SION Vacuum Circuit-Breakers

Medium-Voltage Equipment Selection and Ordering Data Catalog HG 11.02 2008

Answers for energy.

SION Vacuum Circuit-Breakers

Siemens HG 11.02 2008

R-HG11-172.tif

SION Vacuum Circuit-Breakers

Contents

Contents

Page

SION Vacuum Circuit-Breakers


Medium-Voltage Equipment Catalog HG 11.02 2008
Invalid: PDF version of Catalog HG 11.02 2006

Description
General Construction and mode of operation, standards Ambient conditions, current carrying capacity and dielectric strength Product range overview and basic equipment

5
6 7 10 11

Equipment Selection
Ordering data and configuration example

13
14

Selection of basic types, standard circuit-breakers 15 Secondary equipment for standard circuit-breakers 23 Selection of basic types, slide-in modules Secondary equipment for slide-in modules Accessories and spare parts 28 32 37

Technical Data
Electrical data, dimensions and weights: Voltage levels 7.2 kV, 12 kV, 17.5 kV Voltage level 24 kV Operating times, short-circuit protection of motors, consumption data of releases Circuit diagrams

41
42 56 59 60

Annex
Inquiry form Configuration instructions Configuration aid

61
62 63 Foldout page

Siemens HG 11.02 2008

SION Vacuum Circuit-Breakers

Siemens HG 11.02 2008

R-HG11-173.tif

SION Vacuum Circuit-Breakers

Description
Contents

Contents

Page

Description
General Construction and mode of operation: Switching medium Pole assemblies Operating mechanism Trip-free mechanism Releases Closing / Circuit-breaker tripping signal Interlocking Low-voltage interface Slide-in module
R-HG11-174.tif

5
6

7 7 7 7 8 8 8 8 9 9 9 10 10 10 11 11

Standards Maintenance-free design Ambient conditions Current carrying capacity Dielectric strength Product range overview Basic equipment

Industrial application: Refinery

Siemens HG 11.02 2008

Description
General

SION Vacuum Circuit-Breakers

SION vacuum circuit-breaker from 7.2 to 24 kV The Innovative


SION vacuum circuit-breakers control all switching duties in medium-voltage distribution systems and are suitable for installation in all customary air-insulated medium-voltage switchgear types. They are applicable for operation of e.g. overhead lines, cables, transformers, generators, capacitors, filter circuits, motors and reactors. The comprehensive installation accessories enable easy integration in the panel and form maximally equipped as a slide-in module almost the complete circuit-breaker compartment.

SION standard circuit-breaker the Variable

SION slide-in module the Complete

R-HG11-167.eps

Our comprehensive range of standard circuit-breakers offers a wide selection for pole-center distances and widths across flats as well as various installation accessory packages for voltage levels from 7.2 to 24 kV. The drawout element, contact arms, contact systems and bushings enable easy integration in all customary medium-voltage switchgear types. Identical dimensions and connection dimensions across several voltage levels reduce planning costs and the diversity of panel versions. High reliability and availability are just as much a matter of course as 10,000 maintenancefree operating cycles.

The slide-in module contains all components required for the circuit-breaker compartment of a panel. It consists of the circuit-breaker on a drawout element with contact arms, fitted in a cartridge with side and rear walls. The module is equipped with bushings, fixed contacts, shutters and the shutter mechanism. The surfaces of the side and rear walls form the tested connection compartment.

Siemens HG 11.02 2008

R-HG11-168.eps

SION Vacuum Circuit-Breakers

Description
Construction and mode of operation

Switching medium The vacuum switching technology, proven and fully developed for more than 30 years, serves as arc-quenching principle by using vacuum interrupters. Pole assemblies The pole assemblies consist of the vacuum interrupters and the pole shells. The vacuum interrupters are air-insulated and freely accessible. The pole assemblies are fixed on the mounting plate of the operating mechanism and supported by means of the pole shell. The vacuum interrupter (3) is mounted rigidly to the upper interrupter support. The lower part of the interrupter is guided in the lower interrupter support, allowing axial movement. The pole shell (4) absorbs the external forces resulting from switching operations and the contact pressure.
HG11-2500 eps

1
R-HG11-170.eps

Vacuum circuit-breaker 3AE12 17.5 kV / 25 kA / 1250 A

1 2 3 4 5 6
1 Separating shell to the operating mechanism 2 Upper connection 3 Interrupter 4 Pole shell 5 Lower connection 6 Bell-type insulator Pole structure

Operating mechanism The whole operating mechanism is mounted on its mounting plate, including the motor, releases, indicators and actuating devices. Stored-energy operating mechanism The operating mechanism is a stored-energy spring mechanism. The force is transmitted from the operating mechanism to the pole assemblies via operating levers. The closing spring can be charged either electrically or manually and latches automatically in when charging is complete. The closing spring acts as a stored-energy mechanism. To close the breaker, the closing spring can be unlatched either mechanically by means of the local ON pushbutton or electrically by remote control. The closing spring charges the contact-pressure / opening springs as the breaker closes. The now discharged closing spring will be charged again automatically by the mechanism motor. The breaker is now capable of performing the OPEN CLOSE OPEN operating sequence that is required for an unsuccessful auto-reclosing operation on the system side. All storedenergy mechanisms perform the switching duties of synchronizing and rapid load transfer as well as auto-reclosing. Trip-free mechanism SION vacuum circuit-breakers have a trip-free mechanism according to IEC 62271-100. In the event of an opening command being given after a closing operation has been initiated, the moving contacts return to the open position and remain there even if the closing command is sustained. This means that the contacts of the vacuum circuit-breakers are momentarily in the closed position, which is permissible according to IEC 62271-100. The motors for charging the closing spring operate in short-time duty. Therefore the voltage and power consumption might differ from the data of the rating plate.

1
1 Cover of low-voltage interface 2 Central control board
HG11-2501 eps

Front view

3 1 4 5 2
HG11-2502 eps

1 Auxiliary switch 2 1st release 3 Terminal strip 4 Motor 5 Closing solenoid 6 Closing spring 7 Gear

6 7

Operating mechanism without cover

Siemens HG 11.02 2008

Description
Construction and mode of operation

SION Vacuum Circuit-Breakers

Releases A release is a device which transfers electrical commands from an external source, such as a control room, to the latching mechanism of the vacuum circuit-breaker so that it can be opened or closed. The releases are designed for short-time duty up to 1 minute and are reset internally. The various types of releases available are described in detail below:
The closing solenoid unlatches the charged closing spring of the vacuum circuit-breaker, closing it by electrical means. Shunt releases are used for automatic tripping of vacuum circuit-breakers by suitable protection relays and for deliberate tripping by electrical means. They are intended for connection to an external power supply (DC or AC voltage) but, in special cases, may also be connected to a voltage transformer for manual operation. Current-transformer operated releases comprise a stored-energy mechanism, an unlatching mechanism, and an electromagnetic system. They are used when there is no external source of auxiliary power (e.g. a battery). Tripping is effected by means of a protection relay (e.g. overcurrenttime protection) acting on the current-transformer operated release. Undervoltage releases comprise a stored-energy mechanism, an unlatching mechanism and an electromagnetic system which is permanently connected to the secondary or auxiliary voltage while the vacuum circuit-breaker is closed. If the voltage falls below a predetermined value, unlatching of the release is enabled and the circuit-breaker is opened via the stored-energy mechanism.

During electrical opening, the NO contact S6 makes brief contact. This is often used to operate a hazard warning system which should respond to automatic tripping of the circuit-breaker. In case of local control, the NO contact S6 does not close. For the corresponding circuit diagrams, refer to page 60. Interlocking Mechanical interlocking At the interface of the mechanical interlocking of the vacuum circuit-breaker, sensors on the switchgear side can check the switch position and prevent the associated disconnector from being closed while the vacuum circuitbreaker is closed. The system also prevents the vacuum circuit-breaker from being closed while the associated disconnector is in a faulty position. Vacuum circuit-breakers mounted on drawout elements are mechanically interlocked, with the result that the handle for racking the drawout element can only be inserted in the OPEN position. The lock of the drawout element can only be released in the disconnected position by operating the pushing handles. If the vacuum circuit-breaker on the drawout element is in an intermediate position (neither in the service nor in the disconnected position), operation is not possible due to the mechanical interlocking. Electrical interlocking The auxiliary and signaling contacts which show the switch position of the vacuum circuit-breaker or the position of the drawout element can be integrated in the switchgear interlocking concept in order to exclude impermissible switching sequences. Low-voltage interface The separate cover enables easy access to the low-voltage interface. All possible customer-side control and signaling connections are concentrated here.

The maximum equipment are 2 freely selected releases. For release combinations, refer to page 23 or page 32. For consumption data, refer to page 59. Closing / Circuit-breaker tripping signal In the standard version, the vacuum circuit-breakers can be remote-closed electrically. In addition, they can be mechanically closed locally by direct unlatching of the closing spring. If constant CLOSE and OPEN commands are present at the vacuum circuit-breaker at the same time, the vacuum circuitbreaker will return to the open position after closing. It remains in this position until a new CLOSE command is given. In this manner, continuous closing and opening (= pumping) is prevented. The charging status of the closing spring in the vacuum circuit-breaker can be interrogated electrically by means of the position switch.

Siemens HG 11.02 2008

SION Vacuum Circuit-Breakers

Description
Construction and mode of operation, standards

Slide-in module Besides the circuit-breaker installation equipment available for standard circuit-breakers by means of the packages for the drawout element, contact arms, fixed contacts and bushings, it is also possible to supply a complete slide-in module. The slide-in module contains all necessary components for the circuit-breaker compartment of a panel. It consists of the circuit-breaker on a drawout element with contact arms, mounted in a cartridge with side and rear walls, equipped with bushings, fixed contacts, shutters and shutter mechanism. The surfaces of the side and rear walls form the tested connection compartment. The vacuum circuit-breaker on the drawout element is racked into the cartridge with the associated handle by the rotary movement of the spindle. The shutter mechanism is controlled by lateral gates, and the shutters are opened for contacting. Signals for the service and disconnected positions are transmitted to the module connector at the low-voltage interface of the vacuum circuit-breaker via the position switches of the drawout element. Standards The vacuum circuit-breakers conform to the following standards:

1
R-HG11-171.eps

Slide-in module 1 Contact system 2 Fixed contact 3 Shutter 4 Bushing 5 Cartridge 6 Contact arm 7 Low-voltage interface 8 Vacuum circuit-breaker 9 Drawout element

IEC 62271-1 (former IEC 60694) IEC 62271-100 (former IEC 60056)
All SION vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The slide-in modules have been tested according to

IEC 62271-200 regarding


Dielectric strength Temperature rise Switching capacity. Maintenance-free design SION vacuum circuit-breakers are maintenance-free:

Under normal ambient conditions according to


IEC 62271-1 (former IEC 60694)

Up to 10,000 operating cycles, no regreasing no readjusting,


the ratings are independent within their tolerances of the switching rate or standing times without switching.

Siemens HG 11.02 2008

Description
Ambient conditions, current carrying capacity and dielectric strength

SION Vacuum Circuit-Breakers

Ambient conditions The vacuum circuit-breakers are designed for the normal operating conditions defined in IEC 62271-100. Condensation can occasionally occur under the ambient conditions shown opposite.

40C

SION vacuum circuit-breakers are suitable for use in the following climatic classes according to IEC 60721, Part 3-3:
max. 95% per day max. 90% per month

Climatic ambient conditions: Biological ambient conditions: Mechanical ambient conditions: Chemically-active substances:
HG11-2515_en eps

Class 3K41) Class 3B1 Class 3M2 Class 3C22) Class 3S23)

-5C

Mechanically-active substances:
1) Low temperature limit: 5 C 2) Without icing and wind-driven precipitation 3) Restriction: Clean insulation parts

Current carrying capacity


HG11-2516a_en eps

Rated normal current

3400 A 3000 2600 2200 1800 1400

The rated normal currents specified in the diagram have been defined according to IEC 62271-100 for an ambient air temperature of + 40 C and apply to open switchgear. For enclosed switchgear the data of the switchgear manufacturer applies. At ambient air temperatures below + 40 C, higher normal currents can be carried (see diagram): Characteristics curve 1 = Rated normal current 800 A Characteristics curve 2 = Rated normal current 1250 A Characteristics curve 3 = Rated normal current 2000 A Characteristics curve 4 = Rated normal current 2500 A Characteristics curve 5 = Rated normal current 3150 A Dielectric strength The dielectric strength of air insulation decreases with increasing altitude due to low air density. According to IEC 62271-1, the values of the rated lightning impulse withstand voltage and the rated short-duration powerfrequency withstand voltage specified in the chapter Technical Data apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite diagram. The characteristic shown applies to both rated withstand voltages. To select the devices, the following applies: U W U0 x Ka
U U0 Ka Rated withstand voltage under reference atmosphere Rated withstand voltage requested for the place of installation Altitude correction factor according to the opposite diagram

4 3

2 1000 600 10 20 30 1 40 50 60 C 70 Ambient air temperature

1.50 Altitude correction factor

1.40

1.30

1.20
HG11-2517c_en eps

1.10

1.00 1000

1500

2000

2500

3000 3500 m 4000 Site altitude

Example For a requested rated lightning impulse withstand voltage of 75 kV at an altitude of 2500 m, an insulation level of 90 kV under reference atmosphere is required as a minimum: 90 kV W 75 kV x 1.2

