Você está na página 1de 158

Technical Data

1756 ControlLogix I/O Modules

Catalog Numbers 1756 series


Topic Available 1756 I/O Modules Environmental Specifications - 1756 I/O Modules Digital I/O Modules Analog I/O Modules Specialty I/O Modules Module Specifications ControlLogix I/O Accessories Page page 2 page 3 page 3 page 5 page 6 page 7 page 156

The ControlLogix architecture provides a wide range of input and output modules to span many applications, from high-speed digital to process control. The ControlLogix architecture uses Producer-Consumer technology, which allows input information and output status to be shared among multiple ControlLogix controllers.

ControlLogix Controllers Output Modules Input Modules

Each ControlLogix I/O module mounts in a ControlLogix chassis and requires either a removable terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring. RTBs and IFMs are not included with the I/O modules. They must be ordered separately.

1756 ControlLogix I/O Modules

Available 1756 I/O Modules


I/O Type AC digital Catalog Number 1756-IA8D 1756-IA16 1756-IA16I 1756-IA32 1756-IM16I 1756-IN16 1756-IB16 1756-IB16D 1756-IB16I 1756-IB16ISOE 1756-IC16 1756-IG16 1756-IH16I 1756-IH16ISOE 1756-IV16 1756-IV32 page 7 page 9 page 11 page 13 page 57 page 59 page 15 page 17 page 19 page 21 page 26 page 50 page 53 page 55 page 71 page 73 1756-OA8 1756-OA8D 1756-OA8E 1756-OA16 1756-OA16I 1756-ON8 1756-OB8 1756-OB8EI 1756-OB8I 1756-OB16D 1756-OB16E 1756-OB16I 1756-OB16IS 1756-OB32 1756-OC8 1756-OG16 1756-OH8I 1756-OV16E 1756-OV32E 1756-OX8I 1756-OF4 1756-OF6CI 1756-OF6VI 1756-OF8 page 76 page 79 page 82 page 85 page 88 page 130 page 91 page 93 page 96 page 98 page 101 page 103 page 105 page 107 page 109 page 125 page 128 page 133 page 136 page 142 page 111 page 114 page 117 page 119

DC digital

Contact Analog

1756-OW16I 1756-IF6CIS 1756-IF6I 1756-IF8 1756-IF16 1756-IF4FXOF2F 1756-IR6I 1756-IT6I 1756-IT6I2 1756-IF8H 1756-CFM 1756-HSC

page 139 page 28 page 32 page 36 page 43 page 47 page 61 page 65 page 68 page 40 page 145 page 149

HART interface Specialty

1756-OF8H 1756-PLS

page 122 page 152

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Environmental Specifications - 1756 I/O Modules


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Value 060 C (32140 F)

-4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g

Digital I/O Modules

The 1756 digital I/O modules support these features: Variety of voltage interface capabilities Isolated and nonisolated module types Point-level output fault states Direct-connect or rack-optimized communication Field-side diagnostics on select modules In addition, you can select these types of digital I/O modules.
Description These modules provide diagnostic features to the point level. These modules have a D at the end of the catalog number. These modules have internal electronic fusing to prevent too much current from flowing through the module. These modules have an E at the end of the catalog number. These modules have individually isolated inputs or outputs. These modules have an I at the end of the catalog number.

Digital I/O Type Diagnostic Electronic fusing Individually isolated

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Module Type 1756 digital AC input modules

Features Change of state: Software configurable Timestamp of inputs: 200 s Module keying: Electronic, software configurable RTB keying: User-defined mechanical

1756 digital AC output modules

Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time Fault states per point: Hold last state, on or off (off is default) States in Program mode per point: Hold last state, on or off (off is default) Fusing: 1756-OA8D, 1756-OA8E: Electronically fused per point 1756-OA16: Mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A interruption current, Littelfuse p/n H2153.15 All other modules: Not protected. A fused IFM is recommended to protect outputs (see publication 1492-2.12) Module keying: Electronic, software configurable RTB keying: User-defined mechanical

1756 digital DC input modules

Reverse polarity protection: All modules except 1756-IG16 module Change of state: Software configurable Timestamp of inputs: 100 s for sequence of events modules 200 s for all other modules Module keying: Electronic, software configurable RTB Keying: User-defined mechanical

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Module Type 1756 digital DC output modules

Features Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time Fault states per point: Hold last state, on or off (off is default) States in Program mode per point: Hold last state, on or off (off is default) Fusing: 1756-OB8EI, 1756-OB16D, 1756-OB16E, 1756-OV16E, 1756-OV32E: Electronically fused per point All other modules. Not protected. A fused IFM is recommended to protect outputs (see publication 1492-2.12) Module keying: Electronic, software configurable RTB keying: User-defined mechanical

1756 digital contact modules

Scheduled outputs: Synchronization within 16.7 seconds maximum, reference to the Coordinated System Time Configurable fault states per point: Hold last state, on or off (off is default) Configurable states in Program mode per point: Hold last state, on or off (off is default) Fusing: Not protected. A fused IFM is recommended to protect outputs (See publication 1492-2.12) Module keying: Electronic, software configurable RTB keying: User-defined mechanical

Analog I/O Modules


Module Type 1756 analog input modules

The 1756 digital I/O modules support these features:


Features On-board data alarming Scaling to engineering units Real-time channel sampling Data Format: Integer mode (left justified, 2s complement) IEEE 32-bit floating point Module conversion method: Sigma-Delta

1756 analog output modules

Data format: Integer mode (left justified, 2s complement) IEEE 32-bit floating point Module conversion method: R-Ladder DAC, monotonicity with no missing codes Module keying: Electronic, software configurable RTB keying: User-defined mechanical

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Module Type 1756 high-speed analog combination module

Features Data format: Integer mode (left justified, 2s complement) IEEE 32-bit floating point Input conversion method: Successive approximation Output conversion method: R-Ladder DAC, monotonicity with no missing codes Module keying: Electronic, software configurable RTB keying: User-defined mechanical

1756 analog RTD and thermocouple modules

Data Format: Integer mode (left justified, 2s complement) IEEE 32-bit floating point Module conversion method: Sigma-Delta Module keying: Electronic, software configurable RTB keying: User-defined mechanical

1756 analog modules with HART interface

Data format: Integer mode (left justified, 2s complement), Floating point IEEE 32 bit Input conversion method: Successive approximation Output conversion method: R-Ladder DAC, monotonicity with no missing codes Module keying: Electronic, software configurable RTB keying: User-defined mechanical

Specialty I/O Modules


Module Type 1756-CFM configurable flow meter module

These specialty modules are available:


Features The 1756-CFM module provides Totalizer mode for metering applications, or high-speed frequency measurements for speed or rate control applications, on two channels connected to flowmeters. Totalizer fill and prover High-resolution 100 kHz max Frequency 0.0005 Hz resolution Reverse polarity protection: Outputs only Module keying: Electronic, software configurable RTB keying: User-defined mechanical

1756-HSC high-speed counter module

The 1756-HSC module provides four high-speed, output-switching, on-off windows. The module uses pulses for counting and frequency. Counter: 1 MHz max Rate Measurement: 500 kHz max Encoder: 250 kHz max Debounce filter: 70 Hz max Module keying: Electronic, software configurable RTB keying: User-defined mechanical keying

1756-PLS programmable limit switch module

The 1756-PLS module supports enhanced packaging applications. Requires three contiguous slots in chassis RTB keying: User-defined mechanical

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IA8D
ControlLogix AC (79...132V) diagnostic input module
Simplified Schematic +5V
Not Used Daisy Chain to Other RTBs 1756-IA8D
2 4 1

L1-0 Loss of Field Power


3

Input Display GND


+5V ControlLogix Backplane Interface Open Wire Display

L2-0
6 5

IN-0 IN-1
8 7

L2-0 Group 0 L2-0


10 9

IN-2 IN-3
12 11

Group 0

L2-0 L2-1
14 13

47 k, 1/2 W 5% Resistor

IN-4 IN-5
16 15

GND

ControlLogix Backplane Interface

L2-1 Group 1 L2-1


18 17

IN-6 IN-7
20 19

Group 1

47 k, 1/2 W, 5% Resistor

L2-1 L2-1 L2 L1

L1-1 Loss of Field Power

Diagnostics - 1756-IA8D
Attribute Open wire Loss of power Timestamp of diagnostics 1756-IA8D Off-state leakage current 1.5 mA min Transition range 4685V AC 1 ms

AC INPUT
ST 0 1 2 3 4 5 6 7 O FL 0 1 2 3 4 5 6 7 K T

Technical Specifications - 1756-IA8D


Attribute Inputs Voltage category Operating voltage range 1756-IA8D 8 diagnostic (4 points/group) 120V AC 79132V AC, 4763 Hz 1 or 2 ms 10 ms + filter 9 or 18 ms 8 ms + filter 100 mA 3 mA 4.5 W @ 60 C 15.35 BTU/hr

DIAG STIC NO

Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Isolation voltage

1756-IA8D 20V 2.5 mA 5 mA @ 74V AC 16 mA @ 132V AC 250 mA 8.25 k @ 132V AC, 60 Hz 200 s...750 ms 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IA8D
Certification(1) c-UL-us 1756-IA8D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IA16
ControlLogix AC (79...132V) input module
1756-IA16
2 1

Simplified Schematic
IN-1

IN-0
4 3

IN-O L2-0 GND

+5V

Group 0 Daisy Chain to Other RTBs IN-3

IN-2
6 5

IN-5
8 7

IN-4 IN-6
10 9

Group 0

IN-7 L2-0
12 11

ControlLogix Display Backplane Interface

L2-0 IN-8
14 13

IN-9 IN-11
16 15

IN-10 IN-12
18 17

Group 1

IN-13 IN-15
20 19

Group 1

IN-14 L2-1

L2-1

L2

L1

AC INPUT
ST 0 1 2 3 4 5 6 7 O FL 0 1 2 3 4 5 6 7 K T

Technical Specifications - 1756-IA16


Attribute Inputs Voltage category 1756-IA16 16 (8 points/group) 120V AC 74132V AC, 4763 Hz 1 or 2 ms 10 ms + filter 9 or 18 ms 8 ms + filter 105 mA 2 mA 5.8 W @ 60 C 18.41 BTU/hr 20V 2.5 mA 5 mA @ 74V AC 13 mA @ 132V AC

DIAG STIC NO

Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Inrush current, max Input impedance, max Cyclic update time Isolation voltage

1756-IA16 250 mA peak (decaying to <37% in 22 ms, without activation) 10.15 k @ 132V AC, 60 Hz 100 s...750 ms 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IA16
Certification(1) c-UL-us 1756-IA16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

10

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IA16I
ControlLogix AC (79...132V) isolated input module
Simplified Schematic IN-O L2-0
L2-4 Isolated Wiring L2-0 L2-2 L2-0 L2-1 L2-2 L2-3 L2-4 L2-5 L2-6 1756-IA16I
2 4 6 8 10 1 3 5 7 9

+5V

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used

L1-0 L1-2 L1-4

GND ControlLogix Display Backplane Interface


Jumper Bar (Cut to Length)

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

L2-7 L2-8 L2-9 L2-10 L2-11 Nonisolated Wiring L2-12 L2-13 L2-14 L2-15 L2 L2-15 Not used

The jumper bar part number is 97739201 and is included with the module.

L1

Daisy Chain to Other RTBs

Technical Specifications - 1756-IA16I


AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

Attribute Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max

1756-IA16I 16 individually isolated 120V AC 79132V AC, 4763 Hz 1 or 2 ms 10 ms + filter 9 or 18 ms 8 ms + filter 125 mA 3 mA 4.9 W @ 60 C 16.71 BTU/hr 20V 2.5 mA 5 mA @ 79V AC, 4763 Hz 15 mA @ 132V AC, 4763 Hz 250 mA

Publication 1756-TD002A-EN-E - May 2009

11

1756 ControlLogix I/O Modules

Attribute Input impedance, max Cyclic update time Isolation voltage

1756-IA16I 8.8 k @ 132V AC, 60Hz 100 s...750 ms 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IA16I
Certification(1) c-UL-us 1756-IA16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

12

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IA32
ControlLogix AC (74...132V) input module
Simplified Schematic IN-O L2-0 GND ControlLogix Display Backplane Interface +5V
IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 L2-0 IN-17 IN-19 IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 L2-1
1756-IA32

2 4 6 8 10

1 3 5 7 9

Group 0 Daisy Chain to Other RTBs

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 L2-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 L2-1

Group 0

Group 1

Group 1

L1

L2

Technical Specifications - 1756-IA32


AC INPUT
ST 0 1 2 3 4 5 6 7

Attribute Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max

1756-IA32 32 diagnostic (4 points/group) 120V AC 74132V AC, 4763 Hz 1 or 2 ms 10 ms + filter 9 or 18 ms 8 ms + filter 165 mA 2 mA 6.1 W @ 60 C 20.8 BTU/hr 20V 2.5 mA 5 mA @ 74V AC 15 mA @ 132V AC 390 mA 14.0 k @ 132V AC, 60 Hz

1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6

1 1 1 9 2 7

1 2 2 0 2 8

1 3 2 1 2 9

1 4 2 2 3 0

1 O 5 K 2 3 3 1

Publication 1756-TD002A-EN-E - May 2009

13

1756 ControlLogix I/O Modules

Attribute Cyclic update time Isolation voltage Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

1756-IA32 200 s...750 ms 250V continuous I/O group to group, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IA32
Certification(1) c-UL-us 1756-IA32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick
(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

14

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IB16
ControlLogix DC (10...31.2V) input module
Simplified Schematic +5V IN-0 GND-0 GND ControlLogix Backplane Interface Display
GND-0
? ?

1756-IB16

IN-1

IN-0
? ?

Group 0
IN-3

IN-2
? ?

Daisy Chain to Other RTBs

IN-5
? ?

IN-4 IN-6
?

Group 0

IN-7

GND-0 IN-8
? ?

IN-9 IN-11

IN-10
? ?

Group 1

IN-13
? ?

IN-12 IN14
? ?

Group 1

IN-15 GND-1

GND-1

DC COM

Technical Specifications - 1756-IB16


DC INPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1756-IB16 16 (8 points/group) 12/24V DC sink 10...31.2V DC 0, 1, or 2 ms 1 ms + filter 0, 1, 2, 9, or 18 ms 2 ms + filter 100 mA 2 mA 5.1 W @ 60 C 17.39 BTU/hr 5V 1.5 mA 2 mA @ 10V DC 10 mA @ 31.2V DC

Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max

Publication 1756-TD002A-EN-E - May 2009

15

1756 ControlLogix I/O Modules

Attribute Inrush current, max Input impedance, max Cyclic update time Isolation voltage

1756-IB16 250 mA peak (decaying to < 37% in 22 ms, without activation) 3.12 k @ 31.2V DC 100 s...750 ms 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IB16
Certification(1) c-UL-us 1756-IB16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

16

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IB16D
ControlLogix DC (10...30V) diagnostic input module
Simplified Schematic Input +5V IN-0 ControlLogix Backplane Interface Display
Daisy Chain to Other RTBs GND-0 Group 0 GND-0 GND-0 GND-0 GND-1 GND-1 GND-1 GND-1 1756-IB16D
2 4 6 8 1 3 5 7

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used Group 3 14.3 k, 1/4 W 2% Resistor Group 14.3 k, 1/4 W 2% Resistor Group

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

GND-0 GND

Group 1

Group

GND-2 Group 2 GND-2 GND-2 GND-2 GND-3 GND-3 Group 3 GND-3 GND-3 GND-3 Not Used

Open Wire

DC COM

Diagnostics - 1756-IB16D
Attribute Open wire Timestamp of diagnostics 1756-IB16D Off-state leakage current 1.2 mA min 1 ms

Technical Specifications - 1756-IB16D


DC INPUT
Attribute
ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7 O K ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15 DIAGNOSTIC

1756-IB16D 16 diagnostic (4 points/group) 12/24V DC sink 10...30V DC 0, 1, or 2 ms 1 ms + filter 0, 1, 2, 9, or 18 ms 4 ms + filter 150 mA 3 mA 5.8 W @ 60 C 19.78 BTU/hr 5V

Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max

Publication 1756-TD002A-EN-E - May 2009

17

1756 ControlLogix I/O Modules

Attribute Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Isolation voltage

1756-IB16D 1.5 mA 2 mA @ 10V DC 13 mA @ 30V DC 250 mA 2.31 k @ 30V DC 200 s...750 ms 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IB16D
Certifications(1) c-UL-us 1756-IB16D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

18

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IB16I
ControlLogix DC (10...30V) isolated input module
Simplified Schematic +5V IN-0 GND-0 GND ControlLogix Display Backplane Interface
Isolated Wiring DC-0 (-) DC-1 (-) GND-0 GND-1 GND-2 Source Input Wiring DC-5 (-) DC-6 (-) GND-3 GND-4
10

1756-IB16I DC-0 (+) DC-1 (+)

1 3 5 7 9

2 4 6 8

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used

+ +

GND-5 GND-6 GND-7 GND-8 GND-9 GND-10 GND-11 GND-12 GND-13 GND-14 GND-15

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

(+) DC-5 (+) (+) DC-6 (+)

Jumper Bar (Cut to Length)

Nonisolated wWi ring

Sink Input Wiring

DC (-)

GND-15 Not Used

DC (+)

