Hz

Options
None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator

Type
RS43* RS43M1* RS43P14* RS43M1P14* RSD43* RSD43M1* RSD43P14* RSD43M1P14*

DC

Pilot Light Manual Operator and Pilot Light

RS41 and RSD41 relays have a B300 rating.

Stocked Relays
AC Voltage 50/60 Hz Type 6
Voltage Code RS41 RS41M1 RS41P14 RS41M1P14 RS42 RS42M1 RS42P14 RS42M1P14 RS43 RS43M1 RS43P14 RS43M1P14 RS44 RS44M1 RS44P14 RS44M1P14 S S S S S S S S S S S S S S S V35

DC Voltage Type 6
Voltage Code RSD41 RSD41M1 RSD41P14 RSD41M1P14 S RSD42 RSD42M1 RSD42P14 RSD42M1P14 RSD43 RSD43M1 RSD43P14 RSD43M1P14 RSD44 RSD44M1 RSD44P14 RSD44M1P14 S S S S S S S S S

Input Voltage 110


V60 4PDT AC 50/60 Hz

Options
None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator

Type
RS44* RS44M1* RS44P14* RS44M1P14* RSD44* RSD44M1* RSD44P14* RSD44M1P14*

12
V36

24
V14 S S S S S

120 240
V20 S S S S S V24

12
V51 S

24
V53 S S S S

V50

S Silver Cadmium Oxide Contacts

DC

Pilot Light Manual Operator and Pilot Light

Voltage code must be specified to order this product. Refer to standard voltage codes listed in the Stocked Relay table to the left and insert as shown in How To Order.

How to Order:
To Order Specify:
Class Number Type Number Voltage Code (See Stocked Relay Table to left)

Catalog Number
Class 8501 Type RS42 Voltage Code V20

Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6

S Stocked Factory Order items require a minimum order quantity of 25 and have a lead time of 12 weeks.

2003-2008 Schneider Electric All Rights Reserved

3 08/2008

Type R Miniature Plug-in Relay


General and Order Information
8501 R relays are suited for use as logic elements and power switching output devices. The short stroke motion of the armature provides long mechanical life required for high speed operation of control systems. Different contact compositions allow these relays to be used in a variety of applications. Fine silver (gold flashed) and bifurcated crossbar (gold overlay silver) are suitable for high contact reliability and low level switching requirements. Silver cadmium oxide is best suited for inductive loads. Hermetically sealed relays can be used in adverse environments. 1, 3, or 5 Ampere Versions 4PDT Complete Socket Line
5A Input Voltage

8501 RS4V14 Pilot Light Option An Internal green pilot light is available in both AC and DC versions for positive indication of power to the coil. The pilot lights are bidirectional LEDs. 8501 RSD14P14V53 Manual Operation Option To speed circuit testing, a manual operator can be provided. The relay can be manually switched to simulate normal operation. NOTE: All Type R relays with a manual operator must be used on circuits of same polarity. 8501 RS14M1V14

Horsepower Rated AC or DC Operation Manual Operator/ Pilot Light Options


Options
None

Type
RS14 RS14M1 RS14P14 RS14M1P14 RSD14 RSD14M1 RSD14P14 RSD14M1P14

For switching inductive loads Contacts: Silver Cadmium Oxide

AC 50/60 Hz

Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator

DC

Pilot Light Manual Operator and Pilot Light

3A

Input Voltage

Options
None

Type
RS4 RS4M1 RS4P14 RS4M1P14 RSD4 RSD4M1 RSD4P14 RSD4M1P14

Contact Ratings
Type
RS4 h RSD4
h

For low level switching Contacts: Fine Silver (Gold Flashed)

AC 50/60 Hz

Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator

Voltage
120/240 VAC 30 VDC 120/240 VAC 30 VDC 120/240 VAC 30 VDC 120/240 VAC 30 VDC

Continuous Current Rating


3 3 5 5 1 1 5 5

Horsepower Rating
1/ 10

1/ 6

RS14 h RSD14 h RS24 RSD24

DC

Pilot Light Manual Operator and Pilot Light

1/ 16 a

1A
Best for low level switching Bifurcated Silver Gold Plated Contacts

Input Voltage
AC 50/60 Hz DC

Type
RS24
h

RS34 RSD34

RSD24

RS4/RSD4, RS14/RSD14 have C300 pilot duty rating. a Horsepower rating at 120 VAC.

