Você está na página 1de 20

MATERIALS 1.

General copper tubes, which are used for positives pressure and suction pipelines, shall be of as drawn seamless tube, manufactured in accordance with British standard BSEN 1057 (seamless round copper tubes for medical gases or vacuum), AS/NZS 1571, EN 13348, or B 280 for medical gas purposes. Brand/manufacturer: CRANE & ENFIELD or KEMBLA NOTE : the installation of suction pipelines using PVC and other similar plastics material can results in cracks and leakage as the materials degrade with age. 2. Oxygen compability of components. All components of a pipeline system for all medical gases and suction shall compatible with oxygen under normal working conditions and shall be clean and free from oil, grease and particulate matter. Components shall included, but not be limited to, containers, pipes, valves seats, lubricants, fitting and gaskets. NOTES: Appendix D gives recommendations for the use of materials in pipeline systems Compability involves both combustibility and ease of ignation. Materials that burn in air will burn violently in pure oxygen, particularly oxygen under pressure. Similarly, materials that can be ignited by friction at a valve seat or stem packing or by adiabatic compression produced when oxygen at high pressure is rapidly introduced into a system initially at low pressure. The requirement of this clause includes components for gases other than oxygen or oxygen mixtures because it is difficult to segregate materials in stores and particularly on construction sites during installation. 3. Cleaning of pipelines and components General as all pipe supplied in accordance with AS/NZS 1571 are factory cleaned, degrease and capped prior to delivery, the pipes shall not be cleaned on site, except for necessary purging operations to remove any particles entrained during installation. Valves and fitting shall be delivered clean, and shall be protected from contamination during delivery to the site. All valves shall have labels attached, stating cleaned for oxygen service Particular care shall be exercised in the storage and handling of all pipe fittings. After cutting, pipes shall be temporarily capped or plugged to prevent contamination while awaiting installation. On site communication when a fitting or other component becomes contaminated onsite, it shall be returned to the supplier for cleaning.

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 1 of 20

REQUIREMENTS FOR PIPELINES 1. General Pipelines and fittings sizes shall be selected to provide the required design flow of the entire health care facility. 2. Pipeline design pressure and flows The nominal design working pressure shall be 415 kPa for medical gas supply, 60 kPa for medical suction and 1400 kPa for surgical tool gas supply. Flow requirements should be determined on the basis of discussions with the health care facility to ascertain the expected and projected gas usage and number of terminal units required, as the number of terminal units required depends on the particular health care facilitys requirements. 3. Surgical tool gas The gas used to drive surgical tools shall be medical breathing air, with a water content of not more than 25 ppm NOTES : i. This level of dryness cannot be achieved by conventional refrigeration drying. ii. Nitrogen and nitrous oxide do not support life and cannot be differentiated by the commonly used oxygen analyzer. Because of the ever present risk of error of connection at the input to a pipeline or cross connection (or both) in the pipe-work (following alterations), medical nitrogen is not recommended for used with gas powered tools in healthcare facilities. Medical breathing air for surgical tools should have a specific outlet. Tools gas is usually supplied at a pressure about 1400 kPa which may damage ventilators and other equipment if used as medical breathing air. iii. Cylinder manifolds are generally the preferred method of supply for surgical tool gas as the dryness requirement of 25 p.p.m of moisture is usually difficult, requires frequent or continuous monitoring and is expensive to attain, if using compressors. 4. In-line fittings and valves Where in line fittings and valves are used for pipelines the fittings shall not be less than the bore of the piping connected to them. Fittings and joints which permit disconnection shall not be installed in any buried pipeline. Couplings shall at all times be easily accessible for inspection and maintenance. 5. Surgical tools gas regulator Surgical tool gas outlets should have a variable regulator immediately upstream of the terminal units. Adjustment of this regulator should be available to medical and nursing staff within the operating room.