Daisy Chain to Other RTBs

Technical Specifications 1756-IB16I


DC INPUT
Attribute Inputs
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

1756-IB16I 16 individually isolated 12/24V DC sink/source 10...30V DC 0, 1, or 2 ms 1 ms + filter 0, 1, 2, 9, or 18 ms 4 ms + filter 100 mA 3 mA 5 W @ 60 C 17.05 BTU/hr 5V 1.5 mA 2 mA @ 10 V DC 10 mA @ 30V DC 250 mA peak (decaying to < 37% in 22 ms, without activation)

Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max

Publication 1756-TD002A-EN-E - May 2009

19

1756 ControlLogix I/O Modules

Attribute Input impedance, max Cyclic update time Isolation voltage

1756-IB16I 3 k @ 30V DC 100 s...750 ms 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IB16I
Certification(1) c-UL-us 1756-IB16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

20

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IB16ISOE
ControlLogix DC (10...55V) sequence of events input module
Simplified Schematic Electronic Current Limit Circuit +5V IN-0
Isolated Wiring GND-0 GND-1 GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 GND-6 DC-6 (-) GND-7 GND-8 Jumper Bar GND-9 Display (Cut to Length) GND-10 GND-11 Nonisolated GND-12 Wiring GND-13 GND-14 GND-15 GND-15 DC (-) Not Used DC-0 (-)
2 4 6 8 1 3 5 7

1756-IB16ISOE

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

GND-0 ControlLogix Backplane Interface

Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC - 6 ( + ) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)

Daisy Chain to Other RTBs

Technical Specifications - 1756-IB16ISOE


SOE INPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1756-IB16ISOE(1) 16 individually isolated, sequence of events 24/48V DC sink/source 10...55V DC 050 ms Hardware delay (10 s nominal/20 s max) + Firmware scan (up to 25 s) + Input filter time (user selectable time: 0ms...50ms) + ASIC delay (175 s - FIFO/625 s - Coordinated System Time per point) Hardware delay (25 s nominal/50 s max) + Firmware scan (up to 25 s) + Input filter time (user selectable time: 0ms...50ms) + ASIC delay (175 s - FIFO/625 s - Coordinated System Time per point) 320 mA 2 mA 5.5 W @ 60 C 17.22 BTU/hr 5V 1.5 mA 2.0 mA @ 9V DC 5.1 mA @ 4855V DC

Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on

Input delay, on to off

Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max

Publication 1756-TD002A-EN-E - May 2009

21

1756 ControlLogix I/O Modules

Attribute Input impedance, max Cyclic update time Isolation voltage Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating

1756-IB16ISOE(1) 10.8 k @ 55V DC 250 s...750 ms 250V continuous, inputs to system 125V continuous, channel to channel 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 1(3) Copper None (open-style)

(1) If you use 1756-IB16ISOE or 1756-IH16ISOE modules in a remote rack, you must use a 1756-SYNCH SynchLink module to coordinate system time. (2) (3)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IB16ISOE
Certification(1) c-UL-us 1756-IB16ISOE UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

22

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IB32
ControlLogix DC (10...31.2V) input module
Simplified Schematic +5V IN-0 GND-0 GND ControlLogix Backplane Interface Display
Group 0 Daisy Chain to Other RTBs IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 GND-0 IN-17 IN-19 IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 GND-1 1756-IB32
2 4 6 8 10 1 3 5 7 9

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Group 1

IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 GND-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 GND-1

Group 0

Group 1

DC COM

Diagnostics - 1756-IB32
Attribute Change of state Timestamp of diagnostics 1756-IB32 Software configurable 200 s

Technical Specifications - 1756-IB32


DC INPUT
ST 0 1 2 3 4 5 6 7

Attribute Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V

1756-IB32 32 (16 points/group) 12/24V DC sink 10...31.2V DC 0, 1, or 2 ms 380 s + filter 0, 1, 2, 9, or 18 ms 420 s + filter 120 mA 2 mA

ST 8 9 1 ST 6 2 ST 4 1 7 2 5

1 0 1 8 2 6

1 1 1 9 2 7

1 2 2 0 2 8

1 3 2 1 2 9

1 4 2 2 3 0

1 O 5 K 2 3 3 1

Publication 1756-TD002A-EN-E - May 2009

23

1756 ControlLogix I/O Modules

Attribute Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Isolation voltage

1756-IB32 6.2 W @ 60 C 21.1 BTU/hr @ 60 C 5V 1.5 mA 2 mA 5.5 mA 250 mA (decaying to < 37% in 22 ms, without activation) 5.67 k @ 31.2V DC 100 s...750 ms 250V (continuous), Reinforced Insulation Type between Input group to system 250V (continuous), Basic insulation type between Input group to Input group Routine tested at 1900V AC for 2 s, between Input group to Input group and Input group to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1 - on signal ports(2) Copper None (open-style)

Removable terminal block Slot width Module Location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

24

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-IB32
Certification(1) c-UL-us 1756-IB32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

25

1756 ControlLogix I/O Modules

1756-IC16
ControlLogix DC (30...60V) input module
1756-IC16

Simplified Schematic
IN-1

IN-0
4 3

IN-0 GND-0 GND

+5V
IN-3

IN-2
6 5

Group 0

IN-5
8 7

IN-4 IN-6
10 9

Group 0

IN-7 GND-0
12 11

ControlLogix Display Backplane Interface

GND-0 IN-8
14 13

IN-9 IN-11
16 15

IN-10 IN-11
18 17

Group 1

IN-13 IN-15
20 19

Group 1

IN-14 GND-1

GND-1

Daisy Chain to Other RTBs

DC COM

Technical Specifications - 1756-IC16


DC INPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1756-IC16 16 (8 points/group) 48V DC sink 30...55V DC @ 60 C 30...60V DC @ 55 C 0, 1, or 2 ms 1 ms + filter 0, 1, 2, 9, or 18 ms 4 ms + filter 100 mA 3 mA 5.2 W @ 60 C 17.73 BTU/hr 10V 1.5 mA 2 mA @ 30V DC

Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min

26

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute On-state current, max Inrush current, max Input impedance, max Cyclic update time Isolation voltage

1756-IC16 7 mA @ 60V DC 250 mA 8.57 k @ 60V DC 200 s...750 ms 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IC16
Certification(1) c-UL-us 1756-IC16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

27

1756 ControlLogix I/O Modules

1756-IF6CIS
ControlLogix sourcing current loop analog input module
1756-IF6CIS 2-wire Transmitter Connected to the Module and the Module Providing 24V DC Loop Power
2 1

1756-IF6CIS 2-wire Transmitter Connected to the Module and an External, User-provided Power Supply Providing 24V DC Loop Power
2 1

+ VOUT-0 2-wire Transmitter i RTN-0 VOUT-1

VOUT-1
4 3

VOUT-0
4 3

IN-1/I
6 5

IN-0/I

IN-1/I
6 5

IN-0/I RTN-0
8 7

RTN-1
8 7

RTN-1 VOUT-3 Shield Ground


10 9

24V DC +

2-wire Transmitter

VOUT-3
10 9

VOUT-2 IN-2/I
12 11

VOUT-2 IN-2/I
12 11

IN-3/I RTN-3
14 13

IN-3/I RTN-3
14 13

RTN-2 Not Used


16 15

RTN-2 Not Used


16 15

Shield Ground

Not Used VOUT-5


18 17

Not Used VOUT-5


18 17

VOUT-4 IN-4/I
20 19

VOUT-4 IN-4/I
20 19

IN-5/I RTN-5

IN-5/I RTN-5

RTN-4

RTN-4

Do not connect more than two wires to any single terminal. Place additional loop devices (e.g. strip chart recorders) at either A location in the current loop.

If separate power sources are used, do not exceed the specified isolation voltage. Do not connect more than two wires to any single terminal. Place additional loop devices (such as strip chart recorders) at either A location in the current loop.

28

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IF6CIS 4-wire Transmitter Connected to the Module and an External, User-provided Power Supply Providing 24V DC Loop Power
2 1

VOUT-1
4 3

VOUT-0 IN-0/I
6 5

IN-1/I RTN-1
8 7

+ 4-wire Transmitter

+ 24V DC

RTN-0 VOUT-2
10 9

VOUT-3 IN-3/I
12 11

IN-2/I RTN-2
14 13

RTN-3 Not Used


16 15

Shield Ground

Not Used VOUT-4


18 17

VOUT-5 IN-5/I
20 19

IN-4/I RTN-4

RTN-5

If separate power sources are used, do not exceed the specified isolation voltage. Do not connect more than two wires to any single terminal. Place additional loop devices (such as strip chart recorders) at either A location in the current loop.

Input Signal to User Count Conversion - 1756-IF6CIS


Range 020 mA Low Signal and User Counts 0 mA -32768 counts High Signal and User Counts 21.09376 mA 32767 counts

Technical Specifications - 1756-IF6CIS


ANALOG INPUT CAL OK
Attribute Inputs Input range Resolution Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation 1756-IF6CIS 6 individually isolated current sourcing 021 mA 16 bits 0.34 A/bit 250 mA 275 mA 5.1 W @ 60 C 17.4 BTU/hr

Publication 1756-TD002A-EN-E - May 2009

29

1756 ControlLogix I/O Modules

Attribute Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy 25 C Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min Isolation voltage

1756-IF6CIS 215 , approx Zero reading within 5 s 30V AC/DC with PTC and sense resistor 60 dB @ 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 3262 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 12 months 200 A/C 17 ppm/C, 35 ppm/C max 0.36 A/C, 0.74 A/C max 0.2% of range 25 ms min floating point 10 ms min integer 250V continuous Tested at 1900V DC for 60 s, channel to channel Tested at 3250V DC for 60 s, channels to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 2(3) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2) (3)

Notch filter dependent. Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

30

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-IF6CIS
Certification(1) c-UL-us 1756-IF6CIS UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

31

1756 ControlLogix I/O Modules

1756-IF6I
ControlLogix isolated voltage/current analog input module
1756-IF6I Current 2-wire
2 1

1756-IF6I Current 4-wire


2 1

IN-1/V
4 3

IN-0/V IN-0/I
6 5

+
2-wire Transmitter

IN-1/V
4 3

IN-0/V

IN-1/I RET-1
8 7

i A A

+
IN-0/I

IN-1/I
6 5

A A

4-wire Transmitter

RET-0 IN-2/V
10 9

RET-1
8 7

RET-0 IN-2/V
10 9

IN-3/V IN-3/I
12 11

IN-3/V IN-3/I
12 11

IN-2/I RET-2
14 13

IN-2/I RET-2
14 13

RET-3 Not Used


16 15

RET-3 Not Used


16 15

Shield Ground

Not Used IN-4/V


18 17

Not Used IN-4/V


18 17

IN-5/V IN-5/I IN-4/I


20 19

IN-5/V IN-5/I
20 19

IN-4/I RET-4

RET-5 RET-4

RET-5

Place additional loop devices (such as strip chart recorders) at either A location.

Place additional loop devices (such as strip chart recorders) at either A location.

32

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IF6I Voltage Voltage Input


2 1

IN-1/V
4 3

IN-0/V IN-0/I
6 5

+
User Analog Input Device

IN-1/I RET-1
8 7

RET-0 IN-2/V
10 9

Device External Power

IN-3/V IN-3/I
12 11

IN-2/I RET-2
14 13

RET-3 Not Used


16 15

Not Used IN-4/V


18 17

IN-5/V IN-5/I
20 19

IN-4/I RET-4

Shield Ground

RET-5

Do not connect more than 2 wires to any single terminal.

Input Signal to User Count Conversion - 1756-IF6I


Range 10V 010V 05V 020 mA Low Signal and User Counts -10.54688V -32768 counts 0V -32768 counts 0V -32768 counts 0 mA -32768 counts High Signal and User Counts 10.54688V 32767 counts 10.54688V 32767 counts 5.27344V 32767 counts 21.09376V 32767 counts

Publication 1756-TD002A-EN-E - May 2009

33

1756 ControlLogix I/O Modules

Technical Specifications - 1756-IF6I


ANALOG INPUT CAL OK
Attribute Inputs Input range 1756-IF6I 6 individually isolated 10.5V 010.5V 05.25V 021 mA 16 bits 10.5V: 343 V/bit 010.5V: 171 V/bit 05.25V: 86 V/bit 021 mA: 0.34 A/bit 250 mA 100 mA Voltage: 3.7 W Current: 4.3 W Voltage: 12.62 BTU/hr Current: 14.32 BTU/hr Voltage: > 10 M Current: 249 Positive full scale reading within 5 s Voltage: 120V AC/DC Current: 8V AC/DC (with on-board current resistor) 60 dB @ 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 15 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 6 months 2 V/C Voltage: 35 ppm/C, 80 ppm/C max Current: 45 ppm/C, 90 ppm/C max 0.54% of range 25 ms min floating point 10 ms min integer(1) 250V continuous Tested at 1700V DC for 1 s, channel to channel, channels to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 2(3)

Resolution

Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy 25 C Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min Isolation voltage

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category

34

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Wire type Enclosure type rating


(1) (2)

1756-IF6I Copper None (open-style)

Notch filter dependent. Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IF6I
Certification(1) c-UL-us 1756-IF6I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

35

1756 ControlLogix I/O Modules

1756-IF8
ControlLogix voltage/current analog input module
1756-IF8 Differential Current Channel 0 Channel 0 1756-IF8 Differential Voltage

i
A

IN-0 IN-1 IN-2 IN-3 RTN IN-4

2 4 6 8 10

1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used

IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used

2 4 6 8 10

1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Shield Ground Channel 3 Jumper Wires Shield Ground

Shield Ground Channel 3 2-wire Transmitter

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used

i
A

Use this table when wiring your module in differential mode.

Use this table when wiring your module in differential mode.

This channel
Channel 0 Channel 1 Channel 2 Channel 3

Uses these terminals


IN-0 (+), IN-1 (-), i RTN-0 IN-2 (+), IN-3 (-), i RTN-2 IN-4 (+), IN-5 (-), i RTN-4 IN-6 (+), IN-7 (-), i RTN-6

This channel
Channel 0 Channel 1 Channel 2 Channel 3

Uses these terminals


IN-0 (+), IN-1 (-) IN-2 (+), IN-3 (-) IN-4 (+), IN-5 (-) IN-6 (+), IN-7 (-)

All terminals marked RTN are connected internally. A 249-current loop resistor is located between IN-x and i RTN-x terminals. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. Do not connect more than two wires to any single terminal. IMPORTANT: When operating in 2 channel, High Speed mode, only use channels 0 and 2.

All terminals marked RTN are connected internally. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Terminals marked RTN or iRTN are not used for differential voltage wiring. Do not connect more than two wires to any single terminal. IMPORTANT: When operating in 2 channel, High Speed mode, only use channels 0 and 2.

36

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IF8 Single-ended Current Channel 0

1756-IF8 Single-ended Voltage

i
IN-0 IN-1 IN-2
2 4 6 8 10 1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Jumper Wires

Channel 0

+
IN-0
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used

Shield Ground Channel 5

IN-1 IN-2 IN-3

IN-3 RTN

Shield Ground Channel 1

i
2-wire Transmitter

IN-4 IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

RTN IN-4 IN-5 IN-6 IN-7 Not Used Not Used

Shield Ground

Not Used Not Used Not Used Not Used Not Used Not Used Not Used

All terminals marked RTN are connected internally. For current applications, all terminals marked iRTN must be wired to terminals marked RTN. A -49 current loop resistor is located between IN-x and i RTN-x terminals. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. Do not connect more than two wires to any single terminal.

All terminals marked RTN are connected internally. Terminals marked iRTN are not used for single-ended voltage wiring. Do not connect more than two wires to any single terminal.

