Transformer is a static device which transforms a.c. Electrical power from one voltage to another voltage keeping the frequency same by electromagnetic induction. Lransformer ls shown ln Lhe ad[acenL flgure. 1he prlmary and secondary colls are wrapped around a core of very hlgh magneLlc permeablllllly, such as lron, so LhaL mosL of Lhe
Transformer is a static device which transforms a.c. Electrical power from one voltage to another voltage keeping the frequency same by electromagnetic induction. Lransformer ls shown ln Lhe ad[acenL flgure. 1he prlmary and secondary colls are wrapped around a core of very hlgh magneLlc permeablllllly, such as lron, so LhaL mosL of Lhe
Direitos autorais:
Attribution Non-Commercial (BY-NC)
Formatos disponíveis
Baixe no formato PDF, TXT ou leia online no Scribd
Transformer is a static device which transforms a.c. Electrical power from one voltage to another voltage keeping the frequency same by electromagnetic induction. Lransformer ls shown ln Lhe ad[acenL flgure. 1he prlmary and secondary colls are wrapped around a core of very hlgh magneLlc permeablllllly, such as lron, so LhaL mosL of Lhe
Direitos autorais:
Attribution Non-Commercial (BY-NC)
Formatos disponíveis
Baixe no formato PDF, TXT ou leia online no Scribd
Transformer is a static device which transforms a.c. electrical power from one voltage to another voltage keeping the frequency same by electromagnetic induction. Lransformer ls shown ln Lhe ad[acenL flgure. CurrenL passlng Lhro magneLlc fleld. 1he prlmary and secondary colls are wrapped around a core of very hlgh magneLlc permeablllLy, such as lron, so LhaL mosL of Lhe magneLlc flux passes Lhrough boLh Lhe prlmary and secondary colls. 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F TRAtSF0RHFRS TRAtSF0RHFRS TRAtSF0RHFRS TRAtSF0RHFRS Pluce oI Observution: ENGINEERING (E Transformer is a static device which transforms a.c. electrical power from one voltage to another voltage keeping the frequency same by electromagnetic induction. Lransformer ls shown ln Lhe ad[acenL flgure. CurrenL passlng Lhro magneLlc fleld. 1he prlmary and secondary colls are wrapped around a core of very hlgh magneLlc permeablllLy, such as lron, so LhaL mosL of Lhe magneLlc flux passes Lhrough boLh Lhe prlmary and secondary colls. 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F TRAtSF0RHFRS TRAtSF0RHFRS TRAtSF0RHFRS TRAtSF0RHFRS Pluce oI Observution:- (E-M) Transformer is a static device which transforms a.c. electrical power from one voltage to another voltage keeping the frequency same by electromagnetic Lransformer ls shown ln Lhe ad[acenL flgure. CurrenL passlng Lhro magneLlc fleld. 1he prlmary and secondary colls are wrapped around a core of very hlgh magneLlc permeablllLy, such as lron, so LhaL mosL of Lhe magneLlc flux passes Lhrough boLh Lhe prlmary and secondary colls. 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F -FRONTIER Transformer is a static device which transforms a.c. electrical power from one voltage to another voltage keeping the frequency same by electromagnetic Lransformer ls shown ln Lhe ad[acenL flgure. CurrenL passlng Lhro magneLlc fleld. 1he prlmary and secondary colls are wrapped around a core of very hlgh magneLlc permeablllLy, such as lron, so LhaL mosL of Lhe magneLlc flux passes Lhrough boLh Lhe 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F 0FSl6t At0 C0tSTRuCTl0t 0F FRONTIER Transformer is a static device which transforms a.c. electrical power from one voltage to another voltage keeping the frequency same by electromagnetic . ASlC PRltClPlFS ASlC PRltClPlFS ASlC PRltClPlFS ASlC PRltClPlFS 1he Lransformer ls based on Lwo prlnclples: flrsL, LhaL an elecLrlc currenL can produce a magneLlc fleld (elecLromagneLlsm), and, second LhaL a changlng magneLlc fleld wlLhln a coll of wlre lnduces a volLage across Lhe ends of Lhe coll ( Changlng Lhe currenL ln Lhe prlmary coll changes Lhe magneLlc flux LhaL ls developed. 1he changlng magneLlc flux lnduces a volLage ln Lhe secondary coll. An ldeal Lransformer ls shown ln Lhe ad[acenL flgure. CurrenL passlng Lhro magneLlc fleld. 1he prlmary and secondary colls are wrapped around a core of very hlgh magneLlc permeablllLy, such as lron, so LhaL mosL of Lhe magneLlc flux passes Lhrough boLh Lhe ASlC PRltClPlFS ASlC PRltClPlFS ASlC PRltClPlFS ASlC PRltClPlFS 1he Lransformer ls based on Lwo prlnclples: flrsL, LhaL an elecLrlc currenL can produce a magneLlc fleld (elecLromagneLlsm), and, second LhaL a changlng magneLlc fleld wlLhln a coll of wlre lnduces a volLage across Lhe ends of Lhe coll ( Changlng Lhe currenL ln Lhe prlmary coll changes Lhe magneLlc flux LhaL ls developed. 1he changlng magneLlc flux lnduces a volLage ln Lhe secondary coll. An ldeal Lransformer ls shown ln Lhe ad[acenL flgure. CurrenL passlng Lhrough Lhe prlmary coll creaLes a magneLlc fleld. 1he prlmary and secondary colls are wrapped around a core of very hlgh magneLlc permeablllLy, such as lron, so LhaL mosL of Lhe magneLlc flux passes Lhrough boLh Lhe ASlC PRltClPlFS ASlC PRltClPlFS ASlC PRltClPlFS ASlC PRltClPlFS 1he Lransformer ls based on Lwo prlnclples: flrsL, LhaL an elecLrlc currenL can produce a magneLlc fleld (elecLromagneLlsm), and, second LhaL a changlng magneLlc fleld wlLhln a coll of wlre lnduces a volLage across Lhe ends of Lhe coll (elecLromagneLlc lnducLlon). Changlng Lhe currenL ln Lhe prlmary coll changes Lhe magneLlc flux LhaL ls developed. 1he changlng magneLlc flux lnduces a volLage ln Lhe secondary coll. An ldeal ugh Lhe prlmary coll creaLes a magneLlc fleld. 1he prlmary and secondary colls are wrapped around a core of very hlgh magneLlc permeablllLy, such as lron, so LhaL mosL of Lhe magneLlc flux passes Lhrough boLh Lhe 1he Lransformer ls based on Lwo prlnclples: flrsL, LhaL an elecLrlc currenL can produce a magneLlc fleld (elecLromagneLlsm), and, second LhaL a changlng magneLlc fleld wlLhln a coll of wlre lnduces a volLage across Lhe elecLromagneLlc lnducLlon). Changlng Lhe currenL ln Lhe prlmary coll changes Lhe magneLlc flux LhaL ls developed. 1he changlng magneLlc flux lnduces a volLage ln Lhe secondary coll. An ldeal ugh Lhe prlmary coll creaLes a magneLlc fleld. 1he prlmary and secondary colls are wrapped around a core of very hlgh magneLlc permeablllLy, such as lron, so LhaL mosL of Lhe magneLlc flux passes Lhrough boLh Lhe 1he Lransformer ls based on Lwo prlnclples: flrsL, LhaL an elecLrlc currenL can produce a magneLlc fleld (elecLromagneLlsm), and, second LhaL a changlng magneLlc fleld wlLhln a coll of wlre lnduces a volLage across Lhe elecLromagneLlc lnducLlon). Changlng Lhe currenL ln Lhe prlmary coll changes Lhe magneLlc flux LhaL ls developed. ugh Lhe prlmary coll creaLes a magneLlc permeablllLy, such as lron, so LhaL mosL of Lhe magneLlc flux passes Lhrough boLh Lhe TYPFS TYPFS TYPFS TYPFS DISTRIBUTION TRANSFORMER POWER CURRENT POTENTIAL FURNACE BOOSTER RECTIFIER LOCOMOTIVE MINING PHASE WELDING HIGH GROUNDING CONVERTER
0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR TRANSORMER WHCH S USED OR THE PURPOSE O DSTRBUTON O POWER. 11KVJqV Is LIe sLundurd voILuge ruLIng. STANDARD KVA ruLIngs ure z,6,1oo,16 S-zoz6 Is LIe NATONA S STANDARD. HAlt FFATuRFS HAlt FFATuRFS HAlt FFATuRFS HAlt FFATuRFS Outdoor, Oil cooled phase Primary is delta connected and secondary is star connected. Naturally cooled Amongst all the transformers this is the most required and most used type.
