Você está na página 1de 92

Belimo Aircontrols, Inc.

(USA)

Basic Hydronic Training

BELIMO Aircontrols

Basic Hydronic Training 1

System Components

BELIMO Aircontrols

Basic Hydronic Training 2

Components in a Hydronic System

6 7 1
Source

3
4

1. 2. 3. 4. 5. 6. 7.

Pump Load Control Valve Balancing Valve Source Air Removal System Expansion Unit

Load

BELIMO Aircontrols

Basic Hydronic Training 3

Source Carrier Load


Water, Air, Refrigerant, Electricity

Heating Cooling

Source

Load

Heating Load Cooling Load

BELIMO Aircontrols

Basic Hydronic Training 4

Hydronic Systems
Cooling
43F 40F
Chiller

Heating 245F

45F
Cooling Coil

250F
Boiler

240F
Heating Coil

57F

55F

185F

190F

BELIMO Aircontrols

Basic Hydronic Training 5

Water Systems

Load

Source

Source

Expansion Chamber
Closed System
BELIMO Aircontrols

Open System
Basic Hydronic Training 6

Load

Closed Water Systems


Low Temperature Water (LTW) - Max. 160PSI and max. 250F Medium Temperature Water (MTW) -Max. 160PSI / 250F to 350F High Temperature Water (HTW) -Max. 300 PSI and max. 350F Chilled Water Systems (CWS) - Max. 120 PSI / 40F to 55F (44F or 45F)

BELIMO Aircontrols

Basic Hydronic Training 7

Piping Circuits
Two Pipe System Three Pipe System Four Pipe System Direct and Reverse Return Systems Primary-Secondary System

BELIMO Aircontrols

Basic Hydronic Training 8

Two Pipe System


Main Supply Chilled Water or Heat Water Supply one pipe, Return one pipe Cooling or heating at source Loads must all require cooling or heating coincidentally

BELIMO Aircontrols

Basic Hydronic Training 9

Two Pipe System

Chiller

Boiler

Load

Load

BELIMO Aircontrols

Basic Hydronic Training 10

Load

Two Pipe System

BELIMO Aircontrols

Basic Hydronic Training 11

Three Pipe System

Chiller

Boiler

Load

Load

BELIMO Aircontrols

Basic Hydronic Training 12

Load

Three Pipe System

BELIMO Aircontrols

Basic Hydronic Training 13

Three-Pipe System

BELIMO Aircontrols

Basic Hydronic Training 14

Four Pipe System

BELIMO Aircontrols

Basic Hydronic Training 15

Four Pipe System with One Coil

BELIMO Aircontrols

Basic Hydronic Training 16

Four Pipe System with H&C Coil

BELIMO Aircontrols

Basic Hydronic Training 17

Cost for Four Pipe System


High first cost due to the second water system and the need for either two coils or more costly control valves at each terminal unit. High operating cost due to the two pumps operating, but do provide good flexibility in meeting varying loads.

BELIMO Aircontrols

Basic Hydronic Training 18

Advantages of Four Pipe Systems


All year availability of heating and cooling with individual zone temperature control

Chilled and hot water are typically only simultaneously supplied during the Spring and Fall seasons
Elimination of zoning cost and complexity Simpler changeover decisions The lowest and quietest fan speed is adequate most of the time.

BELIMO Aircontrols

Basic Hydronic Training 19

Piping - Direct Return Piping


Coil #4 0 - 100 gpm

Coil #3 0 - 100 gpm

Coil #2 0 - 100 gpm

Coil #1 0 - 100 gpm

Source

BELIMO Aircontrols

Basic Hydronic Training 20

Piping - Reverse Return Piping


Coil #4 0 - 100 gpm

Coil #3 0 - 100 gpm

Coil #2 0 - 100 gpm

Coil #1 0 - 100 gpm

Source

BELIMO Aircontrols

Basic Hydronic Training 21

Primary Secondary System

Source

Source

Source

Load

Load

BELIMO Aircontrols

Basic Hydronic Training 22

Load

Pipe Design

BELIMO Aircontrols

Basic Hydronic Training 23

Bernoullis Law
pstat pdyn const.

