Appendix C Fire resistance level and burning group of construction material and component Minimum thickness or sizes of component

cross section (cm) (2) 6.0 11 12 33 6 11 22 33 2.5 5 6 11 15 17 22 Fire resistance level (minute) (3) 145 150 330 660 30 90 240 420 18 36 45 150 222 270 360 Burning grou p (4) Incombustible

Componentlist

(1) 1. Walls and Partition: Walls and partition made of silica brick, common brick and hollow clay tile 2. Walls made by natural stone, light concrete and ceramic compound, light building brick blocks reinforced by light concrete, asbestos sheathing uninflammable or incombustible material 3. Walls and Partition: Concrete, reinforced concrete or rubble concrete, as well as panel walls or concrete and reinforced concrete block. (See note item 1)

Incombustible

Incombustible

4. Panel walls with solid section made of beehive-type concrete a) Keramzit concrete or cinder concrete with volume weight 1500 1800 kg/m3 (See note item 1) b) Beehive-type light concrete or light concrete with volume weight 900 1200 kg/m3 (See note item 1) c) Above material with volume weight 700 900 kg/m3 (See note item 1) 5. Block walls with vertical section made of beehive-type concrete with volume weight 900 1200 kg/m3 6. Panel walls made of reinforced brick silicate brick and normal clay brick (See note item1) 7. Three-layer panel walls consisting of edge reinforced concrete plate and asbestos sheathing made of incombustible and uninflammable asbestos or fibrolite plate: a) For panel walls

Incombustible 12 270

20

360

20 30 40 16

360 480 660 222 Incombustible

Incombustible

15 22

Not less than 60

Incombustible

Componentlist

(1) b) For bearing walls with thickness of internal concrete layer of 10 cm made of mark 200 concrete and pressing stress of 25 kg/cm2 and less (See note item 15) c) Above material with concrete of 14 cm thickness made of mark 300 concrete and pressing stress of 100 kg/cm2 and less (See note item 15) 8. Three-layer panel walls, with framework made of cement and two side asbestos cement and fastened by steel pin when the asbestos sheathing are made of: a) Incombustible and uninflammable asbestos b) Cellular plastic 9. Three-layer panel walls, with framework made of wood and press two asbestos cement together and fastened by steel pin when the asbestos sheathing are made of: a) Incombustible and uninflammable asbestos or glass concrete plate b) Cellular plastic 10. Walls and partition made of asbestos cement plate or steel plate (flat or corrugated), steel frame 11. Parapet walls and partition made of brick, concrete block and natural stone block with steel frame: a) Not protective layer b) Being located in the thickest wall, walls gap none protection or partition insert frame c) Protection plastering layer with thickness of 2cm on steel layer d) Hollow bricks with hollow gap of 6.5 cm 12 cm 12. Partition made of plaster, plaster slag and plaster fiber with organic content to 8% by weight 13. Partition made from hollow construction glass block

Minimum thickness or sizes of component cross section (cm) (2) 25

Fire resistance level (minute) (3) Not less than 150

Burning grou p (4) Incombustible

27

150

Incombustible

12

45 30

Incombustible Uninflammable

60 30 15

Uninflammable Uninflammable Incombustible

15 45 60 150 360 78 132 162 180 15 15

Incombustible Incombustible Incombustible Incombustible Uninflammable

5 8 10 11 6 10

Uninflammable

Componentlist

(1) 14. Partition made from hollow construction keramzit block (See note item 5) 15. Walls and partition made of fibrolite or plaster slag with wooden framework plaster both sides 16. Wooden walls and partition, plaster both sides, thickness of motar layer is 2cm 17. Walls and partition with wooden plaster frame or plaster both sides with dry plaster mortar or reinforced fibro-cement a) Made from flammable material b) Made from incombustible material Column and abutment 18. Brick, section (cm) 22 x 22 22 x 23 33 x 33 33 x 45 45 x 45 19. Concrete and steel-reinforced concrete with load-bearing hard frame a) Not over 75% section provision (cm) 20 x 20 20 x 30 b) Not over 75% section provision (cm) 20 x 20 20 x 30 20 x 40 20 x 30 v 20 x 50 30 x 50 40 x 40 20. Unprotected steel when thickness of minimum component is: To 12 mm From 13 to 20 (mm) From 21 to 30 (mm) From 31 to 50 (mm)