0F TRAtS 0F TRAtS 0F TRAtS 0F TRAtS DISTRIBUTION TRANSFORMER POWER TRANSFORMER CURRENT TRANSFORMER POTENTIAL FURNACE TRANSFORMER BOOSTER TRANSFORMER RECTIFIER LOCOMOTIVE MINING TRANSFORMER PHASE SHIFTING TRANSFORMER WELDING TRANSFORMER HIGH VOLTAGE TESTING/SC TESTING TRF. GROUNDING CONVERTER
0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR TRANSORMER WHCH S USED OR THE PURPOSE O DSTRBUTON O POWER. 11KVJqV Is LIe sLundurd voILuge ruLIng. STANDARD KVA ruLIngs ure z,6,1oo,16o,zoo,zo,1,qoo,oo,6o,;o,1ooo, zoz6 Is LIe NATONA S STANDARD. HAlt FFATuRFS HAlt FFATuRFS HAlt FFATuRFS HAlt FFATuRFS Outdoor, Oil cooled phase,50HZ Primary is delta connected and secondary is star connected. Naturally cooled Amongst all the transformers this is the most required and most used type. 0F TRAtS 0F TRAtS 0F TRAtS 0F TRAtSF0RHFRS F0RHFRS F0RHFRS F0RHFRS DISTRIBUTION TRANSFORMER TRANSFORMER TRANSFORMER POTENTIAL TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER LOCOMOTIVE TRANSFORMER TRANSFORMER SHIFTING TRANSFORMER TRANSFORMER VOLTAGE TESTING/SC TESTING TRF. GROUNDING TRANSFORMERS CONVERTER TRANSFORMER 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR TRANSORMER WHCH S USED OR THE PURPOSE O DSTRBUTON O 11KVJqV Is LIe sLundurd voILuge ruLIng. STANDARD KVA ruLIngs ure o,zoo,zo,1,qoo,oo,6o,;o,1ooo, zoz6 Is LIe NATONA S STANDARD. HAlt FFATuRFS HAlt FFATuRFS HAlt FFATuRFS HAlt FFATuRFS Outdoor, Oil cooled, 3
Primary is delta connected and secondary is star connected. Naturally cooled (ONAN Amongst all the types of transformers this is the most required and most used type. F0RHFRS F0RHFRS F0RHFRS F0RHFRS DISTRIBUTION TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER SHIFTING TRANSFORMER TRANSFORMER VOLTAGE TESTING/SC TESTING TRF. TRANSFORMERS TRANSFORMER 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR TRANSORMER WHCH S USED OR THE PURPOSE O DSTRBUTON O 11KVJqV Is LIe sLundurd voILuge ruLIng. STANDARD KVA ruLIngs ure o,zoo,zo,1,qoo,oo,6o,;o,1ooo, zoz6 Is LIe NATONA S STANDARD. Primary is delta connected and secondary is star connected. (ONAN type). types of transformers this is the most required and most used type.
SHIFTING TRANSFORMER VOLTAGE TESTING/SC TESTING TRF. 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR 0lSTRluTl0t TRAtSF0RHFR TRANSORMER WHCH S USED OR THE PURPOSE O DSTRBUTON O 11KVJqV Is LIe sLundurd voILuge ruLIng. o,zoo,zo,1,qoo,oo,6o,;o,1ooo, zoz6 Is LIe NATONA S STANDARD. VOLTAGE TESTING/SC TESTING TRF. TRANSORMER WHCH S USED OR THE PURPOSE O DSTRBUTON O o,zoo,zo,1,qoo,oo,6o,;o,1ooo,1zo,1oo,zooo,zoo KVA. TRANSORMER WHCH S USED OR THE PURPOSE O DSTRBUTON O 1zo,1oo,zooo,zoo KVA. TRANSORMER WHCH S USED OR THE PURPOSE O DSTRBUTON O 1zo,1oo,zooo,zoo KVA. TRANSORMER WHCH S USED OR THE PURPOSE O DSTRBUTON O
C0tSTRuCTl0t C0tSTRuCTl0t C0tSTRuCTl0t C0tSTRuCTl0t The transformers for these are made much the same way smaller transformers are made. Most use a "C" or "E" shaped core made from laminations of sheet steel stacked and together with resin or banded together with steel straps. The low current, high voltage primaries are wound from enamel coated copper wire and the high current, low voltage secondaries are wound using a thick ribbon of aluminum or copper insul entire assembly is baked to cure the resin then submerged in a large (usually gray) powder coated steel tank which is then filled with high purity mineral oil, which is inert and non The mineral oil helps on the surface of the oil. The tank is temporarily depressurized to remove any remaining moisture that would cause arcing and is sealed against the weather with a gasket at the top
Cores { Transformers typically have cores made of high permeability silicon steel. The steel has a permeability many times that of free the core thus serves to greatly reduce the magnetizing current, and confine the flux to a path which closely couples the windings. transformer developers soon realized that cores constructed from solid iron resulted in prohibitive eddy designs mitigated this effect with cores consisting of bundles of insulated iron wires. Later designs constructed the core by stacking layers of thin steel laminations, a principle that has remained in use. Each lamination is insulated fro transformer equation indicates a minimum cross Windings: The conducting material used for the windings depends upon the individual turns must be electrically insulated from each other to ensure that the current travels throughout every insulated by DPC (Double Paper
C0tSTRuCTl0t C0tSTRuCTl0t C0tSTRuCTl0t C0tSTRuCTl0t The transformers for these are made much the same way smaller transformers are made. Most use a "C" or "E" shaped core made from laminations of sheet steel stacked and together with resin or banded together with steel straps. The low current, high voltage primaries are wound from enamel coated copper wire and the high current, low voltage secondaries are wound using a thick ribbon of aluminum or copper insul entire assembly is baked to cure the resin then submerged in a large (usually gray) powder coated steel tank which is then filled with high purity mineral oil, which is inert and non The mineral oil helps on the surface of the oil. The tank is temporarily depressurized to remove any remaining moisture that would cause arcing and is sealed against the weather with a gasket at the top Cores {Luminuted cores Transformers typically have cores made of high permeability silicon steel. The steel has a permeability many times that of free the core thus serves to greatly reduce the magnetizing current, and confine the flux to a path which closely couples the windings. transformer developers soon realized that cores constructed from solid iron resulted in prohibitive eddy-current l designs mitigated this effect with cores consisting of bundles of insulated iron wires. Later designs constructed the core by stacking layers of thin steel laminations, a principle that has remained in use. Each lamination is insulated from its neighbors by a thin non transformer equation indicates a minimum cross Windings:- The conducting material used for the windings depends upon the individual turns must be electrically insulated from each other to ensure that the current travels hroughout every turn. Here insulated by DPC (Double Paper