Input Signal to User Count Conversion - 1756-IF8


Range 10V 010V 05V 020 mA Low Signal and User Counts -10.25V -32768 counts 0V -32768 counts 0V -32768 counts 0 mA -32768 counts High Signal and User Counts 10.25V 32767 counts 10.25V 32767 counts 5.125V 32767 counts 20.58V 32767 counts

Publication 1756-TD002A-EN-E - May 2009

37

1756 ControlLogix I/O Modules

Technical Specifications - 1756-IF8


ANALOG INPUT CAL OK
Input range Attribute Inputs 1756-IF8 8 single-ended 4 differential 2 high-speed differential 10.25V 0...10.25V 0...5.125V 020.5 mA 10.25V: 320 V/cnt (15 bits plus sign bipolar) 010.25V: 160 V/cnt (16 bits) 05.125V: 80 /V cnt (16 bits) 020.5mA: 0.32 A/cnt (16 bits) 150 mA 40 mA Voltage: 1.73 W Current: 2.33 W Voltage: 5.88 BTU/hr Current: 7.92 BTU/hr Voltage: >1 M Current: 249 Differential voltage: Positive full scale reading within 5 s Single-ended/diff. current: Negative full scale reading within 5 s Single-ended voltage: Even numbered channels go to positive full scale reading within 5 s, odd numbered channels go to negative full scale reading within 5 s Voltage: 30V DC Current: 8V DC >80 dB @ 50/60 Hz(1) >100 dB @ 50/60 Hz Voltage: Better than 0.05% of range Current: Better than 0.15% of range 12 months 45 V/C Voltage: 15 ppm/C Current: 20 ppm/C Voltage: 0.1% of range Current: 0.3% of range 8 pt single-ended (floating point): 16488 ms 4 pt differential (floating point): 8244 ms 2 pt differential (floating point): 5122 m(1) Tested at 2500V DC for 1 s, field-side to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2)

Resolution

Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Input impedance Open circuit detection time

Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Calibrated accuracy 25 C Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min

Isolation voltage Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size

38

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Wire category Wire type Enclosure type rating


(1) (2)

1756-IF8 2(3) Copper None (open-style)

Notch filter dependent. Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IF8
Certification(1) c-UL-us 1756-IF8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

39

1756 ControlLogix I/O Modules

1756-IF8H
ControlLogix voltage/current analog input module with HART protocol
1756-IF8H Current
+V IN0+
2-wire Current Input
2 Wire XMTR

Voltage Input

1756-IF8H Voltage
2 4 6 8 1 3 5 7 I RTN-0 NC I RTN-1 NC RTN I RTN-2 NC I RTN-3 NC I RTN-4 NC I RTN-5 NC RTN I RTN-6 NC I RTN-7 NC

-V
IN0+ IN0IN1+ 2 4 6 8 1 3 5 7

IN0IN1+

24V DC Power Supply

+ -

+-

I RTN-0 NC I RTN-1 NC RTN I RTN-2 NC I RTN-3 NC I RTN-4 NC I RTN-5 NC RTN I RTN-6 NC I RTN-7 NC

IN1RTN IN2+ IN2IN3+ IN3IN4+ IN4IN5+ IN5RTN IN6+ IN6IN7+ IN7-

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

4-wire Current Input

IN1RTN IN2+ IN2IN3+ IN3IN4+ IN4IN5+ IN5RTN IN6+ IN6IN7+ IN7-

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

24V DC Power Supply

+ + Wire + 4 XMTR - - -

Input Signal to User Count Conversion - 1756-IF8H


Range 10V 010V 05V 020 mA Low Signal and User Counts -10.25V -32768 counts 0V -32768 counts 0V -32768 counts 0 mA -32768 counts High Signal and User Counts 10.25V 32767 counts 10.25V 32767 counts 5.125V 32767 counts 20.58V 32767 counts

Technical Specifications - 1756-IF8H


ANALOG OUTPUT
Attribute 1756-IF8H 8 differential voltage or current 10V 0...5V 15V 0...10V 020 mA 420 mA 1621 bits 300 mA 70 mA Voltage: 3.21 W Current: 4.01 W Voltage: 11.0 BTU/hr Current: 13.7 BTU/hr

CAL OK HART

Inputs Input range

Resolution Current draw @ 5V Current draw @ 24V Power dissipation, max Thermal dissipation

40

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min Module HART scan time

1756-IF8H > 1 M voltage 250 current Positive full scale reading within 5 s Voltage: 30V DC Current: 8V DC > 80 dB @ 50/60 Hz > 100 dB @ 50/60 Hz Voltage: Better than 0.05% of range Current: Better than 0.15% of range 12 months 90 V/C Voltage: 10 ppm/C Current: 20 ppm/C Voltage: 0.1% of range Current: 0.3% of range 18...488 ms (filter dependent) Typically 1 s per HART channel enabled. Estimate 10 s if all 8 channels have HART enabled Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time 50 V (continuous), Basic Insulation Type Tested at 1500V AC for 60 s, I/O to backplane 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.25...2.5 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 2 - on signal ports(2) Copper None (open-style)

Isolation voltage Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

41

1756 ControlLogix I/O Modules

Certifications - 1756-IF8H
Certification(1) c-UL-us 1756-IF8H UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

42

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IF16
ControlLogix voltage/current analog input module
1756-IF16 Differential Current Channel 0 1756-IF16 Differential Voltage Channel 0 IN-0 IN-1 IN-2 Shield Ground Channel 3 2-wire Transmitter IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10 1 3 5 7 9

i
A i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15

IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15

2 4 6 8 10

1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15

Jumper Wires Shield Ground

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

i
A

Channel 3

Shield Ground

Use this table when wiring your module in differential mode.

Use this table when wiring your module in differential mode.

This channel
Channel 0 Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7

Uses these terminals


IN-0 (+), IN-1 (-), i RTN-0 IN-2 (+), IN-3 (-), i RTN-2 IN-4 (+), IN-5 (-), i RTN-4 IN-6 (+), IN-7 (-), i RTN-6 IN-8 (+), IN-9 (-), i RTN-8 IN-10 (+), IN-11 (-), i RTN-10 IN-12 (+), IN-13 (-), i RTN-12 IN-14 (+), IN-15 (-), i RTN-14

This channel
Channel 0 Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7

Uses these terminals


IN-0 (+), IN-1 (-) IN-2 (+), IN-3 (-) IN-4 (+), IN-5 (-) IN-6 (+), IN-7 (-) IN-8 (+), IN-9 (-) IN-10 (+), IN-11 (-) IN-12 (+), IN-13 (-) IN-14 (+), IN-15 (-)

All terminals marked RTN are connected internally. A 249-current loop resistor is located between IN-x and i RTN-x terminals. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. Do not connect more than two wires to any single terminal. IMPORTANT: When operating in 4 channel, High Speed mode, only use channels 0, 2, 4 and 6.

All terminals marked RTN are connected internally. If multiple (+) or multiple (-) terminals are tied together, conne that tie point to a RTN terminal to maintain the modules accuracy. Terminals marked RTN or iRTN are not used for differential voltage wiring. Do not connect more than two wires to any single terminal. IMPORTANT: When operating in 4 channel, High Speed mode, only us channels 0, 2, 4 and 6.

Publication 1756-TD002A-EN-E - May 2009

43

1756 ControlLogix I/O Modules

1756-IF16 Single-ended Current

1756-IF16 Single-ended Voltage

i
IN-0 IN-1 IN-2 Shield Ground 2-wire Transmitter IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10 1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15 Jumper Wires Shield Ground

IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15

2 4 6 8 10

1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15

i
A

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Shield Ground

All terminals marked RTN are connected internally. For current applications, all terminals marked iRTN must be wired to terminals marked RTN. A 249-current loop resistor is located between IN-x and i RTN-x terminals. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. Do not connect more than two wires to any single terminal.

All terminals marked RTN are connected internally. Terminals marked iRTN are not used for single-ended voltage wiring. Do not connect more than two wires to any single terminal.

Input Signal to User Count Conversion - 1756-IF16


Range 10V 010V 05V 020 mA Low Signal and User Counts -10.25V -32768 counts 0V -32768 counts 0V -32768 counts 0 mA -32768 counts High Signal and User Counts 10.25V 32767 counts 10.25V 32767 counts 5.125V 32767 counts 20.58V 32767 counts

44

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

ANALOG INPUT CAL OK

Technical Specifications - 1756-IF16


Attribute Inputs Input range 1756-IF16 16 single ended, 8 differential or 4 differential (high speed) 10.5V 010.5V 05.25V 021 mA 16 bits 10.5V: 343 V/bit 010.5V: 171 V/bit 05.25V: 86 V/bit 021 mA: 0.34 A/bit 250 mA 100 mA Voltage: 3.7 W Current: 4.3 W Voltage: 12.62 BTU/hr Current: 14.32 BTU/hr Voltage: >10 M Current: 249 Positive full scale reading within 5 s Voltage: 120V AC/DC Current: 8V AC/DC (with on-board current resistor) 60 dB @ 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 15 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 6 months 2 V/C Voltage: 35 ppm/C, 80 ppm/C max Current: 45 ppm/C, 90 ppm/C max 0.54% of range 25 ms min floating point 10 ms min integer(1) 250V continuous Tested at 1700V DC for 1 s, channel to channel, channels to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2)

HART
Resolution

Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy 25 C Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min Isolation voltage

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size

Publication 1756-TD002A-EN-E - May 2009

45

1756 ControlLogix I/O Modules

Attribute Wire category Wire type Enclosure type rating


(1) (2) (3)

1756-IF16 2(3) Copper None (open-style)

Notch filter dependent. Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IF16
Certification(1) c-UL-us 1756-IF16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

46

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IF4FXOF2F
ControlLogix high-speed input/output analog module
1756-IF4FXOF2F Current
(-) i

1756-IF4FXOF2F Voltage (+) (+) User Analog Input Device (-) Shield Ground +IN-1/V IN-1/I -IN-1 +IN-3/V IN-3/I -IN-3 Not Used Not Used V OUT-1 I OUT-1 RTN-1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used

(+)

2-wire A Transmitter
A

+IN-1/V IN-1/I -IN-1 +IN-3/V IN-3/I -IN-3 Not Used Not Used V OUT-1 I OUT-1 RTN-1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used

2 4 6

1 3 5

+IN-0/V IN-0/I -IN-0 +IN-2/V IN-2/I -IN-2 Not Used Not Used V OUT-0 i I OUT-0 RTN-0 Not Used Not Used Not Used Not Used Not Used Not Used Not Used
A

2 4 6 8

1 3 5 7

+IN-0/V IN-0/I -IN-0 +IN-2/V IN-2/I -IN-2 Not Used Not Used V OUT-0 I OUT-0 RTN-0 Not Used (-) Not Used Not Used Not Used Not Used Not Used Not Used Shield Ground (+)

8 7 10 9 12 11 14 13 16 15 18 17 20 19 22 24 26 28 21 23 25 27

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Curren Output Load Shield Ground

30 29 32 31 34 33 36 35

A = Inline field device (such as a strip chart recorder or meter)

Technical Specifications - 1756-IF4FXOF2F


ANALOG INPUT ANALOG OUTPUT CAL OK
Attribute Inputs Outputs Current draw at 5.1V Current draw at 24V Power dissipation, max Thermal dissipation, max Isolation voltage 1756-IF4FXOF2 4 high-speed, sub-millisecond, differential 2 high-speed voltage or current 375 mA 100 mA Voltage: 4.3 W Current: 4.7 W Voltage: 14.66 BTU/hr Current: 16.02 BTU/hr 250V (continuous), Basic Insulation Type 125V (continuous), Reinforced Insulation Type Type Tested at 3100V DC for 60 s, I/O to system Routine Tested at 2121V DC for 2 s, I/O to system No isolation between channels 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B

Removable terminal block Slot width Module location Chassis Power supply, standard

Publication 1756-TD002A-EN-E - May 2009

47

1756 ControlLogix I/O Modules

Attribute Power supply, redundant Wire size Wire category Wire type North American temperature code IEC temperature code Enclosure type rating
(1) (2)

1756-IF4FXOF2 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 2(2) Copper T4A T4 None (open-style)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

1756-IF4FXOF2F Input and Output Specifications Attribute Number Output range Inputs 4 high-speed, sub-millisecond, differential 10.5V 010.5V 05.25V 021 mA Approx. 14 bits across 10V DC (21V total) 10V: 1.3 mV/bit, 14-bit effective 010.5V: 1.3 mV/bit, 13-bit effective 05.25V: 1.3 mV/bit, 12-bit effective Approx. 12 bits across 21 mA 021 mA: 5.25 A/bit Voltage: >1 M Current: 249 Positive full-scale reading within 1 s Voltage: 30V DC Current: 8V AC/DC 0.05% of range immediately after calibration Better than 0.1% of range within calibration interval 12 months Voltage: 25 ppm/C max Current: 35 ppm/C max 0.2% of range 300 s min(1) 50 V/ C 1 A/ C Voltage: 25 ppm/C max Current: 50 ppm/C max Voltage: 0.2% of range Current: 0.3% of range Outputs 2 high-speed voltage or current 10.4V 021 mA

Resolution

13 bits across 21 mA = 2.8 A/bit 14 bits across 21.8V = 1.3 mV/bit

Impedance Open circuit detection Overvoltage protection Short circuit protection Drive capability Settling time Calibrated accuracy @ 25 C Calibration interval Offset drift Gain drift with temperature Module error Module scan time
(1)

Current output only (Output must be set to >0.1 mA) 24V DC Electronically current limited to 21 mA or less Voltage: >2000 Current: 0750 < 2 ms to 95% of final value with resistive loads

300 s min for 1756-IF4FXOF2F, Series B, firmware revision 3.x or greater. 400 s min for 1756-IF4FXOF2F, Series A, firmware revision 1.x.

48

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-IF4FXOF2F
Certification(1) c-UL-us 1756-IF4FXOF2 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

49

1756 ControlLogix I/O Modules

1756-IG16
ControlLogix TTL input module
Standard Wiring
1756-IG16
DC
2
2 1

CE Compliant Wiring
1756-IG16
1

I/O Wire

IN-1
IN-0
4 3

IN-0 IN-2
6 5

IN-1
4 3

IN-3 IN-5
8 7

5V DC

IN-3
6 5

IN-2 IN-4
8 7

IN-4 IN-6
10 9

IN-5 IN-7
10 9

I/O Wire

+
TTL Input Device

IN-6
DC COM 0
12 11

DC Power Wire

IN-7 DC-0(+)
12 11

DC COM 0

+ DC

DC-0(+) IN-9
14 13

IN-9
IN-8 IN-10
5V DC Power
14 13

IN-8 IN-10
16 15

IN-11 IN-13
18 17

IN-11
16 15

IN-12 IN-14
20 19

IN-13
18 17

IN-12 IN-14
20 19

Capacitor 0.01 F Typical (See notes below.)

IN-15 DC-1(+)

IN-15 DC-1(+)

DC COM 1

DC COM 1

Simplified Schematic
+5 DC 1.5 K IN 1K 74HCT14 560

1.5 K IN 1K 74HCT14 560

DC COM

Low to True Format - 1756-IG16


-0.20.8V = Input guaranteed to be in on-state 0.82.0V = Input state not guaranteed 2.05.5V = Input guaranteed to be in off-state

50

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Technical Specifications - 1756-IG16


DC INPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1756-IG16 16 (8 points/group) 5V DC TTL source (Low=True)(1) 4.5...5.5V DC 50 mV P-P ripple max 0, 1, or 2 ms 450 s + filter 0, 1, 2, 9, or 18 ms 700 s + filter 110 mA 2 mA 1.4 W @ 60 C 4.8 BTU/hr @ 60 C 2V 4.1 mA 3.7 mA @ 5V DC 4.1 mA @ 5V DC 1.4 k min 1.5 k typical 100 s...750 ms 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 2(3) Copper None (open-style)

Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Input impedance, max Cyclic update time Isolation voltage

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

TTL inputs are inverted (-0.2 to +0.8 = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic. Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

(3) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

51

1756 ControlLogix I/O Modules

Certifications - 1756-IG16
Certification(1) c-UL-us 1756-IG16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick
(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

52

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IH16I
ControlLogix DC (90...146V) isolated input module
1756-IH16I

Simplified Schematic +5V IN-0 GND-0 GND ControlLogix Display Backplane Interface
DC-7 (-) Jumper Bar (Cut to Length) DC-0 (-) Isolated Wiring DC-3 (-) GND-0 GND-1 GND-2 GND-3 GND-4 GND-5 GND-6 GND-7 GND-8 GND-9 GND-10 GND-11 GND-12 GND-13 GND-14 GND-15 GND-15 Not Used
2 4 6 8 1 3 5 7

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Ysed

DC-0 (+)

DC-3 (+)

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

D C-7 (+ )

Nonisolated Wiring

DC (-)

DC (+)

Daisy Chain to Other RTBs

Technical Specifications - 1756-IH16I


DC INPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1756-IH16I 16 individually isolated 125V DC sink/source 90...146V DC(1) 0, 1, or 2 ms 2 ms + filter 0, 1, 2, 9, or 18 ms 6 ms + filter 125 mA 3 mA 5 W @ 60 C 17.05 BTU/hr 20V DC 0.8 mA 1 mA @ 90V DC 3 mA @ 146V DC 250 mA 48.67 k @ 146V DC 200 s...750 ms

Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time

Publication 1756-TD002A-EN-E - May 2009

53

1756 ControlLogix I/O Modules

Attribute Isolation voltage

1756-IH16I 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 1(3) Copper None (open-style)

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

90...146V DC @ 50C,12 channels on 90...132V DC @ 55C, 14 channels on 90...125V DC @ 60C, 16 channels on 90...146V DC @ 30C, 16 channels on. Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) (3)

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IH16I
Certification(1) c-UL-us 1756-IH16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

54

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IH16ISOE
ControlLogix DC (90...140V) sequence of events input module
Simplified Schematic +5V IN-0
1756-IH16ISOE

Isolated Wiring GND-0 GND-1 GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 GND-6 DC-6 (-) GND-7 GND-8 Display Jumper Bar GND-9 (Cut to Length) GND-10 GND-11 Nonisolated GND-12 Wiring GND-13 GND-14 GND-15 GND-15 DC (-) Not Used DC-0 (-)
2 4 6 8 1 3 5 7

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

GND-0

ControlLogix Backplane Interface

Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC - 6 ( + ) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)

Daisy Chain to Other RTBs

Technical Specifications - 1756-IH16ISOE


SOE INPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1756-IH16ISOE(1) 16 individually isolated, sequence of events 125V DC sink/source 90...140V DC 050 ms 20 s 0...50 ms 75 s 275 mA 2 mA 5.5 W @ 60 C 17.22 BTU/hr 20V 0.3 mA 1.15 mA @ 90V DC 1.85 mA @ 140V DC 74.8 k 200 s...750 ms 250V continuous, channel to channel, channels to system 1756-TBCH 1756-TBS6H

Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Input impedance, max Cyclic update time Isolation voltage Removable terminal block

Publication 1756-TD002A-EN-E - May 2009

55

1756 ControlLogix I/O Modules

Attribute Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating

1756-IH16ISOE(1) 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 1(3) Copper None (open-style)

(1) If you use 1756-IB16ISOE or 1756-IH16ISOE modules in a remote rack, you must use a 1756-SYNCH SynchLink module to coordinate system time. (2) (3)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IH16ISOE
Certification(1) c-UL-us 1756-IH16ISOE UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick
(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

56

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IM16I
ControlLogix AC (159...265V) input module
Simplified Schematic
Isolated Wiring 1756-IM16I

IN-O L2-0

+5V

L2-0 L2-2 L2-4

L2-0 L2-1 L2-2 L2-3 L2-4 L2-5 L2-6 L2-7 L2-8 L2-9 L2-10 L2-11

2 4 6 8 10

1 3 5 7 9

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used L1

L1-0 L1-2 L1-4

GND ControlLogix Display Backplane Interface


Jumper Bar (Cut to Length)

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Nonisolated Wiring

L2-12 L2-13 L2-14 L2-15 L2-15 Not Used

L2

Daisy Chain to Other RTBs

Technical Specifications - 1756-IM16I


AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

Attribute Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max

1756-IM16I 16 individually isolated 240V AC 159265V AC, 4763 Hz(1) 1 or 2 ms 10 ms + filter 9 or 18 ms 8 ms + filter 100 mA 3 mA 5.8 W @ 60 C 19.78 BTU/hr 40V 2.5 mA 5 mA @ 159V AC, 60 Hz 13 mA @ 265V AC, 60 Hz 250 mA 20.38 k @ 265V AC, 60 Hz

Publication 1756-TD002A-EN-E - May 2009

57

1756 ControlLogix I/O Modules

Attribute Cyclic update time Isolation voltage

1756-IM16I 200 s...750 ms 265V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 1(3) Copper None (open-style)

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

159265V AC, 4763Hz @ 30C all channels on 159265V AC, 4763Hz @ 40C 8 points on 159253V AC, 4763Hz @ 45C all channels on 159242V AC, 4763Hz @ 60C all channels on. Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) (3)

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IM16I
Certification(1) c-UL-us 1756-IM16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

58

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IN16
ControlLogix AC (10...30V) input module
Simplified Schematic IN-O L2-0 GND
L2 Group 0 IN-7
10 9

1756-IN16

+5V
IN-1 L1 IN-3

IN-0
4 3

IN-2
6 5

IN-5
8 7

IN-4 Group 0 IN-6 L2-0


12 11

ControlLogix Display Backplane Interface

L2-0 IN-9
14 13

IN-8 IN-10
16 15

IN-11 Group 1 IN-13


18 17

IN-12 IN-14
20 19

Group 1

IN-15 L2-1

L2-1

Daisy Chain to Other RTBs

Technical Specifications - 1756-IN16


AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

Attribute Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max

1756-IN16 16 (8 points/group) 24V AC 1030V AC, 4763 Hz 1 or 2 ms 10 ms + filter 9 or 18 ms 8 ms + filter 100 mA 2 mA 5.1 W @ 60 C 17.39 BTU/hr 5V 2.75 mA 5 mA @ 10V AC, 60 Hz 1.2 mA @ 30V AC, 60 Hz 250 mA

Publication 1756-TD002A-EN-E - May 2009

59

1756 ControlLogix I/O Modules

Attribute Input impedance, max Cyclic update time Isolation voltage

1756-IN16 2.5 k @ 30V AC, 60 Hz 200 s...750 ms 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IN16
Certification(1) c-UL-us 1756-IN16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

60

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IR6I
ControlLogix temperature sensing analog input module
1756-IR6I 3-wire RTD
2 1

IN-1/A
4 3

IN-0/A IN-0/B
6 5

IN-1/B RTN-1/C
8 7

RTN-0/C 3-wire RTD IN-2/A


10 9

IN-3/A IN-3/B
12 11

IN-2/B RTN-2/C
14 13

RTN-3/C Not used


16 15

Shield Ground

Not used IN-4/A


18 17

IN-5/A IN-5/B
20 19

IN-4/B RTN-4/C

RTN-5/C

Do not connect more than two wires to any single terminal. IMPORTANT: For 2-wire resistor applications including calibration, make sure IN-x/B and RTN-x/C are shorted together as shown.

Publication 1756-TD002A-EN-E - May 2009

61

1756 ControlLogix I/O Modules

1756-IR6I 4-wire RTD

IN-1/A
4 3

IN-0/A IN-0/B
6 5

IN-1/B RTN-1/C
8 7

RTN-0/C 4-wire RTD IN-2/A


10 9

IN-3/A IN-3/B
12 11

IN-2/B RTN-2/C
14 13

RTN-3/C Not used


16 15

Shield Ground

Not used IN-4/A


18 17

IN-5/A IN-5/B
20 19

IN-4/B RTN-4/C

RTN-5/C

Do not connect more than two wires to any single terminal. Wiring is exactly the same as the 3-wire RTD with one wire left open.

Input Signal to User Count Conversion - 1756-IR6I


Range 1...487 2...1000 4...2000 8...4020 Low Signal and User Counts 0.859068653 -32768 counts 2 -32768 counts 4 -32768 counts 8 -32768 counts High Signal and User Counts 507.862 32767 counts 1016.502 32767 counts 2033.780 32767 counts 4068.392 32767 counts

62

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Technical Specifications - 1756-IR6I


ANALOG INPUT CAL OK
Attribute Inputs Input range 1756-IR6I 6 individually isolated RTD 1487 21000 42000 84020 16 bits 1487 : 7.7 m/bit 21000 :15 m/bit 42000 :30 m/bit 84020 :60 m/bit 100, 200, 500, 1000 Platinum, alpha=385 100, 200, 500, 1000 Platinum, alpha=3916 120 Nickel, alpha=672 100, 120, 200, 500 Nickel, alpha=618 10 Copper 250 mA 125 mA 4.3 W 14.66 BTU/hr Negative full scale reading within 5 s with any combination of lost wires, except input terminal A alone. If input terminal A is lost by itself, the module reads a positive full scale reading within 5 s 24V AC/DC 60 dB at 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 15 Hz(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 6 months 10 M/C 50 ppm/C, 90 ppm/C max 0.54% of range 25 ms min floating point (ohms) 50 ms min floating point (temperature) 10 ms min integer (ohms)(1) 250V continuous Tested at 1700V DC for 1 s, channel to channel, channels to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2

Resolution

Sensors supported

Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Open circuit detection time

Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy @ 25 C Calibration interval Offset drift Gain drift with temperature Module error Module scan time

Isolation voltage

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant

Publication 1756-TD002A-EN-E - May 2009

63

1756 ControlLogix I/O Modules

Attribute Wire size Wire category Wire type Enclosure type rating
(1) (2) (3)

1756-IR6I 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 2(3) Copper None (open-style)

Notch filter dependent. Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IR6I
Certification(1) c-UL-us 1756-IR6I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

64

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IT6I
ControlLogix temperature sensing analog input module
1756-IT6I
2 1

+
IN-0

IN-0
4 3

Not Used Cold Junction Sensor Lug


6 5

Not Used RTN-0


8 7

RTN-1

IN-2 Thermocouple

IN-3
10 9

CJC+
12 11

Not Used

RTN-3
14 13

RTN-2 Not Used


16 15

CJC-

Wire

IN-5
18 17

IN-4 Not Used


20 19

Not Used RTN-5

RTN-4

Do not connect more than two wires to any single terminal. One CJC, part number 94238301, is shipped with the module. A replacement can be ordered as RP-94238301.

Input Signal to User Count Conversion - 1756-IT6I


Range -12...30 mV -12...78 mV Low Signal and User Counts -15.80323 mV -32768 counts -15.15836 mV -32768 counts High Signal and User Counts 31.396 mV 32767 counts 79.241 mV 32767 counts

Publication 1756-TD002A-EN-E - May 2009

65

1756 ControlLogix I/O Modules

Technical Specifications - 1756-IT6I


ANALOG INPUT CAL OK
Input range Resolution Attribute Inputs 1756-IT6I 6 individually isolated thermocouple 1 CJC -1278 mV -1230 mV 16 bits -12...78 mV: 1.4 V/bit -12...30 mV: 0.7 V/bit B, E, J, K, R, S, T, N, C 250 mA 125 mA 4.3 W 14.66 BTU/hr >10 M Positive full scale reading within 2 s 120V AC/DC 60 dB at 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 15 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 6 months 0.33.2 C, depending on channel 0.3 C 0.5 V/C 65 ppm/C, 80 ppm/C max 0.5% of range 25 ms min floating point (millivolt) 50 ms min floating point (temperature) 10 ms min integer (millivolt)(1) 250V continuous Tested at 1700V DC for 1 s, channel to channel, channels to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2)

Thermocouples Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy @ 25 C Calibration interval Local CJC sensor accuracy Remote CJC sensor accuracy Offset drift Gain drift with temperature Module error Module scan time

Isolation voltage

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size

66

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Wire category Wire type Enclosure type rating


(1) (2)

1756-IT6I 2(3) Copper None (open-style)

Notch filter dependent. Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IT6I
Certification(1) c-UL-us 1756-IF4FXOF2 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

67

1756 ControlLogix I/O Modules

1756-IT6I2
ControlLogix enhanced thermocouple analog input module
1756-IT6I Cold Junction Sensor

Wire

Spade Lug

Not Used CJC RTN-0 RTN-1 RTNRTN-3 RTNRTN-5 CJC Not used

Not Used CJC+

Thermocouple

IN-0 IN-1 IN-2

?
IN-3 IN-4 IN-5 CJC+ Not used

Wire

Cold Junction Sensor

Spade Lug

Do not connect more than two wires to any single terminal. Two CJCs, part number 94286501, are shipped with the module. Replacements can be ordered as RP-94286501.

Input Signal to User Count Conversion - 1756-IT6I2


Range -12...30 mV -12...78 mV Low Signal and User Counts -15.80323 mV -32768 counts -15.15836 mV -32768 counts High Signal and User Counts 31.396 mV 32767 counts 79.241 mV 32767 counts

Analog Input
CAL OK

Technical Specifications - 1756-IT6I2


Attribute Inputs Input range Resolution 1756-IT6I2 6 individually isolated thermocouple 2 CJC -1278 mV (1.4 V per bit) -1230 mV (0.7 V per bit high resolution range) 16 bits -12...78 mV: 1.4 V/bit -12...30 mV: 0.7 V/bit

68

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Thermocouples Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy @ 25 C Calibration interval Local CJC sensor accuracy Remote CJC sensor accuracy Offset drift Gain drift with temperature

1756-IT6I2 B, E, J, K, R, S, T, N, C, D, L (TXK/XK) 200 mA 150 mA 4.6 W 15.7 BTU/hr Positive full scale reading within 2 s 120V AC/DC 60 dB at 60 Hz(1) 160 dB min, tested at 600V AC/60 Hz applied with 100 differential resistance 15 Hz(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 12 months 0.3 C 0.3 C 0.5 V/C 15 ppm/C, 25 ppm/C max 1.4 V/C, 2.3 V/C max, -1278 mV 0.6 V/C, 1.1 V/C max, -1230 mV 0.15% of range 25 ms min floating point (millivolt) 50 ms min floating point (temperature) 10 ms min integer (millivolt)(1) 250V (continuous), Reinforced Insulation Type, user to system, tested at 3250V DC for 60 s 250V (continuous), Reinforced Insulation Type, group to group, tested at 1900V DC for 60 s 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.25...2.5 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 2(3) Copper None (open-style)

Module error Module scan time

Isolation voltage

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2) (3)

Notch filter dependent. Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

69

1756 ControlLogix I/O Modules

Certifications - 1756-IT6I2
Certification(1) c-UL-us 1756-IT6I2 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations TV Certified for Functional Safety: up to and including SIL 2

C-Tick FM TV
(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

70

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IV16
ControlLogix DC (10...30V) sourcing input module
1756-IV16

Simplified Schematic +5V DC-0+ IN-0 GND ControlLogix Display Backplane Interface
Group 0 IN-5 IN-1

IN-0
4 3

IN-3
6 5

IN-2 Group 0 IN-4


8 7

IN-7
10 9

IN-6 DC-0 +
12 11

DC-0 + IN-9
14 13

IN-8 IN-10
16 15

IN-11 Group 1 IN-13


18 17

IN-12 IN-14
20 19

Group 1

IN-15 DC-1 +

DC-1 +

+
Daisy Chain to Other RTBs

DC COM

Technical Specifications - 1756-IV16


DC INPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 1 1 21 1 5 K 0 11 3 41

1756-IV16 16 (8 points/group) 12/24V DC source 10...30V DC 0, 1, or 2 ms 1 ms + filter 0, 1, 2, 9, or 18 ms 2 ms + filter 110 mA 2 mA 5.41 W @ 60 C 18.47 BTU/hr 5V DC 1.5 mA 2 mA @ 10V DC 10 mA @ 30V DC 250 mA

Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max

Publication 1756-TD002A-EN-E - May 2009

71

1756 ControlLogix I/O Modules

Attribute Input impedance, max Cyclic update time Isolation voltage

1756-IV16 3.2 k @ 30V DC 100 s...750 ms 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block housing Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-IV16
Certification(1) c-UL-us 1756-IV16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

72

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-IV32
ControlLogix DC (10...30V) sourcing input module
Simplified Schematic +5V DC-0+
Group 0 IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 1756-IV32
2 4 6 8 10 1 3 5 7 9

IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 DC-0 (+) IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 DC-1 (+) Group 1 Group 0

IN-0

GND ControlLogix Display Backplane Interface


Daisy Chain to Other RTBs

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

IN-13 IN-15 DC-0 (+) IN-17 IN-19

Jumper Wire

IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 DC-1 (+)

Group 1

DC COM

Diagnostics - 1756-IV32
Attribute Change of state Timestamp of diagnostics 1756-IV32 Software configurable 200 s

DC INPUT
ST 0 1 2 1 ST 8 9 0 11 1 ST 6 7 8 22 2 ST 4 5 6 3 1 1 1 9 2 7 4 1 2 2 0 2 8 5 1 3 2 1 2 9 6 1 4 2 2 3 0 7 1 O 5 K 2 3 3 1

Technical Specifications - 1756-IV32


Attribute Inputs Voltage category Operating voltage range Digital filter, off to on Input delay, off to on Digital filter, on to off Input delay, on to off Current draw @ 5.1V Current draw @ 24V 1756-IV32 32 (16 points/group) 12/24V DC source 10...30V DC 0, 1, or 2 ms 1 ms + filter 0, 1, 2, 9, or 18 ms 2 ms + filter 120 mA 2 mA

Publication 1756-TD002A-EN-E - May 2009

73

1756 ControlLogix I/O Modules

Attribute Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Isolation voltage

1756-IV32 4.1 W @ 60 C 14 BTU/hr @ 60 C 5V 1.5 mA 2 mA 3.5 mA 250 mA (decaying to <37% in 22 ms, without activation) 8.6 k @ 30V DC 100 s...750 ms 250V (continuous), Reinforced Insulation Type between Input group to system 250V (continuous), Basic insulation type between Input group to Input group Routine tested at 1900V AC for 2 s, between Input group to Input group and Input group to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1 - on signal ports(2) Copper None (open-style)

Removable terminal block Slot width Module Location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

74

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-IV32
Certification(1) c-UL-us 1756-IV32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

75

1756 ControlLogix I/O Modules

1756-OA8
ControlLogix AC (74...265V) output module
Simplified Schematic +5V L1-0
2 1

1756-OA8

L1-0
4 3

OUT-0 OUT-1
6 5

L1-0

OUT-0 ControlLogix Backplane Interface Display Surge Current Chart

Group 0

L1-0
8 7

OUT-2 OUT-3
10 9

Group 0

L1-0 L1-0
12 11

Not used OUT-4


14 13

L1-1

20 A Current

Surge
L1-1 Group 1 L1-1

OUT-5
16 15

OUT-6
18 17

Group 1

L1-1
20 19

OUT-7 Not Used L2

2A 0 43 ms

L1-1

Time

Daisy Chain to Other RTBs L1

Technical Specifications - 1756-OA8


AC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O K

1756-OA8 8 (4 points/group) 120/240V AC 79265V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 200 mA 2 mA 5.1 W @ 60 C 17.39 BTU/hr 3 mA per point 1.5V peak @ 2 A 6V peak @ <50 mA 2 A @ 60 C (linear derating) 5 A @ 30 C (linear derating) 4 A @ 60 C (linear derating)

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max

76

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Surge current per point Load current, min Commutating voltage Isolation voltage

1756-OA8 20 A for 43 ms per point, repeatable every 2 s @ 60 C 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) 265V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system Zero crossing 60V peak 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 1(3) Copper None (open style)

Inhibit voltage, max Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

(3) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

77

1756 ControlLogix I/O Modules

Certifications - 1756-OA8
Certification(1) c-UL-us 1756-OA8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

78

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OA8D
ControlLogix AC (74...132V) diagnostic output module
Simplified Schematic ControlLogix Backplane Interface Diagnostic Control Block with Opto and Transformer Isolation
VAC Short Verify/ No Load GATE
Group 0
2