10

Siemens HG 11.02 2008

SION Vacuum Circuit-Breakers

Description
Product range overview and basic equipment

Product range overview


Rated shortcircuit breaking current Rated normal current Pole-center distance (in mm) 150 160 Width across flats (in mm) 205 n n n n 275 no no no no 310 no no no no 205 n n n n 275 n n n n 310 n n n n 205 n n n n 275 no no no no 310 no no no no no no no no no no no no no no no no no no no no no no no no no no no no no no 310 210 275

Rated voltage

Type 3AE10

kV 7.2

kA 16 20 25 25 31.5 31.5 40 40 16 20 25 25 31.5 31.5 40 40 12.5 16 25 25 31.5 31.5 40 40 12.5 16 20 20 25 25

A 800/1250 800/1250 800/1250 2000 800/1250 2000/2500 1250/2000 2500/3150 800/1250 800/1250 800/1250 2000/2500 800/1250 2000/2500 1250/2000 2500/3150 800/1250 800/1250 800/1250 2000/2500 800/1250 2000/2500 1250/2000 2500/3150 800/1250 800/1250/2000 800/1250 2000/2500 800/1250 2000/2500

3AE11

12

n n n n

no no no no

no no no no

n n n n

n n n n

n n n n

n n n n

no no no no

3AE12

17.5

n n n n

no no no no

no no no no

n n n n

n n n n

n n n n

n n n n

no no no no

3AE13

24

no no no no no

n Standard circuit-breaker (fixed-mounted/drawout version with installation accessories)

o Slide-in module

Basic equipment
Features Operating mechanism Closing 1st release 2nd release Varistor circuit Auxiliary switch Plug connection Anti-pumping Circuit-breaker tripping signal Operations counter Position switches Mechanical interlocking Installation accessories Minimum equipment Electrical operating mechanism Closing solenoid and mechanical manual closing Shunt release Without Installed with W 60 V DC 6 NO + 6 NC 27-pole terminal strip Available Without Available 1 NO + 1 NC Available for slide-in module Fixed-mounted Alternative equipment None None Undervoltage release, c.t.-operated release Shunt release, undervoltage release, c.t.-operated release None 12 NO + 12 NC 24-pole plug, 64-pole plug None Possible None None Mechanical interlocking for circuit-breaker With drawout element, contact arms, contact system, with fixed contacts and bushings, complete slide-in module Remarks Also for manual operation For limiting switching overvoltages 12 NO + 12 NC not available with 24-pole plug Required for slide-in module

Siemens HG 11.02 2008

11

SION Vacuum Circuit-Breakers

12

Siemens HG 11.02 2008

R-HG11-175.tif

SION Vacuum Circuit-Breakers

Equipment Selection
Contents

Contents

Page

Equipment Selection
Ordering data and configuration example Selection of basic types, standard circuit-breakers: Voltage level 7.2 kV Voltage level 12 kV Voltage level 17.5 kV Voltage level 24 kV Secondary equipment for standard circuit-breakers Additional equipment for standard circuit-breakers Selection of basic types, slide-in modules:
R-HG11-176.eps

13
14

15 17 20 22 23 27

Voltage level 7.2 kV Voltage level 12 kV Voltage level 17.5 kV Voltage level 24 kV Secondary equipment for slide-in modules Additional equipment for slide-in modules Accessories and spare parts

28 29 30 31 32 36 37

Standard circuit-breaker

Slide-in module

R-HG11-168.eps

Siemens HG 11.02 2008

13

Equipment Selection
Ordering data and configuration example

SION Vacuum Circuit-Breakers

Order number structure The SION vacuum circuit-breakers consist of a primary and a secondary part. The relevant data make up the 16-digit order number. The primary part covers the main electrical data of the circuit-breaker poles. The secondary part covers the auxiliary devices which are necessary for operating and controlling the vacuum circuit-breaker. Order codes Individual equipment versions, marked with 9 or Z in the 9th to 16th position, are explained more in detail by a 3-digit order code. Several order codes can be added to the order number in succession and in any sequence.

Special versions () In case of special versions, -Z is added to the order number and a descriptive order code follows. If several special versions are required, the suffix -Z is listed only once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identified with Y 9 9 after consultation. The agreement hereto is made directly between your responsible sales partner and the order processing department in the Switchgear Factory Berlin.

2
1st position 2nd position 3rd position 4th to 8th position Primary part Superior group Switching devices Main group Circuit-breaker Subgroup Circuit-breaker type series Basic equipment Design and ratings primary part

a: alphabetical
Position: 1 2 3 4 5

n: numerical
6 7 8 9 10 11 12 13 14 15 16 Order codes

Order No.:

3 A

n n n

9th to 16th position

Secondary part Secondary equipment Operating mechanism, releases, operating voltages and further auxiliary equipment Order codes Group of 3 after the Order No. Format: a n a Special versions () Initiated with -Z Group of 3 after the Order No. Format: a n n

Configuration example In order to simplify the selection of the correct order number for the requested circuit-breaker type, you will find a configuration example on each page of the chapter Equipment Selection. For the selection of the secondary part, always the last example of the primary part was taken over and continued, so that at the end of the equipment selection (pages 27 and 36) a completely configured circuit-breaker results as an example.

On the foldout page we offer a configuring aid. Here you can fill in the order number you have determined for your circuit-breaker.

Example for Order No.: Order codes:

3 A

2 n n n n n n n n

14

Siemens HG 11.02 2008

SION Vacuum Circuit-Breakers

Equipment Selection
Selection of basic types, standard circuit-breakers

7.2 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 23

See page 23

See page 24

See page 24

See page 25

See page 25

See page 26

See page 26

Rated voltage

Ur kV 7.2

Up kV 60

Ud kV 20

Isc kA 16

Ima kA 40/42 mm 210 mm 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2

See page 27

160

150

7.2

60

20

20

50/52

210

160

150

Configuration example SION vacuum circuit-breaker Rated voltage Ur = 7.2 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 60 kV Rated short-circuit breaking current Isc = 20 kA Rated normal current Ir = 1250 A Pole-center distance = 210 mm, width across flats = 310 mm Example for Order No.: Order codes:

3 A

0 3 A E 1 0

8 8

3 3

2 2 n n n n n n n n

Siemens HG 11.02 2008

15

Equipment Selection
Selection of basic types, standard circuit-breakers

SION Vacuum Circuit-Breakers

7.2 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 23

See page 23

See page 24

See page 24

See page 25

See page 25

See page 26

See page 26

Rated voltage

Ur kV 7.2

Up kV 60

Ud kV 20

Isc kA 25

Ima kA 63/65 mm 210 mm 310 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310

Ir A 800 1250 2000 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 1250 2000 2500 3150 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 6 6 6 6 1 2 4 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 2 4 6 7

160

150

7.2

60

20

31.5

80/82

210

160

150

7.2

60

20

40

100/104

210

Configuration example SION vacuum circuit-breaker Rated voltage Ur = 7.2 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 60 kV Rated short-circuit breaking current Isc = 40 kA Rated normal current Ir = 2000 A Pole-center distance = 210 mm, width across flats = 310 mm Example for Order No.: Order codes:

3 A

0 3 A E 1 0

8 8

6 6

4 4 n n n n n n n n

16

Siemens HG 11.02 2008

See page 27

SION Vacuum Circuit-Breakers

Equipment Selection
Selection of basic types, standard circuit-breakers

12 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 23

See page 23

See page 24

See page 24

See page 25

See page 25

See page 26

See page 26

Rated voltage

Ur kV 12

Up kV 75

Ud kV 28

Isc kA 16

Ima kA 40/42 mm 210 mm

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Z E 1 3

310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205 12 75 28 20 50/52 210 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205 Special version (available for all 12 kV standard circuit-breakers) Ud = 42 kV

See page 27

Configuration example SION vacuum circuit-breaker Rated voltage Ur = 12 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 75 kV Rated short-circuit breaking current Isc = 16 kA Rated normal current Ir = 800 A Pole-center distance = 160 mm, width across flats = 275 mm Rated short-duration power-frequency withstand voltage Ud = 42 kV Example for Order No.: Order codes:

3 A

1 Z Z E 1 3 1 n n n n n n n n

3 A E 1

E 3

Siemens HG 11.02 2008

17

Equipment Selection
Selection of basic types, standard circuit-breakers

SION Vacuum Circuit-Breakers

12 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 23

See page 23

See page 24

See page 24

See page 25

See page 25

See page 26

See page 26

Rated voltage

Ur kV 12

Up kV 75

Ud kV 28

Isc kA 25

Ima kA 63/65 mm 210 mm

Ir A 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 1 2 4 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Z E 1 3

310 310 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205 12 75 28 31.5 80/82 210 310 310 310 310 275 275 205 205 160 310 310 275 275 205 205 150 310 310 275 275 205 205 Special version (available for all 12 kV standard circuit-breakers) Ud = 42 kV Configuration example SION vacuum circuit-breaker Rated voltage Ur = 12 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 75 kV Rated short-circuit breaking current Isc = 31.5 kA Rated normal current Ir = 1250 A Pole-center distance = 150 mm, width across flats = 205 mm

3 A

1 3 A E 1 1

0 0

5 5

2 2 n n n n n n n n

Example for Order No.: Order codes:

18

Siemens HG 11.02 2008

See page 27

SION Vacuum Circuit-Breakers

Equipment Selection
Selection of basic types, standard circuit-breakers

12 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 23

See page 23

See page 24

See page 24

See page 25

See page 25

See page 26

See page 26

Rated voltage

Ur kV 12

Up kV 75

Ud kV 28

Isc kA 40

Ima kA 100/104 mm 210 mm

Ir A 1250 2000 2500 3150 3 3 3 3 A A A A E E E E 1 1 1 1 1 1 1 1 8 8 8 8 6 6 6 6 2 4 6 7 Z E 1 3

310 310 310 310 Special version (available for all 12 kV standard circuit-breakers) Ud = 42 kV

See page 27

Circuit-breaker for installation in NXAIR 12 75 28 31.5 80/82

210 160 210

12

75

28

40

100/104

275 275 275 275 275 275 275

1250 2500 1250 1250 2000 2500 3150

3 3 3 3 3 3 3

A A A A A A A

E E E E E E E

1 1 1 1 1 1 1

5 5 5 5 5 5 5

7 7 4 7 7 7 7

5 5 5 6 6 6 6

2 6 2 2 4 6 7

Special version (available for all 12 kV standard circuit-breakers) Ud = 42 kV

Configuration example SION vacuum circuit-breaker Rated voltage Ur = 12 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 75 kV Rated short-circuit breaking current Isc = 40 kA Rated normal current Ir = 1250 A Pole-center distance = 210 mm, width across flats = 310 mm Example for Order No.: Order codes:

3 A

1 3 A E 1 1

8 8

6 6

2 2 n n n n n n n n

Siemens HG 11.02 2008

19

Equipment Selection
Selection of basic types, standard circuit-breakers

SION Vacuum Circuit-Breakers

17.5 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 23

See page 23

See page 24

See page 24

See page 25

See page 25

See page 26

See page 26

Rated voltage

Ur kV 17.5

Up kV 95

Ud kV 38

Isc kA 12.5

Ima kA 31/33 mm 210 mm 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 4 4 4 4 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6

160

150

17.5

95

38

16

40/42

210

160

150

17.5

95

38

25

63/65

210

Configuration example SION vacuum circuit-breaker Rated voltage Ur = 17.5 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 95 kV Rated short-circuit breaking current Isc = 16 kA Rated normal current Ir = 1250 A Pole-center distance = 210 mm, width across flats = 275 mm Example for Order No.: Order codes:

3 A

2 3 A E 1 2

7 7

2 2

2 2 n n n n n n n n

20

Siemens HG 11.02 2008

See page 27

SION Vacuum Circuit-Breakers

Equipment Selection
Selection of basic types, standard circuit-breakers

17.5 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 23

See page 23

See page 24

See page 24

See page 25

See page 25

See page 26

See page 26

Rated voltage

Ur kV 17.5

Up kV 95

Ud kV 38

Isc kA 25

Ima kA 63/65 mm 210 mm 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310 275 275 205 205 310 310 275 275 205 205 310 310 275 275 205 205 310 310 310 310

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 1250 2000 2500 3150 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 0 8 8 8 8 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 6 6 6 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 2 4 6 7

160

See page 27

150

17.5

95

38

31.5

80/82

210

160

150

17.5

95

38

40

100/104

210

Configuration example SION vacuum circuit-breaker Rated voltage Ur = 17.5 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 95 kV Rated short-circuit breaking current Isc = 31.5 kA Rated normal current Ir = 2500 A Pole-center distance = 210 mm, width across flats = 310 mm Example for Order No.: Order codes:

3 A

2 3 A E 1 2

8 8

5 5

6 6 n n n n n n n n

Siemens HG 11.02 2008

21

Equipment Selection
Selection of basic types, standard circuit-breakers

SION Vacuum Circuit-Breakers

24 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 23

See page 23

See page 24

See page 24

See page 25

See page 25

See page 26

See page 26

Rated voltage

Ur kV 24

Up kV 125

Ud kV 50

Isc kA 12.5

Ima kA 31/33 mm 210 mm

Ir A 800 1250 800 1250 2000 800 1250 2000 800 1250 2000 2500 800 1250 2000 2500 800 1250 2000 2500 800 1250 2000 2500 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 2 2 2 2 2 5 5 5 2 2 2 2 5 5 5 5 2 2 2 2 5 5 5 5 1 1 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 1 2 1 2 4 1 2 4 1 2 4 6 1 2 4 6 1 2 4 6 1 2 4 6 Z Z E E 5 6 5 5