Hermetically Sealed
5 Ampere Resistive q Silver Cadmium Oxide Contacts Suitable for Class I Division 2 Locations

Input Voltage
AC 50/60 Hz DC

Type
RS34 RSD34

How to Order:
To Order Specify:
Class Number Type Number Voltage Code (See Stocked Relay Table on page 5)

Catalog Number
Class 8501 Type RS4 Voltage Code V20

Voltage code must be specified to order this product. Refer to standard voltage codes listed in the Stocked Relays table on page 5 and insert as shown in How To Order. Do not ground frame.

Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6 Sockets and Holddown Clips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14

4 08/2008 2003-2008 Schneider Electric All Rights Reserved

Type R Miniature Plug-in Relay


Ordering Information and Application Data
Stocked Relays
AC Voltage 50/60 Hz Type 6
Voltage Code RS4 RS4M1 RS4P14 RS4M1P14 RS14 RS14M1 RS14P14 RS14M1P14 RS24 RS34 S S V35

DC Voltage Type 240


V24 Voltage Code RSD4 RSD4M1 RSD4P14 RSD4M1P14 RSD14 RSD14M1 RSD14P14 S RSD14M1P14 RSD24 RSD34 S S S S S S S S S S S S S S

12
V36

24
V14 S

48
V17

120
V20 S S S S S S S S S S

6
V50

12
V51 S

24
V53 S

48
V56

110
V60

S Stocked Factory Order items require a minimum order quantity of 25 and have a lead time of 12 weeks. Class 8501 Type Pick-Up Time Operating Data Drop-Out Time Operating Temperature Range Duty Cycle Voltage Range Coil AC Coils 1.2 VA sealed 1.2 VA sealed 1.2 VA sealed 1.2 VA sealed RS4 RSD4 RS14 RSD14 RS24 RSD24 RS34 RSD34 RS41 RSD41 RS42 RSD42 RS43 RSD43 RS44 RSD44

25 ms Maximum 25 ms Maximum -40 C to +70 C (-40 F to +158 F)

13 ms Max. 6 ms Max. -45 C to +70 C (-49 F to +158 F) Continuous AC coils +10%, -15% of nominal DC coils +10%, -20% of nominal 1.5 VA inrush, 1.1 VA sealed 2.2 VA inrush, 1.3 VA sealed

20 ms Maximum 20 ms Maximum -40 C to +70 C (-40 F to +158 F)

2.9 VA inrush, 2.0 VA sealed

3.7 VA inrush, 2.6 VA sealed

DC Coils File CCN

0.9 watt

0.9 watt E197072 NRNT2

0.9 watt

0.9 watt

0.7 watt E78351 NLDX2

0.9 watt

1.0 watt E78427 NRNT2

1.0 watt

N/A

File CCN

E197072 NRNT8 (Approved but not marked) 211268 3211 07

E196809 NQMJ2, NQMJ8

N/A

File Class

N/A

211268 3211 07

Yes

File CCN

E78351 NLDX

E123950 NPKR, NPKR7

E78351 NLDX

N/A

When

used with the appropriate 8501 NR socket.

2003-2008 Schneider Electric All Rights Reserved

5 08/2008

Type R Miniature Plug-in Relay


Dimensions and Wiring Diagram
Wiring Diagrams

1 5 9 13 14

1 3 5 7
RS42, RSD42

2 4 6 8

1 4 7 10

2 5 8

3 6 9 11

1 5 9 13

2 6 10
RS44, RSD44

3 7 11

4 8 12 14

1 5 9 13

2 6 10

3 7 11

4 8 12 14

RS41, RSD41

RS43, RSD43

RS4, RSD4, RS14, RSD14, RS24, RS24, RSD24, RS34, RSD34


.91 23.1 .75 19 .31 B65112-124 1 5 8 2 6 10 3 7 11 4 8 12 14 1.16 29.5

.21 5

For devices with manual operator .25 .04 6 1

.86 21.8 .75 19 .31 B65112-124 1 5 8 2 6 10 3 7 11 4 8 12 14 1.10 27.9

.04 1

.25 6

#3-48 NC2A THREAD

9 13

#3-48 NC2A THREAD

9 13

.26 7 1.40 35.6 .31 8 .26 7 .42 11 1.28 33 .31 8

.26 7 .26 7 .42 11

.52 13

.52 13

RS4, RSD4, RS14, RSD14, RS24, RSD24

RS34, RSD34

1.10 27.9

0.070 1.77 (When Provided) 0.070 1.77 (When Provided)