The transformers for these are made much the same way smaller transformers are made. Most use a "C" or "E" shaped core made from laminations of sheet steel stacked and together with resin or banded together with steel straps. The low current, high voltage primaries are wound from enamel coated copper wire and the high current, low voltage secondaries are wound using a thick ribbon of aluminum or copper insul entire assembly is baked to cure the resin then submerged in a large (usually gray) powder coated steel tank which is then filled with high purity mineral oil, which is inert and non The mineral oil helps dissipate heat and protects the transformer from moisture, which will float on the surface of the oil. The tank is temporarily depressurized to remove any remaining moisture that would cause arcing and is sealed against the weather with a gasket at the top Luminuted cores Transformers typically have cores made of high permeability silicon steel. The steel has a permeability many times that of free the core thus serves to greatly reduce the magnetizing current, and confine the flux to a path which closely couples the windings. transformer developers soon realized that cores constructed from solid iron resulted in current losses, and their designs mitigated this effect with cores consisting of bundles of insulated iron wires. Later designs constructed the core by stacking layers of thin steel laminations, a principle that has remained in use. Each lamination is m its neighbors by a thin non transformer equation indicates a minimum cross The conducting material used for the windings depends upon the individual turns must be electrically insulated from each other to ensure that the current travels turn. Here transformers are wound with aluminium or copper strip conductors insulated by DPC (Double Paper The transformers for these are made much the same way smaller transformers are made. Most use a "C" or "E" shaped core made from laminations of sheet steel stacked and together with resin or banded together with steel straps. The low current, high voltage primaries are wound from enamel coated copper wire and the high current, low voltage secondaries are wound using a thick ribbon of aluminum or copper insul entire assembly is baked to cure the resin then submerged in a large (usually gray) powder coated steel tank which is then filled with high purity mineral oil, which is inert and non dissipate heat and protects the transformer from moisture, which will float on the surface of the oil. The tank is temporarily depressurized to remove any remaining moisture that would cause arcing and is sealed against the weather with a gasket at the top Luminuted cores):- Transformers typically have cores made of high permeability silicon steel. The steel has a permeability many times that of free space and the core thus serves to greatly reduce the magnetizing current, and confine the flux to a path which closely couples the windings. Early transformer developers soon realized that cores constructed from solid iron resulted in osses, and their designs mitigated this effect with cores consisting of bundles of insulated iron wires. Later designs constructed the core by stacking layers of thin steel laminations, a principle that has remained in use. Each lamination is m its neighbors by a thin non-conducting layer of insulation transformer equation indicates a minimum cross The conducting material used for the windings depends upon the individual turns must be electrically insulated from each other to ensure that the current travels transformers are wound with aluminium or copper strip conductors insulated by DPC (Double Paper Coating) and Blocks of pressboard The transformers for these are made much the same way smaller transformers are made. Most use a "C" or "E" shaped core made from laminations of sheet steel stacked and together with resin or banded together with steel straps. The low current, high voltage primaries are wound from enamel coated copper wire and the high current, low voltage secondaries are wound using a thick ribbon of aluminum or copper insulated with resin entire assembly is baked to cure the resin then submerged in a large (usually gray) powder coated steel tank which is then filled with high purity mineral oil, which is inert and non dissipate heat and protects the transformer from moisture, which will float on the surface of the oil. The tank is temporarily depressurized to remove any remaining moisture that would cause arcing and is sealed against the weather with a gasket at the top high permeability silicon steel. The steel has a and magnetizing current, and confine the flux to a Early cores constructed from solid iron resulted in consisting of bundles of insulated iron wires. Later designs constructed the core by stacking layers of thin steel laminations, a principle that conducting layer of insulation transformer equation indicates a minimum cross-sectional area for the core to avoid saturation The conducting material used for the windings depends upon the individual turns must be electrically insulated from each other to ensure that the current travels transformers are wound with aluminium or copper strip conductors Coating) and Blocks of pressboard The transformers for these are made much the same way smaller transformers are made. Most use a "C" or "E" shaped core made from laminations of sheet steel stacked and together with resin or banded together with steel straps. The low current, high voltage primaries are wound from enamel coated copper wire and the high current, low voltage secondaries are ated with resin entire assembly is baked to cure the resin then submerged in a large (usually gray) powder coated steel tank which is then filled with high purity mineral oil, which is inert and non dissipate heat and protects the transformer from moisture, which will float on the surface of the oil. The tank is temporarily depressurized to remove any remaining moisture that would cause arcing and is sealed against the weather with a gasket at the top conducting layer of insulation sectional area for the core to avoid saturation The conducting material used for the windings depends upon the application, but in all cases the individual turns must be electrically insulated from each other to ensure that the current travels transformers are wound with aluminium or copper strip conductors Coating) and Blocks of pressboard The transformers for these are made much the same way smaller transformers are made. Most use a "C" or "E" shaped core made from laminations of sheet steel stacked and either glued together with resin or banded together with steel straps. The low current, high voltage primaries are wound from enamel coated copper wire and the high current, low voltage secondaries are ated with resin-impregnated paper. The entire assembly is baked to cure the resin then submerged in a large (usually gray) powder coated steel tank which is then filled with high purity mineral oil, which is inert and non dissipate heat and protects the transformer from moisture, which will float on the surface of the oil. The tank is temporarily depressurized to remove any remaining moisture that would cause arcing and is sealed against the weather with a gasket at the top conducting layer of insulation. The universal sectional area for the core to avoid saturation application, but in all cases the individual turns must be electrically insulated from each other to ensure that the current travels transformers are wound with aluminium or copper strip conductors