310 310 24 125 50 16 40/42 210 310 310 310 275 310 310 310 24 125 50 20 50/52 210 310 310 310 310 275 310 310 310 310 24 125 50 25 63/65 210 310 310 310 310 275 310 310 310 310 Special versions (available for all 24 kV standard circuit-breakers) Ud = 55 kV Ud = 65 kV

Circuit-breaker for installation in NXAIR 24 125 50 25 63/65

320 320 320 275 320 Special versions (available for all 24 kV standard circuit-breakers) Ud = 55 kV Ud = 65 kV

210

1250 2000 2500 2500

3 3 3 3

A A A A

E E E E

1 1 1 1

7 7 7 7

2 2 2 5

4 4 4 4

2 4 6 6 Z Z E E 5 6 5 5

Configuration example SION vacuum circuit-breaker Rated voltage Ur = 24 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 125 kV Rated short-circuit breaking current Isc = 25 kA Rated normal current Ir = 2000 A Pole-center distance = 275 mm, width across flats = 310 mm Example for Order No.: Order codes:

3 A

3 3 A E 1 3

5 5

4 4

4 4 n n n n n n n n

22

Siemens HG 11.02 2008

See page 27

SION Vacuum Circuit-Breakers

Equipment Selection
Secondary equipment for standard circuit-breakers

9th position Release combination

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

1st shunt release

C.t.-operated release with tripping pulse W 0.1 Ws (20 O)

2nd shunt release

Undervoltage release

C.t.-operated release 0.5 A

C.t.-operated release 1.0 A

See page 24

See page 24

See page 25

See page 25

See page 26

See page 26

n n n n n n

n n n n n n n n n

n n n n n n

A B C G H F E N P Q J L M

See page 27

10th position Operating voltage of the closing solenoid

Standard voltages

Special voltages

24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 110 V AC 230 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1)

B C D E F H J K M N P Q R S U V W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 26)

Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 1st shunt release Operating voltage of the closing solenoid 48 V DC Example for Order No.: Order codes:

3 A

1 3 5 4 4 A C A C n n n n n n

3 A

Siemens HG 11.02 2008

23

Equipment Selection
Secondary equipment for standard circuit-breakers

SION Vacuum Circuit-Breakers

11th position Operating voltage of the 1st release

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n See page 25 See page 25 See page 26 See page 26 See page 27

n n n

Standard voltages

Special voltages

C.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1)

0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9

With order code With order code With order code With order code With order code With order code With order code With order code With order code

L L L L L L L L L

1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M

12th position Operating voltage of the 2nd release

Standard voltages

Special voltages

Without, or c.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1)

0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9

With order code With order code With order code With order code With order code With order code With order code With order code With order code

M M M M M M M M M

1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 26)

Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) Operating voltage of the 1st release 32 V DC Without 2nd release Example for Order No.: Order codes:

3 A

1 3 5 4 4 A C 9 0 n n n n L 1 B

3 A L 1

E B

A C

24

Siemens HG 11.02 2008

SION Vacuum Circuit-Breakers

Equipment Selection
Secondary equipment for standard circuit-breakers

13th position Circuit-breaker installation accessories

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n See page 26 See page 26 See page 27

n n n

Options

Without circuit-breaker installation accessories, fixed-mounted circuit-breaker With drawout element With drawout element, contact arms and contact system With drawout element, contact arms and contact system, fixed contacts and bushings

0 1 2 3

14th position Operating voltage of the motor operating mechanism


Standard voltages Special voltages

24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 110 V AC 230 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1)

B C D E F H J K M N P Q R S U V W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 26)

Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) Fixed-mounted circuit-breaker Operating voltage of the motor operating mechanism 230 V AC Example for Order No.: Order codes:

3 A

1 3 5 4 4 A C 9 0 0 K K n n

3 A L 1

E B

Siemens HG 11.02 2008

25

Equipment Selection
Secondary equipment for standard circuit-breakers

SION Vacuum Circuit-Breakers

15th position Interlocking, auxiliary switch, circuit-breaker tripping signal and control cable connection
Auxiliary switch

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Control cable connection

12 NO + 12 NC

Circuit-breaker tripping signal

27-pole terminal strip

24-pole plug

n n n n n n n n n n n n n n n n n n n n n n n n

n n n n n n n n

n n n n n n n n n n n n n n n n

64-pole plug

6 NO + 6 NC

Mechanical interlocking

B D F H K M R Q A C E G J L N P

Special versions Auxiliary switch contacts 12 NO + 12 NC and pins of the 64-pole plug connector gold-plated Key-interlocking (RONIS-lock at the vacuum circuit-breaker) Only for circuit-breakers without mechanical interlocking

See page 27 Z Z A J

2 6

1 0

16th position AC frequency of operating voltages Languages of operating instructions and rating plate
Language selection Frequency selection

50 Hz and DC

n n n n n n n n Other languages on request

n n n n

n n n n

n n n n n n n n n n n n

60 Hz and DC

German

Spanish

English

French

50 Hz

60 Hz

DC

0 1 2 3 4 5 6 7

Configuration example SION vacuum circuit-breaker 3 A E 1 (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 3 5 With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug Frequency of the operating voltage 50 Hz and DC, operating instructions and rating plate in German Example for Order No.: Order codes: 3 A L 1 E B 1 3 5

A C

K N 0

A C

K N 0

26

Siemens HG 11.02 2008

SION Vacuum Circuit-Breakers

Equipment Selection
Additional equipment for standard circuit-breakers

Additional equipment

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Options

Wiring cables, halogen-free and flame-retardant Condensation protection, heating for 230 V AC, 50 W Silicone-free design For circuit-breaker operation at ambient air temperatures down to 25 C Electrical closing lock-out Additional rating plate, loose delivery Separating shell towards contact arm side (standard version) Separating shell towards contact arm side (short version, for 24 kV only) Routine test certificate (enclosed with delivery) Routine test certificate (with stamp and signature) Routine test certificate (to orderer) Special operating sequence (up to 31.5 kA): O - 0.3 s - CO - 15 s - CO Hand crank (for manual charging of the closing spring) Hand crank, long version Handle for drawout element (for racking the circuit-breaker on the drawout element) Key interlocking (only for designs with mechanical interlocking) Indication of disconnected position of the circuit-breaker (circuit-breaker with drawout element)

Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z

A A A A A B D D F F F F F F F J J

1 3 3 4 4 0 9 9 2 2 2 2 3 3 3 6 6

0 0 1 0 7 0 0 1 0 1 3 8 0 1 2 0 1

Configuration example SION vacuum circuit-breaker 3 A E 1 (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 4 1st shunt release Operating voltage of the closing solenoid 48 V DC Operating voltage of the 1st release 32 V DC Without 2nd release Fixed-mounted circuit-breaker Operating voltage of the motor operating mechanism 230 V AC With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug Frequency of the operating voltage 50 Hz and DC, operating instructions and rating plate in German Hand crank Example for Order No.: Order codes: 3 A L 1 E B 1 + 3 F 5 3 4 0 4

A C 9 0 0 K N 0 A C 9 0 0 K N 0 Z Z F 3 0 L 1 B

Siemens HG 11.02 2008

27

Equipment Selection
Selection of basic types, slide-in modules

SION Vacuum Circuit-Breakers

7.2 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 32

See page 32

See page 33

See page 33

See page 34

See page 34

See page 35

See page 35

Rated voltage

Ur kV 7.2

Up kV 60

Ud kV 20

Isc kA 16

Ima kA 40/42 mm 210 mm 310 310 275 275 310 310 275 275 310 310 275 275 310 310 275 275 310 310 310 275 275 310 310 275 275 310 310 310 310 275 275 310 310 275 275 310 310 310 310

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 1250 2000 2500 3150 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 8 8 7 7 2 2 1 1 8 8 7 7 2 2 1 1 8 8 8 7 7 2 2 1 1 8 8 8 8 7 7 2 2 1 1 8 8 8 8 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 6 6 6 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 2 4 6 7

150

2
7.2 60 20 20 50/52 210 150

7.2

60

20

25

63/65

210

150

7.2

60

20

31.5

80/82

210

150

7.2

60

20

40

100/104

210

Configuration example SION vacuum circuit-breaker Rated voltage Ur = 7.2 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 60 kV Rated short-circuit breaking current Isc = 20 kA Rated normal current Ir = 1250 A Pole-center distance = 210 mm, width across flats = 310 mm Example for Order No.: Order codes:

3 A

0 3 A E 1 0

8 8

3 3

2 2 n n n n n n n n

28

Siemens HG 11.02 2008

See page 36

SION Vacuum Circuit-Breakers

Equipment Selection
Selection of basic types, slide-in modules

12 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 32

See page 32

See page 33

See page 33

See page 34

See page 34

See page 35

See page 35

Rated voltage

Ur kV 12

Up kV 75

Ud kV 28

Isc kA 16

Ima kA 40/42 mm 210 mm 310 310 275 275 310 310 275 275 310 310 275 275 310 310 275 275 310 310 310 310 275 275 310 310 275 275 310 310 310 310 275 275 310 310 275 275 310 310 310 310

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 1250 2000 2500 3150 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 8 8 7 7 2 2 1 1 8 8 7 7 2 2 1 1 8 8 8 8 7 7 2 2 1 1 8 8 8 8 7 7 2 2 1 1 8 8 8 8 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 6 6 6 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 2 4 6 7 3 A E 1 Z E 1 3

150

See page 36

12

75

28

20

50/52

210

150

12

75

28

25

63/65

210

150

12

75

28

31.5

80/82

210

150

12

75

28

40

100/104

210

Special version (available for all 12 kV slide-in modules) Ud = 42 kV Configuration example SION vacuum circuit-breaker Rated voltage Ur = 12 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 75 kV Rated short-circuit breaking current Isc = 25 kA Rated normal current Ir = 800 A Pole-center distance = 150 mm, width across flats = 275 mm Rated short-duration power-frequency withstand voltage Ud = 42 kV Example for Order No.: Order codes:

1 Z Z E 1 3 1 n n n n n n n n

3 A E 1

E 3

Siemens HG 11.02 2008

29

Equipment Selection
Selection of basic types, slide-in modules

SION Vacuum Circuit-Breakers

17.5 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 32

See page 32

See page 33

See page 33

See page 34

See page 34

See page 35

See page 35

Rated voltage

Ur kV 17.5

Up kV 95

Ud kV 38

Isc kA 12.5

Ima kA 31/33 mm 210 mm 310 310 275 275 310 310 275 275 310 310 275 275 310 310 275 275 310 310 310 310 275 275 310 310 275 275 310 310 310 310 275 275 310 310 275 275 310 310 310 310

Ir A 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 800 1250 2000 2500 800 1250 800 1250 800 1250 1250 2000 2500 3150 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 8 8 7 7 2 2 1 1 8 8 7 7 2 2 1 1 8 8 8 8 7 7 2 2 1 1 8 8 8 8 7 7 2 2 1 1 8 8 8 8 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 6 6 6 6 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 1 2 4 6 1 2 1 2 1 2 2 4 6 7

150

2
17.5 95 38 16 40/42 210 150

17.5

95

38

25

63/65

210

150

17.5

95

38

31.5

80/82

210

150

17.5

95

38

40

100/104

210

Configuration example SION vacuum circuit-breaker Rated voltage Ur = 17.5 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 95 kV Rated short-circuit breaking current Isc = 16 kA Rated normal current Ir = 1250 A Pole-center distance = 210 mm, width across flats = 275 mm Example for Order No.: Order codes:

3 A

2 3 A E 1 2

7 7

2 2

2 2 n n n n n n n n

30

Siemens HG 11.02 2008

See page 36

SION Vacuum Circuit-Breakers

Equipment Selection
Selection of basic types, slide-in modules

24 kV
50/60 Hz Rated lightning impulse withstand voltage Rated short-circuit breaking current at 36 % DC component Rated short-duration power-frequency withstand voltage Pole-center distance

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Rated short-circuit making current (at 50/60 Hz)

Width across flats

Rated normal current

See page 32

See page 32

See page 33

See page 33

See page 34

See page 34

See page 35

See page 35

Rated voltage

Ur kV 24 24

Up kV 125 125

Ud kV 50 50

Isc kA 12.5 16

Ima kA 31/33 40/42 mm 210 210 mm 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310 310

Ir A 800 1250 800 1250 2000 800 1250 2000 800 1250 2000 2500 800 1250 2000 2500 800 1250 2000 2500 800 1250 2000 2500 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 A A A A A A A A A A A A A A A A A A A A A A A A E E E E E E E E E E E E E E E E E E E E E E E E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 2 2 2 2 2 5 5 5 2 2 2 2 5 5 5 5 2 2 2 2 5 5 5 5 1 1 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 1 2 1 2 4 1 2 4 1 2 4 6 1 2 4 6 1 2 4 6 1 2 4 6

See page 36

275

24

125

50

20

50/52

210

275

24

125

50

25

63/65

210

275

Configuration example SION vacuum circuit-breaker Rated voltage Ur = 24 kV, 50/60 Hz Rated lightning impulse withstand voltage Up = 125 kV Rated short-circuit breaking current Isc = 25 kA Rated normal current Ir = 2000 A Pole-center distance = 275 mm, width across flats = 310 mm Example for Order No.: Order codes:

3 A

3 3 A E 1 3

5 5

4 4

4 4 n n n n n n n n

Siemens HG 11.02 2008

31

Equipment Selection
Secondary equipment for slide-in modules

SION Vacuum Circuit-Breakers

9th position Release combination

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

1st shunt release

C.t.-operated release with tripping pulse W 0.1 Ws (20 O)