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 2 of 20

PIPELINE SHUT OFF VALVES 1. General All valves in the high pressure side in a medical gas pipeline system shall be slow opening so that velocity surges are not introduced into the pipeline. Other valves in the medical gas pipeline system, except those in the source of supply and those in terminal units, should intrinsically indicate the valve status. NOTE : Ball and butterfly valves are unsuitable on the high pressure side, prior to the first stage regulator. 2. Valve boxes General, Isolating valves which if unprotected and are readily accessible to unauthorized persons, shall be installed in secure valve boxes, preferably located for easy use by Fire Brigade Officers. Box windows, Boxes shall have transparent windows, capable of providing access, large enough to allow visual confirmation of valve status and be able to permit manual operation of the valve. For easily action and maintenance pull out access window for opening the box is recommended. The window/door shall be able to provide security with valves in either the open or closed position and be kept in a secured position at all times, except when valves are being opened by an authorized person. NOTE: It may be necessary to remove the handles of valves while they are in the off position so that the box may be secured. Labelling, All valves and valve boxes shall carry the name of the gas and the area served. The box shall be labeled caution (name of medical gas) valves, do not closed except in emergency or for authorized work. (Name of medical gas) supply to (area served) Lettering shall be at least 6mm high, of vertical block type block type characters and shall be easily distinguishable from the background. Valve box technical specification for MRCCH: The wall box unit has a front surround to suit varying wall surface thickness. It also features a pullout polycarbonate access window. The box can have the access window in place with the valves in either the open or closed position. Fully galvanized with finishing polyester powder coating Fitted with pressure gauge and pressure switches and 3 way valves Each box is factory assembled to specific requirements :

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 3 of 20

Valve size 15mm 20mm 25mm 32mm 40mm 50mm

Copper tube size 12.70 OD 19.05 OD 25.40 OD 31.75 OD 38.10 OD 50.80 OD

Medical Gas Line valves (lockable) Materials: Body and side plates grade 385 brass Ball Grade 385 brass, hard nickel plated Stem Grade 303 stainless steel Seals precison moulded nitrile co polymer Clamp plates & handles grade 1018 steel Tail pipe, copper tube to relevant standard Operation rotate handle through 90 degree between stop Maximum working pressure: Valve size F tail pipe outside diameter & type Max working pressure (kPa) 2400 kPa 2400 kPa 2400 kPa 2400 kPa 2400 kPa 1800 kPa

15mm 20mm 25mm 32mm 40mm 50mm

12.70 OD x 0.91 AS 1432 type B 19.05 OD x 0.91 to AS 1432 type B 25.40 OD x 1.22 to AS 1432 type B 31.75 OD x 1.22 to AS 1432 type B 38.10 OD x 1.22 to AS 1432 type B 50.80 OD x 1.22 to AS 1432 type B

3. Positioning All valves should be positioned for convenient operation The main medical gas and suction supply pipelines shall be provided with an isolating valve adjacent to the source. Where the source supplies more than one building, isolating valves to control supply to each building may be appropriate. An isolating valve shall be provided in each gas pipeline serving each anaesthetizing location and special care areas. NOTES: i. For the purpose of this clause, the operating room and its associated anesthetic room are considered as one anaesthetizing location. ii. For servicing, it may be desirable to have additional isolating valves for the group of anaesthetizing locations or special care locations.

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 4 of 20

PRESSURE GAUGE Mechanical gauges shall be a minimum 30mm diameter and shall include colour sectors clearly indicating the acceptable working range. The sectors shall be as follows for the respect nomina system pressures: a. 415 kPa nominal system pressure (oxygen, nitrous oxide, breathing air, carbon dioxide, gas mixtures, eg. 50/50 nitrous oxide/oxygen mixtures). 0 375 kPa ..........red 375 460 kPa ................... green 460 to end of scale ....... red 1400 kPa nominal system pressure (surgical tools gas) 0 to 1260 kPa ........................... red 1260 to 1550 kPa ...................... green 1540 to end of scale ................... red -60 kPa nominal system pressure (vacuum) 0 50 kPa .................................... red -50 kPa to end of scale ...................green

b.

c.

Gauge layout and colour densites should be chosen to give maximum contrast between gauge face and level indicator (eg. needle). Electronic pressure representation screens, whether of the bar type or numerical value type shall clearly indicate that the displayed value is within or outside the acceptable pressure limits. The display shall be clearly visible under all background lighting conditions.

TERMINAL UNIT AND CONNECTORS Each terminal unit for medical gas shall be equipped with a self sealing valve, except for ventury ejector suction which shall be controlled with a flow control valve. Terminal unit shall be gas specific and not interchangeable with other connectors in the health care facility Terminal unit shall be provided with permanent identification which shall take the form of background colour coding in accordance with AS 2700 /refer to pantone matching system) : Oxygen white Breathing air black & white Surgical tool air aqua (pantone 632) Nitrogen black Nitrous oxide ultramarine (B21 or equal to pantone 293) Suction primrose (Y21 or equal to pantone 100) AGSS yellow and blue (Y21 & B21 BS5682) Carbon Dioxide green grey (N32 or equal to pantone 5935)

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 5 of 20

All gas specific components of the terminal unit shall be permanently identified with gas name in 3mm minimum high letters and shall be legible at a distance of 4 metres. Each terminal unit except for suction terminal units shall be provided with a secondary shutt of valve incorporated in manner that will allow maintenance of the maintenance of the terminal unit without loss of gas from the system. Where multiple terminal units are installed, a minimum of 100mm between individual outlet center shall be provided to facilitate equipment manipulation, except multiple terminal units sited on operating room pendants and booms, the minimum distance between outlet center may be reduced to centres of 70mm.