0.55 14.0

1.100 27.94

0.080 2.032 (When Provided) 1.420 36.068

0.830 21.08 0.630 16.002

0.850 21.6 (When Provided)

1.42 36.1

0.870 22.10

(When Provided)

0.130 3.3
1

0.130 (When Provided) 3.302


RS42, RSD42

13 14

1 3

2 4

6 8

RS41, RSD41

1.10 27.9

0.080 2.032 (When Provided)

1.10 27.9
1.24 31.49

0.080 2.032 (When Provided)


1.42 36.07

1.63 41.40
(When Provided)

(When Provided)

0.630 16.002

0.630 16.002

1.42 36.07

0.870 22.10

0.130 (When Provided) 3.302

0.870 22.10
9 13 1 5

0.130 (When Provided) 3.302

Dual Dimensions:

7 10 8 9 11

10

1 4 2 5 3 6

2 6 3 7 4 8

11 12 14

RS43, RSD43

RS44, RSD44

Inches Millimeters

6 08/2008 2003-2008 Schneider Electric All Rights Reserved

Type K - Plug-in Relay


Dimensions and Wiring Diagram
8501 K relays are designed for multipole switching applications at 240 volts or lower. These relays have industry standard wiring and pin arrangements which allows for their use as replacements for many similar relays without wiring or hardware modifications. 10 or 15 Ampere Versions DPDT or 3PDT Manual Operator/ Red Pilot Light Options Horsepower Rated DPDT Latching Relay AC or DC Operation Type KP Tubular Terminals
Input Voltage
AC 50/60 Hz

Contact Arrangement
DPDT DPDT 3PDT 3PDT DPDT DPDT 3PDT 3PDT

Options
None Pilot Light None Pilot Light None Pilot Light None Pilot Light

Type
KP12 KP12P14 KP13 KP13P14 KPD12 KPD12P14 KPD13 KPD13P14

DC

Type KF c Flange Mounted Spade Terminals


Input Voltage
AC 50/60 Hz

Type KU Spade Terminals


Type
KF12

Contact Arrangement
DPDT

Options

Input Contact Voltage Arrangement


DPDT DPDT DPDT AC 50/60 Hz DPDT 3PDT 3PDT 3PDT

Options
None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator Pilot Light Manual Operator and Pilot Light None Manual Operator Pilot Light Manual Operator and Pilot Light

Type
KU12 KU12M1 KU12P14 KU12M1P14 KU13 KU13M1 KU13P14 KU13M1P14 KUD12 KUD12M1 KUD12P14 KUD12M1P14 KUD13 KUD13M1 KUD13P14 KUD13M1P14

None Available 3PDT DPDT KF13 KFD12 None Available 3PDT KFD13

DC

Socket is not required with Type KF relays.

Type KL Latching Relay Spade Terminals


Input Voltage
AC 50/60 Hz

3PDT DPDT

Contact Arrangement
DPDT

Options

Type

DPDT DPDT

None Available

KL12 DC

DPDT 3PDT 3PDT 3PDT 3PDT

DC

DPDT

None Available

KLD12

Stocked Relays
Type AC Voltage 50/60 Hz 6 12 24 120 240 Type 6 12 DC Voltage 24 48 110 125

Voltage V35 V36 V14 V20 V24 Voltage Codes V50 V51 V53 V56 V60 V63 Codes KP12 S S S S S KPD12 S S S S S S KP12P14 S S S S KPD12P14 S S S S KP13 S S S S KPD13 S S S S S KP13P14 S S S KPD13P14 S S KU12 S S S S KUD12 S S KU12M1 KUD12M1 S KU12P14 S S KUD12P14 KU12M1P14 S S S KUD12M1P14 S KU13 S S S S KUD13 S S S S KU13M1 KUD13M1 S KU13P14 S S KUD13P14 KU13M1P14 S S S KUD13M1P14 S S S KF12 S S S KFD12 S S KF13 S S KFD13 S KL12 S S S KLD12 S S S Stocked Factory Order items require a minimum order quantity of 25 and have a lead time of 12 weeks. Voltage code must be specified to order this product. Refer to standard voltage codes listed in the Stocked Relays table above and insert as shown in How To Order.

