Dipl.-Ing Rainer Bufe

AirSystem
Founded in: 1958 Employees: 48 Products: Aircontrol LabControl Medicine electronic Consumer electronic Own research and development Own production All products made in Germany

LabSystem

Clean room

Company details

AirSystem
1992 - SMD in line production 1995 - Fume hood monitor 1997 - Fume hood controller (1 st. generation) 1998 - Sash controller 1999 - VAV for supply and exhaust air (AirSystem) 2002 - Clean room controller 2006 - Fume hood controller (5 th. generation)

LabSystem

Clean room

2008 - Airvolume priorised pressure controller VCP (EP-patent)

Product overview

LabSystem - AirSystem

AirSystem

LabSystem

Clean room

Typical clean room

AirSystem
changing room 5 Pa

LabSystem
35 Pa overpressure

Clean room

personnel lock 15 Pa 25 Pa

clean room

clean room

grey room

material lock 5 Pa

equipment

Laboratory Air change rate Room = 150 m3 8 times 1.200 m3/h

clean room

0 Pa

Clean room 60 - 600 times 9.000 90.000 m3/h

Room pressure and air change rate

AirSystem
7,00 m
Clean room (+) = overpressure

LabSystem
Mechanical CAV

Clean room

Tolerance 15 % (one CAV) Tolerance 22 % (two CAVs)

Room height = 3,06 m Room volume = 150 m 3 Room leakage 200 m3/h

Supply air 1.500 m3/h

7,00 m

Exhaust air 1.300 m3/h

VAV or CAV

VAV or CAV

Electrically operated CAV/VAV Tolerance 5 % (one CAV/VAV) Tolerance 7,5 % (two CAVs/VAVs)

35 Pa overpressure

Room pressure with Air Volume Controller

AirSystem
2

LabSystem

Clean room

p =

V A 3600

Bernoulli - formula
= air density 1,2 kg/m3 = constant value 0,72

General views

AirSystem
VSUPPLY VEXHAUST = VDIFF 1500 m3/h - 1300 m3/h = 200 m3/h => 35 Pa with 0,01 m2 room leakage With tolerances 7,5 % 1500 m3/h 7,5 % = 112,5 m3/h VMAXDIFF = 200 + 112,5 = 312,5 m3/h VMINDIFF = 200 - 112,5 = 87,5 m3/h

LabSystem
2

Clean room
2

p =

V A 3600

pMIN=6,8 Pa

pMAX=87,2 Pa

pressure range 6,83587,2 !!! => not acceptable!!!


8

Detailed view (with tolerances)

AirSystem
RESULT:

LabSystem

Clean room

Room pressure with CAV/VAV - Controller


Even with very low tolerances not suitable in airtight rooms (small room leakage) air volume, room volume and room leakage have strong impact on differential pressure

SOLUTION:

Room pressure with pressure controller CRP


Better than CAV/VAV - Controller but even not satisfying in airtight rooms (very small room leakage) be careful with high air volume and very small room leakage

Room pressure with VAV - Controller

AirSystem
Very important:
Floor (-) = underpressure

LabSystem
CAV
Room exhaust air (constant)

Clean room
Roon exhaust air (constant)

Air lock (+) = overpressure

CAV

Room 1 (+) = operpressure against air lock

use common reference - ----point for measuring the -------underpressure (-) reference point must be -------nonventilated use actuators without ------hystersis (instaed of -.-analogue input direct -----------drive actuator) use actuators with high --- ---resolution (< 0,5 => 0,5 %)

24V AC

dP

+
CRP

Room supply air (variable)

24V AC

dP

+
CRP

Room supply air (variable)

instable control

24V AC

dP

+
CRP Room 2 (+++) = overpressure against floor
Room exhaust air (constant)

Room supply air (variable)

CAV

Room pressure with CRP - Controller

10

AirSystem
7,00 m
Clean room (+) = overpressure

LabSystem

Clean room

Electrically operated CAV/VAV and CRP Tolerance 5 % (one CAV/VAV) Tolerance 1,11 % with actuator resolution 1 (usual value) Tolerance 0,5 % with CRP and direct drive actuator from SCHNEIDER (resolution < 0,5 and non hysteresis)

Room height = 3,06 m Room volume = 150 m 3 Room leakage 200 m3/h

dP

7,00 m

Exhaust air 1.300 m3/h

CRP

Supply air 1.500 m3/h

VAV or CAV

35 Pa overpressure

Room pressure with CRP - Controller

11

AirSystem
=> 35 Pa with 0,01 m2 room leakage

LabSystem
2

Clean room
2

With tolerances 0,5 % (CRP-resolution) 1500 m3/h 0,5 % = 7,5 m3/h VMAXDIFF = 200 + 7,5 = 207,5 m3/h VMINDIFF = 200 - 7,5 = 192,5 m3/h

p =

V A 3600

pMAX=38,4 Pa pMIN=33,1 Pa

pressure range 33,13538,4 => acceptable with given room -------leakage 0,01 m2

Room pressure controller CRP

12

AirSystem
RESULT:

LabSystem

Clean room

Room pressure with pressure controller CRP


Acceptable with high resolution actuator and non hysteresis actuator in airtight rooms (room leakage > 0,01 m2) not suitable in airtight rooms (room leakage < 0,01 m2)