Technical Specifications of medical gas outlet for MRCCH : SIS type terminal unit to Australian Standard 2896 Solid Brass body and indexing sleeve Front removable main valve for fast and easy seal replacement Side entry gas supply tube positioned at 45 degree to suit multiple installations Secondary valves that automatically shuts off gas supply when main valve is removed Low profile body 20mm allows back to back installation in shallow depth walls Complete with flush mounted wall panels manufactured from 1,5mm grade 302 stainless steel

ALARM The alarm system has two function, one function is the normal operating alarms and the other function is the emergency alarms. These alarms would include the diagnostic signals of the alarm itself to cover the following status level : a. All systems normal signal indicated that all gas supplies are operating within designed limits that the alarm system it self is operating normally. It is indicated by a green colour with audible alarm off. b. All systems normal signal but action required. Indicates that one or more gas supplies have reached a point where operator action e.g reordering of gas is required. It is indicated by green colour off and amber colour on (flashing) with the audible alarm on the suitable area. c. Emergency condition signal. Indicates an abnormal alarm conditions. This will usually be activation of the emergency supply. If unattended, it could elevate into a failure of supply. It is indicated by extinction of the green and amber colour. The red colour shall be on (steady) with the audible alarm on. This alarm will be in continuous observation areas and may alaso active in some special care area. d. Supply failure signal. Indicates a high priority alarm condition which requires immediate action. It is indicate by the extinction of the green and
G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc Page 6 of 20

e.

amber colour. The red colour shall be on (flashing) with the audible alarm on. This alarm will be in the continuous observation areas and also will be activate in special care areas. Information/diagnostic conditions signal. Indicates a routine action is required to maintain gas supplies or a malfunction of the alarm system has occurred. This signal may be linked of the gas signals or be shown on a separate panel in the same or separate location.

Each signal shall be appropriately labeled with a description of its function and be clearly visible under all background lighting conditions, including no light If the audibly of the alarm is adjustable the set point shall be indicated continuously or on operator demand. At minimum setting the volume should be discernible to a person with normal hearing, above a background white noise level of 55 dBA at a distance of 3m from the alarm panel. If means of muting the audible component of the alarm provided, then the muted period before resounding shall not exceed 4h Visible indication of status and audible signal for low pressure and failure shall be installed for the medical gas pipeline system. Each visible signal shall indicate normal conditions and power on with green colour, secondary supply with amber and emergency condition/supply failure red. Flashing lights for indication of activation of the secondary supply and for supply failure shall be included For medical breathing air and venture suction, the alarm shall operate when the line pressure falls to 20% below the nominal working pressure. For vacuum generated suction, the alarm shall operate when the suction pressure falls 20% from the normal working pressure (changing from 80kPa gauge pressure to 73kPa gauge pressure) Area alarm technical specification for MRCCH: The area alarm Panel is designed to monitor up to 8 local inputs. Both audible and visual indication of any alarm condition is provided. Networked input information is obtained from other panels connected to the network. The main electronics PCB is mounted to a metal backing plate. The front panel present the operator with the following items: Three LEDs (1 x Red, 1 x Amber, 1x Green) Three switches (Test, Mute, Audio level check) A single digit 7 segment LED display A twenty digit 5 x 7 dot matrix vacuum fluorescent display Each local or networked input can be programmed to have a unique message assigned to it which will be displayed when the inputs is in the alarm condition.