1756-OA8D
1

L1

Not Used
4 3

L2-0 OUT-0
6 5

L1-0 L1-0
8 7

OUT-1 OUT-2
10 9

Group 0

OUT L2
L1-0 L1-0

Display

Loss of Field Power


Daisy Chain to Other RTBs

OUT-3
12 11

Surge Current Chart 8A Current 5A 1A 500 mA 0 Time Surge @ 30 C Surge @ 60 C Continuous @ 30 C Continuous @ 60 C 43 ms

L1-1
14 13

OUT-4 OUT-5
16 15

L1-1 L1-1

OUT-6
18 17

Group 1 L1-1

Group 1 OUT-7

20

19

L1-1

L2-1 L2 Daisy Chain to Other RTBs L1

Diagnostics - 1756-OA8D
Attribute Short trip, min No load Output verification Pulse test Field power loss (zero cross) Time stamp of diagnostics 1756-OA8D 12 A for 500 s Off-state detection only On-state detection only Configurable maximum width and max time delay from zero cross Detects at 25V peak min (firmware phase locked loop) 1 ms

Technical Specifications - 1756-OA8D


AC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O K FLT 0 1 2 3 4 5 6 7

1756-OA8D 8 diagnostic, electronic fusing (4 points/group) 120V AC 74132V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz

Outputs Voltage category Operating voltage range

DIAGNOSTIC

Output delay, off to on

Publication 1756-TD002A-EN-E - May 2009

79

1756 ControlLogix I/O Modules

Attribute Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Isolation voltage

1756-OA8D 9.3 ms @ 60 Hz 11 ms @ 50 Hz 175 mA 250 mA 5.3 W @ 60 C 18.0 BTU/hr 3 mA per point 2.5V peak @ 0.5 A 3V peak @ 1 A 1 A @ 30 C (linear derating) 0.5 A @ 60 C (linear derating) 8 A @ 30 C (linear derating) 4 A @ 60 C (linear derating) 8 A for 43 ms per point, repeatable every 2 s @ 30 C 5 A for 43 ms per point, repeatable every 1 s @ 60 C 10 mA per point 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system Zero crossing 25V peak 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open style)

Inhibit voltage, max Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

80

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OA8D
Certification(1) c-UL-us 1756-OA8D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

81

1756 ControlLogix I/O Modules

1756-OA8E
ControlLogix AC (74...132V) electronically-fused output module
Simplified Schematic ControlLogix Backplane Interface Opto and Transformer Isolation
VAC Short GATE
L1-0
6 5 2

1756-OA8E
1

L1

Not Used
4 3

L2-0 OUT-0 OUT-1


8 7

OUT L2 Display Loss of Field Power

Group 0

L1-0 L1-0
10 9

Group 0

OUT-2 OUT-3
12 11

L1-0 Daisy Chain to Other RTBs L1-1


14 13

Surge Current Chart 20 A Current Surge

OUT-4 OUT-5
16 15

L1-1 L1-1
18 17

OUT-6 OUT-7
20 19

Group 1

L1-1 L1-1

Group 1

L2-1 L2

2A 0 43 ms
Daisy Chain to Other RTBs

Time

L1

Diagnostics - 1756-OA8E
Attribute Short trip, min Field power loss (zero cross) Time stamp of diagnostics 1756-OA8E >20 A for 100 ms Detects at 25V peak min (firmware phase locked loop) 1 ms

Technical Specifications - 1756-OA8E


Attribute 1756-OA8E 8 electronic fusing (4 points/group) 120V AC 74132V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 200 mA 250 mA

AC OUTPUT
ST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7K

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V

ELECTRONICALLY FUSED

82

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Power dissipation, max Thermal dissipation, max Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Isolation voltage

1756-OA8E 5.5 W @ 60 C 18.76 BTU/hr 3 mA per point 4V peak @ 2 A 2 A @ 60 C 8 A @ 30 C (linear derating) 4 A @ 60 C (linear derating) 20 A for 43 ms per point, repeatable every 2 s @ 60 C 10 mA per point 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system Zero crossing 25V peak 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open style)

Inhibit voltage, max Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

83

1756 ControlLogix I/O Modules

Certifications - 1756-OA8E
Certification(1) c-UL-us 1756-OA8E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

84

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OA16
ControlLogix AC (74...265V) output module
Simplified Schematic ControlLogix Backplane +5V Interface L1-0
OUT-1 Group 0 Daisy Chain to Other RTBs
4 3

1756-OA16
2 1

OUT-0 OUT-2
6 5

OUT-3 OUT-5
8 7

OUT-4 OUT-6
10 9

Group 0

(Fused per Group) Display

OUT-7 L1-0
12 11

L2-0 OUT-8
14 13

OUT-0 ControlLogix Backplane Interface


Group 1

OUT-9 OUT-11
16 15

OUT-10 OUT-12
18 17

OUT-13 OUT-15

Surge Current Chart Surge Per Group Per Group


L1
L1-1

Group 1

L1 OUT-14
L2-1

20

19

20 A Current 5A 2A 500 mA 0

L2

43 ms Time

Diagnostics - 1756-OA16
Attribute Time stamp of diagnostics Fuse blown 1756-OA16 1 ms 1 fuse and indicator/group

Technical Specifications - 1756-OA16


AC OUTPUT
ST 0 1 2 3 4 5 6 7 FUSE ST 8 9 10 11 12 13 14 15 FUSE O K

Attribute Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off

1756-OA16 16 mechanically fused/group (8 points/group) 120/240V AC 74265V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz

Publication 1756-TD002A-EN-E - May 2009

85

1756 ControlLogix I/O Modules

Attribute Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Commutating voltage Isolation voltage

1756-OA16 400 mA 2 mA 6.5 W @ 60 C 22.17 BTU/hr 3 mA per point 1.5V @ 0.5 A 5.7V @ load current < 50 mA 0.5 A @ 60 C 4 A @ 60 C 5 A for 43 ms per point, repeatable every 2 s @ 60 C 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) 265V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system Zero crossing 60V peak 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 1(3) Copper None (open style)

Inhibit voltage, max Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) (3)

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

86

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OA16
Certification(1) c-UL-us 1756-OA16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

87

1756 ControlLogix I/O Modules

1756-OA16I
ControlLogix AC (74...265V) isolated output module
Simplified Schematic
1756-OA16I Isolated Wiring

+5V

L1-0

L1-0 L1-2 L1-4

L1-0 L1-1 L1-2 L1-3 L1-4 L1-5 L1-6 L1-7


10

1 3 5 7 9

2 4 6 8

OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used L2

L2-0 L2-2 L2-4

OUT-0 ControlLogix Backplane Interface Display Surge Current Chart 20 A Current


Nonisolated Wiring

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Jumper Bar (Cut to Length)

L1-8 L1-9 L1-10 L1-11 L1-12 L1-13 L1-14 L1-15

L1

2A 1A 0 Time

Continuous @ 30C Continuous @ 60C 43 ms

L1-15 Not Used

Daisy Chain to Other RTBs

Technical Specifications - 1756-OA16I


AC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

1756-OA16I 16 individually isolated 120/240V AC 74265V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 300 mA 2.5 mA 5.5 W @ 60 C 18.76 BTU/hr 3 mA per point 1.5V peak @ 2 A 6V peak @ load current < 50 mA 2 A @ 30 C (linear derating) 1 A @ 60 C (linear derating)

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current, max On-state voltage drop, max Current per point, max

88

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Current per module, max Surge current per point Load current, min Commutating voltage Isolation voltage

1756-OA16I 5 A @ 30 C (linear derating) 4 A @ 60 C (linear derating) 20 A for 43 ms per point, repeatable every 2 s @ 60 C 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) 265V continuous Tested at 2546V DC for 1 s, channel to channel, I/O to system Zero crossing 60V peak 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 1(3) Copper None (open style)

Inhibit voltage, max Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

(3) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

89

1756 ControlLogix I/O Modules

Certifications - 1756-OA16I
Certification(1) c-UL-us 1756-OA16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

90

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB8
ControlLogix DC (10...30V) output module
Simplified Schematic +5V OUT-0
Group 0 1756-OB8
2 1

DC-0(+)

Daisy Chain to Other RTBs DC-0 (+)


4

OUT-0
3

DC-0 (+)
6 5

OUT-1 OUT-2
8 7

Group 0

DC-0 (+)

ControlLogix Backplane Interface Display

RTN OUT-0

DC-0 (+)
10 9

OUT-3 RTN OUT-0


12 11

RTN OUT-0

Surge Current Chart


DC-1 (+)

4A Current

Surge
DC-1 (+) Group 1

OUT-4
14 13

OUT-5
16 15

Group 1 OUT-6

Continuous @ 60o C 2A

DC-1 (+)
18 17

DC-1 (+)
20 19

OUT-7 RTN OUT-1

RTN OUT-1

0 Time

10 ms
Daisy Chain to Other RTBs

DC COM

Technical Specifications - 1756-OB8


DC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O K

1756-OB8 8 electronically fused, individually isolated 12/24V DC source 10...30V DC 1 ms 2 ms 250 mA 2 mA 4.7 W @ 60 C 16.03 BTU/hr 1 mA per point 1.2V DC @ 2A 2 A @ 60 C 16 A @ 55 C (linear derating) 10 A @ 60 C 4 A for 10 ms per point, repeatable every 2 s

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point

Publication 1756-TD002A-EN-E - May 2009

91

1756 ControlLogix I/O Modules

Attribute Load current, min Isolation voltage

1756-OB8 3 mA per point 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB8
Certification(1) c-UL-us 1756-OB8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

92

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB8EI
ControlLogix DC (10...30V) electronically-fused, isolated output module
1756-OB8EI

+5V

Simplified Schematic DC-0(+)


Isolated Wiring + DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1
1 3 5 7 10 9 2 4 6 8

OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used

OUT-0 OUT-0 Display ControlLogix Backplane Interface Output Device RTN OUT-0
Nonisolated Wiring

DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not Used Not Used

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Surge Current Chart 4A Current Surge

Daisy Chain to Other RTBs

Daisy Chain to Other RTBs

2A

Continuous @ 60o C

0 Time

10 ms

DC COM

Diagnostics - 1756-OB8EI
Attribute Short trip Timestamp of diagnostics 1756-OB8EI > 4.5 A for 500 s max (output on, then short) > 4.5 A for 1.5 ms max (output on into short) 1 ms

Technical Specifications - 1756-OB8EI


DC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7 K

1756-OB8EI 8 individually isolated 12/24V DC source 10...30V DC 1 ms 2 ms 165 mA 2 mA

Outputs Voltage category Operating voltage range

ELECTRONICALLY FUSED

Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V

Publication 1756-TD002A-EN-E - May 2009

93

1756 ControlLogix I/O Modules

Attribute Power dissipation, max Thermal dissipation, max Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Isolation voltage

1756-OB8EI 4.6W A @ 60 C 15.70 BTU/hr 0.5 mA per point 0.5V DC @ 2 A 2 A @ 60 C 16 A @ 60 C 4 A for 10 ms each, repeatable every 1 s @ 60 C 2 mA 250V user to backplane, Reinforced Insulation Type 250V channel to channel, Basic Insulation Type Tested to withstand 1900V DC for 2 s user to backplane Tested to withstand 1900V DC for 2 s channel to channel 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.25...2.5 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

94

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OB8EI
Certification(1) c-UL-us 1756-OB8EI UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

95

1756 ControlLogix I/O Modules

1756-OB8I
ControlLogix DC (10...30V) isolated output module
+5V Simplified Schematic DC-0(+)
Isolated Wiring 1756-OBI

OUT-0 OUT-0 Display ControlLogix Backplane Interface Output Device RTN OUT-0

Surge Current Chart 4A Current Surge


Nonisolated Wiring

Daisy Chain to Other RTBs

2A

Continuous @ 60 oC

Daisy Chain to Other RTBs

DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1 DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not Used Not Used

2 4 6 8

1 3 5 7

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used

0 Time

10 ms

Technical Specifications - 1756-OB8I


DC OUTPUT
Attribute 1756-OB8I 8 individually isolated 12/24V DC source 10...30V DC 1 ms 2 ms 165 mA 2 mA 4.6W A @ 60 C 15.70 BTU/hr 0.5 mA per point 0.5V DC @ 2 A 2 A @ 60 C 16 A @ 60 C 4 A for 10 ms each, repeatable every 1 s @ 60 C 2 mA

ST

01234567 O K

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min

96

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Isolation voltage

1756-OB8I 250V user to backplane, Reinforced Insulation Type 250V channel to channel, Basic Insulation Type Tested to withstand 1900V DC for 2 s user to backplane Tested to withstand 1900V DC for 2 s channel to channel 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.25...2.5 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB8I
Certification(1) c-UL-us 1756-OB8I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

97

1756 ControlLogix I/O Modules

1756-OB16D
ControlLogix DC (19.2...30V) diagnostic output module
Simplified schematic +5V +5V Short Circuit Detect Optoisolation +5V + DC
Daisy Chain to Other RTBs +DC-0 +DC-0 +DC-0 +DC-0 Group 0 +DC-0 +DC-0 +DC-0 GND-0 +DC-1 +DC-1 +DC-1 1756-OB16D

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35

OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used Group 1 Group 0

OUT ControlLogix Backplane Interface Display Output Verify/No Load Surge Current Chart 4A Current Surge
Group 1

RTN

+DC-1 +DC-1 +DC-1 +DC-1 GND-1 GND-1 Not Used Daisy Chain to Other RTBs

2A

Continuous @ 30 C Continuous @ 60 C

32
34 36

0 Time

10 ms

DC COM

Diagnostics - 1756-OB16D
Attribute Short trip No load Output verification Pulse test Time stamp of diagnostics 1756-OB16D 8 A for 180 ms 10 A for 120 ms Off-state detection only On-state detection only Configurable maximum pulse width 1 ms

Technical Specifications - 1756-OB16D


DC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7 K ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15 DIAGNOSTIC

1756-OB16D 16 diagnostic (8 points/group) 24V DC source 19.2...30V DC 1 ms 5 ms

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off

98

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Isolation voltage

1756-OB16D 250 mA 140 mA 3.3 W @ 60 C 11.25 BTU/hr 1 mA per point 1.2V DC @ 2A 2 A @ 30 C (linear derating) 1 A @ 60 C (linear derating) 8 A @ 30 C (linear derating) 4 A @ 60 C (linear derating) 4 A for 10 ms per point, repeatable every 1 s 3 mA per point 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Slot width
(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

99

1756 ControlLogix I/O Modules

Certifications - 1756-OB16D
Certification(1) c-UL-us 1756-OB16D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

100

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB16E
ControlLogix DC (10...31.2V) electronically-fused output module
Simplified Schematic Optoisolation
1756-OB16E

Display

DC-0(+)
OUT-1 OUT-3

OUT-0
4 3

Group 0

OUT-2
6 5

Group 0

OUT-0 ControlLogix Backplane Interface Electronic Fuse Circuitry Surge Current Chart RTN OUT-0

Daisy Chain to Other RTBs

OUT-5
8 7

OUT-4 OUT-6
10 9

OUT-7 DC-0(+)
12 11

RTN OUT-0 OUT-8


14 13

OUT-9 OUT-11
16 15

OUT-10 OUT-12
18 17

OUT-13

2A Current 1A 0

Surge Continuous @ 60o C

Group 1 OUT-15

Group 1 OUT-14

20

19

DC-1(+)

RTN OUT-1

10 ms Time

DC COM

Technical Specifications - 1756-OB16E


DC OUTPUT
ST 0 1 2 3 4 5 6 7 O FUSE K ST 8 9 10 11 12 13 14 15 FUSE ELECTRONICALLY FUSED

Attribute Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min

1756-OB16E 16 electronically fused (8 points/group) 12/24V DC source 10...31.2V DC 1 ms 1 ms 250 mA 2 mA 4.1 W @ 60 C 13.98 BTU/hr 1 mA per point 400 mV DC @ 1 A 1 A @ 60 C 8 A @ 60 C 2 A for 10 ms per point, repeatable every 2 s @ 60 C 3 mA per point

Publication 1756-TD002A-EN-E - May 2009

101

1756 ControlLogix I/O Modules

Attribute Isolation voltage

1756-OB16E 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Slot width
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB16E
Certification(1) c-UL-us 1756-OB16E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

102

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB16I
ControlLogix DC (10...30V) isolated output module
Simplified Schematic
Isolated Wiring 1756-OB16I Isolated Sourcing Output Wiring OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used DC(-) Nonisolated Sourcing Output Wiring DC-6 (-) DC-2 (-) DC-0 (-)

DC-0(+) +5V

DC-0 (+) DC-2 (+)

DC-0 (+) DC-1 (+) DC-2 (+) DC-3 (+) DC-4 (+)

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35

OUT-0 ControlLogix Backplane Interface Display

Sinking Output Wiring DC-6 (+) Jumper Bar (Cut to Length)

DC-5 (+) DC-6 (+) DC-7 (+) DC-8 (+) DC-9 (+) DC-10 (+) DC-11 (+) DC-12 (+) DC-13 (+) DC-14 (+) DC-15 (+)

Surge Current Chart 4A Current Surge

Nonisolated Wiring

2A

Continuous @ 30o C Continuous @ 60o C

DC(+)