The transformers for these are made much the same way smaller transformers are made. Most either glued together with resin or banded together with steel straps. The low current, high voltage primaries are wound from enamel coated copper wire and the high current, low voltage secondaries are impregnated paper. The entire assembly is baked to cure the resin then submerged in a large (usually gray) powder coated steel tank which is then filled with high purity mineral oil, which is inert and non-conductive. dissipate heat and protects the transformer from moisture, which will float on the surface of the oil. The tank is temporarily depressurized to remove any remaining moisture that would cause arcing and is sealed against the weather with a gasket at the top. The universal sectional area for the core to avoid saturation application, but in all cases the individual turns must be electrically insulated from each other to ensure that the current travels transformers are wound with aluminium or copper strip conductors The transformers for these are made much the same way smaller transformers are made. Most together with resin or banded together with steel straps. The low current, high voltage primaries are wound from enamel coated copper wire and the high current, low voltage secondaries are impregnated paper. The entire assembly is baked to cure the resin then submerged in a large (usually gray) powder coated conductive. dissipate heat and protects the transformer from moisture, which will float sectional area for the core to avoid saturation application, but in all cases the individual turns must be electrically insulated from each other to ensure that the current travels transformers are wound with aluminium or copper strip conductors Coolunt:- High temperatures will damage the winding insulation. Small transformers do not generate significant heat and are cooled by air circulation and radiation of heat. Power transformers rated up to several hundred KVA can be adequately cooled by natural convective air-cooling, sometimes assisted by fans. In larger transformers, part of the design problem is removal of heat. Some power transformers are immersed in transformer oil that both cools and insulates the windings. The oil is a highly refined mineral oil that remains stable at transformer operating temperature. Indoor liquid-filled transformers are required by building regulations in many jurisdictions to use a non-flammable liquid, or to be located in fire-resistant rooms. Air-cooled dry transformers are preferred for indoor applications even at capacity ratings where oil-cooled construction would be more economical, because their cost is offset by the reduced building construction cost. Insolution drying:- Construction of oil-filled transformers requires that the insulation covering the windings be thoroughly dried before the oil is introduced. There are several different methods of drying. Common for all is that they are carried out in vacuum environment. For distribution transformers, which are smaller and have a smaller insulation weight, resistance heating can be used. This is a method where current is injected in the windings to heat the insulation. The benefit is that the heating can be controlled very well and it is energy efficient. Terminuls:- Very small transformers will have wire leads connected directly to the ends of the coils, and brought out to the base of the unit for circuit connections. Larger transformers may have heavy bolted terminals, bus bars or high-voltage insulated bushings made of polymers or porcelain. A large bushing can be a complex structure since it must provide careful control of the electric field gradient without letting the transformer leak oil.
PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR MAN RADATORS CONSERVATOR EXPOSON VENT TNG UGS AR REEASE PUG O EVE NDCATOR TAP CHANGER WHEES HVJV BUSHNGS TER VAVES O NG PUG DRAN PUG CABE BOX
PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR MAN TANK RADATORS CONSERVATOR EXPOSON VENT TNG UGS AR REEASE PUG O EVE NDCATOR TAP CHANGER WHEES HVJV BUSHNGS TER VAVES O NG PUG DRAN PUG CABE BOX PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR TANK RADATORS CONSERVATOR EXPOSON VENT TNG UGS AR REEASE PUG O EVE NDCATOR TAP CHANGER
HVJV BUSHNGS TER VAVES O NG PUG DRAN PUG CABE BOX
PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR PARTS 0F TRAtSF0RHFR EXPOSON VENT AR REEASE PUG O EVE NDCATOR HVJV BUSHNGS O NG PUG
TFSTlt6 0F TRAtSF0RHFRS TFSTlt6 0F TRAtSF0RHFRS TFSTlt6 0F TRAtSF0RHFRS TFSTlt6 0F TRAtSF0RHFRS Pluce oI Observution:-TRANS-TECH ENGINEERING Testing of Transformer is done to determine their electrical, thermal and mechanical suitability for the system where they will be used or applied. Most of the tests performed on the transformers are defined in national or international standards created by IEEE, NEMA and ANSI, whose purpose is to define uniform set of tests recognized by both the manufacturer and user.
Here TISTING IS CARRII OLT AS PIR IS-o6.
R0uTltF TFSTS R0uTltF TFSTS R0uTltF TFSTS R0uTltF TFSTS (T0 (T0 (T0 (T0 F CARRlF0 0uT 0t FACH J0) F CARRlF0 0uT 0t FACH J0) F CARRlF0 0uT 0t FACH J0) F CARRlF0 0uT 0t FACH J0)
Measurement of winding resistance Measurement of insulation resistance Separate source voltage withstand test (High Voltage tests on HV & LV) Induced Over voltage Withstand test (DVDF test) Measurement of voltage ratio Measurement of NO LOAD LOSS & current. Measurement of LOAD LOSS & IMPEDENCE.(EFFICIENCY & REGULATION) Oil BDV test.
TYPF TFST TYPF TFST TYPF TFST TYPF TFST
THISI TISTS ARI CARRII OLT ONLY ON ONI TRANSIORMIR OI THI LOT. All routine tests Additionally following tests are included in type tests 1. Lightening Impulse test. 2. Temperature rise test
Additional Impulse test Short circuit test Measurement of zero Phase sequence Impedance test. Measurement of acoustic noise level. Measurement of harmonics of the no load current. Magnetic balance test.
Some TesLs LIuL were observed by us wIIcI were dIscussed Iere brIeIIy.
A continuity test complete circuit). A continuity test is performed by placing a small path. If electron flow is inhibited by broken conductors, damaged component resistance, the circuit is flow of the current. Measures the insulation resistance of HV & LV windings with respect to earth (body between LV & HV winding. NSUATON TESTER OR MEGGER S USED. Recommended Values are 2000Mobms fot nv & 500 Mobms fot lv.
Additional Impulse test Short circuit test Measurement of zero Phase sequence Impedance test. Measurement of acoustic noise level. Measurement of harmonics of the no load current. Magnetic balance test. Some TesLs LIuL were observed by us wIIcI were dIscussed Iere brIeIIy. C0tTltulTY TFST C0tTltulTY TFST C0tTltulTY TFST C0tTltulTY TFST Meusorement oI insolution resistunce continuity test is the checking of an electric circuit to see if current flows (that it is in fact a complete circuit). A continuity test is performed by placing a small path. If electron flow is inhibited by broken conductors, damaged component resistance, the circuit is flow of the current. Measures the insulation resistance of HV & LV windings with respect to earth (body between LV & HV winding. NSUATON TESTER OR MEGGER S USED. Recommended Values are 2000Mobms fot nv & 500 Mobms fot lv.
