Escolar Documentos
Profissional Documentos
Cultura Documentos
L
Antriebstechnik Operating Instructions
These operating instructions are valid for controllers with the nameplate designation
E 3A E 3A E 3A
05/1996 02/2004
To locate information on specific topics, simply refer to the table of contents at the beginning and to the index at the end of this manual. The manual uses a series of different symbols to provide quick reference and to highlight important items.
Notes which should be observed to avoid health risks to the operating personnel.
5. Electrical connection When working on live drive controllers the valid national regulations for the prevention of accidents (e.g. VBG 4) must be observed. The electrical installation must be carried out according to the appropriate regulations (e.g. cable cross-sections, fuses, PE connection). More detained information is included in the documtenation. Notes concerning the installation in compliance with EMC like screening, grounding, arrangement of filters and laying of cables - are included in the documentation of the drive controllers. These notes must also be observed in all cases for drive controllers with the CE mark. The compliance with the required limit values demanded by the EMC legislation is the responsibility of the manufacturer of the system or machine.
2. Application as directed Drive controllers are components which are designed for installation into electrical systems or machinery. When installing into machines, commissioning of the drive controllers (i.e. the starting of operation as directed) is prohibited until it is proven that the machine corresponds to the regulations of the EC Directive 89/392/EWG (Machinery Directive); EN 60204 must be observed. Commissioning (i.e. starting of operation as directed) is only allowed when there is compliance with the EMC Directive (89/336/EWG). The drive controllers meet the requirements of the Low Voltage Directive 73/23/EWG. The harmonized standards of the prEN 50178/ DIN VDE 0160 series together with EN 60439-1/DIN VDE 0660 part 500 and EN 60146/DIN VDE 0558 are applicable to drive controllers. The technical data and information about the connection conditions must be obtained from the nameplate and must be observed in all cases.
6. Operation Systems where drive controllers are installed must be equipped, if necessary, with additional monitoring and protective devices according to the valid safety regulations, e.g. law on technical tools, regulations for the prevention of accidents, etc. Modifications of the drive controllers and the operating software are prohibited. After disconnecting the drive controllers from the supply voltage, live parts of the controller and power connections must not be touched immediately because of possibly charged capacitors. For this, observe the corresponding labels on the drive controllers. During operation, all covers and doors must be closed.
3. Transport, storage Notes on transport, storage and appropriate handling must be observed. Climatic conditions must be observed according to prEN 50178.
7. Maintenance and servicing The manufacturers documentation must be observed. This safety information must be preserved! The product-specific safety and application notes in these operating instructions must also be observed!
Contents
1 2 2.1 2.2 2.3 2.4 3 4 4.1 4.2 4.2.1 4.2.2 4.3 4.4 4.5 4.5.1 4.5.2 4.6 4.7 5 5.1 5.2 5.3 6 6.1 6.2 6.3 6.4. Index Features of the 470 series of controllers Technical data Controller-specific data Controller dimensions Scope of supply Application as directed Accessories Installation Installation Connection Installation corresponding to EMC CE-typical drive system Connection diagram Connection of type 472 for mains connection 190 ... 265 V Special field voltages for the types 472 and 473 Field voltage > 0.9 x VL1, N Field connection without neutral conductor Additional terminals Replacing the fuses Commissioning Setting the current limit Armature voltage control with "I x R compensation" Speed control with tacho feedback Switching operation Controller enable Controller inhibit Electrodynamic braking Reversing 5 6 6 7 7 8 9 12 12 12 14 15 18 20 20 20 21 22 22 23 23 23 24 25 25 25 26 28 29
The 470 series of controllers comprises three single quadrant controllers with output powers from 1.3 kW to 7 kW. The most important features include: Compact controllers with isolated heatsink Operation with tacho or armature voltage feedback with "I x R compensation" Isolation of control electronics and power stage when tacho feedback is used Self-synchronization of the phase shifter for 50 ... 60-Hz mains High interference margin due to integrated synchronizing filter Burst-gate thyristor control in the power stage Reliable operation also for mains voltage fluctuations and short-term mains failures due to static and dynamic voltage monitoring Display of the operating states using LEDs Free connections for set-value delay, actual value differential component, speed reset time Option board can be retrofitted: Set-value integrator 2003 Winding calculator 1071 Compliance with the CE directives for the erection of a CE conform drive system