DC-15 (+) Not Used

Daisy Chain to Other RTBs

0 Time

10 ms

Technical Specifications - 1756-OB16I


DC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1756-OB16I 16 individually isolated 12/24V DC sink/source 10...30V DC 1 ms 2 ms 350 mA 2.5 mA 3.6 W @ 60 C 12.28 BTU/hr 0.5 mA per point 1.2V DC @ 2 A 2 A @ 30 C 1 A @ 60 C 8 A @ 30 C 4 A @ 60 C 4 A for 10 ms per point, repeatable every 2 s 1 mA per point

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min

Publication 1756-TD002A-EN-E - May 2009

103

1756 ControlLogix I/O Modules

Attribute Isolation voltage

1756-OB16I 250V continuous Tested at 2546V DC for 1 s, channel to channel, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Slot width
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB16I
Certification(1) c-UL-us 1756-OB16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

104

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB16IS
ControlLogix DC (10...30V) scheduled, isolated output module
Simplified Schematic
Isolated Wiring 1756-OB16IS Isolated Sourcing Output Wiring DC-0 (-) DC-2 (-)

DC-0(+) +5V

OUT-0 ControlLogix Backplane Interface Display

Surge Current Chart 4A Current


Surge

2A

Continuous @ 30o C Continuous @ 60o C

DC-0 (+) DC-1 (+) DC-2 (+) DC-2 (+) DC-3 (+) DC-4 (+) Sinking Output Wiring DC-5 (+) DC-6 (+) DC-6 (+) + DC-7 (+) Jumper Bar DC-8 (+) (Cut to Length) DC-9 (+) DC-10 (+) DC-11 (+) Nonisolated DC-12 (+) Wiring DC-13 (+) DC-14 (+) DC-15 (+) DC(+) DC-15 (+) Not Used DC-0 (+)

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35

OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used

DC-6 (-)

Nonisolated Sourcing Output Wiring

DC(-)

Daisy Chain to Other RTBs

0 Time

10 ms

Technical Specifications - 1756-OB16IS


DC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1756-OB16IS 16 individually isolated, 8 scheduled 12/24V DC sink/source 10...30V DC 1 ms 2 ms 350 mA 2.5 mA 3.6 W @ 60 C 12.28 BTU/hr 0.5 mA per point 1.2V DC @ 2 A 2 A @ 30 C 1 A @ 60 C 8 A @ 30 C 4 A @ 60 C 4 A for 10 ms per point, repeatable every 2 s 1 mA per point

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min

Publication 1756-TD002A-EN-E - May 2009

105

1756 ControlLogix I/O Modules

Attribute Isolation voltage

1756-OB16IS 250V continuous Tested at 2546V DC for 1 s, channel to channel, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Slot width
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB16IS
Certification(1) c-UL-us 1756-OB16IS UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick
(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

106

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OB32
ControlLogix DC (10...31.2V) output module
1756-OB32

Simplified Schematic +5V

DC-0(+ OUT-0 RTN OUT-0


Group 0 OUT-1 OUT-3 OUT-5 OUT-7 OUT-9 OUT-11 OUT-13 OUT-15 DC-0(+) OUT-17 OUT-19 OUT-21 OUT-23 OUT-25 OUT-27 OUT-29 OUT-31 DC-1(+)
2 4 6 8 10 1 3 5 7 9

ControlLogix Backplane Interface Display

Daisy Chain to Other RTBs

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10 OUT-12 OUT-14 RTN OUT-0 OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26 OUT-28 OUT-30 RTN OUT-1

Group 0

Surge Current Chart Surge Continuous @ 60o C 0.5 A 0 Time 10 ms


Group 1

Group 1

1A Current

_
DC COM

Technical Specifications - 1756-OB32


DC OUTPUT
ST 0 1 2 1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6 3 4 11 12 12 90 22 78 5 6 11 3 4 22 1 2 23 9 0 7 1 O 5 K 2 3 3 1

Attribute Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min

1756-OB32 32 (16 points/group) 12/24V DC source 10...31.2V DC 1 ms 1 ms 300 mA 2 mA 4.8 W @ 60 C 16.37 BTU/hr 0.5 mA per point 200 mV DC @ 0.5 A 0.5 A @ 50 C (linear derating) 0.35 A @ 60 C 16 A @ 50 C (linear derating) 10 A @ 60 C 1 A for 10 ms per point, repeatable every 2 s @ 60 C 3 mA per point

Publication 1756-TD002A-EN-E - May 2009

107

1756 ControlLogix I/O Modules

Attribute Isolation voltage

1756-OB32 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style) c-UL-us, CE, CSA, C-Tick, FM, ATEX

Removable terminal block Slot width Module Location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating Certifications
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OB32
Certification(1) c-UL-us 1756-OB32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

108

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OC8
ControlLogix DC (30...60V) output module
Simplified Schematic +5V OUT-0
DC-0 (+) Group 0 DC-0 (+)
8 7

Daisy Chain to Other RTBs

1756-OC8
2 1

DC-0(+
DC-0 (+)
4 3

OUT-0 OUT-1
6 5

RTN OUT-0 ControlLogix Backplane Interface Display

Group 0 OUT-2 OUT-3

DC-0 (+)
10 9

RTN OUT-0
12 11

RTN OUT-0 OUT-4


14 13

DC-1(+)

Surge Current Chart 4A Current Surge


Group 1

DC-1(+)
16 15

OUT-5 Group 1 OUT-6


18 17

DC-1(+) DC-1(+)

OUT-7
20 19

2A

Continuous @ 60o C
RTN OUT-1

RTN OUT-1

0 Time

10 ms

DC COM

Daisy Chain to Other RTBs

Technical Specifications - 1756-OC8


DC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O K

1756-OC8 8 (4 points/group) 48V DC source 30...60V DC 1 ms 2 ms 165 mA 2 mA 4.9 W @ 60 C 16.71 BTU/hr 1 mA per point 2V DC @ 2 A 2 A @ 60 C 8 A @ 60 C 4 A for 10 ms per point, repeatable every 1 s @ 60 C 2 mA per point

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min

Publication 1756-TD002A-EN-E - May 2009

109

1756 ControlLogix I/O Modules

Attribute Isolation voltage

1756-OC8 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE. Maximum wire size requires extended housing, cat. no. 1756-TBE. Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

(2)

Certifications - 1756-OC8
Certification(1) c-UL-us 1756-OC8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

110

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OF4
ControlLogix voltage/current output analog module
1756-OF4 Current
2 1

1756-OF4 Voltage

Not Used
4 3

VOUT-0 IOUT-0
6 5

i
A Current Output Load

+
VOUT-0 IOUT-0

Not Used
4 3

Not Used RTN


8 7

Not Used
6 5

RTN VOUT-1
10 9

RTN
8 7

RTN VOUT-1
10 9

Not Used Not Used


12 11

Not Used Not Used Shield Ground


12 11

IOUT-1 VOUT-2
14 13

IOUT-1 VOUT-2
14 13

Shield Ground

Not Used Not Used


16 15

Not Used Not Used


16 15

IOUT-2 RTN
18 17

IOUT-2 RTN
18 17

RTN Not Used


20 19

RTN Not Used


20 19

VOUT-3 IOUT-3

VOUT-3 IOUT-3

Not Used

Not Used

Place additional loop devices (such as strip chart recorders) at the A location noted above. Do not connect more than two wires to any single terminal. All terminals marked RTN are connected internally.

Do not connect more than two wires to any single terminal. All terminals marked RTN are connected internally.

Input Signal to User Count Conversion - 1756-OF4


Range 0...20 mA 10V Low Signal and User Counts 0 mA -32768 counts -10.4336V -32768 counts High Signal and User Counts 21.2916 mA 32767 counts 10.4336V 32767 counts

Technical Specifications - 1756-OF4


ANALOG OUTPUT
Attribute 1756-OF4 8 voltage or current 10.4V 021 mA Voltage: 15 bits across 10.5V, 320 V/bit Current: 15 bits across 21mA, 650 nA/bit 150 mA

CAL OK

Outputs Output range Resolution Current draw @ 5.1V

Publication 1756-TD002A-EN-E - May 2009

111

1756 ControlLogix I/O Modules

Attribute Current draw @ 24V Power dissipation, max Thermal dissipation Open circuit detection Overvoltage protection Short circuit protection Drive capability Settling time Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module scan time Isolation voltage Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating Certifications
(1) (2)

1756-OF4 120 mA 3.25 W, 4 channel current 10.91 BTU/hr Current output only (Output must be set to >0.1 mA) 24V DC Electronically current limited to 21mA or less Voltage: >2000 Current: 0750 <2 ms to 95% of final value with resistive loads 421 mA, -10.410.4V: Better than 0.05% of range @ 25 C 12 months 50 V/ C 100 nA/C Voltage: 25 ppm/C, 520 V/C Current: 50 ppm/C, 1050 A/C Voltage: 0.15% of range Current: 0.3% of range 12 ms floating point 8 ms integer Tested at 2550V DC for 1 s, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 2(2) Copper None (open-style) c-UL-us, CE, CSA, C-Tick, FM, ATEX

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

112

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OF4
Certification(1) c-UL-us 1756-OF4 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

113

1756 ControlLogix I/O Modules

1756-OF6CI
ControlLogix current loop output analog module
1756-OF6CI 0...550
2 1

1756-OF6CI 551...1000
2 1

OUT-1
4 3

OUT-0

OUT-1

OUT-0
4 3

i
User Analog Output Device

i
User Analog Output Device

ALT-1
6 5

ALT-0 RTN-0
8 7

ALT-1
6 5

ALT-0 RTN-0
8 7

RTN-1 OUT-3
10 9

RTN-1 OUT-3
10 9

OUT-2

OUT-2

ALT-3
12 11

ALT-2 RTN-2
14 13

ALT-3
12 11

ALT-2 RTN-2
14 13

RTN-3 Not Used


16 15

RTN-3
Shield Ground

Not Used

Shield Ground Not Used

Not Used
16 15

OUT-5
18 17

OUT-4 ALT-4
20 19

OUT-5
18 17

OUT-4 ALT-4
20 19

ALT-5 RTN-5

ALT-5 RTN-5

RTN-4

RTN-4

Place additional devices anywhere in the loop. Do not connect more than two wires to any single terminal.

Place additional devices anywhere in the loop. Do not connect more than two wires to any single terminal.

Input Signal to User Count Conversion - 1756-OF6CI


Range 0...20 mA Low Signal and User Counts 0 mA -32768 counts High Signal and User Counts 21.074 mA 32767 counts

ANALOG OUTPUT CAL OK

Technical Specifications - 1756-OF6CI


Attribute Outputs Output range Resolution Current draw @ 5.1V 1756-OF6CI 6 individually isolated 021 mA 13 bits across 21 mA (2.7 A) 250 mA for 0...550 W loads terminated on OUTs and RTNs (Total backplane power in this range 6.7 W) 250 mA for 551...1000 W loads terminated on OUTs and ALTs (Total backplane power in this range 8.5 W)

114

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Current draw @ 24V

1756-OF6CI 225 mA for 0...550 W loads terminated on OUTs and RTNs (Total backplane power in this range 6.7 W) 300 mA for 551...1000 W loads terminated on OUTs and ALTs (Total backplane power in this range 8.5 W) 5.5 W (0550 loads) 6.1 W (5511000 loads) 18.76 BTU/hr (0550 loads) 20.80 BTU/hr (5511000 loads) None 24V DC Electronically current limited to 21mA or less 01000 Separate field terminations for 0550 and 5511000 < 2 ms to 95% of final value with resistive loads 421 mA: Better than 0.1% of range @ 25 C 6 months 1 A/C 60 ppm/C, 100 ppm/C max 0.6% of range 25 ms max floating point 10 ms max integer 250V continuous Tested at 1700V DC for 1 s, channel to channel, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 2(2) Copper None (open-style)

Power dissipation, max Thermal dissipation Open circuit detection Overvoltage protection Short circuit protection Drive capability

Settling time Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module scan time Isolation voltage

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

115

1756 ControlLogix I/O Modules

Certifications - 1756-OF6CI
Certification(1) c-UL-us 1756-OF6CI UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

116

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OF6VI
ControlLogix voltage loop output analog module
1756-OF6VI
2 1

+
OUT-0 Not Used User Analog Output Device

OUT-1
4 3 5

Not Used
6

RTN-1
8 7

RTN-0 OUT-2
10 9

OUT-3 Not Used


12 11

Not Used RTN-2


14 13

RTN-3 Not Used


16 15

Shield Ground Not Used OUT-4

OUT-5
18 17

Not Used
20 19

Not Used RTN-4

RTN-5

Place additional devices anywhere in the loop. Do not connect more than two wires to any single terminal.

Input Signal to User Count Conversion - 1756-OF6V


Range 10V Low Signal and User Counts -10.517V -32768 counts High Signal and User Counts 10.517V 32767 counts

Technical Specifications - 1756-OF6VI


ANALOG OUTPUT CAL OK
Attribute Outputs Output range Resolution Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation Output impedance Open circuit detection Overvoltage protection Short circuit protection Drive capability 1756-OF6VI 6 individually isolated 10.5V 14 bits across 21V (1.3 mV) (13 bits across 10.5V +sign bit) 250 mA 175 mA 4.85 W 16.54 BTU/hr <1 None 24V DC Electronically current limited > 1000 loads, 10 mA

Publication 1756-TD002A-EN-E - May 2009

117

1756 ControlLogix I/O Modules

Attribute Settling time Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module scan time Isolation voltage

1756-OF6VI < 2 ms to 95% of final value with resistive loads 421 mA: Better than 0.1% of range @ 25 C 6 months 60 V/ C 50 ppm/C, 80 ppm/C max 0.5% of range 25 ms floating point 10 ms integer 250V continuous Tested at 1700V DC for 1 s, channel to channel, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 2(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OF6VI
Certification(1) c-UL-us 1756-OF6VI UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

118

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OF8
ControlLogix voltage/current output analog module
1756-OF8 Current
2 1

1756-OF8 Voltage
2 1

VOUT-4
4 3

VOUT-0 IOUT-0
6 5

i
A

VOUT-4
4 3

VOUT-0 IOUT-0
6 5

IOUT-4 RTN
8 7

RTN VOUT-1
10 9

Current IOUT-4 Output RTN Load

RTN
8 7

VOUT-5 IOUT-5
12 11

VOUT-5
10 9

VOUT-1 Shield Ground IOUT-1


12 11

IOUT-1 Shield Ground VOUT-2


14 13

IOUT-5 VOUT-6
14 13

VOUT-6 IOUT-6
16 15

VOUT-2 IOUT-2
16 15

IOUT-2 RTN
18 17

IOUT-6 RTN
18 17

RTN VOUT-7
20 19

RTN VOUT-3
20 19

VOUT-3

VOUT-7
IOUT-3

IOUT-7

IOUT-7

IOUT-3

Place additional loop devices (such as strip chart recorders) at the A location noted above. Do not connect more than two wires to any single terminal. All terminals marked RTN are connected internally.

Do not connect more than two wires to any single terminal. All terminals marked RTN are connected internally.