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 7 of 20

In addition to the message, one of two LEDs can be selected to provide a steady or flashing status. If non-alarm condition is satisfied on all inputs used, a common system normal message is displayed along with the green LED If more than one alarm condition exists simultaneously, the appropriate messages are displayed in sequence, however the highest priority LED (Red) will always be displayed should one of the messages require it. This warns the operator that an emergency message is contained in the rotating sequence even if the current message being displayed is of a low priority. The number of messages in alarm is also displayed on the single digit 7 seg. Display. If there are more than 9 alarm messages the 7 seg. Display will flash 9. The audible alarm is sounded with each new alarm condition detected. It can be muted using the mute switch, however it will sound again after a predefined time should the alarm condition still exist. Local input connections and network connection to the alarm is made via plug in terminal blocks and 8 way plug/socket respectively. The terminal blocks and 8 way sockets are mounted on a separate dedicated PCB that can be suitably mounted at the installation wiring stage. This allow the main electronics to be kept safely out of harms way until final commissioning of the system, at which point, the main electronics is plugged into the connector PCB via a ribbon cable and a network link cable. If networking is not required, it can be disabled by removing a plug in link on the connector PCB, the unit then functions as a local 8 input stand alone alarm panel. Power Consumption: o Operating voltage : 12 Volts AC +/- 10% o Current consumption : -0,6 Amps o Power consumption: 7 watts o Inputs: all input device should be of a passive nature o No externally generated voltages should be applied o Maximum current supplied by an input cable: 150 ohms o Relay output: alarm status relay contact rating = 1A @30 V DC o Serial output format: 1200 Baud, 8 Bit, 1 Stop, No parity o Cable type Category 5 UTP Solid o Network frequency : 78 kbps o Socket connections: pin numbering runs left to right, applies to both 4 way RS232 socket and 8 way network sockets:

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 8 of 20

Master Alarm technical specification for MRCCH : The Master Alarm Panel is designed to monitor up to 24 local inputs and up to 150 networked inputs. Both audible and visual indication of any alarm condition is provided. Networked input information is obtained from other panels connected to the network. The main electronics PCB is mounted to a metal backing plate The front panel presents the operator with the following items: - A 40 digit 5 x 7 dot matrix vacuum fluorescent display - Three LEDs, 1 x Red, 1 x Amber, 1 x Green - A single digit 7 seg. Display Each local or networked input can be programmed to have a unique message assigned to it which will be displayed when the input is in the alarm condition In addition to the message, one of two LEDs can be selected to provide a steady or flashing status. If the non-alarm condition is satisfied on all inputs used, a common system normal message is displayed along with the green LED. If more than one alarm condition exists simultaneously, the appropriate messages are displayed in sequence, however the highest priority LED (Red) will always be displayed should one of the messages require it. This warns the operators than an emergency message is contained in the rotating sequence even if the current message being displayed is of allow priority. A single digit seven segment display is also provided to display how many messages are in the queue, if there are more than 9 messages, the number nine will continue to be displayed and will flash. The audible alarm is sounded with each new alarm condition detected. It can be muted using the mute switch, however it will sound again after a predefined time should the alarm condition still exist. Local input connection to the Master Alarm is made via plug in terminal blocks. The terminal blocks are mounted on a separate dedicated PCB that can be suitably mounted at the installation wiring stage. This allows the main electronics to be kept safely out of harms way until final commissioning of the system, at which point, the main electronics is plugged into the connector PCB via a ribbon cable. Network connection is made directly to the main electronics via an 8 way plug. Master alarm programming is done via a 4 pin RS232 plug and socket that couples it to a computer. This feature permits full custom set up of messages, LEDs, input type, Audio Repeat Period, etc.

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 9 of 20

SOURCE OF SUPPLY

1. GENERAL The source of supply shall be : a. a system of cylinders and necessary supply equipment assembled as described in clause 4 b. a cryogenic liquid supply system in accordance with clause 8 c. a medical breathing air or medical suction system as described in clause 2.9 and 2.10 respectively The source of supply shall be protected from over pressurization as described in clause 2.7 2. PROVISION IN CASE OF FAILURE OF SUPPLY Special care location for medical gas pipeline system in special care locations where patients are dependent on specific gases, a complete alternative local source for the area, of such dependent gas or gases shall be installed if only a local area failure alarm is provided. If in addition an emergency gas supply alarm is provided, the capacity of the emergency gas supply shall be such that it should continue to supply for a time estimates to be twice that required to obtain an additional gas supply. NOTES : 1. Medical advice within the health care facility should be sought on the degree of protection of each gas supply for each special care location. Normally, areas with patients undergoing ventilation should have at least the oxygen and medical breathing supplies protected. In a high dependency unit, only oxygen may be protected. In coronary care, the level of protection may be two portable cylinders as alternative sources. 2. Gas consumption should be estimated as normal average consumption, but the time taken to obtain an alternative source should be estimated on a worst case basis, i.e. as occurring late at night, on holidays or weekends. Cryogenic liquid systems In cryogenic liquid systems an inlet to the system for connecting a temporary auxiliary source of gas supply for emergency situations shall be incorporated in a location that is easily accessible as a service facility inlet. The inlet shall be physically protected to prevent tampering and unauthorized access and shall have a gas specific inlet. Additional service facility Consideration should be given to a second service facility inlet for oxygen, remote to the primary to the primary source of oxygen, ideally situated adjacent to the user areas, and adequately protected and accessible to connection of an emergency supply. 3. CYLINDERS AND CYLINDER VALVES Cylinders and cylinder valves shall be designed, constructed, tested, and maintained in accordance with AS 2030.1.1.