2
2.1
Technical data
Controller-specific data
Pel [kW] f [Hz] V [V] VA [V] IA [A] VF [V] IF [A] FFmax 471 1.3 190...265 190...265 160 8 0.8 1.4 1.2 Imax [A] VLN [V] VTN [V] nmin [nN] Ta [C] R FF16A/600V 10 x 38 EFSFF0160AYE not necessary 0...8 16 0.9 x VL1, N 2 472 2.5 50...60 340...460 190...265 260 27 2.5 4 473 7
UL1, L2 UL1, N
Armature voltage Armature current Field voltage Max. field current Perm. form factor - without choke - with choke Current limitation Rated master voltage Rated tacho voltage Min. speed Operating ambient temperature Set-value potentiometer Type Power stage fuse Type Electronics fuse Type Weight approx. Chassis type E
1.2 0...16 10...180 10...180 0...0.25 0...45 10k / 1W lin. ER00322194 FF25A/600V 14 x 51 EFSFF0250AYH FF4A/500V 6.3 x 32 EFSFF0040AWB 2.1 33.472__E
1.2 0...27
m [kg]
1.2 33.471__E
2.2
Controller dimensions
1 2 3 5 4
d
e
c a
Explanations
Type 471 472 473
1)
LEDs Trimmers Measuring point "M1" Connecting terminals a [mm] 150 150 240 b [mm] 220 220 160
VCC, RSP, Imax Imax, I R, Vp, nmin, ULeit fein, ULeit grob, nmax
Spacers for the attachment of the protective cover and the option board
The dimension (e) is the installation height of the base controller including protective cover.
2.3
Scope of supply
The scope of supply includes: the controller 47x_E set-value potentiometer 10 k the operating instructions
2.4
Application as directed
The controllers of the types 47x are electrical equipment for the installation into control cabinets of electrical systems or machinery. The controllers of the types 47x are designed as components for the control of speed-variable drives with separately-excited DC motors or for the assembly with other components to form a machine or system. Drive systems with drive controllers 471 and 472 which are installed according to the definition of a CE-typical drive system (see chapter 4.2.2), correspond to the EC EMC Directive and the standards mentioned below. CE-typical drive systems are - suitable for the operation on public and non-public mains and - provided for industrial applications. Because the ground potential reference of the RFI filters, the CEtypical drive system which is described is not suitable for the connection to IT mains (mains without ground potential reference). The drive controllers are not domestic appliances, but are designed for drive systems for commercial use. The controllers of the types 47x themselves are not machines according to the EC Machinery Directive. The final function is only determined when integrated into the machine construction of the user. The user must consider measures in his machine construction which limit the consequences in case of malfunction or failure of the drive controller (increase of the motor speed or sudden motor stop) so that hazards for persons or material assets cannot be caused, such as: further independent equipment for the monitoring of safetyrelevant variables (speed, travel, end positions, etc.) electrical or non-electrical protective equipment (latching or mechanical blocking) measures covering the complete system
Accessories
The following components can be ordered separately: RFI filter Mains choke Armature choke Zinc oxyde varistor Mains fuses and fuse holders for the types 473 Knob and scale for set-value potentiometer Option board 2003 and 1071
Typet RFI filter type Mains choke LK Type Number of mains chokes per controller Zinc oxyde varistor RU Part no. Power stage fuse Type Fuse holder type
1) 2)
B32 K275 1) e.g. B32 K460 2) 308 935 (Siemens) Internal fuse FF40A/600V (see chapter 2.1 "Controller-specific data") 22 x 58 EFSFF0400AYI EF00357279 not necessary
Mains choke
k
e f
m c a
n d b
Type Mains choke type L [mH] l [A] a [mm] b [mm] c [mm] d [mm] e [mm] f [mm] k [mm] m [mm] n [mm] Weight [kg]
10
RFI filter
Design A
c b
f d a
Design B
c b
g e f d a
Design C
e b
d c f a
Type RFI filter type Rated current [A] Voltage Vmax Design a [mm] b [mm] c [mm] d [mm] e [mm] f [mm] g [mm] Fixing Weight [kg]
472 EZF1_018A0011) 18 250 V 0% C 123 85 39 108 50,8 100 4 x M4 0.7 EZF3_016A001 16 440 V 0% B 220 115 100 180 60 17 115 4 x M6 1.9
11
4
4.1
Installation
Installation
When installing into an enclosure ensure sufficient ventilation. The ambient temperature must not exceed +45 C. Install the controller with the terminals at the bottom. External operating elements (e.g. switch, fuses) must not be arranged close ( 250 mm) to the controller 470. If this distance is not observed, a suitable cover must be provided in order to avoid accidental contact with the controller board.