2nd shunt release

Undervoltage release

C.t.-operated release 0.5 A

C.t.-operated release 1.0 A

See page 33

See page 33

See page 34

See page 34

See page 35

See page 35

n n n n n n

n n n n n n n n n

n n n n n n

A B C G H F E N P Q J L M

10th position Operating voltage of the closing solenoid

Standard voltages

Special voltages

24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 110 V AC 230 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1)

B C D E F H J K M N P Q R S U V W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 35)

Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 1st shunt release Operating voltage of the closing solenoid 48 V DC Example for Order No.: Order codes:

3 A

1 3 5 4 4 A C C n n n n n n

3 A

32

Siemens HG 11.02 2008

See page 36

SION Vacuum Circuit-Breakers

Equipment Selection
Secondary equipment for slide-in modules

11th position Operating voltage of the 1st release

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n See page 34 See page 34 See page 35 See page 35 See page 36

n n n

Standard voltages

Special voltages

C.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1)

0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9

With order code With order code With order code With order code With order code With order code With order code With order code With order code

L L L L L L L L L

1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M

12th position Operating voltage of the 2nd release

Standard voltages

Special voltages

Without, or c.t.-operated release 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 50/60 Hz 1) 110 V AC 50/60 Hz 1) 230 V AC 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1)

0 1 2 3 4 5 6 7 8 9 9 9 9 9 9 9 9 9

With order code With order code With order code With order code With order code With order code With order code With order code With order code

M M M M M M M M M

1 A 1 B 1 C 1 D 1 E 1 F 1 K 1 L 1 M

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 35)

Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) Operating voltage of the 1st release 32 V DC Without 2nd release Example for Order No.: Order codes:

3 A

1 3 5 4 4 A C 9 0 n n n n L 1 B

3 A L 1

E B

Siemens HG 11.02 2008

33

Equipment Selection
Secondary equipment for slide-in modules

SION Vacuum Circuit-Breakers

13th position Circuit-breaker installation accessories

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n See page 35 See page 35 See page 36

n n n

Options

On cartridge, with drawout element, contact arms, contact system, fixed contacts, bushings and shutters On cartridge, with drawout element, contact arms, contact system, fixed contacts, bushings, shutters and earthing switch with short-circuit making capacity Drawings of the fully equipped slide-in-module. Scope of supply includes fixed-mounted circuit-breaker

6 8

14th position Operating voltage of the motor operating mechanism

Standard voltages

Special voltages

24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 100 V AC 110 V AC 230 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1) 30 V DC 32 V DC 120 V DC 125 V DC 127 V DC 240 V DC 120 V AC 125 V AC 240 V AC

50/60 Hz 1) 50/60 Hz 1) 50/60 Hz 1)

B C D E F H J K M N P Q R S U V W

1) The AC frequency 50 or 60 Hz is selected at the 16th position of the order number together with the language (see page 35)

Configuration example SION vacuum circuit-breaker (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) Circuit-breaker on cartridge, with drawout element, contact arms, contact system, fixed contacts, bushings and shutters Operating voltage of the motor operating mechanism 240 V DC Example for Order No.: Order codes:

3 A

1 3 5 4 4 A C 9 0 5 S n n

3 A L 1

E B

34

Siemens HG 11.02 2008

SION Vacuum Circuit-Breakers

Equipment Selection
Secondary equipment for slide-in modules

15th position Interlocking, auxiliary switch, circuit-breaker tripping signal and control cable connection
Auxiliary switch

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Control cable connection

12 NO + 12 NC

Circuit-breaker tripping signal

27-pole terminal strip

64-pole plug

n n n n n n

n n n n n n

6 NO + 6 NC

Mechanical interlocking

n n n

n n n n n n

A C J L N P

Special versions Auxiliary switch contacts 12 NO + 12 NC and pins of the 64-pole plug connector gold-plated

See page 36

16th position AC frequency of operating voltages Languages of operating instructions and rating plate
Language selection Frequency selection

50 Hz and DC

n n n n n n n n Other languages on request

n n n n

n n n n

n n n n n n n n n n n n

60 Hz and DC

German

Spanish

English

French

50 Hz

60 Hz

DC

0 1 2 3 4 5 6 7

Configuration example SION vacuum circuit-breaker 3 A E 1 (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 4 With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug Frequency of the operating voltage DC, operating instruction and rating plate in Spanish Auxiliary switch contacts 12 NO + 12 NC and plug pins gold-plated Example for Order No.: Order codes: 3 A L 1 E B 1 3 5 2 4 1 4

A C

S N 6 Z Z A 2 1

A C

S N 6

+ A

Siemens HG 11.02 2008

35

Equipment Selection
Additional equipment for slide-in modules

SION Vacuum Circuit-Breakers

Additional equipment

Position:

10 11 12

13 14 15 16

Order codes

Order No.:

3 A

1 n n n n n n n n n n n n

n n n

Options

Wiring cables, halogen-free and flame-retardant Condensation protection, heating for 230 V AC, 50 W Silicone-free design For circuit-breaker operation at ambient air temperatures down to 25 C Electrical closing lock-out Additional rating plate, loose delivery Routine test certificate (enclosed with delivery) Routine test certificate (with stamp and signature) Routine test certificate (to orderer) Special operating sequence (up to 31.5 kA): O - 0.3 s - CO - 15 s - CO Hand crank (for manual charging of the closing spring) Hand crank, long version Handle for drawout element (for racking the circuit-breaker on the drawout element) Handle for earthing switch (for operating the earthing switch at the module) Key interlocking (only for designs with mechanical interlocking)

Z Z Z Z Z Z Z Z Z Z Z Z Z Z Z

A A A A A B F F F F F F F F J

1 3 3 4 4 0 2 2 2 2 3 3 3 3 6

0 0 1 0 7 0 0 1 3 8 0 1 2 4 0

Configuration example SION vacuum circuit-breaker 3 A E 1 (Ur = 24 kV, 50/60 Hz, Up = 125 kV, Isc = 25 kA, Ir = 2000 A, pole-center distance = 275 mm, width across flats = 310 mm) 3 5 4 4 1st shunt release Operating voltage of the closing solenoid 48 V DC Operating voltage of the 1st release 32 V DC Without 2nd release Circuit-breaker on cartridge, with drawout element, contact arms, contact system, fixed contacts, bushings and shutters Operating voltage of the motor operating mechanism 240 V DC With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug Frequency of the operating voltage DC, operating instructions and rating plate in Spanish Auxiliary switch contacts 12 NO + 12 NC and plug pins gold-plated Wiring cables halogen-free and flame-retardant Silicone-free design Electrical closing lock-out Example for Order No.: Order codes: 3 A L 1 E B 1 3 5 2 4 1 4

A C 9 0 5 S N 6 A C 1 0 9 + 0 A 3 5 1 S N 6 + A 4 7 Z Z Z Z Z A A A A 2 1 3 4 1 0 1 7 L 1 B

+ A

+ A

36

Siemens HG 11.02 2008

SION Vacuum Circuit-Breakers

Equipment Selection
Accessories and spare parts

Retrofitting When releases/solenoids are retrofitted, the order numbers of the mounting parts must also be specified. For other additional equipment, the required mounting parts are included in the delivery. Spare parts When releases/solenoids are required as spare parts, the order number and the type of construction of the associated circuit-breaker type must also be specified. Remark for orders The order numbers are applicable to vacuum circuitbreakers of current manufacture. When mounting parts or spare parts are being ordered for an existing vacuum circuit-breaker, always quote the type designation, serial number, design code and the year of manufacture of the circuit-breaker to be sure to get the correct delivery.

Accessories for the plug connector Included in the scope of supply of the basic equipment for SION vacuum circuit-breakers: For 24-pole plug connector Lower part of plug Crimp sockets according to number of contacts Upper part of plug with screwed contacts (no crimp sockets required) For 64-pole plug connector Lower part of plug Upper part of plug Crimp sockets according to number of contacts Vacuum interrupters and other spare parts must only be replaced by instructed personnel.

2
Operating voltage Order No.

Designation

Remarks

Handles

Lubricant

Operating solenoid

Hand crank for circuit-breaker Long hand crank for circuit-breaker Handle for drawout element Handle for earthing switch (for modules up to 31.5 kA) Handle for earthing switch (for 40 kA modules) 180 g of Klber-Isoflex Topas L32N 1 kg of Klber-Isoflex Topas L32N 1 kg of Molykote grease Used as closing solenoid or 1st shunt release

2nd shunt release

24 V DC 30/32 V DC 48 V DC 60 V DC 100/124 V DC 125/144 V DC 220/250 V DC 100/125 V AC, 50/60 Hz 230/240 V AC, 50/60 Hz 24 32 V DC 48 60 V DC 110 127 V DC 220 240 V DC 100 125 V AC, 50 Hz 230 240 V AC, 50 Hz 100 125 V AC, 60 Hz 230 240 V AC, 60 Hz

Mounting parts Current-transformer operated release

For 2nd shunt release For rated normal current 0.5 A For rated normal current 1 A For tripping pulse W 0.1 Ws, 20 O for protection relay 7SJ45 For current-transformer operated release

3AX15 30-2B 3AX14 30-2B 3AX14 30-2C 3AX14 30-2D 3AX14 30-3D 3AX11 33-3H 3AX11 33-3E 3AX11 33-2L 3AY15 10-5B 3AY15 10-5M 3AY15 10-5C 3AY15 10-5D 3AY15 10-5E 3AY15 10-5N 3AY15 10-5F 3AY15 10-5E 3AY15 10-5F 3AX11 01-2B 3AX11 01-2C 3AX11 01-2E 3AX11 01-2F 3AX11 01-2G 3AX11 01-2J 3AX11 01-3G 3AX11 01-3J 3AX14 11-2A 3AX11 02-2A 3AX11 02-2B 3AX11 04-2B 3AX14 11-2A

Mounting parts

Siemens HG 11.02 2008

37

Equipment Selection
Accessories and spare parts

SION Vacuum Circuit-Breakers

Designation

Remarks

Operating voltage

Order No.

Undervoltage release

24 V DC 30/32 V DC 48 V DC 60 V DC 110 V DC 120/127 V DC 220 V DC 240 V DC 100 V AC, 50 Hz 110/125 V AC, 50 Hz 230 V AC, 50 Hz 240 V AC, 50 Hz 100 V AC, 60 Hz 110/125 V AC, 60 Hz 230 V AC, 60 Hz 240 V AC, 60 Hz For undervoltage release 24/30/32 V DC 48 V DC 60 V DC 100/110/125 V DC/AC 220 V DC/230 V AC Type 3RH11 22 for anti-pumping 24 V DC 30/32 V DC 48 V DC 60 V DC 110 V DC 120/127 V DC 220 V DC 240/250 V DC 110 V AC, 50/60 Hz 120 V AC, 50/60 Hz 125 V AC, 50/60 Hz 230 V AC, 50/60 Hz 240 V AC, 50/60 Hz Nos. 1 1 2 1 2 1 10

Mounting parts Drive motor

3AX11 03-2B 3AX11 03-2L 3AX11 03-2C 3AX11 03-2D 3AX11 03-2E 3AX11 03-2N 3AX11 03-2F 3AX11 03-2P 3AX11 03-2G 3AX11 03-2H 3AX11 03-2J 3AX11 03-2M 3AX11 03-3G 3AX11 03-3H 3AX11 03-3J 3AX11 03-3M 3AX14 13-2A 3AY17 11-2B 3AY17 11-2C 3AY17 11-2D 3AY17 11-2E 3AY17 11-2F SWB: 55656 SWB: 55658 SWB: 55659 SWB: 55660 SWB: 55661 SWB: 55662 SWB: 55663 SWB: 55665 SWB: 55666 SWB: 55667 SWB: 55668 SWB: 55669 SWB: 55670 SWB: 46677

Auxiliary contactor

Position switch

Auxiliary switch (-S1) Mechanical interlocking Key-operated interlocking Module connector Accessories for plug connector

Type SE4 without installation accessories Used for: Electrical anti-pumping (-S3) Electrical interlocking (-S12) Motor control (-S21, -S22) Closing spring charged (-S4) Circuit-breaker tripping signal (-S6) Electrical closing lock-out (-S5) Drawout element (-S1.0 to - S1.9) 6 NO + 6 NC 12 NO + 12 NC

State position indicator of drawout element (for conductor cross-section 1.5 mm) Crimp pins (for lower part of plug) Crimp sockets (for upper part of plug) Crimping pliers Disassembly tool Plug connector, complete

3SV92 73-2AA0 3SV92 74-2AA0 3AX14 20-2A 3AX14 37-2A 3AX14 60-2A 24-pole 64-pole 64-pole 3AX11 34-3A 3AX11 34-4B 3AX11 34-4C 3AX11 34-4D 3AX11 34-4G 3AX11 34-7A 3AX11 34-6A

24-pole 64-pole

38

Siemens HG 11.02 2008

SION Vacuum Circuit-Breakers

Equipment Selection
Accessories and spare parts

Designation

Remarks

Operating voltage

Order No.