SOLUTION:

Air volume priorised constant room pressure controller VCP (European-Patent)


Highest accuracy in the market with electrical controller Very stable control even in airtight rooms with room leakage < 0,001 m2

equals to 1mm clearance between door frame and door leave!! Room pressure with VAV - Controller
13

AirSystem
1500 m3/h 7,5 %
Floor (-) = underpressure 24V AC VCP-L dP

LabSystem

Clean room

Electrically operated CAV/VAV and VCP Tolerance 5 % (one CAV/VAV) Tolerance 7,5 % (two CAV/VAV) Tolerance 1,11 % with actuator resolution 1 (usual value) Tolerance 0,5 % with VCP and direct drive actuator from SCHNEIDER (resolution < 0,5 and non hysteresis)
Clean room (+) = overpressure

room air volume

+
VAV-L

room pressure

LON-NETWORK, FTT-10A

1500 m3/h 35 Pa overpressure

112,5 m3/h 0,5 %


R Building management system

Volume priorised pressure controller VCP

14

AirSystem

LabSystem

Clean room

=> 35 Pa with 0,001 m2 room leakage => Air volume VDIFFERENTIAL = 20 m3/h With tolerances: 1. Air volume: 1500 m3/h 7,5 % = 112,5 m3/h 2. Room pressure: 112,5 m3/h 0,5 % (VCP-resolution) = 0,5625 m3/h 35 Pa => VDIFFERENTIAL = 20 m3/h VMAXDIFF = 20 + 0,5625 = 20,56 m3/h VMINDIFF = 20 0,5625 = 19,44 m3/h pMIN=33,75 Pa pMAX=37,75 Pa

pressure range 33,753537,75 => very good result with given ----- room leakage 0,001 m2 or ---------even smaller

Volume priorised pressure controller VCP

15

AirSystem
Very important:
use common reference - ----point for measuring the -------underpressure (-) reference point must be -------nonventilated use VCP for airtight rooms-- with small room leakage use actuators with high --- ---resolution (< 0,5 => 0,5 %)

LabSystem

Clean room

Volume priorised pressure controller VCP

16

AirSystem

LabSystem

Clean room

Advantages of the VCP and room pressure control via bypass:


very high resolution of the actuator in the bypass. Controlling of the room pressure via actuator with Direct-Drive-Modus (no hysteresis, resolution < 0,5 ) avoids oscillating of the system multitasking system with one common microprocessor unit and internal communicating between air volume control device and pressure control device max. allowed range of 3 Pa always possible, even over different pressure steps suitable for controlling of safety laboratory class S1-S4 as well as clean room class A-D for controlling laboratory class S4 it is mandatory for safety reasons to use redundant systems
17

Volume priorised pressure controller VCP

AirSystem
More advantages of the VCP:

LabSystem

Clean room

sudden loss of room pressure (open of door or window) will be recongised and the damper gets freezed for a certain time (max. 20 s) no door contacts needed very precise and stable room pressure control system room pressure damper (bypass) always between 2080 % => good control position complete parametrising via service module SVM100 or PC-software PC2500 suitable for safety laboratory with very high airtight doors and rooms (e.g. animal laboratory) suitable for supply or exhaust air systems BMS controlling via network. LON, BACnet or Modbus available
18

Volume priorised pressure controller VCP

AirSystem

LabSystem

Clean room

Reference project: Paul-Ehrlich-Institut, Langen safety laboratory class S3, animal laboratory for BSE-research

Reference project with VCP

19

AirSystem

LabSystem

Clean room

Reference project: Paul-Ehrlich-Institut, Langen safety laboratory class S3, animal laboratory for BSE-research Room specification:
- Room volume 48,7 m - Room air change rate 8/12/16 h-1 (Night-Day-Cleaning) - Exhaust air volume 390-585-780 m/h - Pressure control value - 40 Pa - External differential pressure transmitter with 2----- analogue outputs (controlling and monitoring via LON-network to Honeywell-BMS)

Reference project with VCP

20

AirSystem

LabSystem

Clean room

VCP- drawing with additional manual damper

21

AirSystem

LabSystem

Clean room

Remote maintenance and diagnosis via Internet/Intranet Easy administrating of error- and maintenance reports

Building management system Intranet Infranet Internet

22

AirSystem Chemie/Pharmacie
AVENTIS AG BASF AG BAYER AG BOEHRINGER Ingelheim BYK GULDEN CLARIANT HOFFMANN LA ROCHE AG GOEDECKE / PFIZER GRNENTHAL NOVARTIS AG SCHERING AG

LabSystem Universities
Freiburg
Potsdam/Golm Regensburg Tbingen Wuppertal Zrich

Clean room

Instituts
MAX-PLANCK-INSTITUT FRAUNHOFER-INSTITUT ADLERSHOF and more

LabSystem Reference list

23

AirSystem

LabSystem

Clean room

Our main customers - Fume cupboard maker

24

AirSystem

LabSystem

Clean room

Our main customers projects

25

AirSystem

LabSystem

Clean room

Thank you for your attention


More information www.schneider-elektronik.de rainer.bufe@schneider-elektronik.de Discussion Questions

Welcome at our Stand Hall 6.2, Stand C27-C29

26

Você também pode gostar