4.2
Connection
The controllers contain electrostatically sensitive components. Prior to assembly and servicing the personnel must be free of electrostatic charges. Discharging is possible by touching the PE fixing screw or another grounded metal part in the control cabinet. If you use residual current devices: The controllers have an internal mains rectifier. After a shortcircuit to frame a DC fault current may prevent the tripping of the residual current device. Therefore, take additional measures like zeroing or use universal current e.l.c.b. Observe for the dimensioning of the release current of e.l.c.b. that capacitive compensating currents of the cable screens and RFI filters occuring during normal operation may cause false tripping. Note for the use of universal e.l.c.b.: The preliminary standard prEN50178 (in the past VDE0160) about the use of universal e.l.c.b. has been decided by the German committee K226. The final decision about the use in compliance with the standard is made by the CENELEC/CS (European Committee for Electrotechnical Standardization) in Brussels. Further information on the use of universal current e.l.c.b. can be obtained from the supplier. All cables from and to the controller must be screened. Connect the screening at both ends, close to the cable ends, to the central PE connection. When using the supplied set-value potentiometer, the mechanical screw fixing must have an additional PE connection and the connections must be insulated and covered. Caution! In the operating mode "armature voltage control with I x R compensation" all control terminals carry mains potential. It is therefore necessary that all input and output signals required for the control of the controller are, electrically, safely separated by measures outside the controller and have another protection against direct contact (double basic insulation).
12
For operation with tacho voltage feedback the control electronics has a simple basic insulation. Take measures outside the controller to ensure that input and output signals of the control have a double basic insulation. The protective cover above the controller board reduces the hazard of accidental touching of live components. For the assembly and during commissioning the cover must be removed. Caution! Removal of the protective cover and all settings must only be carried out by qualified skilled personnel. With removed cover, there is increased danger of accidental contact with bare, live components on the controller board. The protective cover must only be attached and removed when no voltage is applied. The cover must be replaced after setting.
13
14
Mains cable between RFI filter and mains choke and between mains choke and controller Control cables Motor
Screened signal cable type LIYCY DC motor with separate excitation Lenze series GFQ, GFR or similar
Note: Controller, RFI filter, and mains choke are located on one mounting plate. Installation of the CE typical drive system The electromagnetic compatibility of a drive system depends on the type and accuracy of the installation. Take special care with filters screening grounding Filters Only use the RFI filters and mains chokes allocated to the controllers RFI filters reduce non-permissible high-frequency interferences to a permissible value. Mains chokes reduce low-frequency interferences which depends primarily on the motor cables and their length. For motor cables which are longer than 50 m additional measures are required. Screening Screen all cables from and to the controller. Make sure that motor cables are separated from signal and mains cables when laying the cables. Avoid a common terminal board for mains input and motor output. The cables must be laid as close as possible to the reference potential. Dangling cables are like antennas. Grounding Ground all conductive metal components (controllers, RFI filters, mains chokes) by suitable cables from a central grounding point (PE bar). Observe the minimum cross-sections prescribed in the safety information. However, for EMC the surface of the contact is important and not the cross-section.