SPFClAl TFST SPFClAl TFST SPFClAl TFST SPFClAl TFST Additional Impulse test Short circuit test Measurement of zero Phase sequence Impedance test. Measurement of acoustic noise level. Measurement of harmonics of the no load current. Magnetic balance test. Some TesLs LIuL were observed by us wIIcI were dIscussed Iere brIeIIy. C0tTltulTY TFST C0tTltulTY TFST C0tTltulTY TFST C0tTltulTY TFST Meusorement oI insolution resistunce is the checking of an electric circuit to see if current flows (that it is in fact a complete circuit). A continuity test is performed by placing a small path. If electron flow is inhibited by broken conductors, damaged component resistance, the circuit is "open. Measures the insulation resistance of HV & LV windings with respect to earth (body between LV & HV winding. NSUATON TESTER OR MEGGER S USED. Recommended Values are 2000Mobms fot nv & 500 Mobms fot lv. Measurement of zero Phase sequence Impedance test. Measurement of acoustic noise level. Measurement of harmonics of the no load current. Some TesLs LIuL were observed by us wIIcI were Meusorement oI insolution resistunce is the checking of an electric circuit to see if current flows (that it is in fact a complete circuit). A continuity test is performed by placing a small path. If electron flow is inhibited by broken conductors, damaged component Insulation resistance is the resistance Measures the insulation resistance of HV & LV windings with respect to earth (body NSUATON TESTER OR MEGGER S USED. 2000Mobms fot nv & 500 Mobms fot lv. Measurement of zero Phase sequence Impedance test.
Measurement of harmonics of the no load current. Some TesLs LIuL were observed by us wIIcI were Meusorement oI insolution resistunce is the checking of an electric circuit to see if current flows (that it is in fact a complete circuit). A continuity test is performed by placing a small path. If electron flow is inhibited by broken conductors, damaged component resistance is the resistance Measures the insulation resistance of HV & LV windings with respect to earth (body NSUATON TESTER OR MEGGER S USED. 2000Mobms fot nv & 500 Mobms fot lv. Measurement of zero Phase sequence Impedance test. Measurement of harmonics of the no load current. Some TesLs LIuL were observed by us wIIcI were muInIy RouLIne TesLs ure Meusorement oI insolution resistunce is the checking of an electric circuit to see if current flows (that it is in fact a complete circuit). A continuity test is performed by placing a small path. If electron flow is inhibited by broken conductors, damaged component resistance is the resistance Measures the insulation resistance of HV & LV windings with respect to earth (body NSUATON TESTER OR MEGGER S USED.
muInIy RouLIne TesLs ure is the checking of an electric circuit to see if current flows (that it is in fact a complete circuit). A continuity test is performed by placing a small voltage across path. If electron flow is inhibited by broken conductors, damaged component resistance is the resistance offered radially to the axial Measures the insulation resistance of HV & LV windings with respect to earth (body muInIy RouLIne TesLs ure is the checking of an electric circuit to see if current flows (that it is in fact a voltage across the chosen path. If electron flow is inhibited by broken conductors, damaged components, or excessive radially to the axial Measures the insulation resistance of HV & LV windings with respect to earth (body) and muInIy RouLIne TesLs ure is the checking of an electric circuit to see if current flows (that it is in fact a the chosen s, or excessive radially to the axial TuRtS RATl0 TFST TuRtS RATl0 TFST TuRtS RATl0 TFST TuRtS RATl0 TFST
Turns ratio test is very important in order to find out that the transformer has the right ratio corresponding on its rated transformer is subjected to turns ratio test when each phase has equal turns ratio then the transformer is balance. electrical pr tested to verify that their electrical properties have not changed from design specifications. This test measures the voltage ratio as per the customers requirement. V1/V2 = The voltage ratio is equal to the turns ratio in a transformer. Using this principle, the turns ratio is measured with the help of a turns ratio meter. If it is be correct. EquIpmenL
This nothing but the resistance measurement of the windings by applying a small d.c voltage to the winding and measuring the current through the same. The ratio gives the winding resistance, more commonly feasible with windings a resistance resistance by applying skin effect corrections
This is needed for identifying the primary and secondary ph a must for poly phase connections. Both a.c. and d.c methods can be used for detecting the polarities of the induced emfs. The dot method discussed earlier is used to indicate the polarities. The transformer is connected to a low vo as shown in the fig supply voltage Vs is applied to the primary and the readings of the voltmeters V1, V2 and V3 are noted. locations are correct ( connection shown). The beginning and end of the primary and secondary may then be marked by A1 A2 and a1 the voltage rises from A1 to A2 in the primary, at any instant it from a1 to a2 in the secondary. If more secondary present due to taps taken from the TuRtS RATl0 TFST TuRtS RATl0 TFST TuRtS RATl0 TFST TuRtS RATl0 TFST Turns ratio test is very important in order to find out that the transformer has the right ratio corresponding on its rated transformer is subjected to turns ratio test when each phase has equal turns ratio then the transformer is balance. electrical properties of its windings. To ensure continued proper operation, transformers are tested to verify that their electrical properties have not changed from design specifications. This test measures the voltage ratio as per the customers requirement. V1/V2 = N1/N2 The voltage ratio is equal to the turns ratio in a transformer. Using this principle, the turns ratio is measured with the help of a turns ratio meter. If it is be correct. EquIpmenL used: wlt0lt6 RFSlSTAtCF TFST wlt0lt6 RFSlSTAtCF TFST wlt0lt6 RFSlSTAtCF TFST wlt0lt6 RFSlSTAtCF TFST This nothing but the resistance measurement of the windings by applying a small d.c voltage to the winding and measuring the current through the same. The ratio gives the winding resistance, more commonly feasible with windings a resistance resistance by applying skin effect corrections P0lARlTY TFST P0lARlTY TFST P0lARlTY TFST P0lARlTY TFST This is needed for identifying the primary and secondary ph a must for poly phase connections. Both a.c. and d.c methods can be used for detecting the polarities of the induced emfs. The dot method discussed earlier is used to indicate the polarities. The transformer is connected to a low vo as shown in the fig supply voltage Vs is applied to the primary and the readings of the voltmeters V1, V2 and V3 are noted. locations are correct ( connection shown). The beginning and end of the primary and secondary may then be marked by A2 and a1 a2 respectively. If the voltage rises from A1 to A2 in the primary, at any instant it from a1 to a2 in the secondary. If secondary terminals are present due to taps taken from the TuRtS RATl0 TFST TuRtS RATl0 TFST TuRtS RATl0 TFST TuRtS RATl0 TFST Turns ratio test is very important in order to find out that the transformer has the right ratio corresponding on its rated voltage in primary and secondary. For example, three phase transformer is subjected to turns ratio test when each phase has equal turns ratio then the transformer is balance. The proper operation of a transformer relies almost entirely on the operties of its windings. To ensure continued proper operation, transformers are tested to verify that their electrical properties have not changed from design specifications. This test measures the voltage ratio as per the customers requirement. The voltage ratio is equal to the turns ratio in a transformer. Using this principle, the turns ratio is measured with the help of a turns ratio meter. If it is used: Turns Rctiometer wlt0lt6 RFSlSTAtCF TFST wlt0lt6 RFSlSTAtCF TFST wlt0lt6 RFSlSTAtCF TFST wlt0lt6 RFSlSTAtCF TFST This nothing but the resistance measurement of the windings by applying a small d.c voltage to the winding and measuring the current through the same. The ratio gives the winding resistance, more commonly feasible with windings a resistance-bridge method can be used. From the d.c resistance one can get the a.c. resistance by applying skin effect corrections P0lARlTY TFST P0lARlTY TFST P0lARlTY TFST P0lARlTY TFST This is needed for identifying the primary and secondary ph a must for poly phase connections. Both a.c. and d.c methods can be used for detecting the polarities of the induced emfs. The dot method discussed earlier is used to indicate the