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 10 of 20

4. CYLINDER SUPPLY SYSTEM General The cylinder supply system shall consist of an automatic changeover manifold with both working (primary) side and secondary side of the manifold containing each a minimum of one working days supply, unless delivery schedules indicate that greater volumes should be held. Automatic Manifold The automatic manifold shall be of a design and material suitable for the pressure, gas and service conditions involved and shall be connected to the gas supply cylinders by flexible leads manufactured. This unit simultaneously reducing the cylinder pressure and changing the supply from one bank of cylinders to the other when cylinder pressure in selected primary bank falls to a non usable level. Pressure switches between the unit are used to signal via separately available remote display unit(s), the status of the system. A separate inlet port is provided to allow servicing of all components of the console without interrupting supply to patients. All units are pressure tested prior to delivery and come complete with a maintenance and spare parts manual. The high pressure components of the units are suitable for pressure up to 200 bar. Technical specification automatic manifold for MRCCH : Maximum inlet (cylinder) pressure . Outlet line pressure : a. Oxygen/Medical Air/Nitrous Oxide ...... b. Surgical tool air ...... Outlet connection : Male 5/8 SAE flare Emergency inlet connection .. Sleeve index gas specific as per AS 2896 Terminal unit Nitrous oxide Oxygen Medical air Tool air M16 x 1.5 M18 x 1.5 M20 x 1.5 M20 x 1.5 23000 kPa

450 kPa 1450 kPa

Header block connections ..

Design capacity for : Oxygen central N2O central : N2 central :

: 2 x 10 cylinder 2 x 3 cylinder 2 x 3 cylinder

Manifold isolation The manifold system shall be provided with an isolating valve in the low pressure reticulation piping. A service facility connection shall be provided with an isolating valve in the low pressure reticulation piping. A service facility connection shall be provided for use during manifold maintenance or in the event of failure of the manifold pressure regulators.
G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc Page 11 of 20

Manifold reset The manifold shall, in a single action, reset both the primary and secondary sides to their alternative supply pressures. Manifold headers Each cylinder connected to the system shall be provided with an individual header block incorporating a non return valve to minimize the loss of gas in the event of cylinder lead failure. Each header shall have a gas specific threaded nipple for the connection of the cylinder lead. Manifold control panel The control panel shall contain provision for selection of the primary and secondary bank of cylinders and shall contain clear operating instructions. Cylinder rack The cylinders on a manifold should be mounted upright in a rack with safety retaining chains of straps. Marking of maximum working pressure The maximum working pressure of the manifold shall be prominently marked on the control panel above each group of working cylinders and on all detachable components of the manifold system e.g. cylinder leads modular headers. Cylinder lead Each gas supply cylinder shall be connected to the manifold system by a replaceable flexible lead manufactured from material which are compatible with the gas, and suitable for the pressures and service conditions involved. Non metallic flexible leads shall be fitted with restraining cable or equivalent to prevent hose whip in the event of lead failure. At the cylinder end, the lead shall have a brazed-on or otherwise permanently attached gas specific yoke or screwed gas specific in accordance with AS 2472. Non metallic leads for oxygen service shall have 5 m sintered filter, constructed from a copper base alloy (monel, copper, brass, or bronze material) fitted to the inlet of this yoke or connection. At the header block end, it shall have a brazed-on or otherwise permanently attached ferrule. NOTES : Non metallic flexible leads made of chlorinated or fluorinated hydrocarbons are not suitable for use with oxygen or nitrous oxide for medical use. Emergency gas supply For oxygen and medical breathing air gas pipeline system where the source is a cylinder manifolds that supplies one or more special care locations, the source should have an emergency supply. Such supply may be the last portion of the gas in the secondary cylinder bank. 5. REGULATORS Source, main and secondary pipeline pressure regulators (where fitted) shall together be capable of maintaining the required pressure when delivering flows.