Electrical closing lock-out

24 V DC 30/32 V DC 48 V DC 60 V DC 110/127 V DC 220/240 V DC 100 V AC, 50/60 Hz 110/125 V AC, 50/60 Hz 220/240 V AC, 50/60 Hz For electrical closing lock-out 7.2 to 17.5 kV to 1250 A 7.2 to 17.5 kV to 3150 A 24 kV to 2500 A Additional shielding for narrow mounting conditions Standard version, width across flats 310 mm Standard version, width across flats 275 mm Standard version, width across flats 205 mm Standard version, width across flats 310 mm Short version, width across flats 310 mm Short version 7.2 to 17.5 kV 7.2 to 17.5 kV 7.2 to 17.5 kV 24 kV 24 kV 7.2/12/24 kV, 800 to 1250 A 17.5 kV, 800 to 1250 A 7.2/12/24 kV, to 3150 A 17.5 kV, to 3150 A 7.2/12 kV, up to 31.5 kA, up to 1250 A 7.2/12 kV, up to 31.5 kA, up to 2500 A 17.5 kV, up to 31.5 kA, up to 1250 A 17.5 kV, up to 31.5 kA, up to 2500 A 24 kV, up to 25 kA, up to 1250 A 24 kV, up to 25 kA, up to 2500 A 7.2/12 kV, 40 kA, up to 1250 A 7.2/12 kV, 40 kA, up to 3150 A 17.5 kV, 40 kA, up to 1250 A 17.5 kV, 40 kA, up to 3150 A 7.2/12/17.5 kV, up to 31.5 kA, up to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, up to 2500 A 7.2/12/17.5 kV, 40 kA, up to 3150 A 24 kV, up to 25 kA, up to 2500 A 7.2/12/17.5 kV, up to 31.5 kA, up to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, up to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, up to 1250 A 7.2/12/17.5 kV, up to 31.5 kA, up to 2500 A 7.2/12/17.5 kV, 40 kA, up to 3150 A 24 kV, up to 25 kA, up to 1250 A 24 kV, up to 25 kA, up to 1250 A 24 kV, up to 25 kA, up to 2500 A 24 kV, up to 25 kA, up to 2500 A

Mounting parts Bushing

3AX14 05-2B 3AX14 05-2K 3AX14 05-2C 3AX14 05-2D 3AX14 05-2E 3AX14 05-2F 3AX14 05-2G 3AX14 05-2H 3AX14 05-2J 3AX14 15-2A 3AX14 51-2A 3AX14 51-2B 3AX14 51-2B 3AX14 38-2A 3AX14 38-2C 3AX14 38-2D 3AX14 38-2B 3AX14 38-3B 3AX14 52-2B 3AX14 42-2A 3AX14 42-2B 3AX14 42-2C 3AX14 42-2D 3AX14 43-2A 3AX14 43-2B 3AX14 43-2C 3AX14 43-2D 3AX14 43-2E 3AX14 43-2F 3AX14 43-2G 3AX14 43-2H 3AX14 43-2J 3AX14 43-2K 3AX14 44-2A 3AX14 44-2B 3AX14 44-2A 3AX14 44-2C 3AX14 55-2A 3AX14 55-2A 3AX14 55-2B 3AX14 55-2C 3AX14 55-2D 3AX14 55-2E 3AX14 55-2F 3AX14 55-2G 3AX14 55-2H

Separating shell towards contact arm side, for standard circuit-breakers only

Gate for cartridge Contact system

Contact arm, complete with contact system

Fixed contact

Conductor bars (1 set each) for earthing switch connection

150/210 mm pole-center distance, 275 mm width across flats 150 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 275 mm pole-center distance, 310 mm width across flats 210 mm pole-center distance, 310 mm width across flats 275 mm pole-center distance, 310 mm width across flats

Data on the rating plate Note: For any query regarding spare parts, subsequent deliveries, etc., the following four details are necessary: Type designation Serial No. Design code Year of manufacture
HG11-2518_en eps

Siemens HG 11.02 2008

39

SION Vacuum Circuit-Breakers

40

Siemens HG 11.02 2008

R-HG11-177.tif

SION Vacuum Circuit-Breakers

Technical Data
Contents

Contents

Page

Technical Data
Electrical data, dimensions and weights: Voltage level 7.2 kV Voltage level 12 kV Voltage level 17.5 kV Voltage level 24 kV Dimension drawings: Voltage levels 7.2 to 17.5 kV Voltage level 24 kV Operating times Short-circuit protection of motors
R-HG11-178.eps

41
42 46 50 56

54 58 59 59 59 60

Consumption data of releases Circuit diagrams

SION vacuum circuit-breaker with drawout element, contact arms and contact system

SION vacuum circuit-breaker with drawout element, contact arms and contact system

R-HG11-179.eps

Siemens HG 11.02 2008

41

Technical Data
Electrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

7.2 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 002-1 ... 3AE1 002-2 ... 3AE1 003-1 ... 3AE1 003-2 ... 3AE1 004-1 ... 3AE1 004-2 ... 3AE1 005-1 ... 3AE1 005-2 ... mm mm n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 35.4 35.4

Ima kA 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82

Up kV 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

Ud kV 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 1 1 2 2 3 3 4 4 1 1 2 2 3 3 4 4 1 1 2 2 3 3 4 4 K/ K/ K/ K/ K/ K/ K/ K/ I/J I/J I/J I/J I/J I/J I/J I/J H/J H/J H/J H/J H/J H/J H/J H/J

800 205 150 1250 205 150 800 205 150 1250 205 150 800 205 150 1250 205 150 800 205 150 1250 205 150 800 275 150 1250 275 150 800 275 150 1250 275 150 800 275 150 1250 275 150 800 275 150 1250 275 150 800 310 150 1250 310 150 800 310 150 1250 310 150 800 310 150 1250 310 150 800 310 150 1250 310 150

3AE1 012-1 ... 3AE1 012-2 ... 3AE1 013-1 ... 3AE1 013-2 ... 3AE1 014-1 ... 3AE1 014-2 ... 3AE1 015-1 ... 3AE1 015-2 ... 3AE1 022-1 ... 3AE1 022-2 ... 3AE1 023-1 ... 3AE1 023-2 ... 3AE1 024-1 ... 3AE1 024-2 ... 3AE1 025-1 ... 3AE1 025-2 ...

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55

42

Siemens HG 11.02 2008

Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module)

Operating cycle diagram no. (see page 45)

Rated lightning impulse withstand voltage

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

SION Vacuum Circuit-Breakers

Technical Data
Electrical data, dimensions and weights

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

7.2 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 032-1 ... 3AE1 032-2 ... 3AE1 033-1 ... 3AE1 033-2 ... 3AE1 034-1 ... 3AE1 034-2 ... 3AE1 035-1 ... 3AE1 035-2 ... 3AE1 042-1 ... 3AE1 042-2 ... 3AE1 043-1 ... 3AE1 043-2 ... 3AE1 044-1 ... 3AE1 044-2 ... 3AE1 045-1 ... 3AE1 045-2 ... 3AE1 052-1 ... 3AE1 052-2 ... 3AE1 053-1 ... 3AE1 053-2 ... 3AE1 054-1 ... 3AE1 054-2 ... 3AE1 055-1 ... 3AE1 055-2 ... 3AE1 062-1 ... 3AE1 062-2 ... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9

Ima kA 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42

Up kV 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

Ud kV 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 165 129 140 165 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 90/ 90/ 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02022 001 3M 442 02022 001 1 1 2 2 3 3 4 4 1 1 2 2 3 3 4 4 1 1 2 2 3 3 4 4 1 1 G/ G/ G/ G/ G/ G/ G/ G/ F/ F/ F/ F/ F/ F/ F/ F/ E/ E/ E/ E/ E/ E/ E/ E/ D/ D/

800 205 160 1250 205 160 800 205 160 1250 205 160 800 205 160 1250 205 160 800 205 160 1250 205 160 800 275 160 1250 275 160 800 275 160 1250 275 160 800 275 160 1250 275 160 800 275 160 1250 275 160 800 310 160 1250 310 160 800 310 160 1250 310 160 800 310 160 1250 310 160 800 310 160 1250 310 160 800 205 210 1250 205 210

Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module)

Operating cycle diagram no. (see page 45)

Rated lightning impulse withstand voltage

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 Siemens HG 11.02 2008

43

Technical Data
Electrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

7.2 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 063-1 ... 3AE1 063-2 ... 3AE1 064-1 ... 3AE1 064-2 ... 3AE1 065-1 ... 3AE1 065-2 ... 3AE1 072-1 ... 3AE1 072-2 ... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 25 31.5 31.5 31.5 31.5 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 28 35.4 35.4 35.4 35.4

Ima kA 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 63/ 65 80/ 82 80/ 82 80/ 82 80/ 82

Up kV 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60

Ud kV 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.5 2.1 2.1 1.5 1.5 mm mm mm mm 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 160 129 140 160 129 140 160 129 140 160 129 140 160 129 140 160 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 90/ 90/ 90/ 90/ 90/ 90/ 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 110/ 150 90/ 130 90/ 130 110/ 150 110/ 150 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02028 001 3M 442 02024 001 3M 442 02024 001 3M 442 02028 001 3M 442 02028 001 2 2 3 3 4 4 1 1 2 2 3 3 4 4 1 1 2 2 3 3 3 4 4 4 4 D/ D/ D/ D/ D/ D/ B/C B/C B/C B/C B/C B/C B/C B/C A/C A/C A/C A/C A/C A/C L/C A/C A/C L/C L/C

800 205 210 1250 205 210 800 205 210 1250 205 210 800 205 210 1250 205 210 800 275 210 1250 275 210 800 275 210 1250 275 210 800 275 210 1250 275 210 800 275 210 1250 275 210 800 310 210 1250 310 210 800 310 210 1250 310 210 800 310 210 1250 310 210 2000 310 210 800 310 210 1250 310 210 2000 310 210 2500 310 210

3AE1 073-1 ... 3AE1 073-2 ... 3AE1 074-1 ... 3AE1 074-2 ... 3AE1 075-1 ... 3AE1 075-2 ... 3AE1 082-1 ... 3AE1 082-2 ... 3AE1 083-1 ... 3AE1 083-2 ... 3AE1 084-1 ... 3AE1 084-2 ... 3AE1 084-4 ... 3AE1 085-1 ... 3AE1 085-2 ... 3AE1 085-4 ... 3AE1 085-6 ...

129 265 130 130 129 140 160 129 140 160 75 75

129 265 130 130 129 265 130 130

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55

44

Siemens HG 11.02 2008

Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module)

Operating cycle diagram no. (see page 45)

Rated lightning impulse withstand voltage

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

SION Vacuum Circuit-Breakers

Technical Data
Electrical data, dimensions and weights

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

7.2 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 086-2 ... 3AE1 086-4 ... 3AE1 086-6 ... 3AE1 086-7 ... mm mm n n n n

tk s 3 3 3 3

Isc kA 40 40 40 40 % 36 36 36 36 kA 44.9 44.9 44.9 44.9

Ima kA 100/ 104 100/ 104 100/ 104 100/ 104

Up kV 60 60 60 60

Ud kV 20 20 20 20 mV 1.7 1.0 1.0 1.0 mm mm mm mm 145 155 169 140 145 249 149 140 145 249 149 140 145 249 149 140 kg 120/ 160 160/ 210 160/ 210 160/ 210 3M 442 02070 001 3M 442 02071 001 3M 442 02071 001 3M 442 02071 001 5 5 5 5 M/C M/C M/C M/C

1250 310 210 2000 310 210 2500 310 210 3150 310 210

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55

Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module)

Rated lightning impulse withstand voltage

Operating cycle diagram no. (see below)

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

3
Operating cycle diagrams for 7.2 kV
The permissible number of
20 000

electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve shape beyond the parameters defined in
HG11-2539b_en eps

20 000

Operating cycle No.

5 000 2 000 1 000 500

Operating cycle No.

10 000

10 000 5 000 2 000 1 000 500 200

180 80 50

200 100

130 50

average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application.

20 10 0.5 1 2

20 10 0.5 1 2

5 kA 10 16 20 25 Breaking current (r.m.s. value)

40 50

20 31.5 50 5 kA 10 Breaking current (r.m.s. value)

Siemens HG 11.02 2008

HG11-2540a_en eps

IEC 62271-100 is based on

100

45

Technical Data
Electrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

12 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 102-1 ... 3AE1 102-2 ... 3AE1 103-1 ... 3AE1 103-2 ... 3AE1 104-1 ... 3AE1 104-2 ... 3AE1 105-1 ... 3AE1 105-2 ... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9

Ima kA 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42

Up kV 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75

Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 105 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 100 129 140 115 129 140 115 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 80/ 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02010 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02011 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02012 001 3M 442 02016 001 3M 442 02016 001 6 6 7 7 8 8 9 9 6 6 7 7 8 8 9 9 6 6 7 7 8 8 9 9 6 6 K/ K/ K/ K/ K/ K/ K/ K/ I/J I/J I/J I/J I/J I/J I/J I/J H/J H/J H/J H/J H/J H/J H/J H/J G/ G/

800 205 150 1250 205 150 800 205 150 1250 205 150 800 205 150 1250 205 150 800 205 150 1250 205 150 800 275 150 1250 275 150 800 275 150 1250 275 150 800 275 150 1250 275 150 800 275 150 1250 275 150 800 310 150 1250 310 150 800 310 150 1250 310 150 800 310 150 1250 310 150 800 310 150 1250 310 150 800 205 160 1250 205 160

3AE1 112-1 ... 3AE1 112-2 ... 3AE1 113-1 ... 3AE1 113-2 ... 3AE1 114-1 ... 3AE1 114-2 ... 3AE1 115-1 ... 3AE1 115-2 ... 3AE1 122-1 ... 3AE1 122-2 ... 3AE1 123-1 ... 3AE1 123-2 ... 3AE1 124-1 ... 3AE1 124-2 ... 3AE1 125-1 ... 3AE1 125-2 ... 3AE1 132-1 ... 3AE1 132-2 ...