Pilot Light Option Available on Types KP and KU. Internal pilot lights are available in both ac and dc versions for positive indication of power to the coil. The pilot light will be a red bidirectional LED. Manual Operator Option Available on Type KU only. To speed circuit testing a manual operator can be provided. With this feature the relay can be manually switched to simulate normal operation. Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8 Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8 Sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14

How to Order:
To Order Specify:
Class Number Type Number Voltage Code (See Stocked Relay Table above)

Catalog Number
Class 8501 Type KP12 Voltage Code V20

2003-2008 Schneider Electric All Rights Reserved

7 08/2008

Type K Plug-in Relay


Application Data, Dimensions, Wiring Diagrams
Contact Ratings
AC Type AC Volts
120 KPl 240 KUl KFl KL 240
l c

Wiring Diagrams
1 3 6 9 2 A B 1 8
A

4 3

5 6

1 4 7

3 6 9 8 RESET B LATCH

DC HP
1/ 3 1/ 2 1/ 3 1/ 2 1/ 3 1/ 2

Resistive 75% PF Continuous Amperes


10 10 c 15q 10c 10 10

DC Volts
28

Resistive Amperes
10

KU12, KUD12 KF12, KFD12


1 4 7 2 5 8 A B 3 6 9

KP12, KPD12
6 5 7 8

COMMON

120 240 120

KL12
1 4 3 6 9

28

10

4 3 2 1 11

28

10

9
7

10
A B LATCH RESET +

8501 KP, KU, and KF relays have a B300 rating. 3 pole devices have a 20 A max. total (sum of currents in all 3 poles), continuous rating. q 3 pole devices have a 30 A max. total (sum of currents in all 3 poles), continuous rating.

KU13, KUD13 KF13, KFD13

KP13, KPD13

KLD12

Operating Data
Type
KP

Approximate Dimensions
Comments
AC coil: approximately 12 ms DC coil: approximately 18 ms AC coil: approximately 8 ms DC coil: approximately 11 ms approximately 25 ms AC coil: approximately 12 ms DC coil: approximately 7 ms AC coil: approximately 8 ms DC coil: approximately 7 ms approximately 25 ms AC: 2 pole: -40C to +55C (-40F to +131F) 3 pole: -40C to +45C (-40F to +113F) DC: -40C to +70C (-40F to +158F) AC/DC: -45C to +70C (-49F to +158F) Type KU Type KP 2PDT or 3PDT (2 or 3 Form C) See contact ratings table above. KF, KU, and KLSilver cadmium oxide KPSilver nickel
1.42 MAX 36.1 .76 19.3 1.52 38.6
MAX

.16 dia. 4.0 1.79 45.5 MAX 2.07 52.6

Typical Pick-Up Time

KF, KU KL KP

1.15 29.3

2.13 54.2 2.66 67.5

Typical Drop-Out Time

KF, KU KL

1.39 35.2

Operating Temperature Range

KF, KP, KU KL

1.39 35.2

Contacts
Configuration Ratings Material

1.90 48.4
MAX

2.18 55.5 0.08 2


R(TYP)

1.79 45.5
MAX

2.61 66.3
MAX

2.38 60.5 0.31 8

Coils
Duty Available Voltages Operate
Continuous rated coils See Stocked Relays page 7. AC: +10, -15% of Nominal Voltage at 25C (77F) DC: +10, -25% of Nominal Voltage at 25C (77F) Types KP, KU, KF AC: 3.6 VA inrush, 2.5 VA sealed DC: 1.5 watts standard, 3 watts maximum AC: 2.0 VA latch, 0.8 VA unlatch DC: 1.2 watts

0.63 16 1.53 38.8


MAX

1.42 36.1
MAX

Typical Burden
Type KL

1.40 35.5

MAX

1.52 38.6
MAX

General Terminals: Solder/plug-in UL/CSA: For 8501 KP, KU, and KF:
File CCN E197072 NRNT2