polarities. The transformer is connected to a low vo as shown in the fig supply voltage Vs is applied to the primary and the readings of the voltmeters V1, V2 and V3 are noted. V1: V2 gives the turns ratio. If V3 reads V1 locations are correct (for the connection shown). The beginning and end of the primary and secondary may then be marked by respectively. If the voltage rises from A1 to A2 in the primary, at any instant it does so from a1 to a2 in the secondary. If terminals are present due to taps taken from the Turns ratio test is very important in order to find out that the transformer has the right ratio voltage in primary and secondary. For example, three phase transformer is subjected to turns ratio test when each phase has equal turns ratio then the The proper operation of a transformer relies almost entirely on the operties of its windings. To ensure continued proper operation, transformers are tested to verify that their electrical properties have not changed from design specifications. This test measures the voltage ratio as per the customers requirement. The voltage ratio is equal to the turns ratio in a transformer. Using this principle, the turns ratio is measured with the help of a turns ratio meter. If it is Rctiometer wlt0lt6 RFSlSTAtCF TFST wlt0lt6 RFSlSTAtCF TFST wlt0lt6 RFSlSTAtCF TFST wlt0lt6 RFSlSTAtCF TFST This nothing but the resistance measurement of the windings by applying a small d.c voltage to the winding and measuring the current through the same. The ratio gives the winding resistance, more commonly feasible with bridge method can be used. From the d.c resistance one can get the a.c. resistance by applying skin effect corrections This is needed for identifying the primary and secondary ph a must for poly phase connections. Both a.c. and d.c methods can be used for detecting the polarities of the induced emfs. The dot method discussed earlier is used to indicate the polarities. The transformer is connected to a low vo as shown in the fig supply voltage Vs is applied to the primary and the readings of the voltmeters V2 gives the turns ratio. If V3 reads V1 connection shown). The beginning secondary may then be marked by respectively. If the voltage rises from A1 to A2 in does so from a1 to a2 in the secondary. If present due to taps taken from the Turns ratio test is very important in order to find out that the transformer has the right ratio voltage in primary and secondary. For example, three phase transformer is subjected to turns ratio test when each phase has equal turns ratio then the The proper operation of a transformer relies almost entirely on the operties of its windings. To ensure continued proper operation, transformers are tested to verify that their electrical properties have not changed from design specifications. This test measures the voltage ratio as per the customers requirement. The voltage ratio is equal to the turns ratio in a transformer. Using this principle, the turns ratio is measured with the help of a turns ratio meter. If it is correct, Rctiometer This nothing but the resistance measurement of the windings by applying a small d.c voltage to the winding and measuring the current through the same. The ratio gives the winding resistance, more commonly feasible with high voltage windings. For low voltage bridge method can be used. From the d.c resistance one can get the a.c. resistance by applying skin effect corrections This is needed for identifying the primary and secondary ph a must for poly phase connections. Both a.c. and d.c methods can be used for detecting the polarities of the induced emfs. The dot method discussed earlier is used to indicate the polarities. The transformer is connected to a low voltage a.c. source with the connections made as shown in the fig supply voltage Vs is applied to the primary and the readings of the voltmeters V2 gives the turns ratio. If V3 reads V1 Turns ratio test is very important in order to find out that the transformer has the right ratio voltage in primary and secondary. For example, three phase transformer is subjected to turns ratio test when each phase has equal turns ratio then the The proper operation of a transformer relies almost entirely on the operties of its windings. To ensure continued proper operation, transformers are tested to verify that their electrical properties have not changed from design specifications. This test measures the voltage ratio as per the customers requirement. The voltage ratio is equal to the turns ratio in a transformer. Using this principle, the turns ratio is correct, then the voltage ratio is assumed to This nothing but the resistance measurement of the windings by applying a small d.c voltage to the winding and measuring the current through the same. The ratio gives the high voltage windings. For low voltage bridge method can be used. From the d.c resistance one can get the a.c. This is needed for identifying the primary and secondary phasor polarities. It is a must for poly phase connections. Both a.c. and d.c methods can be used for detecting the polarities of the induced emfs. The dot method discussed earlier is used to indicate the ltage a.c. source with the connections made as shown in the fig supply voltage Vs is applied to the primary and the readings of the voltmeters V2 gives the turns ratio. If V3 reads V1 Turns ratio test is very important in order to find out that the transformer has the right ratio voltage in primary and secondary. For example, three phase transformer is subjected to turns ratio test when each phase has equal turns ratio then the The proper operation of a transformer relies almost entirely on the operties of its windings. To ensure continued proper operation, transformers are tested to verify that their electrical properties have not changed from design specifications. This test measures the voltage ratio as per the customers requirement. The voltage ratio is equal to the turns ratio in a transformer. Using this principle, the turns ratio is then the voltage ratio is assumed to This nothing but the resistance measurement of the windings by applying a small d.c voltage to the winding and measuring the current through the same. The ratio gives the high voltage windings. For low voltage bridge method can be used. From the d.c resistance one can get the a.c. asor polarities. It is a must for poly phase connections. Both a.c. and d.c methods can be used for detecting the polarities of the induced emfs. The dot method discussed earlier is used to indicate the ltage a.c. source with the connections made as shown in the fig supply voltage Vs is applied to the primary and the readings of the voltmeters V2 gives the turns ratio. If V3 reads V1V2 then assumed dot Turns ratio test is very important in order to find out that the transformer has the right ratio voltage in primary and secondary. For example, three phase transformer is subjected to turns ratio test when each phase has equal turns ratio then the The proper operation of a transformer relies almost entirely on the operties of its windings. To ensure continued proper operation, transformers are tested to verify that their electrical properties have not changed from design specifications. The voltage ratio is equal to the turns ratio in a transformer. Using this principle, the turns ratio is then the voltage ratio is assumed to
d.c voltage to the winding and measuring the current through the same. The ratio gives the high voltage windings. For low voltage bridge method can be used. From the d.c resistance one can get the a.c. a must for poly phase connections. Both a.c. and d.c methods can be used for detecting the polarities of the induced emfs. The dot method discussed earlier is used to indicate the ltage a.c. source with the connections made as shown in the fig supply voltage Vs is applied to the primary and the readings of the voltmeters V2 then assumed dot operties of its windings. To ensure continued proper operation, transformers are The voltage ratio is equal to the turns ratio in a transformer. Using this principle, the turns ratio is then the voltage ratio is assumed to d.c voltage to the winding and measuring the current through the same. The ratio gives the high voltage windings. For low voltage bridge method can be used. From the d.c resistance one can get the a.c. ltage a.c. source with the connections made as shown in the fig supply voltage Vs is applied to the primary and the readings of the voltmeters V2 then assumed dot windings they can be labeled as a3, a4, a5, a6. It is the voltage rising from smaller number towards larger ones in each winding. The same thing holds good if more secondaries are present. Fig. 18(b) shows the secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity is correct. If the meter kicks back the assumed polarity is wrong.