Input Signal to User Count Conversion - 1756-OF8


Range 0...20 mA 10V Low Signal and User Counts 0 mA -32768 counts -10.4336V -32768 counts High Signal and User Counts 21.2916 mA 32767 counts 10.4336V 32767 counts

ANALOG OUTPUT CAL OK

Technical Specifications - 1756-OF8


Attribute Outputs Output range Resolution Current draw @ 5.1V 1756-OF8 8 voltage or current 10.4V 021 mA 15 bits across 21 mA - 650 nA/bit 15 bits across 10.4V - 320 V/bit 150 mA

Publication 1756-TD002A-EN-E - May 2009

119

1756 ControlLogix I/O Modules

Attribute Current draw @ 24V Power dissipation, max Thermal dissipation Open circuit detection Overvoltage protection Short circuit protection Drive capability Settling time Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module scan time Isolation voltage Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

1756-OF8 210 mA 4.92 W, 4 channel current 16.78 BTU/hr Current output only (Output must be set to >0.1 mA) 24V DC Electronically current limited to 21 mA or less Voltage: > 2000 Current: 0750 < 2 ms to 95% of final value with resistive loads 421 mA, -10.410.4V: Better than 0.05% of range @ 25 C 12 months 50 V/C 100 nA/C1 A/C Voltage: 25 ppm/C max Current: 50 ppm/C max Voltage: 0.15% of range Current: 0.3% of range 12 ms min floating point 8 ms min integer Tested at 2550V DC for 1 s, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 2(2) Copper None (open-style)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

120

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OF8
Certification(1) c-UL-us 1756-OF8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

121

1756 ControlLogix I/O Modules

1756-OF8H
ControlLogix voltage/current output analog module with HART protocol
1756-OF8H

Input Signal to User Count Conversion - 1756-OF8


Range 0...20 mA 10V Low Signal and User Counts 0 mA -32768 counts -10.4336V -32768 counts High Signal and User Counts 21.2916 mA 32767 counts 10.4336V 32767 counts

Technical Specifications - 1756-OF8H


ANALOG OUTPUT
Attribute 1756-OF8H 8 voltage or current 10.4V 020 mA 420 mA 1516 bits 200 mA 230 mA 4.92 W, 8 channel current 16.78 BTU/hr Voltage: >2 k @ 10.4V Current: 50750 drive Current output only (output must be set to < 0.1mA) 24V DC Voltage: > 2000 @ 10.4V Current: 50750 with short circuit survival current Voltage: 1 F Current: 10 H

CAL OK HART

Outputs Output range

Resolution Current draw @ 5V Current draw @ 24V Power dissipation, max Thermal dissipation Output impedance Open circuit detection time Overvoltage protection, max Drive capability Load reactance

122

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Settling time

1756-OF8H Current (no HART): < 23 ms to 95% with resistive loads Current (with HART): < 37 ms to 95% with resistive loads Voltage: < 8.5 ms to 95% with resistive loads Voltage: Better than 0.05% of range Current: Better than 0.15% of range 12 months 100 V/C typical 200 nA/C typical Voltage: 20 ppm/C Current: 35 ppm/C Voltage: 0.15% of range Current: 0.3% of range 12 ms floating point Typically 1 s per HART channel enabled Estimate 10 s if all 8 channels have HART enabled Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time 50 V (continuous), Basic Insulation Type Tested at 1500V AC for 60 s, I/O to backplane 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.25...2.5 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 2(2) Copper None (open-style)

Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module output scan time, min Module HART scan time

Isolation voltage Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

123

1756 ControlLogix I/O Modules

Certifications - 1756-OF8H
Certification(1) c-UL-us 1756-OF8H UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

124

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OG16
ControlLogix TTL output module
Standard Wiring
1756-OG16
DC +
2 1

CE Compliant Wiring
1756-OG16
DC Power Wire
2 1 3

OUT-1
4 3

OUT-0 OUT-2
6 5

5V DC Power

OUT-1
4

OUT-0 OUT-2

+5 V DC

OUT-3 OUT-5
8 7

OUT-3
6 5

OUT-4 OUT-6
10 9

OUT-5
8 7 9

OUT-4
10

OUT-7 + DC DC-0(+)
12 11

DC COM 0 OUT-8
14 13

I/O Wire

OUT-7 DC-0(+)
12 11

OUT-6 DC COM 0 OUT-8

OUT-9 OUT-11
16 15 17 19

OUT-10
18 20

TTL Output Device

OUT-9
14 13

OUT-11
Capacitor 0.01 F Typical (See notes below.)
16 15

OUT-10 OUT-12
18 17

OUT-13 OUT-15 DC-1(+)

OUT-12 OUT-14 DC COM 1

OUT-13 OUT-15
20 19

OUT-14 DC COM 1

DC-1(+)

Simplified Schematic
+5 DC 74AC14 OUT

74AC14 OUT

DC COM

Low to True Format - 1756-OG16


00.4V DC = Output guaranteed to be in on-state 0.44.5V DC = Output state not guaranteed 4.55.5V DC = Output guaranteed to be in off-state

Publication 1756-TD002A-EN-E - May 2009

125

1756 ControlLogix I/O Modules

Technical Specifications - 1756-OG16


DC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1756-OG16 16 (8 points/group) 5V DC TTL(1) 4.5...5.5V DC source 50 mV P-P ripple max 450 s 700 s 210 mA 2 mA 1.5 W @ 60 C 5.2 BTU/hr @ 60 C 0.1 mA per point 0.4V DC 24 mA @ 60 C 384 mA @ 60 C 0.15 mA per point 250V continuous, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 2(3) Copper None (open-style)

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Load current, min Isolation voltage Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Slot width
(1)

TTL outputs are inverted (0 to +0.4V dc = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic.
(2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(3)

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

126

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OG16
Certification(1) c-UL-us 1756-OG16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick
(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

127

1756 ControlLogix I/O Modules

1756-OH8I
ControlLogix DC (90...146V) isolated output module
Simplified Schematic +5V OUT-0 RTN OUT-0 ControlLogix Backplane Interface Display Surge Current Chart 4A Current Surge
Daisy chain to other RTBs Non-Isolated Wiring

DC-0

Isolated Wiring +

1756-OH8I

DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1 DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not used Not used

2 4 6 8 10

1 3 5 7 9

OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not used Not used

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Continuous @ 60o C 2A

Time

10 ms

Daisy chain to other RTBs

DC COM

Technical Specifications - 1756-OH8I


DC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O K

1756-OH8I 8 individually isolated 120V DC sink/source 90...146V DC 2 ms 2 ms 210 mA 2 mA 3.3 W @ 60 C 11.25 BTU/hr 1 mA per point 2V DC @ 2 A 2 A @ 60 C 8 A @ 60 C 4 A for 10 ms per point, repeatable every 1 s @ 60 C 2 mA per point

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min

128

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Isolation voltage

1756-OH8I 250V continuous Tested at 2546V DC for 1 s, I/O channel to channel, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Certifications - 1756-OH8I
Certification(1) c-UL-us 1756-OH8I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

129

1756 ControlLogix I/O Modules

1756-ON8
ControlLogix AC (10...30V) output module
Simplified Schematic +5V L1-0
L1-0
4 3

Daisy Chain to Other RTBs


2

1756-ON8
1

OUT-0 OUT-1
6 5

L1-0

OUT-0 ControlLogix Backplane Interface Display

Group 0

L1-0
8 7

OUT-2 OUT-3
10 9

Group 0

L1-0 L1-0

Not Used
12 11

Surge Current Chart


L1-1

OUT-4
14 13

20 A Current

Surge
L1-1 Group 1 L1-1

OUT-5
16 15

Group 1 OUT-6

18

17

L1-1

OUT-7
20 19

2A
L1-1

Not Used

L2

Time

43 ms
L1

Technical Specifications - 1756-ON8


AC OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O K

1756-ON8 8 (4 points/group) 24V AC 1030V AC, current >50 mA, 4763Hz 1630V AC, current <50 mA, 4763Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 200 mA 2 mA 5.1 W @ 60 C 17.39 BTU/hr 3 mA per point 1.5V peak @ 2 A 6V peak @ < 50 mA 2 A @ 60 C

Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current, max On-state voltage drop, max Current per point, max

130

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Current per module, max Surge current per point Load current, min Commutating voltage Isolation voltage

1756-ON8 5 A @ 30 C 4 A @ 60 C (linear derating) 20 A for 43 ms per point, repeatable every 2 s @ 60 C 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(2) 1(3) Copper None (open style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2)

(3) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

131

1756 ControlLogix I/O Modules

Certifications - 1756-ON8
Certification(1) c-UL-us 1756-ON8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

132

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OV16E
ControlLogix DC (10...30V) electronically-fused, sinking output module
Simplified Schematic Display Optoisolation
2

1756-OV16E
1

DC-0(+) OUT-0
Group 0

OUT-1
4 3

OUT-0 OUT-2
6 5

OUT-3 OUT-5
8 7

OUT-4 OUT-6
10 9

Group 0

ControlLogix Backplane Interface

Electronic Fuse Circuitry

RTN OUT-0

OUT-7 DC-0(+)
12 11

RTN OUT-0 OUT-8


14 13

OUT-9 OUT-11

OUT-10
16 15

Surge Current Chart


Group 1

OUT-13
18 17

OUT-12 OUT-14
20 19

Group 1

2A Current 1A 0

Surge Continuous @ 60o C

OUT-15 DC-1(+)

RTN OUT-1

10 ms Time
Daisy Chain to Other RTBs

DC COM Daisy Chain to Other RTBs

Diagnostics - 1756-OV16E
Attribute Short trip Time stamp of diagnostics 1756-OV16E 5 A for 20 ms @ 24V DC (output on, then short) 5 A for 20 ms @ 24V DC (output on into short) 1 ms

Technical Specifications - 1756-OV16E


DC O UTPUT
ST 0 1 2 3 4 5 6 7 FU SE FU SE E C O ALLYFU D LE TR NIC SE O K ST 8 9 1 11 3 1 5 01 21 41

Attribute Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V

1756-OV16E 16 electronically fused (8 points/group) 12/24V DC sink 10...30V DC 1 ms 1 ms 210 mA 2 mA

Publication 1756-TD002A-EN-E - May 2009

133

1756 ControlLogix I/O Modules

Attribute Power dissipation, max Thermal dissipation, max Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Isolation voltage

1756-OV16E 6.72 W @ 60 C 22.94 BTU/hr 1 mA per point 700 mV DC @ 1 A 1 A @ 60 C 8 A @ 60 C 2 A for 10 ms per Point, repeatable every 2 s @ 60 C 2 mA per point 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Slot width
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

134

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OV16E
Certification(1) c-UL-us 1756-OV16E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

135

1756 ControlLogix I/O Modules

1756-OV32E
ControlLogix DC (10...30V) electronically-fused, sinking output module
Simplified Schematic Display Optoisolation DC-0(+) OUT-0
Group 0 Daisy Chain to Other RTBs OUT-1 OUT-3 OUT-5 OUT-7 OUT-9 OUT-11 OUT-13 OUT-15 DC-0(+) OUT-17 OUT-19 OUT-21 1756-OV32E
2 4 6 8 10 1 3 5 7 9

Daisy Chain to Other RTBs OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10 OUT-12 OUT-14 RTN OUT-0 OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26 OUT-28 OUT-30 RTN OUT-1 Group 1

ControlLogix Backplane Interface

Electronic Fuse Circuitry

RTN OUT-0

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Group 0

Surge Current Chart


Group 1

2A Current 1A 0

Surge Continuous @ 60o C

OUT-23 OUT-25 OUT-27 OUT-29 OUT-31 DC-1(+)

10 ms Time

_
DC COM

Diagnostics - 1756-OV32E
Attribute Short trip Time stamp of diagnostics 1756-OV32E 5 A for 20 ms @ 24V DC (output on then short) 5 A for 20 ms @ 24V DC (output into short) 1 ms

Technical Specifications - 1756-OV32E


DC OUTPUT
ST 0 1 2 1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6 3 1 1 1 9 2 7 4 1 2 2 0 2 8 5 6 11 3 4 22 1 2 23 9 0 7 1 5 2 3 3 1 F 0 O K F 1

Attribute Outputs Voltage category Operating voltage range Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max

1756-OV32E 32 electronically fused (16 points/group) 12/24V DC sink 10...30V DC 300 s 1 ms 390 mA 2 mA 5.88 W @ 60 C

ELECTRONIC FUSING

136

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Thermal dissipation, max Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Isolation voltage

1756-OV32E 20.1 BTU/hr 1 mA per point 350 mV DC @ 0.5 A 0.5 A @ 50 C (linear derating) 0.35 A @ 60 C 16 A @ 50 C (linear derating) 10 A @ 60 C 2 A for 10 ms per point, repeatable every 2 s @ 60 C 2 mA per output 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module Location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

137

1756 ControlLogix I/O Modules

Certifications - 1756-OV32E
Certification(1) c-UL-us 1756-OV32E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick
(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

138

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-OW16I
ControlLogix AC (10...265V) DC (5...150V) isolated contact module
Simplified Schematic +24V Display ControlLogix Backplane Interface L1 OUT
1756-OW16I Isolated Wiring L1-0 L1-1 L1-2 L1-2 L1-3 DC-4 (+) L1-4 L1-5 L1-6 L1-7 Jumper Bar L1-8 (Cut to Length) L1-9 L1-10 L1-11 Nonisolated L1-12 Wiring L1-13 L1-14 L1-15 L1-15 L1 Not Used Daisy Chain to Other RTBs L1-0
2 4 6 8 10 1 3 5 7 9

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

OUT-0 OUT-1 N.O. OUT-2 N.O. OUT-3 N.O. OUT-4 N.O. OUT-5 N.O. OUT-6 N.O. OUT-7 N.O. OUT-8 N.O. OUT-9 N.O. OUT-10 N.O. OUT-11 N.O. OUT-12 N.O. OUT-13 N.O. OUT-14 N.O. OUT-15 N.O Not Used Not Used L2

L2-0 L2-2
DC-4 (-)

Technical Specifications - 1756-OW16I


RELAY OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1756-OW16I 16 N.O. individually isolated 5...150V DC 10...265V AC 530V DC @ 2 A resistive 48V DC @ 0.5 A resistive 125V DC @ 0.25 A resistive 125V AC @ 2 A resistive 240V AC @ 2 A resistive 2 A @ 530V DC 0.5 A @ 48V DC 0.25 A @ 125V DC 2 A @ 125/240V AC 2 A steady state @ 530V DC 0.5 A steady state @ 48V DC 0.25 A steady state @ 125V DC 2 A steady state, 15 A make @ 125V AC 2 A steady state, 15 A make @ 240 V AC 250 W for 125V AC resistive output 480 W for 240V AC resistive output 60 W for 30V DC resistive output 24 W for 48V DC resistive output 31 W for 125V DC resistive output 250VA for 125V AC inductive output 480VA for 240V AC inductive output 60VA for 30V DC inductive output 24VA for 48V DC inductive output 31VA for 125V DC inductive output

Outputs Operating voltage range Load dependent output voltage range

Resistive output current rating (at rated power)

Inductive output current rating (at rated power)

Power rating (steady state), max

Publication 1756-TD002A-EN-E - May 2009

139

1756 ControlLogix I/O Modules

Attribute Output delay, off to on Output delay, on to off Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current per point, max Initial contact resistance, max Switching frequency, max Bounce time, mean Expected contact life Isolation voltage

1756-OW16I 13 ms 13 ms 150 mA 150 mA 4.5 W @ 60 C 15.35 BTU/hr 1.5 mA per point 30 M 1 operation/3 s (0.3 Hz at rated load) 1.2 ms 300 K cycles resistive 100 K cycles inductive 265V continuous Tested at 2546V DC for 1 s, channel to channel, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

140

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Certifications - 1756-OW16I
Certification(1) c-UL-us 1756-OW16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

Publication 1756-TD002A-EN-E - May 2009

141

1756 ControlLogix I/O Modules

1756-OX8I
ControlLogix AC (10...265V) DC (5...150V) isolated contact module
1756-OX8I

Simplified Schematic +24V L1-0


L1-0 L1-0 L1-1 L1-1 DC-2 (+) L1-2 L1-2 L1-3 Jumper Bar (Cut to Length) L1-3 (Part number 97739201) L1-4 L1-4 L1-5 L1-5 L1-6 Nonisolated Wiring L1-6 L1-7 L1-7 L1-7 L1 Not Used L1-0 Isolated Wiring
2 4 6 8 10 1 3 5 7 9

ControlLogix Backplane Interface Display

OUT-0 N.C.

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

OUT-0 N.O.

OUT-0 N.C. OUT-0 N.O. OUT-1 N.C. OUT-1 N.O. OUT-2 N.C. OUT-2 N.O. OUT-3 N.C. OUT-3 N.O. OUT-4 N.C. OUT-4 N.O. OUT-5 N.C. OUT-5 N.O. OUT-6 N.C. OUT-6 N.O. OUT-7 N.C. OUT-7 N.O Not Used Not Used L2

L2-0

DC-2 (-)

Daisy Chain to Other RTBs

Technical Specifications - 1756-OX8I


RELAY OUTPUT
Attribute
ST 0 1 2 3 4 5 6 7 O K

1756-OX8I 8 N.O. 8 N.C. individually isolated (2 points/group) 5...150V DC 10...265V AC @ 4763 530V DC @ 2 A resistive 48V DC @ 0.5 A resistive 125V DC @ 0.25 A resistive 125V AC @ 2 A resistive 240V AC @ 2 A resistive 2 A @ 530V DC 0.5 A @ 48V DC 0.25 A @ 125V DC 2 A @ 125/240V AC 2 A steady state @ 530V DC 0.5 A steady state @ 48V DC 0.25 A steady state @ 125V DC 2 A steady state, 15 A make @ 125V AC 2 A steady state, 15 A make @ 240 V AC 250 W for 125V AC resistive output 480 W for 240V AC resistive output 60 W for 30V DC resistive output 24 W for 48V DC resistive output 31 W for 125V DC resistive output 250VA for 125V AC inductive output 480VA for 240V AC inductive output 60VA for 30V DC inductive output 24VA for 48V DC inductive output 31VA for 125V DC inductive output 13 ms 13 ms

Outputs Operating voltage range Load dependent output voltage range

Resistive output current rating (at rated power)

Inductive output current rating (at rated power)

Power rating (steady state), max

Output delay, off to on Output delay, on to off

142

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Current draw @ 5.1V Current draw @ 24V Power dissipation, max Thermal dissipation, max Off-state leakage current per point, max Initial contact resistance, max Switching frequency, max Bounce time, mean Expected contact life Isolation voltage Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

1756-OX8I 100 mA 100 mA 3.1 W @ 60 C 10.57 BTU/hr 0 mA 100 M @ 6V 1 A 1 operation/3 s (0.3 Hz at rated load) 1.2 ms 300 K cycles resistive 100 K cycles inductive 265V continuous Tested at 2546V DC for 1 s, channel to channel, I/O to system 1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

143

1756 ControlLogix I/O Modules

Certifications - 1756-OX8I
Certification(1) c-UL-us 1756-OX8I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

C-Tick FM
(1)

144

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-CFM
ControlLogix configurable flow meter module
1756-CFM Standard Magnetic Pickup
2 1

1756-CFM Standard Output

Z0 12-24V DC
4 3

Z1 12-24V DC Z1 5V DC
6 5

Z0 12-24V DC
4 3

Z1 12-24V DC Z1 5V DC
6 5

Z0 5V DC Z0 Return
8 7

Z0 5V DC Z0 Return
8 7

Z1 RET F1
10 9

Z1 RET F1
10 9

Input Device

+
Shield Ground

F0 F0 Return
12 11

F0 F0 Return
12 11

F1 Return Not Used


14 13

F1 Return Not Used


14 13

Not Used Not Used


16 15

Not Used Not Used


16 15

Not Used Output 1


18 17 19

Not Used Output 1


18 17 19

Output 0 Customer VCC


20

Output 0 Customer VCC

Customer Common Customer Common

Customer VCC

+
Load

20

Customer Common Customer Common Load

Customer VCC

This wiring diagram can be used in applications with 50 mV (magnetic pickup), 1.3V (TTL), or 4V (preamp level) thresholds. You must use RSLogix 5000 software to choose the appropriate threshold level for your specific application. If separate power sources are used, do not exceed the specified isolation voltage.