The Bernoullis law is stating the principle of energy conservation. The sum of the two energies represented by static pressure and dynamic pressure is constant between two points in the pipe, assuming no energy exchange with the exterior or transformation of energy into heat by friction between these two points.
BELIMO Aircontrols

Basic Hydronic Training 24

Bernoullis Law

pdyn1
ptotal1 pstatic1

pdyn2

ptotal2

pstatic2

BELIMO Aircontrols

Basic Hydronic Training 25

Z1

V12 2g

P 1
1

Z2

V22 2g

P2
2

hL
V2 P2

hL

V1 P1

Z2
1

Z1
BELIMO Aircontrols

Basic Hydronic Training 26

Pipe Sizing and Pressure Drop Equations


h L f D V2 2g
Darcy-Weisbach Equation

h pressure drop, in ft f friction factor, dimensionl ess (from Moody ) L Length of pipe, ft D Internal Diameter of pipe, in V Fluid average velocity, ft/sec g gravitatio nal constan, 32.2 ft/sec 2
BELIMO Aircontrols

Basic Hydronic Training 27

Sizing a Piping System Pipe Friction Loss


Suggested head loss in range from 1 to 4ft per 100ft - 1997 ASHRAE Handbook-Fundamentals Max. 4 ft/sec velocity in pipe 2 Suggested 4 ft/sec velocity in pipes larger than 2

BELIMO Aircontrols

Basic Hydronic Training 28

Simplified Method
D S Q 0 .4

D = Pipe Diameter Q = Flow Rate, GPM S = Pipe Sizing Constant - S= 0.44, assuming 4 ft head drop/100ft - S = 0.5 assuming 2 ft head drop/ 100ft

BELIMO Aircontrols

Basic Hydronic Training 29

Examples
Load: 100GPM D = SQ0.4 = 0.44 x 1000.4 = 2.78 3

Load: 200GPM D = SQ0.4 = 0.44 x 2000.4 = 3.66 4


Load: 300GPM D = SQ0.4 = 0.44 x 3000.4 = 4.31 4 Load: 400GPM D = SQ0.4 = 0.44 x 4000.4 = 4.83 5
BELIMO Aircontrols

Basic Hydronic Training 30

Head Loss Calculation


Pipes (Friction Loss for Water in Commercial Steel Pipe (Schedule 40) Strainers, Fitting, Elbows, Reduction, etc Valves, Balancing Valves (Valve - Manufacturer)

Head loss Load (Coil, etc.)


Head loss Source (Chiller, etc.)

=Total Head Loss


BELIMO Aircontrols

Basic Hydronic Training 31

Head Loss in Pipes


Head Loss 2.5ft

Pipes (Friction Loss for Water in Commercial Steel Pipe (Schedule 40)

100GPM

Flow Rate

hspec =ft/100ft pipe Total h=L x hspec /100

BELIMO Aircontrols

Basic Hydronic Training 32

Fittings
h V2 k 2g

h = head loss in feet of water k = resistance coefficient for valve or fitting V2/2g = velocity head, ft based on flow gpm in connect pipe (example Figure 2 15 for 2 in) V = fluid velocity, ft/sec g = 32.2 ft/sec2, gravitational constant

BELIMO Aircontrols

Basic Hydronic Training 33

BELIMO Aircontrols

Basic Hydronic Training 34

Which pump do we choose?


Total Pipe length = 300 ft BTU/HR = 500,000 BTU/HR T = 10F GPM = ?

GPM

BTUH T 500

GPM
BELIMO Aircontrols

BTUH T 500

500000 100GPM 10x500


Basic Hydronic Training 35

Chiller

Coil

What is the pipe size?


Required Flow: 100GPM Pipe Diameter: ?
D S Q 0 .4

D = SQ0.4 = 0.44 x 1000.4 = 2.78 3

D = Pipe Diameter Q = Flow Rate, GPM S = Pipe Sizing Constant S= 0.44, assuming 4 ft head loss/100ft S = 0.5 assuming 2 ft head loss/ 100ft
BELIMO Aircontrols

Basic Hydronic Training 36

Head loss elbows?


Pipe: 3, Steel Pipe, screwed Head loss of total elbows?

V2 k 2g
42 0.8 2 32.2 0.2 ft

4 Elbow 0.8ft
BELIMO Aircontrols

Chiller

Basic Hydronic Training 37

Coil

Head loss pipe?


Pipe: 3, Steel Pipe, screwed Total Pipe length = 300 ft

Pipes (Friction Loss for Water in Commercial Steel Pipe (Schedule 40) Figure 2-14 Friction Loss - Water 2.5 ft/100ft

h = 300 x 2.5 /100 = 7.5ft


BELIMO Aircontrols

Chiller

Basic Hydronic Training 38

Coil

Total head loss?