Type KL

Type KF

Dual Dimensions:

Inches Millimeters

File Class

212845 3211 07

For 8501 KL: For 8501 KP, KU, and KL:


File CCN File CCN E78351 NLDX When used with the appropriate 8501NR socket. E78351 NLDX2

File Class

211269 3211 04

8 08/2008 2003-2008 Schneider Electric All Rights Reserved

Type KA Alternating Relays


General Information and Specifications
Type KA Alternating Relay
Input Contact Voltage Arrangement
AC & DC AC & DC AC & DC AC & DC SPDT DPDT DPDT (N.C.) DPDT (N.O.)

Options
LED, Toggle LED, Toggle, Duplex Pumping LED, Toggle LED, Toggle

Type
8501KA81 8501KA82 8501KA112 8501KA112A

Contact Ratings
AC Type DC HP
1/3 1/2

8501 KA alternating relays are designed to minimize pump and motor wear by equalizing run time between parallel components in a multi-pump system. These relays are controlled by an external control switch. This switch may be any type of contact closure; for example, the contacts of a timing relay or the closure of a float switch. The 8501 KA relays also have a toggle switch that allows the operator to lock one side of the duplex system, preventing alternation.
12 A Resistive Rating SPDT or DPDT Toggle switch for load control LED Load Indicators Horsepower Rated AC and DC Control UL Listed w/ SquareD Socket Rohs Compliant

Resistive AC Volts Amperes


120 12 12

Pilot Duty
B300

DC Volts
30

Resistive Amperes
12

8501KA 240 B300

Relay Availability
AC & DC Voltage Type 12
Voltage Code 8501KA 8501KA 8501KA 8501KA V36

AC Voltage 120
V20 S S S S

24
V14 S S S S

240
V24

AC Voltage = 50/60 Hz S Stocked. Stocked items do not require a minimum quantitiy and have a lead time of 2 weeks. All other part numbers require a minimum order quantity of 100 and have a lead time of 18 weeks.

Alternating Functions
Diagram Toggle Switch Position
Alternate A, C & D Lock 1 Lock 2 Alternate Lock 1 B Lock 2

Detail

S1 = Control Switch 1

S2 = Control Switch 2

LA = Load 1

LB = Load 2

Closing S1 alternates the loads between LA and LB. LA is ON and LB is OFF. S1 is not used in this mode. LA is OFF and LB is ON. S1 is not used in this mode. Closing S1 alternates the loads between LA and LB. S2 will only control LA. S1 will control LA and S2 will control LB. S1 will control LB and S2 will control LA.

The cross wired option allows extra system load capacity through simultaneous operation of both motors when needed (LA and LB energize simultaneously when both S1 and S2 are closed - relay contacts are not isolated). All Input voltage must be applied at all times for proper alternation. Use of a solid state control switch for S1 or S2 may not initiate alternation correctly. S1 or S2 voltage must be from the same supply as the units input voltage (see wiring diagrams). Loss of input voltage resets the unit; LA becomes the lead load for the next operation.

2003-2008 Schneider Electric All Rights Reserved

9 08/2008

Type KA Alternating Relays


Wiring Diagrams and Approximate Dimensions
Wiring Diagrams A B

S1

8501KA81 Socket = 8501NR51 or NR52

8501KA82 Socket = 8501NR51 or NR52

8501KA112 Socket = 8501NR61 or NR62

8501KA112A Socket = 8501NR61 or NR62

Approximate Dimensions

FILE CLASS

E78351 NLDX2

FILE CLASS

242675 3211 07

10 08/2008 2003-2008 Schneider Electric All Rights Reserved

Type N Sockets and Accessories


General and Order Information
8501 NR sockets are designed for use with plug-in 8501 K and Type R relays, 8430 MPS phase failure relays and 9050 JCK timers. The 8501 NR45 screw terminal sockets have pressure wire clamps that accept 1 or 2 #16-22 wires. All other sockets have pressure clamps that will accept 1 or 2 #12-22 wires. The recommended tightening torque for all terminals is 7-8 lb-in. All Devices Stocked in Central Warehouse DIN Track Mount or Direct Panel Mount Tubular Sockets Available in Easy-to-Wire Single Tier or Space-Saving Multi-Tier Versions
Snapmount Sockets
For Use With Class 8501 Type Class 8430 Type Class 9050 Type
JCK11 19 JCK31 39 JCK51 59 JCK60 JCK1 F JCK3 F JCK5 F