If separate power sources are used, do not exceed the specified isolation voltage.

Publication 1756-TD002A-EN-E - May 2009

145

1756 ControlLogix I/O Modules

1756-CFM Standard Prover/Store Count

12-24V DC

1 3 5

Z0 12-24V DC
4

Z1 1224V DC Z1 5V DC

Z0 5V DC
6

Shield Ground

Z0 Return
8 7

Z1 RET F1
10 9

Input Device

+
Shield rGound

F0 F0 Return
12 11

F1 Return Not Used


14 13

Not Used Not Used


16 15

Not Used Output 1


18 17 19

Output 0 Customer VCC


20

Customer Common Customer Common

Customer VCC

Detectors 1 and 2 must be wired in parallel. Customer VCC may be used to power detectors. In this case, though, the maximum current on the wiring arm must be less than 4 A. The wiring example above shows a 12-24V DC standard prover connected to the module. If you use a 5V DC standard prover, make sure the positive wire is connected to the 5V terminal (such as Z0 5V DC). If separate power sources are used, do not exceed the specified isolation voltage.

Technical Specifications - 1756-CFM


METERING
F 0 Z 0 O O 0 1 F 1 Z 1 O K

Attribute Inputs Inputs per channel

1756-CFM 4 (2 per channel) 2 Flowmeter (F) inputs used for all modes 2 Gate inputs used in Totalizer mode for prover/store count 2 current sourcing 300 mA 6 mA 1.7 W 6 W @ 60 C 20.4 BTU/hr 125V continuous Tested at 1700V DC, I/O group to group, I/O to system 1756-TBNH 1756-TBSH 1

DC I/O

Outputs Current draw at 5.1V Current draw at 24V Backplane power, total Power dissipation, max Thermal dissipation, max Isolation voltage Removable terminal block Slot width

146

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Attribute Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

1756-CFM Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Belden 8761 or equivalent None (open-style)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

1756-CFM Input Specifications Attributes Inputs Inputs per channel Input type Count range, max Input frequency, max Flowmeter input voltage Value 4 (2 per channel) 2 Flowmeter (F) inputs used for all modes 2 Gate inputs used in Totalizer mode for prover/store count IEC Type 2 (630 mA) @ 24V DC 2,147,483,647 100 kHz @ flowmeter inputs (overrange occurs at 100 kHz) 30V, selectable input thresholds of 50 mV, 1.3V and 4V: 30V peak unterminated open circuit voltage, magnetic pickup TTL compatible, input voltage >1.3V DC is Logic 1 and -0.71.3V DC is Logic 0 1224V DC powered preamp output, 4V DC threshold 5 k 30% resistive Firmware selectable: High-speed 100 kHz or low-pass filter for frequencies < 70 Hz 5V operation: 4.55.5V DC 12/24V operation: 1031.2V DC 4 mA 15 mA Software selectable User Selectable

Flowmeter input impedance Filtering (inputs F0 & F1) Gate input voltage range Gate input on-state current, min Gate input on-state current, nom Mechanical filter debouncing (Z0 & Z1 Inputs) Input sampling period

Publication 1756-TD002A-EN-E - May 2009

147

1756 ControlLogix I/O Modules

1756-CFM Output Specifications Attribute Outputs Output voltage source Output voltage range Output type Output Current per point Surge current, max Off-state leakage current, max On-state voltage drop, max Output control Output switching time Overload current Output short circuit protection Output reverse polarity protection
(1)

Value 2 current sourcing Customer supplied 5V operation: 4.55.5V DC for 320 mA load per point 12/24V operation: 1031.2V DC for 40 mA1 A load per point IEC 1A 24V DC 1 A @ 1031.2V DC 20 mA @ 4.55.5V DC(1) 2 A for 50 ms, repeatable every 2 s < 300 A @ 31.2V DC 0.6 x current Any number of outputs is assignable to any of 2 flowmeter channels Each output can have 2 turn-on and turn-off preset values < 50 s turn on, <300 s turn off Outputs triggered by Total; all other turn-on and turn-off times <1ms Electronic (< 4A) Electronic (No indication of fault. Remove overload and toggle output on/off to restore.) Yes (If wired incorrectly, module outputs may be permanently disabled.)

All outputs can be on simultaneously without derating.

Certifications - 1756-CFM
Certification(1) c-UL-us 1756-CFM UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick
(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

148

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-HSC
ControlLogix high-speed counter module
1756-HSC to Allen-Bradley 845 Incremental Encoder 1756-HSC to Allen-Bradley Series 10,000 Photoelectric Sensor

Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12..24V) B0 (5V) B0 (RET) A0 (12...24V) A0 (5V) A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)

2 4 6 8 10

1 3 5 7 9

Z1 (12...24V) Z1 (5V) Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+)

Green Black Blue Black White Black

Allen-Bradley Bulletin 845 Incremental Encoder

Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12...24V) B0 (5V) B0 (RET) A0 (12...24V) A0 (5V) A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)

2 4 6 8 10

1 3 5 7 9

Z1 (12...24V)

Whit

Photoswitch Series 10,000

Z1 (5V) Blue Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) Black A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+) 12...24V

10-30V DC Not Used

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Differential Line Driver Output

Jumper

1756-HSC to Allen-Bradley 8723-wire DC Proximity Sensor

Allen-Bradley Bulletin 872 3-wire DC Proximity Jumpers Sensor

Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12...24V) B0 (5V) B0 (RET) Black A0 (12...24V) A0 (5V) Blue A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)

2 4 6 8 10

1 3 5 7 9

Z1 (12...24V) Z1 (5V) Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+)

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

12...24V DC

12...24V DC Return

Publication 1756-TD002A-EN-E - May 2009

149

1756 ControlLogix I/O Modules

1756-HSC Technical Specifications


COUNTER
Attribute
A B Z 0 0 0 O O 0 1 A B Z 1 1 1 O K O O 2 3

1756-HSC 2 3 (A, B, Z for gate/reset) 4 (2 points/group) 5V operation: 4.55.5V DC 12/24V operation: 1031.2V DC 300 mA 3 mA 1.9 W 5.6 W @ 60C 19.1 BTU/hr 125V (continuous), basic insulation type between input group to system 30V (continuous), basic insulation type between input group to input group Routine tested at 1700V DC for 1 s, between input group to input group and input group to system

Number of counters Inputs per counter Outputs Operating voltage range Current draw at 5.1V Current draw at 24V Backplane power, total Power dissipation, max Thermal dissipation, max Isolation voltage

DC I/O

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size Wire category Wire type Enclosure type rating
(1) (2)

1756-TBCH 1756-TBS6H 1 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 0.324...2.08 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 1(2) Copper None (open-style)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

1756-HSC Input Specifications Attribute Number of counters Inputs per counter Input frequency, max Value 2 3 (A, B, Z for gate/reset) 1 MHz in counter modes (A input) 500 kHz in rate measurement mode (A input) 250 kHz in encoder mode (A/B inputs, X1 or X4) 70 Hz with filter enabled 016, 777, 214 1000 kHz 4 mA 15 mA

Count range Counting frequency, max Input current, min Input current, nom

150

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-HSC Output Specifications Attribute Outputs Output delay, off to on Output delay, on to off Off-state leakage current per point, max On-state voltage drop, max Output current rating, per point Current limit Surge current per point Load current per point, min Output control Short circuit protection Reverse polarity protection Value 4 (2 per common) 20 s typical, 50 s max 60 s typical, 300 s max 300 A 0.55V 20 mA @ 4.55.5V DC 1.0 A @ 1031.2V DC <9A 2 A for 10 ms every 1s @ 60 C 5V operation: 3 mA 12/24V operation: 40 mA Any number of output channels is assignable to each counter channel Each output can have 2 "turn-on" and "turn-off" preset values Electronic (Remove overload and toggle On/Off to restore.) Yes (If wired incorrectly, module outputs may be permanently disabled.)

Certifications - 1756-HSC
Certification(1) c-UL-us 1756-HSC UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. ATEX CE European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (Zone 2) European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick
(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

151

1756 ControlLogix I/O Modules

1756-PLS
ControlLogix programmable limit switch module
1756-PLS Inputs - Left Side
2 1

1756-PLS Outputs - Right Side


2 1

OUTPUT 0
4 3

INPUT 0 INPUT 1
6 5

OUTPUT 8
4 3

INPUT 8 INPUT 9
6 5

OUTPUT 1 OUTPUT 2
8 7

OUTPUT 9

INPUT 2 INPUT 3
10 9

+ _
10...30V DC

OUTPUT 10
8 7

INPUT 10 INPUT 11
10 9

OUTPUT 3 DC PWR 0...3


12 11

OUTPUT 11 DC PWR 8...11


12 11

DC COM 0...3 INPUT 4


14 13

DC COM 8...11 INPUT 12


14 13

OUTPUT 4 OUTPUT 5
16 15

OUTPUT 12 OUTPUT 13

INPUT 5 INPUT 6
18 17

INPUT 13
16 15

OUTPUT 6 OUTPUT 7
20 19

+ _

OUTPUT 14
18 17

INPUT 14 INPUT 15
20 19

INPUT 7 DC COM 4-...7

OUTPUT 15 DC PWR 12...15

DC PWR 4...7

DC COM 12...15

+ _

1756-PLS Resolver

Do Not Use
4 3

Do Not Use Do Not Use


6 5

Do Not Use Do Not Use


8 7

Do Not Use Do Not Use


10 9

Do Not Use Do Not Use


12 11

Do Not Use Do Not Use


14 13

Do Not Use

Allen-Bradley Resolver 846-SJDA1CG-R3-C

F (S3)
Sine +

Do Not Use
16 15

D (S1) E (S2) G (S4)

Sine
18 17

Do Not Use Reference +


20 19

Cosine + Cosine

A (R1) B (R2)

Reference

152

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

Technical Specifications - 1756-PLS


Indicator for Left Slot I/O Module
PROG. LIMIT SWITCH

Indicator for Resolver Module

Indicator for Right Slot I/O Module


PROG. LIMIT SWITCH

PROG. LIMIT SWITCH

OUT 0 1 2 3 4 5 6 7

O IN 0 1 2 3 4 5 6 7 K

O K

OUT 8 9 10 11 12 13 14 15

O IN 8 9 10 11 12 13 14 15 K

DC I/O

RESOLVER

DC I/O

Attribute Module configuration

1756-PLS Left section: 2 groups of 4 outputs and 4 inputs each Center section: resolver interface and I/O control Right section: 2 groups of 4 outputs and 4 inputs each 1000 mA 125 mA 25.7 W @ 30 C 21.3 W @ 60 C 87.74 BTU/hr @ 30 C 72.72 BTU/hr @ 60 C 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system Requires 3 RTBs: 1756-TBNH or 1756-TBSH 3 Chassis-based, any slot 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 Center: Alpha Cable #6054C (use 3 of 4 twisted pairs) Left and right: 2 mm2 (2214 AWG) stranded, 1.2 mm (3/64 in.) insulation(1) 2 - Center slot 1 - Left & right slots(2) Left and right: Copper None (open style)

Current draw at 5.1V Current draw at 24V Power dissipation, max Thermal dissipation, max Isolation voltage

Removable terminal block Slot width Module location Chassis Power supply, standard Power supply, redundant Wire size

Wire category Wire type Enclosure type rating


(1)

Maximum wire size requires extended housing, cat. no. 1756-TBE.

(2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1756-TD002A-EN-E - May 2009

153

1756 ControlLogix I/O Modules

1756-PLS Resolver Specifications Attribute Resolver location Compatible resolver Resolver interface Reference voltage Reference frequency Digital resolution Angular resolution Digital count range Maximum tracking rate Repeatability Accuracy Isolation voltage Value Center section Allen-Bradley resolver 846-SJxxxx-R3-x (x = customer options) 2V rms, reference output (differential pair) 2V rms, sine and cosine inputs (2 differential pairs) 2V rms 20% 5 kHz 20% 12 bits (4096 counts from hardware) 0.088 /bit 04095 (decimal) 1800 RPM 0.0488% of full scale 0.0976% of full scale 100% tested at 1700V DC for 1 s

1756-PLS Input Specifications Attribute Inputs Voltage category Operating voltage range Input delay, off to on Input delay, on to off Power dissipation, inputs, max Thermal dissipation, inputs, max Off-state voltage, max Off-state current, max On-state current, min On-state current, max Input impedance, max Reverse polarity protection Isolation voltage Value 16 (2 groups of 4 per I/O section) 12/24V DC 10.831.2V DC < 15 s @ 30 C < 150 s @ 60 C < 30 s @ 30 C < 200 s @ 60 C 2.8 W @ 60C 9.56 BTU/hr 5V DC 1.5 mA 3 mA 10 mA 3.3 k @ 24V DC Yes 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system

1756-PLS Output Specifications Attribute Outputs Voltage category Operating voltage range Output delay, off to on Value 16 (2 groups of 4 per I/O section) 12/24V DC 1031.2V DC < 15 s @ 60 C

154

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

1756-PLS Output Specifications Attribute Output delay, on to off Power dissipation, outputs, max Thermal dissipation, outputs, max Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Current limit Surge current per point Load current per point, min Output switching time Short circuit protection Reverse polarity protection Isolation voltage
(1) (2)

Value < 25 s @ 60 C 6 W @ 30 C 3.8 W @ 60 C 21.48 BTU/hr @ 30 C 11.93 BTU/hr @ 60 C 300 A @ 60 C 0.55V DC 1 A @ 30 C(1) 8 A @ 30 C(2) < 4A 2 A for 10 ms every 1s @ 60 C 40 mA Switching 1 A @ 24V DC Electronic (No indication of fault. Remove load and toggle on/off to restore.) Yes, current limited. (If wired incorrectly, outputs may be permanently disabled.) 250V continuous Tested at 2546V DC for 1 s, I/O group to group, I/O to system

Derate 16.7 mA/ C above 30 C: 0.5 A @ 60 C. Derate 133.6 mA/ C above 30 C: 4 A @ 60 C.

Certifications - 1756-PLS
Certification(1) c-UL-us 1756-PLS UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick
(1)

When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1756-TD002A-EN-E - May 2009

155

1756 ControlLogix I/O Modules

ControlLogix I/O Accessories

1756 Removable Terminal Blocks


Removable terminal blocks (RTBs) provide a flexible interconnection between your plant wiring and 1756 I/O modules. The RTB plugs into the front of the I/O module. The type of module determines which RTB you need. You can choose screw-clamp or spring-clamp RTBs. RTBs are not shipped with I/O modules. You must order them separately. The standard housing on the front of the wiring arm is not deep enough for 2.5 mm2 (14 AWG) wiring. If you plan to use 2.5 mm2 (14 AWG) wiring, also order the extended housing.

Attribute Description

1756-TBNH 20-position NEMA screw-clamp removable block 0.81 Nm 79 lbin 8 mm (5/16 in.) max

1756-TBSH 20-pin spring-clamp removable terminal block with standard housing

1756-TBCH 36-pin cage-clamp removable terminal block with standard housing 0.4 Nm 4.4 lbin

1756-TBS6H 36-pin spring-clamp removable terminal block with standard housing

1756-TBE Extended depth terminal block housing

Screw torque Screwdriver width

Wiring Systems
As an alternative to buying RTBs and connecting the wires yourself, you can buy a wiring system of: interface modules (IFMs) that provide the output terminal blocks for digital I/O modules. Use the pre-wired cables that match the I/O module to the IFM. analog interface modules (AIFMs) that provide the output terminal blocks for analog I/O modules. Use the pre-wired cables that match the I/O module to the AIFM. I/O module-ready cables. One end of the cable assembly is an RTB that plugs into the front of the I/O module. The other end has individually color-coded conductors that connect to a standard terminal block.

156

Publication 1756-TD002A-EN-E - May 2009

1756 ControlLogix I/O Modules

PanelConnect Modules
A PanelConnect module and its sensor connection system connect sensors directly to I/O modules by using convenient pre-built cables and connectors. The PanelConnect module mounts on the enclosure and creates the correct seal for the entry of the sensor connections. You do not need to seal the opening where the sensor cables enter the enclosure, create custom connectors, or wire to those custom connectors.

Publication 1756-TD002A-EN-E - May 2009

157

Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.

Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running. United States Outside United States 1.440.646.3434 Monday Friday, 8am 5pm EST Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction Return


Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor in order to complete the return process. Please contact your local Rockwell Automation representative for the return procedure.

Outside United States

Allen-Bradley, Rockwell Automation, and ControlLogix are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1756-TD002A-EN-E - May 2009


Copyright 2009 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

Você também pode gostar