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55

46

Siemens HG 11.02 2008

Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module)

Operating cycle diagram no. (see page 49)

Rated lightning impulse withstand voltage

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

SION Vacuum Circuit-Breakers

Technical Data
Electrical data, dimensions and weights

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

12 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 133-1 ... 3AE1 133-2 ... 3AE1 134-1 ... 3AE1 134-2 ... 3AE1 135-1 ... 3AE1 135-2 ... 3AE1 142-1 ... 3AE1 142-2 ... 3AE1 143-1 ... 3AE1 143-2 ... 3AE1 144-1 ... 3AE1 144-2 ... 3AE1 145-1 ... 3AE1 145-2 ... 3AE1 152-1 ... 3AE1 152-2 ... 3AE1 153-1 ... 3AE1 153-2 ... 3AE1 154-1 ... 3AE1 154-2 ... 3AE1 155-1 ... 3AE1 155-2 ... 3AE1 162-1 ... 3AE1 162-2 ... 3AE1 163-1 ... 3AE1 163-2 ... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4

Ima kA 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52

Up kV 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75

Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 115 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 110 129 140 165 129 140 165 129 140 165 129 140 165 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 90/ 90/ 90/ 90/ 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02016 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02017 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02018 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 7 7 8 8 9 9 6 6 7 7 8 8 9 9 6 6 7 7 8 8 9 9 6 6 7 7 G/ G/ G/ G/ G/ G/ F/ F/ F/ F/ F/ F/ F/ F/ E/ E/ E/ E/ E/ E/ E/ E/ D/ D/ D/ D/

800 205 160 1250 205 160 800 205 160 1250 205 160 800 205 160 1250 205 160 800 275 160 1250 275 160 800 275 160 1250 275 160 800 275 160 1250 275 160 800 275 160 1250 275 160 800 310 160 1250 310 160 800 310 160 1250 310 160 800 310 160 1250 310 160 800 310 160 1250 310 160 800 205 210 1250 205 210 800 205 210 1250 205 210

Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module)

Operating cycle diagram no. (see page 49)

Rated lightning impulse withstand voltage

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 Siemens HG 11.02 2008

47

Technical Data
Electrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

12 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 164-1 ... 3AE1 164-2 ... 3AE1 165-1 ... 3AE1 165-2 ... 3AE1 172-1 ... 3AE1 172-2 ... 3AE1 173-1 ... 3AE1 173-2 ... mm mm n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 25 25 31.5 31.5 16 16 20 20 25 25 31.5 31.5 16 16 20 20 25 25 25 25 31.5 31.5 31.5 31.5 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 35.4 35.4 17.9 17.9 22.4 22.4 28 28 28 28 35.4 35.4 35.4 35.4

Ima kA 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 80/ 82 80/ 82 40/ 42 40/ 42 50/ 52 50/ 52 63/ 65 63/ 65 63/ 65 63/ 65 80/ 82 80/ 82 80/ 82 80/ 82

Up kV 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75

Ud kV 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.5 1.5 2.1 2.1 1.5 1.5 mm mm mm mm 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 165 129 140 160 129 140 160 129 140 160 129 140 160 129 140 160 129 140 160 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 kg 90/ 90/ 90/ 90/ 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 110/ 150 110/ 150 90/ 130 90/ 130 110/ 150 110/ 150 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02022 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02023 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02024 001 3M 442 02028 001 3M 442 02028 001 3M 442 02024 001 3M 442 02024 001 3M 442 02028 001 3M 442 02028 001 8 8 9 9 6 6 7 7 8 8 9 9 6 6 7 7 8 8 8 8 9 9 9 9 D/ D/ D/ D/ B/C B/C B/C B/C B/C B/C B/C B/C A/C A/C A/C A/C A/C A/C L/C L/C A/C A/C L/C L/C

800 205 210 1250 205 210 800 205 210 1250 205 210 800 275 210 1250 275 210 800 275 210 1250 275 210 800 275 210 1250 275 210 800 275 210 1250 275 210 800 310 210 1250 310 210 800 310 210 1250 310 210 800 310 210 1250 310 210 2000 310 210 2500 310 210 800 310 210 1250 310 210 2000 310 210 2500 310 210

3AE1 174-1 ... 3AE1 174-2 ... 3AE1 175-1 ... 3AE1 175-2 ... 3AE1 182-1 ... 3AE1 182-2 ... 3AE1 183-1 ... 3AE1 183-2 ... 3AE1 184-1 ... 3AE1 184-2 ... 3AE1 184-4 ... 3AE1 184-6 ... 3AE1 185-1 ... 3AE1 185-2 ... 3AE1 185-4 ... 3AE1 185-6 ...

129 265 130 130 129 265 130 130 129 140 160 129 140 160 75 75

129 265 130 130 129 265 130 130

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55

48

Siemens HG 11.02 2008

Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module)

Operating cycle diagram no. (see page 49)

Rated lightning impulse withstand voltage

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

SION Vacuum Circuit-Breakers

Technical Data
Electrical data, dimensions and weights

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

12 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 186-2 ... 3AE1 186-4 ... 3AE1 186-6 ... 3AE1 186-7 ... 3AE1 545-2 ... 3AE1 575-2 ... 3AE1 575-6 ... 3AE1 576-2 ... 3AE1 576-4 ... 3AE1 576-6 ... 3AE1 576-7 ... mm mm n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3

Isc kA 40 40 40 40 31.5 31.5 31.5 40 40 40 40 % 36 36 36 36 36 36 36 36 36 36 36 kA 44.9 44.9 44.9 44.9 35.4 35.4 35.4 44.9 44.9 44.9 44.9

Ima kA 100/ 104 100/ 104 100/ 104 100/ 104 80/ 82 80/ 82 80/ 82 100/ 104 100/ 104 100/ 104 100/ 104

Up kV 75 75 75 75 75 75 75 75 75 75 75

Ud kV 28 28 28 28 28 28 28 28 28 28 28 mV 1.7 1.0 1.0 1.0 2.1 2.1 1.5 1.7 1.0 1.0 1.0 mm mm mm mm 145 155 169 140 145 249 149 140 145 249 149 140 145 249 149 140 129 140 115 129 140 160 75 75 kg 120/ 160 160/ 210 160/ 210 160/ 210 80/ 90/ 3M 442 02070 001 3M 442 02071 001 3M 442 02071 001 3M 442 02071 001 10 10 10 10 9 9 9 10 10 10 10 M/C M/C M/C M/C / / / / / / /

1250 310 210 2000 310 210 2500 310 210 3150 310 210 1250 275 160 1250 275 210 2500 275 210 1250 275 210 2000 275 210 2500 310 210 3150 310 210

129 265 130 130 110/ 145 155 169 140 120/ 145 249 149 140 160/ 145 249 149 140 160/ 145 249 149 140 160/

Catalog dimension drawings (see pages 54) (fixed-mounted circuit-breaker/slide-in module)

Rated lightning impulse withstand voltage

Operating cycle diagram no. (see below)

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55

Operating cycle diagrams for 12 kV


The permissible number of
20 000

electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve shape beyond the parameters defined in
HG11-2734_en eps

20 000

Operating cycle No.

5 000 2 000 1 000 500

Operating cycle No.

10 000

10 000 5 000 2 000 1 000 500 200

180 80 50

200 100

130 50

IEC 62271-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application.

100
HG11-2735_en eps

20 10 0.5 1 2

10

20 10 0.5 1 2

5 kA 10 16 20 25 Breaking current (r.m.s. value)

40 50

20 31.5 50 5 kA 10 Breaking current (r.m.s. value)

Siemens HG 11.02 2008

49

Technical Data
Electrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

17.5 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 201-1 ... 3AE1 201-2 ... 3AE1 202-1 ... 3AE1 202-2 ... 3AE1 204-1 ... 3AE1 204-2 ... 3AE1 205-1 ... 3AE1 205-2 ... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 14.9 14.9 17.9 17.9 28 28 35.4 35.4 14.9 14.9 17.9 17.9 28 28 35.4 35.4 14.9 14.9 17.9 17.9 28 28 35.4 35.4 14.9 14.9

Ima kA 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33

Up kV 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95

Ud kV 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 275 237 150 129 275 237 150 129 275 237 150 129 275 237 150 129 275 237 150 129 275 237 150 129 275 237 150 129 275 237 150 129 275 214 150 129 275 214 150 129 275 214 150 129 275 214 150 129 275 214 150 129 275 214 150 129 275 214 150 129 275 214 150 129 275 190 150 129 275 190 150 129 275 190 150 129 275 190 150 129 275 190 150 129 275 190 150 129 275 190 150 129 275 190 150 129 275 247 150 129 275 247 150 kg 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 120 80/ 80/ 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02013 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02014 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02015 001 3M 442 02019 001 3M 442 02019 001 11 11 12 12 13 13 14 14 11 11 12 12 13 13 14 14 11 11 12 12 13 13 14 14 11 11 K/ K/ K/ K/ K/ K/ K/ K/ I/J I/J I/J I/J I/J I/J I/J I/J H/J H/J H/J H/J H/J H/J H/J H/J G/ G/

800 205 150 1250 205 150 800 205 150 1250 205 150 800 205 150 1250 205 150 800 205 150 1250 205 150 800 275 150 1250 275 150 800 275 150 1250 275 150 800 275 150 1250 275 150 800 275 150 1250 275 150 800 310 150 1250 310 150 800 310 150 1250 310 150 800 310 150 1250 310 150 800 310 150 1250 310 150 800 205 160 1250 205 160

3AE1 211-1 ... 3AE1 211-2 ... 3AE1 212-1 ... 3AE1 212-2 ... 3AE1 214-1 ... 3AE1 214-2 ... 3AE1 215-1 ... 3AE1 215-2 ... 3AE1 221-1 ... 3AE1 221-2 ... 3AE1 222-1 ... 3AE1 222-2 ... 3AE1 224-1 ... 3AE1 224-2 ... 3AE1 225-1 ... 3AE1 225-2 ... 3AE1 231-1 ... 3AE1 231-2 ...

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55

50

Siemens HG 11.02 2008

Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module)

Operating cycle diagram no. (see page 53)

Rated lightning impulse withstand voltage

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

SION Vacuum Circuit-Breakers

Technical Data
Electrical data, dimensions and weights

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

17.5 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 232-1 ... 3AE1 232-2 ... 3AE1 234-1 ... 3AE1 234-2 ... 3AE1 235-1 ... 3AE1 235-2 ... 3AE1 241-1 ... 3AE1 241-2 ... 3AE1 242-1 ... 3AE1 242-2 ... 3AE1 244-1 ... 3AE1 244-2 ... 3AE1 245-1 ... 3AE1 245-2 ... 3AE1 251-1 ... 3AE1 251-2 ... 3AE1 252-1 ... 3AE1 252-2 ... 3AE1 254-1 ... 3AE1 254-2 ... 3AE1 255-1 ... 3AE1 255-2 ... 3AE1 261-1 ... 3AE1 261-2 ... 3AE1 262-1 ... 3AE1 262-2 ... mm mm n n n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 16 16 25 25 31.5 31.5 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 16 16 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 17.9 17.9 28 28 35.4 35.4 14.9 14.9 17.9 17.9 28 28 35.4 35.4 14.9 14.9 17.9 17.9 28 28 35.4 35.4 14.9 14.9 17.9 17.9

Ima kA 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42

Up kV 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95

Ud kV 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 mm mm mm mm 129 275 247 150 129 275 247 150 129 275 247 150 129 275 247 150 129 275 247 150 129 275 247 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 224 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 200 150 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 kg 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 80/ 90/ 90/ 90/ 90/ 3M 442 02019 001 3M 442 02019 001 3M 442 02019 001 3M 442 02019 001 3M 442 02019 001 3M 442 02019 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02020 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02021 001 3M 442 02025 001 3M 442 02025 001 3M 442 02025 001 3M 442 02025 001 12 12 13 13 14 14 11 11 12 12 13 13 14 14 11 11 12 12 13 13 14 14 11 11 12 12 G/ G/ G/ G/ G/ G/ F/ F/ F/ F/ F/ F/ F/ F/ E/ E/ E/ E/ E/ E/ E/ E/ D/ D/ D/ D/

800 205 160 1250 205 160 800 205 160 1250 205 160 800 205 160 1250 205 160 800 275 160 1250 275 160 800 275 160 1250 275 160 800 275 160 1250 275 160 800 275 160 1250 275 160 800 310 160 1250 310 160 800 310 160 1250 310 160 800 310 160 1250 310 160 800 310 160 1250 310 160 800 205 210 1250 205 210 800 205 210 1250 205 210

Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module)

Operating cycle diagram no. (see page 53)

Rated lightning impulse withstand voltage

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55 Siemens HG 11.02 2008

51

Technical Data
Electrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

17.5 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 264-1 ... 3AE1 264-2 ... 3AE1 265-1 ... 3AE1 265-2 ... 3AE1 271-1 ... 3AE1 271-2 ... 3AE1 272-1 ... 3AE1 272-2 ... mm mm n n n n n n n n n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 25 25 31.5 31.5 12.5 12.5 16 16 25 25 31.5 31.5 12.5 12.5 16 16 25 25 25 25 31.5 31.5 31.5 31.5 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 28 28 35.4 35.4 14.9 14.9 17.9 17.9 28 28 35.4 35.4 14.9 14.9 17.9 17.9 28 28 28 28 35.4 35.4 35.4 35.4