1 Chiller 9 ft (4PSI, Info Manuf.) 1 Cooling Coil 9 ft (4PSI, Info Manuf.) 1 Control Valve 9 ft (4PSI) 1 Balance Valve 3 ft (1PSI) 4 Elbows each 0.2 ft 0.8 ft 1 Pipe System 7.5 ft

Total Head Loss of 38.3ft at 100GPM


Basic Hydronic Training 39

BELIMO Aircontrols

Chiller

Coil

System Curve
80 60

Head (ft)

40

System Point at design load

20

10

Head Loss of 38.3 at 100GPM


0
20 40 60

80

100

120

140

160

180

200

Flow GPM
BELIMO Aircontrols

Basic Hydronic Training 40

Pumps in HVAC

BELIMO Aircontrols

Basic Hydronic Training 41

Pumps in HVAC
Pumps

Dynamic

Displacement

Centrifugal

Special Effect

Reciprocating

Rotary Pumps

Volute Type

Axial Flow Type

Single Suction

Double Suction

BELIMO Aircontrols

Basic Hydronic Training 42

Outlet Flow

Impeller

Inlet Flow

Blade

BELIMO Aircontrols

Basic Hydronic Training 43

Pump Curve

Pump Head

Pump Characteristic

Chiller

Coil

Operating Point
System Head
V

100%

Volume

BELIMO Aircontrols

Basic Hydronic Training 44

Pump Curve (Steep)

Pump Characteristic

Chiller

Coil

Operating Point

100%

Volume

BELIMO Aircontrols

Basic Hydronic Training 45

Pump Curve (Flat)

Pump Characteristic

Chiller

Coil

Operating Point

25%
V

100%

Volume

BELIMO Aircontrols

Basic Hydronic Training 46

Operating Point
Pump Head Capacity Curve
p

Chiller

Coil

Operating Point
Load 100% Flow

100%

System Head Curve

BELIMO Aircontrols

Basic Hydronic Training 47

System Curves for a Pump Type


80 60

7.0 6.5 6.0 5.5 5.0

70%65% 60% 55%

Head (ft)

40

20

10

20

40

60

80

100

120

140

160

180

200

Flow GPM
BELIMO Aircontrols

Motor Horsepower
Basic Hydronic Training 48

Minimum Flow of Pump


Depends on pump construction and energy generated by pump Not enough flow could result in overheating and cavitation Some low power pumps can operate at zero flow Installation of bypass circuit

BELIMO Aircontrols

Basic Hydronic Training 49

Valves in HVAC

BELIMO Aircontrols

Basic Hydronic Training 50

What Control Characteristic is Preferred?


100 90 80

Heat Output (%)

70 60 50 40 30 20 10

Heat Output

10

20

30

40

50

60

70

80

90

100

Control Signal (%)

BELIMO Aircontrols

Basic Hydronic Training 51

What are the Coil Characteristics?


100

Characteristic of a coil Heat Output (%)

90 80 70 60 50 40 30 20 10

Heat Output

10

20

30

40

50

60

70

80

90

100

Valve Opening (%)

BELIMO Aircontrols

Basic Hydronic Training 52

What are the Valve Characteristics?


100

Flow, Heat Output (%)

Characteristic of a Coil

90 80 70 60 50 40 30 20 10

Heat Output

Characteristic of Control Valve

10

20

30

40

50

60

70

80

90

100

Signal (%)

BELIMO Aircontrols

Basic Hydronic Training 53

Valve Characteristics Modified Equal Percentage


100 Lift 90 80 Theoretical Flow Corrected Flow

100 90

100 80 64

100 80 64

Flow (%)

70 60 50 40 30 20

80

70
60 50 40

51
41 33 26 21 17 13.4 10.7

51
41 33 26 19.5 13 6.5 0

Equal % Linear Curve


10 20 30 40 50 60 70 80 90

30 20 10 0 100

10.7

10

Valve Opening (Signal) (%)