8501 NR51

8501 NR61

Socket Rating Description UL


8 Pin Tubular Single Tier Screw Terminal 8 Pin Tubular Double Tier Screw Terminal 11 Pin Tubular Single Tier Screw Terminal 11 Pin Tubular Double Tier Screw Terminal 11 Pin Spade Double Tier Screw Terminal 5 Pin Spade Double Tier Screw Terminal 8 Pin Spade Double Tier Screw Terminal 11 Pin Spade Double Tier Screw Terminal 14 Pin Spade Double Tier Screw Terminal

CSA

Class 8501 Type

Std. Qty.

8501 NR52

8501 NR62

8501 NR82

KP12 KPD12

MPS (240 volts)

10 A 600 V 10 A 15 A 300 V 300 V 5A 600 V 10 A 16 A 300 V 300 V 5 A 10 600 V 300A V 15 A q 300 V 5 A 10 600 V 300A V 16 A q 300 V 15 A 300 V j 15 A 300 V j 10 A 300 V 10 A 300 V q 10 A 300 V q

NR51 NR51B

1 10

NR52 NR52B

1 10

8501 NR45

8501 NR41

8501 NR42

KP13 KPD13

JCK21 29 JCK41 49 JCK70 JCK2F JCK4F

NR61 NR61B

1 10

NR62 NR62B NR82 NR82B NR41 NR41B NR42 NR42B NR43 NR43B NR34 NR34B

1 10 1 10 1 10 1 10 1 10 1 10 8501NR52

KL KU RS41 RSD41 RS42 RSD42 RS43 RSD43 RS44 RSD44 RS4 RSD4 RS14 RSD14 RS24 RSD24 RS34 RSD34

MPS (480 Volts)

8501 NH7

8501 NR43

8501 NR34

Socket Accessories
Socket
8501NR51

For Use With


8501KP12, KPD12 8430MPSV24 9050JCK 8501KP12, KPD12 8430MPSV24 9050JCK

Description
Hold Down Clip Restraining Strap Restraining Strap Hold Down Clip Restraining Strap Restraining Strap Hold Down Clip Restraining Strap Hold Down Clip Restraining Strap Hold Down Clip Restraining Strap Hold Down Clip Hold Down Clip Hold Down Clip Hold Down Clip

Catalog Number
Not Available 8501NH7 8501NH7 8501NH52 8501NH7 8501NH7 Not Available 8501NH7 8501NH52 8501NH7 8501NH82 8501NH7 Supplied with socket as standard 8501NH42 8501NH42 8501NH42

Std. Pack
1 1 10 1 1 1 10 1 10 1 10 10 10

14 Pin Spade Double Tier Screw Terminal

10 A 300 V

NR45 NR45B

1 10 8501NR61

8501KP13, KPD13 9050JCK

Must be ordered in multiples of the quantity listed. Units provided in standard quantity of one are individually packaged; devices with B suffix have a standard quantity of 10 per bulk pack. Rated for use with Class 8430 Type MPS at 480 Volts. q 20 A maximum total load (CSA)

8501NR62

8501KP13, KPD13 9050JCK

NOTE: For DIN 3 mounting track and end clamps refer to the NEMA type terminal block section 9080CT9601 or the IEC type terminal block section 9080CT9901R5/02.
UL/CSA:

8501NR82

8501KU and KL 8430MPSV29

8501NR41 8501NR42

8501RS41, RSD41 8501RS42, RSD42 8501RS43, RSD43 8501RS44, RSD44 8501RS4, RSD4 8501RS14, RSD14 8501RS24, RSD24 8501RS34, RSD34

File CCN

E66924 SW1V2

File Class

LR84913 3211 07

8501NR43 8501NR34

How to Order: To Order Specify:


Catalog Number
Class Type NR51B 8501

8501NR45

Hold Down Clip

8501NH45

10

Class Number Type Number

Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12 Terminal Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12

2003-2008 Schneider Electric All Rights Reserved

11 08/2008

Type N Sockets and Accessories


General and Order Information
Type NR51
Terminal screws M3 .5 x .6
0.17 4 2.14 54 2.03 51 1.01 26