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 12 of 20

NOTE: Heating of pressure control regulators or associated pipework may be necessary under high-flow conditions to reduce frosting and condensation within the control equipment. Overheating should be avoided. A filter shall be inserted in the line upstream of the regulator. 6. DESIGN OF GAS CONTROL SYSTEMS Control system shall be designed so that regulators, relief valves, safety valve, pressure alarm sensors and changeover valves can be maintained and serviced without interrupting gas supply to the pipeline distribution system. All supply systems shall have a service facility placed so that appropriate access is achieved for connection by compressors or alternate sources of supply such as mobile compressors, manifold cylinders or vacuum-insulted evaporator (VIE). This service facility shall be protected against unauthorized access.

7. DESIGN OF GAS CONTROL SYSTEMS Primary pressure safety valve A primary pressure safety valve shall be installed downstream of the first pressure regulator in each supply line where the service pressure exceeds 2000 kPa. It shall be capable of protecting line pressure regulators from pressures exceeding design limits. Line pressure safety valve A line pressure safety valve shall be set to lift at a pressure of between 30% and 40% above nominal working pressure and shall not allow the pressure within the system to exceed 100% above nominal working pressure under any conditions. The distribution system shall always be in functional continuity with a pressure safety valve. Exhaust Exhaust from both safety and relief valve shall be vented to a safe place. Venting should preferably be discharges directly to a safe place outside the building.

8. CRYOGENIC SYSTEMS General The cryogenic supply system shall consist of at least three sources of supply, namely primary, secondary and emergency supply. Secondary supply The secondary supply, which is contained within the liquid oxygen cryogenic vessel, should contain at least an average days requirements unless delivery schedules indicate that a greater volume should be held.

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 13 of 20

Liquid Oxygen Stationary Tank specification : Type : vertical Net liquid : 1490 gallons (= 5640 litters) Dimension Height : 4.8 meters Diameter : 1.9 meters Weight Tare : 4763 kgs Oxygen : 11249 kgs Max. working pressure : 250 psig (17.2 bar/1724 kPa) Emergency supply The emergency supply should contain at least an average days requirements unless delivery schedules indicate that a greater volume should be held. The supply shall be so arranged that, when operating, the gas supply to the pipeline distribution system can be maintained indefinitely without interruption. The emergency supply shall consist of at least one of the following systems: a. A cylinder manifold containing at least two banks of cylinders b. A system of permanently manifold cylinder contained in road trailers or packs c. A system of cryogenic vessels or containers e.g vacuum insulted evaporators (VIEs) portable liquid containers, pallet tanks. Regardless of which system is selected, the contents of the emergency supply shall be monitored continuously and shall active an alarm on the warning system when a loss of 25% of contents is detected. Primary main check valve Cryogenic supply system shall have a non-return valve in the primary pipeline, upstream of the point of intersection with the emergency supply pipeline. Cryogenic liquid vessel connections Cryogenic liquid vessel fill connections shall be gas specific and non interchangeable between services to avoid risk of liquid nitrogen or argon being filled into a liquid oxygen vessel, or vice versa. Adaptors shall not be used. 9. MEDICAL BREATHING AIR SYSTEM The central supply system for compressed medical breathing air shall supply air of a minimum purity as specified in AS 2586. It shall be installed in accordance with the electrical requirements of AS 3000. A minimum of two air compressors identical shall be installed, each shall be capable of supplying the design flow rate of compressed air on its own. Noise generated from the compressed air plant shall cause sound pressure levels in adjacent areas to exceed levels specified in AS 2107