BELIMO Aircontrols

Basic Hydronic Training 54

Valve Authority

BELIMO Aircontrols

Basic Hydronic Training 55

Authority of Control Valves with Variable Flow Through the Coil


Authority of two way control valves Authority of three way control valves

BELIMO Aircontrols

Basic Hydronic Training 56

3-way Control Valve


4 4 12

20 psi Const

pv100

pv100 pFlowVariable

pv100 pv 0

A
BELIMO Aircontrols

4 8

0.5
Basic Hydronic Training 57

3-way Control Valve


4
A

12

20 psi Const

pv100

pv100 pFlowVariable

pv100 pv 0

A
BELIMO Aircontrols

4 8

0.5
Basic Hydronic Training 58

3-way Control Valve


41 50% 01
20 psi Const

45

1214

BELIMO Aircontrols

Basic Hydronic Training 59

Valve Authority - Flow 100%


Coil

P Terminal

P Terminal =const
BELIMO Aircontrols

P Valve

Basic Hydronic Training 60

Valve Authority - Flow 50%


Coil

P Terminal

P Terminal =const
BELIMO Aircontrols

P Valve

Basic Hydronic Training 61

Valve Authority - Flow 0%


Coil

P Terminal

P Terminal =const
BELIMO Aircontrols

P Valve

Basic Hydronic Training 62

2-way Control Valve


4 4
12

20 psi VFD

pv100

pv100 pFlowVariable

pv100 pv 0

A
BELIMO Aircontrols

4 20

0.2
Basic Hydronic Training 63

2-way Control Valve


41

416 123

50%

20 psi VFD

BELIMO Aircontrols

Basic Hydronic Training 64

Valve Authority - Flow 100%


Coil

P Terminal

P Valve

BELIMO Aircontrols

Basic Hydronic Training 65

Valve Authority - Flow 50%


Coil

P Terminal

P Valve

BELIMO Aircontrols

Basic Hydronic Training 66

Valve Authority - Flow 0%


Coil

P Terminal

P Terminal =const
BELIMO Aircontrols

P Valve

Basic Hydronic Training 67

Sizing Rules

Authority = 0.4 to 0.5


Min. pvalve = 0.25 p pumphead

BELIMO Aircontrols

Basic Hydronic Training 68

Authority Distortion of Linear Flow Characteristics


100 90 80 0.1 0.2 0.4 0.6 0.8 1 40 30 20 10

Flow (%)

70 60 50

10

20

30

40

50

60

70

80

90

100

Valve Opening (%)


BELIMO Aircontrols

Basic Hydronic Training 69

Authority Distortion of Equal Percentage Flow Characteristics


100 90 80 70

Flow (%)

60 50 40 30 20 10

0.1

0.2
0.4 0.6 0.8 1

10

20

30

40

50

60

70

80

90

100

Valve Opening (%)


BELIMO Aircontrols

Basic Hydronic Training 70

Counter-Flow

Cross-Flow

Parallel-Flow

Counter-flow, cross-flow or parallel-flow heat exchangers are used depending on the application. They have different efficiencies.

BELIMO Aircontrols

Basic Hydronic Training 71

Constant or Variable Flow


e.g. air

Regardless of valve position, the full water flow is always circulating through the heat exchanger => Temperature control

Depending of valve position, 0..100% of the water flow circulates through the heat exchanger

=> Flow control

BELIMO Aircontrols

Basic Hydronic Training 72

Constant or Variable Flow


Prevention of freezing Large outside flow? Dehumidification

yes
no

no

yes

no

yes

Are different temperature levels in coil acceptable?

no
Temperature control constant Flow Variable temperature
BELIMO Aircontrols

yes

yes

Flow Control Constant Temperature Variable Flow


Basic Hydronic Training 73

Diverting Circuit with Mixing Valve


pFV

Coil
var var

var

pV100
100%
100%

BELIMO Aircontrols

Basic Hydronic Training 74

Diverting Circuit with Diverting Valve


pFV

Coil
var var var

pV100
100%
100%

BELIMO Aircontrols

Basic Hydronic Training 75

Throttling Circuit
pFV

Coil
var var

pV100

BELIMO Aircontrols

Basic Hydronic Training 76

Mixing Circuit with Mixing Valve Coil


100% p v100 var 100%

var

var

BELIMO Aircontrols

Basic Hydronic Training 77

Heat Exchanger Characteristics


100 90 80 0.05 0.15 0.25 0.4 0.6 0.8 1 1.5 2 3

Energy (%)

70 60 50 40 30 20 10

Application Pre Heating Coil Heating Coil Cooling Coil Radiators Converters

a-Value 0.25 to 0.4 0.15 to 0.4 0.25 to 0.5 0.5 to 0.65 0.5 3.0

10

20

30

40

50

60

70

80

90

100

Flow (%)

BELIMO Aircontrols

Basic Hydronic Training 78

Heat Exchanger Characteristics


100
90 80

Variable Flow

Energy (%)