Type NR52
Terminal Location
6 5 4 3

Terminal screws M3.5 x 7

0.14 4

Terminal Location
2.86 73 2.04 52 0.88 22 3.06 78
1 4

1.57 40

1.30 33 1.60 41

0.77 20 0.97 25

Top View

1.09 28 1.42 36

0.71 18 1.11 28

Top View

Type NR61
Terminal screws 6-32 x 5/16" 0.17 dia. 4 1.30 33 0.96 24 2.04 52 2.16 55
1.07 (27)
TERMINAL LOCATION
8 7 6 5 4

Type NR62
1.03 26 0.62 16
8 11

0.38 10 0.76 19

TERMINAL LOCATION 7 6 5 4 1 3

1.79 46
2.06 52
0.77 20 0.97 25
9 10 11 1 2 3

3.02 77 3.22 82 1.32 34 1.50 38

1.88 48

2.33 59

TOP VIEW

1.44 37

0.71 18

10 TOP VIEW

Type NR82
6 5 4

Type NR45
TERMINAL LOCATION
6 5 2 4 1

MADE

IN

CHINA

0.150 3.81 1.250 31.75

1.210 30.73
5 6 7 8

1.016 25.79 0.718 18.20 0.656 16.66


8 4
1 2

1.55 39.31 1.703 43.25 Terminal Screws M3.5 x 0.6

1.52 38.70

0.680 17.26 0.865 21.97 0.955 24.25 1.030 26.16

B 9 8

A 7
1 4 1 3

TOP VIEW

1 2

Terminal Screws 4-40 x 1/4"

12 2003-2008 Schneider Electric All Rights Reserved


12/03

3.16 80.26 3.00 76.20 1.660 42.16

TERMINAL LOCATION 7 3 6 5 2 1

0.070 1.18

1.250 31.75 0.080 2.032 Typ.

2.750 69.85

14

13

1.265 32.13

2.530 64.29

12 11 10 9 TOP VIEW

1 1

1 0

Type N Sockets and Accessories


General and Order Information
Type NR41
Terminal Screws M3 X 0.5
A1 9 14

Type NR42
Terminal Screws 6-32 x 5/16"
4 3

Terminal Screws M3.5 X 0.6


1 5

TERMINAL LOCATION 5
2.67 REF 67.81

TERMINAL LOCATION
0.170 4.32 DIA. TYP. 1.250 31.75 0.080 2.03 2.720 69.09
4 2 3 1

0.790 20.06 0.680 17.27

2003-2008 Schneider Electric All Rights Reserved

0.675 17.45 1.140 28.95 0.670 17.01 0.16 4.1

11

14

12

A2

13

1.560 39.62

0.165 4.19
1.820 46.22

2.598 65.99

14

13

8 6

7 5

1.299 32.99

9 TOP VIEW
1.390 35.30 2.875 73.02

TOP VIEW
1.178 29.92 0.653 16.59 0.995 25.27

2.637 66.97

Type NR43
Terminal Screws 6-32 x 5.16"
6 5 4
6

Type NR34
Terminal Screws 6-32 x 5.16"
TERMINAL LOCATION
5 2 4

TERMINAL LOCATION 8 4 7 3 6 5 2 1

1
3 1

1.85 47.0 2.58 65.5

2.74 69.6

2.74 69.6

1.85 47.0

0.16 4.11

2.58 65.5

1 1

1.45 36.8

1 0

1.45 36.8
11 9 8 10 7

1 4 1 2 1 1 1 0

1 3

14

13

TOP VIEW

12 11 10 9

1.44 36.6

1.27 32.3 1.59 40.4

1.09 27.7

0.653 16.59

1.63 1.83 41.4 46.5 1.98 50.3

TOP VIEW

1.09 27.7

0.653 16.59

13 08/2008

Type C Power Relays


Application Data, Dimensions, Order Information
Class 8501 Type C relays are ideally suited for controlling small single phase motors and other light loads such as electric heaters, pilot lights or audible signals. 30 Ampere Contact Rating Horsepower Rated UL Listed CSA Certified
Selection Table AC Rated Contacts Number of Fixed Contacts N.O.
SPST DPST SPST SPDT DPDT 1 2 0 1 2