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 14 of 20

Vibration generated from the compressed air plant shall not exceed the levels specified in AS 2625, parts 1-4. Where compressed air is supplied by water scaled compressor in order to guarantee purity, appropriate eliminator shall be installed for water droplets, solids and aerosols. Compressor with oil lubricated compression chambers shall not be used. After coolers capable of cooling compressed air to within 15 degree Celsius of the temperature of the cooling medium should be installed between each compressor and the air receivers. The after cooler shall be fitted with an automatic drain trap complete with a by pass for manual draining. Air receivers One or more air receivers complying with the design requirements of AS 1210 shall be installed in the system. To ensure continuity of medical breathing air supply when the receiver is shut down for survey or maintenance, a manual valve by pass facility shall be installed. The nominal volume of the receiver and pipework should approximately the design flow rate volume per minute of the system. Receiver capacity shall be such that each compressor start less than 10 times per hour during normal working conditions. Protective coatings shall not be applied to the internal surface of air receivers. Air dryness Air dryness shall be achieved as follows : a. Air drying air shall be dried by duplex driers to a dew point of less than the minimum recorded ambient temperature or a maximum dewpoint of 2 degree celcius at pipeline pressure whichever is the drier. The performance of the driers shall be such that dryness can be achieved with one drier removed for servicing. b. Alarms an alarm should be included in the system to identify when pipeline humidity exceeds dryness limits. This alarm shall be located in an appropriate place for timely intervention by regular maintenance staff. Air inlet and filtration shall be provided as follows : a. Air inlet to compressors A separate air intake with an intake filter shall be provided for each compressor. Filters shall be type 1 (dry) complying with AS 1324. b. Final filters A duplicated final filter assembly complete with isolating valves and pressure differential gauge shall be provided in the pipeline after the drier, arranged to enable maintenance or replacement of either filter without interruption to the medical breathing air supply. Each filter shall be sized for not less than the design flow rate. Filter medium shall at least be type 1 (dry) complying with AS 1324, with a penetration not exceeding 0,5% of test dust no. 1, when tested in accordance with AS 1132.5 Air pressure control Duplicate pressure reducing valves, each sized for the full system requirement shall be provided in the piping system prior to the plant room distributor header. Air compressor control Control shall be arranged so that compressors will supply the system in turn or simultaneously on demand. Controls shall be provided to activate any additional units
G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc Page 15 of 20

automatically should the lead unit of the system be incapable of maintaining adequate supply. Controls shall be arranged so that a failure of one compressor control system will not interfere with the correct operation of the remaining plant. Malfunction or incapacity to meet demands shall initiate any alarms. Air compressors shall each be controlled by an independent pressure switch with adjustable differential for cut in and cut out pressure or by continuous running of the lead compressor unloading, with pressure switch control of lagging compressors. An automatic changeover switch for selection of the lead machine shall be provided for alternation of the duty machine after each cycle. Medical Air Central System Technical Specification for MRCCH NO. 1. ITEM Air Compressor SPECIFICATION

2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13.

14. 15. 16. 17. 18.

A Duplex Medical Air System Oil free, reciprocating piston, 9.2 l/s, 5.5 kW, 380V/3ph/50Hz, max. working pressure 10 bar. After Cooler 25 liter/second nominal flow, 0.12 kW, max working pressure 20 bar. Relief Valve Bonze/brass, 1/2 bottom connection Pressure Indicator Line 0-10 bar range, 2.5 diameter Flexible Connection 1 connection, 60 cm length Ball Valve 1 Brass/bronze, 400 kPa Non Return Valve 1 Brass/bronze, 400 kPa Pressure Switch 0-8 bar adjusting pressure Reservoir Tank Capacity : 800 liter, max. pressure 10 bar Automatic Drain for Reservoir Liquid level sensor system, max. pressure 16 Tank bar Pressure Indicator for Reservoir 0-10 bar range, 4 diameter Tank Coalescing Filter Retain particle and oil aerosol to the size of 0.01 micron with integrated 1 micron pre filter Air Dryer Air flow : 19 liter/second, pressure drop : 0.23 bar, max. pressure : 14.5, type : refrigerated dryer Activated Carbon Filter Residual oil content : 0.003 mg/m3 Sterile Filter Bacterial retention : LRV > 7/cm2 for T1 Coliphagen Air Regulator 0-10 bar range Safety Valve Bronze/brass, 10 bar setting Sample Point Valve Bronze/brass, 400 kPa

10. MEDICAL SUCION SYSTEMS In the design of suction systems, the cost and construction penalty for oversizing the pipework is small. The sme is not true of the sizing of the plant. Over sizing of the plant has a major impact on both cost and construction. For this reason, separate design flow rates for pipelines and for plant calculations should be used.