Minimum thickness or sizes of component cross section (cm) (2) 3.5 4 6.5 8 10 10 15 20 25

Fire resistance level (minute) (3) 30 60 90 120 45 36 45 60 75

Burning grou p (4) Uninflammable

Uninflammable

Uninflammable

Uninflammable 30 45 Incombustible 150 180 270 315 390

Incombustible 25 75 150 Incombustible 75 105 150 180 210 210 Incombustible 15 18 20 24 3

Componentlist

(1) 21. Protected steel: a) Plaster mesh surface or thick concrete plate

Minimum thickness or sizes of component cross section (cm) (2) 2.5 5 6 7 6 11 3 6 8 4 5 7 8 10 -

Fire resistance level (minute) (3) 45 120 150 180 120 315 60 24 228 66 90 120 150 192 60

Burning grou p (4) Incombustible

b) Common brick or think silica brick c) Thick perforated brick

Incombustible Incombustible

d) Thick plaster plate

Incombustible

22. Wooden column with sections not less than 20x20cm protected by plaster thickness 2cm Floor and roof 23. Floor and roof make of flat reinforced concrete plain section, when the thickness concrete layer from the lowest side to bearing concrete plate (See note item 9) 20 mm 30 mm 40 mm 50 mm 24. Floor or roof made of reinforced concrete (panel plate) with lower longitudinal bearing edge as well as cross and longitudinal beam when the thickness of concrete layer from the lowest sides or edge side to longitudinal bearing reinforced plate (See note item 10) 20 mm 35 mm 20 mm 35 mm 50 mm and above

Uninflammable

Incombustible

10 -

64 78 78 114 108 174 114 222

6.5 6.5 10 10 10

30 36 42 36 42 42 48 48 54

Incombustible

Componentlist

(1) 20 mm 30 mm 50 mm 20 mm 30 mm 40 mm 50 mm 60 mm 25. Floor and roof on cross steel beam (longitudinal beam, rafter) with incombustible plate: a) When horizontal and longitudinal beam, rafter unprotected b) When horizontal beam on mesh are protected by concrete layer or plaster thickness: 35 mm 10 mm 20 mm 30 mm 26. Wooden floor with batten or pad and plaster on the batten or mesh, when the thickness plaster 20 mm 27. Floor on cross wooden beam with batten made of plaster, when under the horizontal beam is protected by plaster layer or plaster thickness: 20 mm 30 mm 28. Roof made of fibro-cement panel or sheet metal on cross steel beam (longitudinal beam, rafter) unprotection 29. Three-layer panel roof with framework made of fibro-cement with thickness of 10 cm, fastened by steel pins when the asbestos sheathing are made of cellular plastic 30. Mesh concrete roof without protection layer below 31. Structures of steel stair: stair beam, cross beam with plastering 1cm, door cover, window, skylight, portal.

Minimum thickness or sizes of component cross section (cm) (2) 16 16 16 20 and above 20 20 20 20

Fire resistance level (minute) (3) 42 54 48 72 66 84 48 60 66 78 84 108 102 108 132 144

Burning grou p (4)

15

65 -

36 45 90 150 45

Incombustible

Incombustible

Incombustible

60 90 15

14

30

Uninflammable

36 90

Incombustible Incombustible

Componentlist

(1) 32. Door cover made of wide glass block installed by cement mortar and horizontal reinforcement on thickness volume 33. Doors cover made of one-layer steel plate or reinforced concrete with glasses having steel frame, rivet or clamp. 34. As above, by two-layer plates 35. Doorscover made of one-layer steel plate or reinforced concrete with glasses having yoke pin by steel. 36. Doorscover made of one-layer steel plate or reinforced concrete with fixed glasses, clamped by split steel rod or tightening steel rivet. Door, trap, gate 37. With hollow steel plate (having thin air layer) 38. As above, when protecting with thin layer of mineral fiber or asbestos 39. Wooden plate covered with asbestos at least thickness 5mm, with sheet metal (See note item 12) 40. Door made of wooden plate impregnated against fire and two sides plywood Notes:

Minimum thickness or sizes of component cross section (cm) (2) 6 10 10

Fire resistance level (minute) (3) 90 120 45

Burning grou p (4) Incombustible

Incombustible

72

Incombustible

15

8 3 4 5 4 6

30 78 72 78 90 36 60

Incombustible Incombustible Uninflammable

Uninflammable

1) Fire resistance level of bearing walls and partition, covered panel on lining mortar layer, valuation as directed in item 3, 4, 6 with factor calculated according to average stress of standard vertical load combination. a) Walls under item 3 thickness over 10cm when the stress is: 50KG/cm2 and less factor. 70KG/cm2 factor 0.7 Over 70KG/cm2 according to test result. When determining fire resistance level of full-block reinforced concrete walls with thickness over 10cm, higher instructed factor must increase by 20%. Then fire resistance level must be set not over in item 3. b) Walls under item 4a, when the stress is: 10 KG/cm2 and less factor 1 6

20 KG/cm2 and less factor 0.6 Over 20 KG/cm2 according to test result. c) Walls under item 4b, when the stress is: 10 KG/cm2 and less factor 0.5 Over 20 KG/cm2 according to test result. d) Walls under item 6 when the stress is: 30 KG/cm2 and less factor 1 40 KG/cm2 and less factor 0.7 Over 40 KG/cm2 according to test result. 2) Protecting reinforce connector of the component must intensity life time is equal to required fire resistance level value of the component; Fire resistance level of unprotected reinforce steel component, defined according to expectations for steel structure, must be set at 30 minutes; 3) Covering part of the gap at position adjacent to hanging-type walls and bearing-like walls with other part of a building must have fire resistance level equal to those of the walls; 4) When building partition made of hollow construction plaster block, the fire resistance level as instructed in item 12 must decrease to 30%; 5) Walls thickness in hollow keramzit block, as instructed in item 14, defined as total thickness of wall-constructing block; 6) Fire resistance level of light concrete block with volume weight of 1200 kg/m3 and more, as well as one-length bending-resistance structure made of silicate concrete must be set as reinforced concrete; 7) Fire resistance level of light concrete block with lower volume weight of 1200 kg/m3 and beehive-type concrete must be set as reinforced concrete with factor 1.3; 8) Fire resistance level panel and concrete panel of holes with side edge must be set according to items 2; 3 with factor 0.9; 9) Fire resistance level of panel under items 2; 3, depending on calculated scheme of fulcrum, must be set as: a) When fulcrum free two opposite sides factor 1 b) When running along guide way related parties 1:1 with factor 2.5 1:1.5 with factor 1.3 1:1.5 with factor 0.3 c) When bearing on two opposite sides as console, when thickness of panel is: 8cm and less with factor 1.6 10cm and less with factor 1.8 11cm and less with factor 2 12cm and less with factor 2.8 12 cm and less with factor 4 7

10) Fire resistance level of concrete assembly with lower edge as well as horizontal beam, bar and longitudinal beam must be set according to item 2.4 depending on calculated scheme for fulcrum: a) Fulcrum free with factor 1 b) When bearing and related with the area of reinforced section on side bearing and aperture: 0.25:1 with factor 1.22 0.50:1 with factor 1.25 1:1 with factor 1.5 1: 1 with factor 2.5 11) Thickness of wooden panel door and gate as directed in item 3; 9. Asbestos cardboard used wooden wing panel, door, hatche and gate is allowed to replace by wood soaked in clay mortar thickness 15mm, fire resistance level instructed in table 38 need to be reduced to 15%. 12) Thickness of incombustible plastering and alternating floor plastering is the common thickness of the structure. 13) Fire resistance level of partition independent on their door holes. 14) Fire resistance level instructed under item 9a for wooden panel frame walls, at horizontal and longitudinal joint adjacent building incombustible parts are protected direct effects of fire. 15) Fire resistance level of burning group as instructed in item 7a, b, c, the walls with or without opening for window and door in a condition flammable asbestos sheathing, protected at two sides of its next to wooden box thickness not less 40mm. Fire resistance level as instructed in item 7b and 7c, when bearing flat of floor and panel higher than outside walls so internal fire-resisting concrete layer of the panel located lower than the outside walls.