0PFt ClRCu 0PFt ClRCu 0PFt ClRCu 0PFt ClRCu
Meusorement oI NO LOA LOSS & corrent.
The Open circuit test determine the impedance in the excitation branch of a real transformer. Methods The secondary windings of applied to the primary winding. Since the impedance of the series winding of the transformer is very small compared to that of the excitation branch, all of the input voltage is dropped the excitation branch. Current, voltage and power are measured at the primary winding to ascertain the admittance and power factor angle. The iron losses and no load current are measured in this test. The 433V winding is charged at 433V supply & the load is the no load loss in the transformer. Effect of actual frequency must be taken into account. EquIpmenL Wcttmeters or pouer cnclser
windings they can be labeled as a3, a4, a5, a6. It is the voltage rising from smaller number towards larger ones in each winding. The same thing holds good if more secondaries are present. b) shows the secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity is correct. If the meter kicks back the assumed polarity is wrong. 0PFt ClRCu 0PFt ClRCu 0PFt ClRCu 0PFt ClRCulT TFST lT TFST lT TFST lT TFST Meusorement oI NO LOA LOSS & corrent. Open circuit test determine the impedance in the excitation branch of a real transformer. Methods The secondary windings of applied to the primary winding. Since the impedance of the series winding of the transformer is very small compared to that of the excitation branch, all of the input voltage is dropped the excitation branch. Current, voltage and power are measured at the primary winding to ascertain the admittance and power factor angle. The iron losses and no load current are measured in this test. The 433V winding is charged at 433V supply & the 11KV winding is left open .The power consumed by the transformer at no load is the no load loss in the transformer. Effect of actual frequency must be taken into
EquIpmenL used: Wcttmeters or pouer cnclser windings they can be labeled as a3, a4, a5, a6. It is the voltage rising from smaller number towards larger ones in each winding. The same thing holds good if more secondaries are present. b) shows the D.C. method of testing the polarity. When the switch S is closed if the secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity is correct. If the meter kicks back the assumed polarity is wrong. lT TFST lT TFST lT TFST lT TFST Meusorement oI NO LOA LOSS & corrent. Open circuit test, or "no-load test", is one of the methods used in electrical engineering to determine the impedance in the excitation branch of a real transformer. The secondary windings of the transformer are left open applied to the primary winding. Since the impedance of the series winding of the transformer is very small compared to that of the excitation branch, all of the input voltage is dropped the excitation branch. Current, voltage and power are measured at the primary winding to ascertain the admittance and The iron losses and no load current are measured in this test. The 433V winding is charged at 11KV winding is left open .The power consumed by the transformer at no load is the no load loss in the transformer. Effect of actual frequency must be taken into used: Wcttmeters or pouer windings they can be labeled as a3, a4, a5, a6. It is the voltage rising from smaller number towards larger ones in each winding. The same thing holds good if more secondaries are present. . method of testing the polarity. When the switch S is closed if the secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity is correct. If the meter kicks back the assumed polarity is wrong. Meusorement oI NO LOA LOSS & corrent. load test", is one of the methods used in electrical engineering to determine the impedance in the excitation branch of a real transformer. the transformer are left open applied to the primary winding. Since the impedance of the series winding of the transformer is very small compared to that of the excitation branch, all of the input voltage is dropped Current, voltage and power are measured at the primary winding to ascertain the admittance and The iron losses and no load current are measured in this test. The 433V winding is charged at 11KV winding is left open .The power consumed by the transformer at no load is the no load loss in the transformer. windings they can be labeled as a3, a4, a5, a6. It is the voltage rising from smaller number towards larger ones in each winding. The same thing holds good if more secondaries are present. . method of testing the polarity. When the switch S is closed if the secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity is correct. If the meter kicks back the assumed polarity is wrong. Meusorement oI NO LOA LOSS & corrent. load test", is one of the methods used in electrical engineering to determine the impedance in the excitation branch of a real transformer. the transformer are left open- applied to the primary winding. Since the impedance of the series winding of the transformer is very small compared to that of the excitation branch, all of the input voltage is dropped Current, voltage and power are measured at the primary winding to ascertain the admittance and The iron losses and no load current are measured in this test. The 433V winding is charged at 11KV winding is left open .The power consumed by the transformer at no windings they can be labeled as a3, a4, a5, a6. It is the voltage rising from smaller number towards larger ones in each winding. The same thing holds good if more secondaries are present. . method of testing the polarity. When the switch S is closed if the secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity is correct. If the meter kicks back the assumed polarity is wrong. Meusorement oI NO LOA LOSS & corrent. load test", is one of the methods used in electrical engineering to determine the impedance in the excitation branch of a real transformer. -circuited while a full applied to the primary winding. Since the impedance of the series winding of the transformer is very small compared to that of the excitation branch, all of the input voltage is dropped Current, voltage and power are measured at the primary winding to ascertain the admittance and The iron losses and no load current are measured in this test. The 433V winding is charged at 11KV winding is left open .The power consumed by the transformer at no windings they can be labeled as a3, a4, a5, a6. It is the voltage rising from smaller number towards larger ones in each winding. The same thing holds good if more secondaries are present. . method of testing the polarity. When the switch S is closed if the secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity is load test", is one of the methods used in electrical engineering to determine the impedance in the excitation branch of a real transformer. circuited while a full-rated voltage is applied to the primary winding. Since the impedance of the series winding of the transformer is very small compared to that of the excitation branch, all of the input voltage is dropped Current, voltage and power are measured at the primary winding to ascertain the admittance and The iron losses and no load current are measured in this test. The 433V winding is charged at 11KV winding is left open .The power consumed by the transformer at no windings they can be labeled as a3, a4, a5, a6. It is the voltage rising from smaller number towards larger ones in each winding. The same thing holds good if more secondaries are present. . method of testing the polarity. When the switch S is closed if the secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity is load test", is one of the methods used in electrical engineering to rated voltage is applied to the primary winding. Since the impedance of the series winding of the transformer is very small compared to that of the excitation branch, all of the input voltage is dropped across Current, voltage and power are measured at the primary winding to ascertain the admittance and The iron losses and no load current are measured in this test. The 433V winding is charged at 11KV winding is left open .The power consumed by the transformer at no towards larger ones in each winding. The same thing holds good if more secondaries are present. secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity is load test", is one of the methods used in electrical engineering to rated voltage is applied to the primary winding. Since the impedance of the series winding of the transformer is across Current, voltage and power are measured at the primary winding to ascertain the admittance and The iron losses and no load current are measured in this test. The 433V winding is charged at 11KV winding is left open .The power consumed by the transformer at no
SH0RT SH0RT SH0RT SH0RT
The purpose of circuit. as the name suggests, in this test primary applied voltage, the current and power input are measured keeping the secondary terminals short circuited. respectively. The supply voltage required to circulate rated current through the transformer is usually very small and is of the order of a few percent of the nominal voltage. The excitation current which is only 1% or and hence is neglected. The shunt branch is thus assumed to be absent. W copper losses in primary and secondary put together. The reactive power consumed is that absorbed by the leakage reactance of the two windings.