Ima kA 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 80/ 82 80/ 82 31/ 33 31/ 33 40/ 42 40/ 42 63/ 65 63/ 65 63/ 65 63/ 65 80/ 82 80/ 82 80/ 82 80/ 82

Up kV 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95 95

Ud kV 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 38 mV 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 1.5 1.5 2.1 2.1 1.5 1.5 mm mm mm mm 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 129 275 165 150 129 275 160 150 129 275 160 150 129 275 160 150 129 275 160 150 129 275 160 150 129 275 160 150 129 265 130 130 129 265 130 130 129 275 160 150 129 275 160 150 129 265 130 130 129 265 130 130 kg 90/ 90/ 90/ 90/ 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 90/ 130 110/ 150 110/ 150 90/ 130 90/ 130 110/ 150 110/ 150 3M 442 02025 001 3M 442 02025 001 3M 442 02025 001 3M 442 02025 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02026 001 3M 442 02027 001 3M 442 02027 001 3M 442 02027 001 3M 442 02027 001 3M 442 02027 001 3M 442 02027 001 3M 442 02029 001 3M 442 02029 001 3M 442 02027 001 3M 442 02027 001 3M 442 02029 001 3M 442 02029 001 13 13 14 14 11 11 12 12 13 13 14 14 11 11 12 12 13 13 13 13 14 14 14 14 D/ D/ D/ D/ B/C B/C B/C B/C B/C B/C B/C B/C A/C A/C A/C A/C A/C A/C L/C L/C A/C A/C L/C L/C

800 205 210 1250 205 210 800 205 210 1250 205 210 800 275 210 1250 275 210 800 275 210 1250 275 210 800 275 210 1250 275 210 800 275 210 1250 275 210 800 310 210 1250 310 210 800 310 210 1250 310 210 800 310 210 1250 310 210 2000 310 210 2500 310 210 800 310 210 1250 310 210 2000 310 210 2500 310 210

3AE1 274-1 ... 3AE1 274-2 ... 3AE1 275-1 ... 3AE1 275-2 ... 3AE1 281-1 ... 3AE1 281-2 ... 3AE1 282-1 ... 3AE1 282-2 ... 3AE1 284-1 ... 3AE1 284-2 ... 3AE1 284-4 ... 3AE1 284-6 ... 3AE1 285-1 ... 3AE1 285-2 ... 3AE1 285-4 ... 3AE1 285-6 ...

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55

52

Siemens HG 11.02 2008

Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module)

Operating cycle diagram no. (see page 53)

Rated lightning impulse withstand voltage

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

SION Vacuum Circuit-Breakers

Technical Data
Electrical data, dimensions and weights

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

17.5 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 286-2 ... 3AE1 286-4 ... 3AE1 286-6 ... 3AE1 286-7 ... mm mm n n n n

tk s 3 3 3 3

Isc kA 40 40 40 40 % 36 36 36 36 kA 44.9 44.9 44.9 44.9

Ima kA 100/ 104 100/ 104 100/ 104 100/ 104

Up kV 95 95 95 95

Ud kV 38 38 38 38 mV 1.7 1.0 1.0 1.0 mm mm mm mm 145 249 169 140 145 249 149 140 145 249 149 140 145 249 149 140 kg 120/ 160 160/ 210 160/ 210 160/ 210 3M 442 02070 001 3M 442 02071 001 3M 442 02071 001 3M 442 02071 001 15 15 15 15 M/C M/C M/C M/C

1250 310 210 2000 310 210 2500 310 210 3150 310 210

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 55

Catalog dimension drawings (see pages 54/55) (fixed-mounted circuit-breaker/slide-in module)

Rated lightning impulse withstand voltage

Operating cycle diagram no. (see below)

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

3
Operating cycle diagrams for 17.5 kV
The permissible number of
20 000

electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve shape beyond the parameters defined in
HG11-2537b_en eps

20 000

Operating cycle No.

Operating cycle No.

10 000 5 000 2 000 1 000 500

10 000 5 000 2 000 1 000 500 200 100


HG11-2541a_en eps

350

180 200 80 50 100

IEC 62271-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application.

50 20 10 0.5 1 2 11 14

20 10 0.5 1 2

12 13 5 kA 10 16 20 25 Breaking current (r.m.s. value)

15

40 50

5 kA 10 12.5 20 31.5 50 Breaking current (r.m.s. value)

Siemens HG 11.02 2008

53

Technical Data
Dimensions drawings for voltage levels 7.2 kV to 17.5 kV

SION Vacuum Circuit-Breakers

Dimension drawings for 7.2 to 17.5 kV


HG11-2519_en eps

210

210

210

210

310

572.5 517.5

562.5

517.5

237.5

20

310 380

279

20

310 380

279

Dimension drawing A
472/5221) 102 100 30 210 794

Dimension drawing B
210 187
HG11-2521a_en eps

Width across flats mm a


b a

217.5

562.5 275

540

540

Height mm b 905 850

310 275 1) for 40 kA

345

27.5

688/7381)

Dimension drawing C
HG11-2522_en eps

27.5

43

286.5

210

210

562.5 205

572,5 517.5

517.5

562.5

540

540

217.5

20

310 380

279

20

310 380

279

Dimension drawing D
HG11-2524_en eps

Dimension drawing E
160 160
HG11-2525_en eps

ca.93

562.5 275

ca.93

370

465 160 160

370

237.5

310

465

517.5

517.5

217.5

20

310 380

279

20

310 380

279

Dimension drawing F

Dimension drawing G

54

Siemens HG 11.02 2008

217.5

562.5 205

540

540

HG11-2523_en eps

ca.93

ca.93

370

565

370

465 160 160

HG11-2520_en eps

ca.93

ca.93

370

565

370

565

SION Vacuum Circuit-Breakers

Technical Data
Dimensions drawings for voltage levels 7.2 kV to 17.5 kV

Dimension drawings for 7.2 to 17.5 kV


HG11-2526_en eps

310

572.5 517.5

517.5

237.5

20

310 380

279

20

310 380

279

Dimension drawing H
472 102 100 30 150 594 150

Dimension drawing I
147
HG11-2528a_en eps

Width across flats mm a


b a

217.5

562.5 275

562.5

540

540

Height mm b 905 850

310 275

341

688 710

27.5

27.5

43

266.5

HG11-2527_en eps

ca.93

ca.93

370

445 150 150

370

445 150 150

Dimension drawing J
HG11-2529_en eps

3
210 210

562.5 205

581 517.5

517.5

562.5

540

540

20

217.5

310 380

279

20

310 380

279

Dimension drawing K
HG11-2531_en eps

Dimension drawing L
ca.93
210 210

420

PCD 150 160


424

a 529 529 679

237.5

310

c 500 500 650

d 470 470 620

Weight ca. 15 kg ca. 15 kg ca. 20 kg

600

310

210

540

Height of drawout element: 60


107

c
HG11-2589 eps

50

PCD a c d

Pole-center distance Width of drawout elements Total width across wheels Distance between wheels

350 450

279

237.5

Dimension drawing M

Dimension drawing of slide-in module


Siemens HG 11.02 2008

HG11-2530_en eps

ca.93

ca.93

370

445 150 150

370

565

55

Technical Data
Electrical data, dimensions and weights

SION Vacuum Circuit-Breakers

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

Rated short-circuit breaking current

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

24 kV
DC component in % of the rated short-circuit breaking current Rated short-circuit making current (at 50/60 Hz) Asymmetrical breaking current Rated operating sequence: O - 3 min - CO - 3 min - CO

Ir A 3AE1 321-1 ... 3AE1 321-2 ... 3AE1 322-1 ... 3AE1 322-2 ... 3AE1 322-4 ... 3AE1 323-1 ... 3AE1 323-2 ... 3AE1 323-4 ... mm mm n n n n n n n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Isc kA 12.5 12.5 16 16 16 20 20 20 20 25 25 25 25 16 16 16 % 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 kA 14.9 14.9 17.9 17.9 17.9 22.4 22.4 22.4 22.4 28 28 28 28 17.9 17.9 17.9

Ima kA 31/ 33 31/ 33 40/ 42 40/ 42 40/ 42 50/ 52 50/ 52 50/ 52 50/ 52 63/ 65 63/ 65 63/ 65 63/ 65 40/ 42 40/ 42 40/ 42

Up kV 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125 125

Ud kV 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 mV 2.6 2.6 2.6 2.6 2.0 2.6 2.6 2.0 2.0 2.6 2.6 2.0 2.0 2.6 2.6 2.0 mm mm mm mm 200 350 200 210 200 350 200 210 200 350 200 210 200 350 200 210 200 340 200 205 200 350 200 210 200 350 200 210 200 340 200 205 200 340 200 205 200 350 200 210 200 350 200 210 200 340 200 205 200 340 200 205 200 350 265 210 200 350 265 210 200 340 265 205 kg 120/ 160 120/ 160 120/ 160 120/ 160 140/ 180 120/ 160 120/ 160 140/ 180 140/ 180 120/ 160 120/ 160 140/ 180 140/ 180 130/ 180 130/ 180 150/ 200 3M 442 02050 001 3M 442 02050 001 3M 442 02050 001 3M 442 02050 001 3M 442 02051 001 3M 442 02050 001 3M 442 02050 001 3M 442 02051 001 3M 442 02051 001 3M 442 02050 001 3M 442 02050 001 3M 442 02051 001 3M 442 02051 001 3M 442 02052 001 3M 442 02052 001 3M 442 02053 001 16 16 17 17 17 18 18 18 18 19 19 19 19 17 17 17 N/P N/P N/P N/P N/P N/P N/P N/P N/P N/P N/P N/P N/P R/T R/T S/T

800 310 210 1250 310 210 800 310 210 1250 310 210 2000 310 210 800 310 210 1250 310 210 2000 310 210 2500 310 210 800 310 210 1250 310 210 2000 310 210 2500 310 210 800 310 275 1250 310 275 2000 310 275

3AE1 323-6 ... 3AE1 324-1 ... 3AE1 324-2 ... 3AE1 324-4 ... 3AE1 324-6 ... 3AE1 352-1 ... 3AE1 352-2 ... 3AE1 352-4 ...

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 58

56

Siemens HG 11.02 2008

Catalog dimension drawings (see page 58) (fixed-mounted circuit-breaker/slide-in module)

Operating cycle diagram no. (see page 57)

Rated lightning impulse withstand voltage

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

O - 0.3 s - CO - 3 min - CO

O - 0.3 s - CO - 15 s - CO

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

SION Vacuum Circuit-Breakers

Technical Data
Electrical data, dimensions and weights

Weight 1) (fixed-mounted circuit-breaker/slide-in module)

DC component in % of the rated short-circuit breaking current

Rated short-circuit making current (at 50/60 Hz)

50/60 Hz Rated duration of short-circuit

Voltage drop U between connections (according to IEC 60694 at DC 100 A)

Rated short-duration power-frequency withstand voltage

Rated short-circuit breaking current

24 kV
Rated operating sequence: O - 3 min - CO - 3 min - CO O - 0.3 s - CO - 3 min - CO O - 0.3 s - CO - 15 s - CO

Ir A 3AE1 353-1 ... 3AE1 353-2 ... 3AE1 353-4 ... 3AE1 353-6 ... 3AE1 354-1 ... 3AE1 354-2 ... 3AE1 354-4 ... 3AE1 354-6 ... 3AE1 724-2 ... 3AE1 754-6 ... mm mm n n n n n n n n n n

tk s 3 3 3 3 3 3 3 3 3 3

Isc kA 20 20 20 20 25 25 25 25 25 25 % 36 36 36 36 36 36 36 36 36 36 kA 22.4 22.4 22.4 22.4 28 28 28 28 28 28

Ima kA 50/ 52 50/ 52 50/ 52 50/ 52 63/ 65 63/ 65 63/ 65 63/ 65 63/ 65 63/ 65

Up kV 125 125 125 125 125 125 125 125 125 125

Ud kV 50 50 50 50 50 50 50 50 50 50 mV 2.6 2.6 2.0 2.0 2.6 2.6 2.0 2.0 2.6 2.0 mm mm mm mm 200 350 265 210 200 350 265 210 200 340 265 205 200 340 265 205 200 350 265 210 200 350 265 210 200 340 265 205 200 340 265 205 kg 130/ 180 130/ 180 150/ 200 150/ 200 130/ 180 130/ 180 150/ 200 150/ 200 3M 442 02052 001 3M 442 02052 001 3M 442 02053 001 3M 442 02053 001 3M 442 02052 001 3M 442 02052 001 3M 442 02053 001 3M 442 02053 001 18 18 18 18 19 19 19 19 19 19 R/T R/T S/T S/T R/T R/T S/T S/T / /

800 310 275 1250 310 275 2000 310 275 2500 310 275 800 310 275 1250 310 275 2000 310 275 2500 310 275 1250 320 210 2500 320 275

Catalog dimension drawings (see page 58) (fixed-mounted circuit-breaker/slide-in module)

Rated lightning impulse withstand voltage

Operating cycle diagram no. (see below)

Asymmetrical breaking current

Minimum creepage distance, interrupter

Minimum creepage distance, phase-to-earth

Detailed dimension drawing (has to be ordered)

Rated normal current

Pole-center distance

Minimum clearance, phase-to-phase

Minimum clearance, phase-to-earth

Width across flats

Order No.