70 60 50 40 30 20 10

Constant Flow

10

20

30

40

50

60

70

80

90

100

Flow (%)
BELIMO Aircontrols

Basic Hydronic Training 79

Heat Exchanger Characteristics


100
90 80

T = 10F T = 30F

Energy (%)

70 60 50 40 30 20 10

10

20

30

40

50

60

70

80

90

100

Flow (%)
BELIMO Aircontrols

Basic Hydronic Training 80

Heat Exchanger Characteristics


100
90 80

Heating Coil Cooling Coil

Energy (%)

70 60 50 40 30 20 10

10

20

30

40

50

60

70

80

90

100

Flow (%)
BELIMO Aircontrols

Basic Hydronic Training 81

Influencing Factors
Valve with Hydraulics Heat Exchanger

Base Valve Characteristic

Hydraulic System

System Valve Coil Characteristic Characteristic

Resulting Characteristic

BELIMO Aircontrols

Basic Hydronic Training 82

Conventional Sizing Methods

BELIMO Aircontrols

Basic Hydronic Training 83

Application
Pressure Differential Sensor 10 psi p=2 psi

Coil #4 0 - 100 gpm


p=4 psi Coil #3 0 - 100 gpm p=12 psi p=4 psi Coil #2 0 - 100 gpm p=22 psi p=4 psi Coil #1 0 - 100 gpm p=32 psi p=4 psi

10 psi
p =4 psi

20 psi

20 psi
p =4 psi

30 psi

30 psi
p=4 psi

40 psi
p=4 psi

40 psi

Chiller VFD-Pump
BELIMO Aircontrols

Basic Hydronic Training 84

Application
Pressure Differential Sensor 10 psi p=2 psi

Authority
A=4/10=0.4
Flow/Heat output %

Coil #4 0 - 100 gpm


p=4 psi Coil #3 0 - 100 gpm p=12 psi p=4 psi Coil #2 0 - 100 gpm p=22 psi p=4 psi Coil #1 0 - 100 gpm p=32 psi p=4 psi

p =4 psi

20 psi

p =4 psi

A=4/20=0.2

30 psi

p=4 psi

A=4/30=0.14

40 psi

p=4 psi

A=4/40=0.1
Signal
Basic Hydronic Training 85

Chiller VFD-Pump
BELIMO Aircontrols

Shift to Variable Supply with VFD-Pumps and Two-way Valves 4 4 12

20 psi

Const

4
20 psi

12

VFD
BELIMO Aircontrols

Basic Hydronic Training 86

Authority Method

BELIMO Aircontrols

Basic Hydronic Training 87

Application
Pressure Differential Sensor 10 psi p=2 psi

Coil #1 0 - 100 gpm


p=4 psi Coil #2 0 - 100 gpm

Flow/Heatoutput

p =4 psi

A=0.5

20 psi

p=6 psi

p =10psi

p=4 psi Coil #3 0 - 100 gpm

A=0.5 A=0.5

30 psi p=11 psi

p=15 psi

p=4 psi Coil #4 0 - 100 gpm

40 psi p=16 psi

p=4 psi

p=20 psi

A=0.5
Signal
Basic Hydronic Training 88

Chiller VFD-Pump
BELIMO Aircontrols

Current Concepts for Valve Sizing


Exact calculation f( p and V)
Correct sized components Generally less expensive components, like valves Complex procedures for all involved More detailed information is required Consideration of diversity factors No feedback of sized devices from suppliers

Rule: pvalve = pCoil

Rule: pvalve= 3 5 psi


BELIMO Aircontrols

Very simple rule Used by all involved in the project Good base for price comparison Oversized valves overpriced valves Bad authority Hunting Instable control loops
Basic Hydronic Training 89

Additional Valve Sizing Considerations


Two-way valves: For the close-off pressure the pump head needs to be considered. Three-way valves: Pressure difference valve

For the selection of the valve bodies it is necessary to consider elevation of system, pump pressure and fill pressure
BELIMO Aircontrols

Basic Hydronic Training 90

Reference Literature
Total Hydronic Balancing Robert Petitjean, Tour & Andersson Hydronic AB HVAC Pump Handbook James B. Rishel, McGraw-Hill ASHRAE Handbooks HVAC Equations, Data, and Rules of Thumb Bell, McGraw-Hill

BELIMO Aircontrols

Basic Hydronic Training 92

Thank You

BELIMO Aircontrols

Basic Hydronic Training 93