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 16 of 20

Pipeline vacuum system The design of the suction pipeline system and capacity of the pumps shall be such that an occluded suction of not less than 60 kPa gauge pressure and a free airflow or not less than 40L/min shall be achieved at any one suction point. A minimum of two suction pumps, preferably identical shall be installed with each capable of supplying the design flow rate on its own. Suction pump performance shall be specified in volumetric capacity and free air flow. Noise generated from the plant shall not cause sound pressure levels in adjacent areas to exceed the levels stated in AS 2107 for health buildings. Vibration generated from the plant shall not exceed the levels specified in AS 2625 parts 1-4. Electrical requirements The suction source shall be installed accordance with the electrical requirements of AS 3000. Suction receiver Where a receiver is fitted, its quality of materials, welding and general construction shall be in accordance with AS 1210. The nominal volume of the receiver and pipework should approximate the design flowrate volume per minute of the system. Receiver capacity shall be such that no pumps starts more than 10 times per hour during normal working conditions. Pump inlet filters Pump inlet filters shall be installed to remove solids, particulate matter and free moisture to prevent damage to suction pumps. A duplicated filter assembly complete with isolating valves and pressure differential gauge shall be provided in the pipeline, arranged to enable maintenance or replacement or either filter without interruption to the suction system. Each filter shall be sized not less than the design flow rate. Pump discharge The discharge gases shall be vented outside the pump house to atmosphere well away from any ventilation intake, window and areas normally frequented. Suction pump control Controls shall be provided to activate any additional units automatically should the lead unit of the system be incapable of maintaining adequate supply. Controls shall be arranged so that a failure of one pump control system will not interfere with the correct operation of the remaining plant.

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 17 of 20

Vacuum System Technical Specification for MRCCH NO. 1. ITEM Vacuum Pump SPECIFICATION A Duplex Medical Vacuum System Oil Lubricated Rotary Vane Vacuum Pump, Capacity : 184 m3/hour Bronze/Brass Bronze/Brass 400 kPa 50 cm of length, 1 conn. 0-(-760mm Hg), 4 diameter Bronze/Brass 400 kPa Capacity : 1000 liter, Depnaker Certificate

2. 3. 4. 5. 6. 7. 8. 9.

Non Return Valve 1 conn. Ball Valve 1 Flexible Connection Vacuum Switch Vacuum Indicator Ball Valve for drain Vacuum Tank Bacterial Filter

11. LOCATIONS OF SOURCES OF GAS SUPPLY Cryogenic Liquid Systems The location of cryogenic liquid systems shall comply with the requirements of AS 1894. Stationary cryogenic system shall not be installed over subterrancan structures such as underground bunkers and basement rooms and shall be not less than 5 m away from openings trenches, subterrancan structures, manholes, gullies or sumps and not less than 3 m from public access routes. Stationary cryogenic liquid oxygen vessels shall be installed in a position which is well ventilated, with the control equipment protected from the weather and with the area fenced to prevent unauthorized access. When a cryogenic liquid supply plant is to be filled from road tankers, adequate access for the vehicles shall be provided. The vehicle standing/discharge area shall be a minimum of 3 m square concrete apron and of designed strength to withstand any traffic loads. All parts of the area about the depot on which any liquid oxygen is likely to spill shall be paved with smooth trowelled concrete of a designed strength to withstand any traffic load. Gas Manifold System Gas manifold systems may be installed either outdoors or inside a building with sample natural ventilation to open areas, thus ensuring that risk of oxygen enrichment or deficiency in parts or the building is minimized and that no special hazard exists for operators in the operation of the system. 12. ENCLOSURES FOR SUPPLY SYSTEMS

INSTALLATION REQUIREMENTS FOR PIPELINES Riser and Droppers to Terminal Units

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 18 of 20

The minimum outside diameter of any dropper or riser line should be 12 mm. The minimum outside diameter for copper pipes for suction should be 18 mm. Interconnection No two medical gas piping systems containing different gases or the same supply the same system, each shall be connected through a non-return valve at the junction of the source of supply and the pipelines. Pipeline Supports Medical gas pipelines shall be supported at intervals sufficient to prevent sagging or distortion in accordance with table. Supports shall be of proper strength so that the pipeline cannot be moved accidentally from its position. Supports shall be of suitable material, or treated, to prevent corrosion of both pipe and supports. Medical gas pipelines shall not be used as a support for any other pipelines, including medical gas pipelines or conduits. However, a common support bracket of sufficient strength is permitted to independently support each medical gas pipeline. U-bolt pipe supports shall not be used. Where vertical pipes are exposed in rooms, they shall be secured at floor and ceiling; pipes up to 25 mm shall have at least two intermediate supports. Tabel : Intervals Between Pipeline Support Size of piping, Outside diameter mm 15 20 25 32 40 50 65 80 90 100 and over Intervals for horizontal runs, m 1.5 1.8 2.0 2.0 2.5 2.5 2.5 3.0 3.0 4.0 Intervals for verticals runs, m 1.8 2.0 2.5 2.0 3.0 3.0 3.5 3.5 4.0 4.0

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 19 of 20

G:\STANDARD\MI Spec In Progress (OTD )\Medical Gas\Medical Gases Spec.doc

Page 20 of 20

Você também pode gostar