15
Assembly Make the contact from controller, RFI filter, and mains chokes to the grounded mounting plate with as large a surface as possible. Zinc-coated mounting plates allow long-lasting contacts. For painted plates the paint of the mounting plates must be removed in all cases. If you use several mounting plates: Make a conductive connection of the mounting plates with as large a surface as possible (e.g. using copper bands). Connect the screen of the armature and field cable to the mounting plate with as large a surface as possible: Recommendation: Make the large-surface connection of the screens to the mounting plate with earthing clamps on bare metal mounting surfaces.
s c re e n e d c a b le
b a re m e ta l m o u n tin g s u rfa c e
s c re e n b ra id
e a rth in g c la m p
If there are contactors, motor protection switches, or terminals in the armature cable: Contact of the screens of the connected cables to each other and to the mounting plate with as large a surface as possible. In the terminal box, connect the screen of the motor to PE: Metal cable glands at the motor terminal box ensure a largesurface connection of the screen to the motor housing. If the total length of the mains cable between RFI filter and mains chokes and controller exceeds 200 mm: Screen mains cables Connect the screen of the mains cables to the mounting plate with as large a surface as possible. Connect the screen of the control cables to the mounting plate with as large a surface as possible. If you use drive systems with the types 47x in residential areas: Check the compliance with radio interference voltage level (EN55022 class B) at the supply location of the operating area. Check the permissible radio interference emission (EN55022 class B) at the supply location of the operating area. Please note: If devices which do not comply with the CE requirement concerning the noise immunity EN 500882-2 are operated close to the controllers, an electromagnetic disturbance of these devices by the controllers is possible.
16
Part of the CE-typical drive system which is located on the mounting plate
L1 L2 N
LINE
RFI filter
PE
mains chokes
controller
L
PE
L1L2 A B N I K
470
screened control cables
PE
PE bar
PE connection
Connect screen of the motor cables at the motor side as well with a large surface to PE.
17
4.3
Connection diagram
Type 471
Feedback
1
Set-value input
+ Vcc - Vcc
PE
12 14 16 17
31 38 40
PE
+ PE
PE
L1
Explanations
Only the feedback system used can be connected at terminals 1/2 or 3/4.
Type 472
Feedback
1
Set-value input
+ Vcc - Vcc
PE L1 L2
9 12 14 16 17 31 38 40
LK
LD R
nmin PE
nmax
RFR
+ PE -
Explanations
Only the feedback system used can be connected at terminals 1/2 or 3/4.
18
Type 473
Feedback
1
Set-value input
+ Vcc - Vcc
PE L1 L2
12 14 16 17 31 38 40
F1 LK
F1
2 LK
LD R
+ PE -
Explanations Notes 1. If the signals must be changed over via relays, use suitable relay contacts (e.g. gold-plated contacts). 2. When switch RFR is closed the controller is enabled.
Only the feedback system used can be connected at terminals 1/2 or 3/4. For mains fuses see chapter 3 "Accessories"
19
4.4
F2 F1
Transformer
VN VA IA Pel
472 Board
Mains choke LK = 0.98 mH/35 A Type: ELN1_009H035 Mains filter Type: EFZ1_018A001
L1 L2 A B
LK
Mains filter
PE L1 N
Note The controller 472 is factory-set for the operation at mains voltages from 340...460 V. For the operation at 190...265 V remove the standard jumper 1 and solder the jumper 2 on the soldering points. Caution! This modification must only be carried out by skilled qualified personnel when no voltage is applied. After exchanging the jumper, the protective cover must be reassembled.
4.5
T6A 500 V
LK LK
Mains filter
PE
L1
L2
20
PE
L1
L2
LK
LK
Mains filter
PE
L1
L2
PE
L1
L2
LK
LK
Mains filter
PE
L1
L2
21
4.6
Additional terminals
Meaning ^ Input current controller; Ri 10 k, Uiset = 0... -10 V= (-10 V = IAmax) -VCC = -15 V= stabilized. -VCC can be loaded externally with 15 mA. Output actual armature current. The output terminal 31 supplies an output voltage proportional to the armature current. U31 10 V corresponds to the rated controller current. This output can be loaded with a maximum of 3 mA. The output resistance is Ri = 1 k. Freely assignable speed controller input Terminal 38 leads to the summation point of the speed controller via Ri 50 k. The permissible input voltage range is between -10 V and +10 V. Output speed controller; Ri 200 . Terminals 40 and 12 are connected internally via a 2.2-k resistor (on soldering posts). Designation of the 2.2-k resistor R818 R207 R406
Terminal designation 12 14 31
38
40
40
C urrent set-value 10K / 1W
l in .