CE Approved Visible Contacts Low Cost

8501CDO6V51

Application Data AC Contact Ratings Maximum Single Phase Horsepower 120V


2 11/2 2 11/2 11/2

Application Data Coil Burden Nominal Power (VAC Coil)


2 11/2 2 11/2 11/2 10VA 10VA 10VA 10VA 10VA

Contact Arrangement

N.C.
0 0 1 1 2

AC DC Operated Operated Maximum Resistive Ampere Rating 75% Power Factor Coil Coil Contact Open Type Open Type Voltage Type Type 300V 600V
CO6 CO7 CO8 CO15 CO16 CDO6 CDO7 CDO8 CDO15 CDO16 600 600 600 600 600 30 30 30 30 30 10 5 10 5 5

230V
2 11/2 2 11/2 11/2

600V

Nominal DC Burden (VDC Coil)


2W 2W 2W 2W 2W

Selection Table DC Rated Contacts


SPST DPDT

Application Data DC Contact Ratings 110V 220V


8 4 N.A. 500 325 20 10

Application Data Coil Burden


10VA 10VA 2W 2W

1 2

0 2

CO21 CO22

CDO21 CDO22

Voltage code must be specified to order this product. Refer to standard voltage codes listed in the Stocked Relays table below and insert as shown in How to Order.

Enclosure: Separately packed NEMA Type 1 sheet steel enclosure for Types CO & CDO relays order Class 9991 Type UE1 Operating Data
Operating Voltages/ Voltage Range Coil Inrush (VAC Coil) Coils Operating Temp. Range
AC 6 through 480 volts, + 10/-15% of nominal at 25C DC 6 through 110 volts, + 10/-20% of nominal at 25C 15VA Duty: Continuous rated coils. (Non-replaceable) AC: -22F to +122F (-30C to +50C) DC: -22F to +140F (-30C to +60C)

Dimensions
Catalog Number 8501 A B C D E F IN mm IN mm IN mm IN mm IN mm IN mm
8.0 8.0 8.0 8.0 0.81 20.6 2.25 57.2 0.38 0.81 20.6 2.18 55.4 0.38 1.5 1.5 38.1 2.31 58.7 0.38 38.1 2.53 64.3 0.38 9.5 9.5 9.5 9.5

CO6, CO7, CO8, CDO6, CDO7, 2.43 61.7 2.50 63.5 0.31 CDO8 CO15, CO21, CDO15, CDO21 CO16,CDO16 CO22, CDO22 2.43 61.7 2.50 63.5 0.31 3.12 79.2 2.50 63.5 0.31 3.12 79.2 2.50 63.5 0.31

Stocked Relays
Class 8501 Type AC Voltage 50/60 Hz 6 12 24 120 208 240 277 480 Class 8501 Type Voltage Code CDO6 CDO7 CDO8 CDO15 CDO16 CDO21 CDO22 S DC Voltage 6 12 24 110

UL/CSA:
File CCN E78351 NLDX

File Class 04

209683 3211

Voltage V35 V36 V14 V20 V08 V24 V04 V29 Code CO6 CO7 CO8 CO15 CO16 CO21 CO22 S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S

V50 V51 V53 V60 S S S S S S S S S S S S

Approximate Dimensions

S Stocked Factory Order items require a minimum order quantity of 25 and have a lead time of 12 weeks.

How to Order:
To Order Specify:
Class Number Type Number Voltage Code (See Stocked Relay Table above)

Catalog Number
Class 8501 Type CO6 Voltage Code V20

2003-2008 Schneider Electric All Rights Reserved

14 08/2008

Type C Power Relays


Application Data, Dimensions, Order Information

2003-2008 Schneider Electric All Rights Reserved

15 08/2008

Schneider Electric USA


8001 Knightdale Blvd. Knightdale, NC 27545 1-888-SquareD (1-888-778-2733) www.schneider-electric.us

Schneider Electric Canada


19 Waterman Avenue, M4B 1 Y2 Toronto, Ontario 1-800-565-6699 www.schneider-electric.ca

8501CT0301R7/08 2003-2008 Schneider Electric All Rights Reserved Replaces 8501CT0301, December 2003 08/2008