200 350 200 210 120/ 200 340 200 205 150/

n Standard acc. to IEC 62271-100

Possible

Not available as slide-in module

1) The weight of the fixed-mounted circuit-breaker with drawout element increases by the values specified in the dimension drawing of slide-in module, page 58

Operating cycle diagrams for 24 kV


The permissible number of
20 000

electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve shape beyond the parameters defined in IEC 62271-100 is based on
HG11-2538b_en eps

20 000

Operating cycle No.

5 000 2 000 1 000 500

Operating cycle No.

10 000

10 000 5 000 2 000 1 000 500 200 90 30 20 10 0.5 1 2 17 19 100 50


HG11-2542a_en eps

150 50

200 100

average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application.

20 10 0.5 1 2

16

18

5 10 12.5 20 kA Breaking current (r.m.s. value)

50

5 10 16 25 kA 50 Breaking current (r.m.s. value)

Siemens HG 11.02 2008

57

Technical Data
Dimensions drawings for voltage level 24 kV

SION Vacuum Circuit-Breakers

Dimension drawings for 24 kV


210 ca.93 210
HG11-2532 eps

420

570

PCD 210
424

a 679 879

c 650 850

d 620 820

Weight ca. 20 kg ca. 25 kg

275

739 310

Height of drawout element: 60 PCD a c d Pole-center distance Width of drawout element Total width across wheels Distance between wheels
107
c
HG11-2590 eps

739

540

58

360 468

269

283

Dimension drawing N
532 112 100 30 210

Dimension drawing of slide-in module


210 187
HG11-2533b_en eps

794

1040.5

1013

485.5

346

Dimension drawing P
420

27.5

788 810

HG11-2534 eps

275 ca.93

275

275 ca.93

275

739 310

739

540

540

283

58

360 468

269

58

360 468

269

Dimension drawing R
532 112 100 30

Dimension drawing S
275 275 222
HG11-2536b_en eps

994

1040.5

1013

485.5

346

Dimension drawing T

27.5

788 810

58

Siemens HG 11.02 2008

27.5

41.5

332

310

283

739 310

739

HG11-2535 eps

700

420

27.5

41.5

332

310

700

SION Vacuum Circuit-Breakers

Technical Data
Operating times, short-circuit protection of motors, consumption data of releases

Operating times at rated voltage of the secondary circuit


Vacuum circuit-breaker equipment Equipment of circuit-breaker Operating time

Closing time Opening time Arcing time Break time Dead time CLOSE/OPEN contact time Minimum command duration

Pulse time for circuit-breaker tripping signal Charging time for electrical operation Synchronism error between the poles

1st shunt release 2nd release 1st shunt release 2nd release 1st shunt release 2nd release Closing solenoid 1st shunt release 2nd release 1st shunt release 2nd release

< 75 ms < 65 ms < 50 ms < 15 ms < 80 ms < 65 ms 300 ms < 75 ms < 60 ms 45 ms 40 ms 20 ms > 15 ms > 10 ms < 10 s 2 ms

Short-circuit protection of motors (fuse protection of drive motors)


Rated voltage of the motor Operating voltage Power consumption of the motor Smallest possible rated current1) of the m.c.b. (miniature circuit-breaker) with C-characteristic A 8 6 4 2 1.6 2 1.6

V 24 DC 48 DC 60 DC 110 DC 220 DC 110 AC 230 AC

max. V 26 53 66 121 242 121 244

min. V 20 41 51 93 187 93 187

W (at DC) 350 350 350 350 350

VA (at AC) 400 400

1) The current inrush in the drive motor can be neglected due to its very short presence

Consumption data of releases


Release Power consumption Operation at DC approx. W 140 140 70 20 AC 50/60 Hz approx. VA 140 140 50 20 10 2) Tripping voltage at DC 85 to 110 % U 70 to 110 % U 70 to 110 % U 35 to 0%U Tripping ranges Tripping voltage or tripping current at AC 50/60 Hz 85 to 110 % U 85 to 110 % U 85 to 110 % U 35 to 0 % U 90 to 110 % Ia

Closing solenoid 3AY15 10 1st shunt release (without energy store) 3AY15 10 2nd shunt release (with energy store) 3AY11 01 Undervoltage release 3AY11 03 Current-transformer operated release 3AX11 02 (rated normal current 0.5 A or 1 A) Current-transformer operated release 3AX11 04 (tripping pulse W 0.1 Ws)

2) Consumption at pickup current (90 % of the rated normal current) and open armature

Siemens HG 11.02 2008

59

Technical Data
Circuit diagrams

SION Vacuum Circuit-Breakers

Basic equipment
X1
21 22 31 32 A1 A2

-S21

21 22 A1

-K1 -K1 -Y9

13 14

-S3

21 22

-M1

M 1= D2 22 21

-K1

A1 A2

-S1

11 12

23

-S4

13 14

21 22

-Y1

A1

-S1

-S1

11 13 21 23 31 33 41 43 51 53 61 63 12 14 22 24 32 34 42 44 52 54 62 64
HG11-2506 eps

24

-S22

X1

Motor Closing and anti-pumping Signal closing 1st shunt operating for motor operating spring charged release mechanism stored-energy mechanism

HG11-2505 eps

A2

Auxiliary switch 6 NO + 6 NC

Additional equipment
X0 X1
21 22 31 32 A1 A2 13 14
HG11-2507 eps

X0 X1

-X0

-K1 -K1 -Y9 -S5

13 14

-S3

21 22
13

-K1

A1 A2

-S6

14

-S1

11 12

-S1

11 13 21 23 31 33 41 43 51 53 61 63 71 73 81 83 91 93 101 103 111 113 121 123 12 14 22 24 32 34 42 44 52 54 62 64 72 74 82 84 92 94 102 104 112 114 122 124

HG11-2508a eps

-S12 X1 X0

13 14

X1 X0

-X0

Closing and anti-pumping for motor operating stored-energy mechanism

Circuit-breaker tripping signal

Auxiliary switch 12 NO + 12 NC

Additional equipment: Releases (for possible combinations see chapter 2 under Secondary equipment)
X0 X1

X0 X1

X0 X1

X0 X1

-Y7
-S1 -Y2
A1 33 34

D1

D2

-Y4
HG11-2510 eps

A1 A2
HG11-2511 eps

-Y6

A1 A2
HG11-2512 eps

-S1

43 44

X1 X0

X1 X0

X1 X0

X1 X0

2nd shunt release

Current-transformer operated release 0.5 A or 1 A

Low-energy currenttransformer operated release 0.1 Ws

Undervoltage release

Legend
K1 M1 R1 S1 S12 S21 S22 Contactor (anti-pumping) Motor operating mechanism Resistance Auxiliary switch Mechanical interlocking Position switches (to de-energize the motor operating mechanism after charging S3 S4 S5 S6 X0 Position switch (anti-pumping) Position switch (for closing spring charged) Electrical closing lock-out Circuit-breaker tripping signal Plug connector, 24-pole or 64-pole X1 Y1 Y2 Y4 Terminal strip, 27-pole 1st shunt release 2nd shunt release Current-transformer operated release (rated normal current 0.5 A or 1 A) Current-transformer operated release (tripping pulse W W 0.1 Ws) Y7 Y9 Undervoltage release Closing solenoid

HG11-2513 eps

A2

-R1

Abbreviations: NC Normally closed NO Normally open

Y6

The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring

60

Siemens HG 11.02 2008

HG11-2509 eps

SION Vacuum Circuit-Breakers

Annex
Contents

Contents

Page

Annex
Inquiry form Configuration instructions Configuration aid

61
62 63 Foldout page

Brandenburg Gate, Berlin, Germany

R-HG11-181.tif

4
R-HG11-180.eps

Switchgear Factory in Berlin, Germany

Siemens HG 11.02 2008

61

Annex
Inquiry form

SION Vacuum Circuit-Breakers

Please copy, fill in and return to your Siemens partner or you can use our prompted online configurator under www.siemens.com/SION

Inquiry concerning

Technical data
Rated voltage o 7.2 kV o 24 kV o 60 kV o 125 kV o 20 kV o 42 kV o 12.5 kA o 25 kA o 800 A o 2500 A o 150 mm o 205 mm o 12 kV o 17.5 kV

Other values o _ _ _ kV o 75 kV o 95 kV o _ _ _ kV o 28 kV o 50 kV o 16 kA o 31.5 kA o 1250 A o 3150 A o 160 mm o 275 mm o 38 kV o 55 kV o 20 kA o 40 kA o 2000 A o _ _ _ kA o 210 mm o 310 mm o 275 mm

o SION standard circuit-breaker o SION slide-in module

Rated lightning impulse withstand voltage Rated short-duration power-frequency withstand voltage

Please

o _ _ _ kV

o Submit an offer o Call us o Visit us

Rated short-circuit breaking current Rated normal current

o _ _ _ kA

Pole-center distance Width across flats

Your address Secondary equipment


Company Dept. Name Motor operating mechanism Street Postal code/city Phone Current-transformer operated release Fax E-mail Undervoltage release Auxiliary switch Low-voltage connection o o _ _ _ V DC o 6 NO + 6 NC o 27-pole terminal strip o AC _ _ _ V, _ _ _ Hz o 12 NO + 12 NC o 24-pole plug o 64-pole plug Closing solenoid 1
st shunt release

For possible combinations see pages 23 to 26 or 32 to 35


Circuit-breaker equipment (only for standard circuit-breaker) o Fixed mounting o With drawout element o Drawout element, contact arms o Drawout element, contact arms, bushings o _ _ _ V DC o _ _ _ V DC o _ _ _ V DC o _ _ _ V DC o _ _ _ V AC, _ _ _ Hz o _ _ _ V AC, _ _ _ Hz o _ _ _ V AC, _ _ _ Hz o _ _ _ V AC, _ _ _ Hz

2nd shunt release

Siemens AG
Dept. Name Street Postal code/city Fax

o Mechanical interlocking o Circuit-breaker tripping signal o Electrical closing lock-out o Operating instructions o English o German o French o Spanish

Application and other requirements

o Please check off

_ _ _ Please fill in

62

Siemens HG 11.02 2008

You prefer to configure your SION vacuum circuit-breaker on your own?


Please follow the steps for configuration and enter the order number in the configuration aid. Alternatively you can also use our prompted online configurator under www.siemens.com/SION.

For configuration of your SION vacuum circuit-breaker

9 10 11 12

13 14 15 16

Instruction for configuration of the SION vacuum circuit-breaker 1st step: Definition of the primary part (see pages 15 to 22 and pages 28 to 31)
Please specify the following ratings: Possible options:

3 A E

1 n n n n n n n n n n n n Z

See page 15 or 28 to

page 22 or 31

See page 23 or 32 See page 23 or 32

See page 24 or 33

See page 24 or 33

See page 25 or 34

See page 25 or 34 See page 26 or 35

See page 26 or 35

Rated voltage (Ur) Rated lightning impulse withstand voltage (Up) Rated short-duration power-frequency withstand voltage (Ud) Rated short-circuit breaking current (Isc) Rated normal current (Ir) Pole-center distance Width across flats These ratings define the positions 5 to 8 of the order number

Ur: Up: Ud: Isc: Ir:

7.2 kV to 24 kV 60 kV to 125 kV 20 kV to 55 kV 12.5 kA to 40 kA 800 A to 3150 A 150 mm to 275 mm 205 mm to 310 mm

3 A E

1 + +

+ + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +

+ + + + + + + + + + + + + + + + + +

3 A E

2nd step: Definition of the secondary equipment (see pages 23 to 26 and pages 32 to 35)
Please specify the following equipment features: Possible options: 3 A E 1

Release combination (position 9) Closing solenoid (position 10) Operating voltage of the releases (positions 11 / 12) Installation accessories (position 13) Motor operating mechanism (position 14) Number of auxiliary contacts (position 15) Design of the control cable connection (position 15) Mechanical interlocking, circuit-breaker tripping signal (position 15) Language of the documentation (position 16) Frequency of the operating voltage of the secondary equipment at AC (position 16) These equipment features define the positions 9 to 16 of the order number

Shunt release, current-transformer operated release and undervoltage release Operating voltages from 24 V DC to 240 V AC Operating voltages from 24 V DC to 240 V AC Fixed mounting; with drawout element, contact arms, contact system; slide-in module Operating voltages from 24 V DC to 240 V AC 6 NO + 6 NC, 12 NO + 12 NC 3 A E 27-pole terminal strip, 24-pole plug connector 64-pole plug connector With or without English, German, French, Spanish 50 Hz/60 Hz 3 A E 1 1 3 A E 1

3 A E

3rd step: Do you have any further requirements concerning the equipment? (Please refer to pages 27 and 36) Should you still need more options than the possible special equipment like halogen-free and flame-retardant or silicone-free version, condensation protection or an additional rating plate, etc., please contact your responsible sales partner.
3 A E 1

3 A E

Siemens HG 11.02 2008

63

See page 27 or 36

Published by and copyright 2008: Siemens AG Energy Sector Freyeslebenstrasse 1 91058 Erlangen, Germany Siemens AG Energy Sector Power Distribution Division Medium Voltage Nonnendammallee 104 13623 Berlin, Germany www.siemens.com/SION For more information, please contact our Customer Support Center. Phone: +49 180 524 70 00 Fax: +49 180 524 24 71 (Charges depending on provider) E-mail: support.energy@siemens.com KG 08.08 0.0 66 En 6101/13187 103217
All rights reserved. If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract.

Responsible for Technical contents: Siemens AG, E D MV C Berlin General editing: Siemens AG, E CC MCC R Erlangen
R-HG11-182.tif

www.siemens.com/energy

Você também pode gostar