m in
4.7
The fuses protect the controller from non-permissible operating conditions. After the release of such a protective function, the controller and the system must be checked for further faults before replacing the fuses. Remove the protective cover to replace the fuses. Caution! Removal of the protective cover and the replacement of the fuses must only be carried out by qualified skilled personnel when no voltage is applied. Defective fuses must only be replaced by the prescribed type (see chapter 2.1 "Controller-specific data"). The protective cover must be attached again after the fuses are replaced.
22
Commissioning
Turn trimmers "nmin", "nmax", "Vp", "I R" fully counterclockwise. Trimmers "ULeit grob" and "ULeit fein" are factory-set for the setvalue potentiometer connection as a standard. Only if a master voltage is used: "ULeit grob" must be turned fully counterclockwise and "ULeit fein" to a middle position for the subsequent base setting. Trimmer "Imax" is factory-set to rated controller current.
5.1
The current limit only needs to be set if the rated motor current is lower than the rated controller current. Connect a moving coil meter in the armature circuit to measure the current. Block the armature or disconnect the field. Caution: Observe the current capacity of the motor at standstill! Turn trimmer "nmin" fully clockwise and connect the mains. Turn trimmer "Imax" to adjust the armature current. Then turn trimmer "nmin" fully counterclockwise.
5.2
Caution! In this operating mode all control terminals carry mains potential. It is therefore necessary that all input and output signals required for the control of the controller are safely separated electrically by measures outside the controller and have another protection against direct contact (double basic insulation). When using the supplied set-value potentiometer, the mechanical screw fixing must have an additional PE connection and the connections must be insulated and covered. Connect motor terminal A to controller terminal 1 and motor terminal B to controller terminal 2 (see connecting diagram). Set set-value potentiometer or master voltage to zero. Connect mains. LED "RSP" is illuminated. LED "VCC" is illuminated. Set set-value potentiometer or master voltage to maximum. In case of master voltage operation, turn trimmer "ULeit grob" clockwise until '+10 V=' are applied at measuring point "M1" (measured across terminal 3, terminal 7, or terminal 33 = GND; see chapter 2.2 "Controller dimensions"). Close switch "RFR". LED "RSP" is not illuminated. Turn trimmer "nmax" clockwise until the desired maximum speed is obtained. Set set-value potentiometer or master voltage to zero.
23
Turning trimmer "nmin" clockwise increasee the minimum speed. Check the adjustment of the maximum speed, since trimmers "nmax" and "nmin" influence each other. The fine setting of the maximum speed is done using trimmer "ULeit fein". Turn trimmer "Vp" clockwise, until the drive becomes unstable (speed oscillations), then turn trimmer "Vp" approx. 20 % counterclockwise until the drive is stable again. Set the speed stabilization at trimmer "I R" such that the smallest speed change results with the smallest operating speed between idle running and rated load. Then check the compensation for higher speeds.
5.3
Caution! In this operating mode, the control electronics has a simple basic insulation. Take measures outside the controller to ensure that the input and output signals of the control have a double basic insulation. Set set-value potentiometer or master voltage to zero. Connect mains. LED "RSP" is illuminated. LED "VCC" is illuminated. Set set-value potentiometer or master voltage to maximum. In case of master voltage operation, turn trimmer "ULeit grob" clockwise until '+10 V=' are applied at measuring point "M1" (measured across terminal 3, terminal 7, or terminal 33 = GND; see chapter 2.2 "Controller dimensions). Close switch "RFR". LED "RSP" is not illuminated. Caution! In case of uncontrolled acceleration of the motor during speed setting, immediately open switch "RFR". In this case, the tachogenerator feedback is either missing or has incorrect polarity. After checking and correcting the wiring, commissioning can be started again. Turn trimmer "nmax" clockwise until the desired maximum speed is obtained. Set set-value potentiometer of master voltage to zero. Turning trimmer "nmin" clockwise increases the minimum speed. Check the adjustment of the maximum speed since trimmers "nmax" and "nmin" influence each other. The fine setting of the maximum speed is done using trimmer "ULeit fein". Turn trimmer "Vp" clockwise, until the drive becomes unstable (speed oscillations), then turn trimmer "Vp" approx. 5 % counterclockwise until the drive is stable.
24
6
6.1
Switching operation
Controller enable
If switch "RFR" is closed, the controller is enabled. If the switch "controller enable" (RFR) is open the firing pulses are inhibited.
16 17
RFR
Only use low-current contacts for the switching of signal cables (15V / 1.5mA)
6.2
Controller inhibit
The function "RSP", i.e. the inhibiting of the controller with a normally-open contact is possible using the following connection. When "RSP" (controller inhibit) is closed, the firing pulses are inhibited.
16 17
RSP
Only use low-current contacts for the switching of signal cables (15V / 1.5mA)
25
6.3
Electrodynamic braking
L1 L2 N PE
K3 F1
M a in s filte r
LK
LK
K5 N PE 16
K1
K2
L1
L2
17
PE
S1 K3 S2 K1 K1
472
A B I K
RU
K4 K2 K4 K4
LD
K4
RB
K3
K1
K2
K4
K5
A
M
K PE
t> t B
Explanations
K1, K2, K5 S1 S2 Relay On Stop
If the field is excited, the induced armature current is used for braking the motor. Before connecting the brake resistor, the controller is inhibited. The timer relay must be set such that the braking contactor only opens after the motor has stopped (deceleration time of K2 > braking time tB). To limit voltage peaks a zinc oxyde varistor (RU) must connected in parallel at the controller output (see chapter 3 "Accessories").
26
Dimensioning of the brake resistor RB Neglecting the armature feedback for a required initial braking torque MBa, the initial braking current IABa results in: MBa IABa = IAN M N IAN MN MBa = Rated armature current = Rated torque, = Initial braking torque
The braking resistor RB is calculated as follows: RB = UAa IABa A A = UA IA M n UAa A2 IABa = Armature voltage in the motor mode = Initial braking current = Armature efficiency 2Mn UA IA = Armature voltage = Armature curent = Torque = Speed
The size of the brake resistor depends on the braking energy of the drive and the number of brakings. The braking current should not be more than twice the rated armature current and should not exceed the maximum starting current.
27
6.4.
Reversing
L1 L2 N PE
K3 F1 LK LK
M a in s filte r
K7 N PE 16
K5
K6
L1
L2
17
PE
S1 S2 S3
K5 K4
472
A B I K
K1
K2 K5
RU
K2 K1 K4 K6 K4
LD
K4
RB
K1
K2 K1 K2 K3 K5 K6 K4 K7
A
M
t> B t
PE
Explanations
K5, K6, K7 S1 S2 S3 Relay CW rotation On CCW rotation On Stop
Reversing is obtained by changing the armature polarity. The motor is electrodynamically braked to standstill (see chapter 5.3 "Electrodynamic braking"). The braking time must be set at the timer relay such that the motor is safely at standstill before the armature is reversed. To limit the switching voltage peaks, a zinc oxyde varistor (RU) must be connected in parallel to the controller output (see chapter 3 "Accessories").
28
Index
A
Accessories 9 Application as directed 8
C
Commissioning 23 Armature voltage control with "I R compensation" 23 Setting the current limit 23 Controller dimensions 7 Controller features 5 Controller-specific data 6
D
Dimensions Mains choke 10 RFI filter 11
I
Installation 12 CE-typical drive system 15 Connecting diagram 18 Connection 12 Installation 12 Installation corresponding to EMC 14
O
Operating modes Controller enable 25 Controller inhibit 25
R
Replacing the fuses 22
S
Scope of supply 7 Speed control with tacho feedback 24
29
30