Procedore For carrying short circuit test on power transformer: Isolate the power transformer from service. Remove HV/LV jumps disconnect neutral from earth/ground. Short LV phases and connect these short circuited terminals to neutral Energise HV side by LV supply. Measure current in neutral, LV line voltages, HV voltage and HV line currents. Analysis If neutral current is ne If neutral current is higher or equal to line current between LV phase one of the winding is ope
SH0RT SH0RT SH0RT SH0RT ClRCulT TFST ClRCulT TFST ClRCulT TFST ClRCulT TFST The purpose of short circuit circuit. as the name suggests, in this test primary applied voltage, the current and power input are measured keeping the secondary terminals short circuited. respectively. The supply voltage required to circulate rated current through the transformer is usually very small and is of the order of a few percent of the nominal voltage. The excitation current which is only 1% or and hence is neglected. The shunt branch is thus assumed to be absent. W copper losses in primary and secondary put together. The reactive power consumed is that bed by the leakage reactance of the two windings.
Procedore For carrying short circuit test on power transformer: Isolate the power transformer from service. Remove HV/LV jumps and disconnect neutral from earth/ground. Short LV phases and connect these short circuited terminals to neutral Energise HV side by LV supply. Measure current in neutral, LV line voltages, HV voltage and HV line currents. Analysis If neutral current is ne If neutral current is higher or equal to line current between LV phase one of the winding is open
ClRCulT TFST ClRCulT TFST ClRCulT TFST ClRCulT TFST short circuit test circuit. as the name suggests, in this test primary applied voltage, the current and power input are measured keeping the secondary terminals short circuited. respectively. The supply voltage required to circulate rated current through the transformer is usually very small and is of the order of a few percent of the nominal voltage. The excitation current which is only 1% or less even at rated voltage becomes negligibly small during this test and hence is neglected. The shunt branch is thus assumed to be absent. W copper losses in primary and secondary put together. The reactive power consumed is that bed by the leakage reactance of the two windings.
For carrying short circuit test on power transformer: Isolate the power transformer from Remove HV/LV disconnect neutral from earth/ground. Short LV phases and connect these short circuited terminals to neutral Energise HV side by LV supply. Measure current in neutral, LV line voltages, HV voltage and HV line currents. If neutral current is near to zero transformer windings are operational. If neutral current is higher or equal to line current between LV phase one of the winding test is to determine the series branch parameters of the equivalent circuit. as the name suggests, in this test primary applied voltage, the current and power input are measured keeping the secondary terminals short circuited. respectively. The supply voltage required to circulate rated current through the transformer is usually very small and is of the order of a few percent of the nominal voltage. The excitation less even at rated voltage becomes negligibly small during this test and hence is neglected. The shunt branch is thus assumed to be absent. W copper losses in primary and secondary put together. The reactive power consumed is that bed by the leakage reactance of the two windings.
Short LV phases and connect these short circuited terminals to neutral Energise HV side by LV supply. Measure current in neutral, LV line voltages, HV voltage and HV line currents. ar to zero transformer windings are operational. If neutral current is higher or equal to line current between LV phase one of the winding is to determine the series branch parameters of the equivalent circuit. as the name suggests, in this test primary applied voltage, the current and power input are measured keeping the secondary terminals short circuited. respectively. The supply voltage required to circulate rated current through the transformer is usually very small and is of the order of a few percent of the nominal voltage. The excitation less even at rated voltage becomes negligibly small during this test and hence is neglected. The shunt branch is thus assumed to be absent. W copper losses in primary and secondary put together. The reactive power consumed is that bed by the leakage reactance of the two windings.
Short LV phases and connect these short circuited terminals to neutral Measure current in neutral, LV line voltages, HV voltage and HV line currents. ar to zero transformer windings are operational. If neutral current is higher or equal to line current between LV phase one of the winding is to determine the series branch parameters of the equivalent circuit. as the name suggests, in this test primary applied voltage, the current and power input are measured keeping the secondary terminals short circuited. Let these values be V respectively. The supply voltage required to circulate rated current through the transformer is usually very small and is of the order of a few percent of the nominal voltage. The excitation less even at rated voltage becomes negligibly small during this test and hence is neglected. The shunt branch is thus assumed to be absent. W copper losses in primary and secondary put together. The reactive power consumed is that Short LV phases and connect these short circuited terminals to neutral Measure current in neutral, LV line voltages, HV voltage and HV line currents. ar to zero transformer windings are operational. If neutral current is higher or equal to line current between LV phase one of the winding is to determine the series branch parameters of the equivalent circuit. as the name suggests, in this test primary applied voltage, the current and power input are Let these values be V respectively. The supply voltage required to circulate rated current through the transformer is usually very small and is of the order of a few percent of the nominal voltage. The excitation less even at rated voltage becomes negligibly small during this test and hence is neglected. The shunt branch is thus assumed to be absent. W sc is the sum of the copper losses in primary and secondary put together. The reactive power consumed is that Short LV phases and connect these short circuited terminals to neutral Measure current in neutral, LV line voltages, HV voltage and HV line currents. ar to zero transformer windings are operational. If neutral current is higher or equal to line current between LV phase one of the winding is to determine the series branch parameters of the equivalent circuit. as the name suggests, in this test primary applied voltage, the current and power input are Let these values be V sc , I sc and W respectively. The supply voltage required to circulate rated current through the transformer is usually very small and is of the order of a few percent of the nominal voltage. The excitation less even at rated voltage becomes negligibly small during this test is the sum of the copper losses in primary and secondary put together. The reactive power consumed is that Measure current in neutral, LV line voltages, HV voltage and HV line currents. If neutral current is higher or equal to line current between LV phase one of the winding is to determine the series branch parameters of the equivalent circuit. as the name suggests, in this test primary applied voltage, the current and power input are and W sc
respectively. The supply voltage required to circulate rated current through the transformer is usually very small and is of the order of a few percent of the nominal voltage. The excitation less even at rated voltage becomes negligibly small during this test is the sum of the copper losses in primary and secondary put together. The reactive power consumed is that If neutral current is higher or equal to line current between LV phase one of the winding l0A0 TFST l0A0 TFST l0A0 TFST l0A0 TFST
Meusorement oI LOA LOSS & IMPIINCI. {IIIICIINCY & RIGLLATION)
Load Test helps to determine the total loss that takes place, when the transformer is loaded. Unlike the tests described previously, in the present case nominal voltage is applied across the primary and rated current is drown from the secondary. Load test is used mainly
1. To determine the rated load of the machine and the temperature rise 2. To determine the voltage regulation and efficiency of the transformer.
This test measures the power consumed by the transformer when the 433V winding is short circuited and the rated current is passed through the 11KV winding. EquIpmenL used: Wcttmeters or pouer cnclser.
This test checks the insulation property between Primary to earth, Secondary to earth and between Primary & Secondary.
HV IIgI voILuge LesL: Lv wlndlng connecLed LogeLher and earLhed. Pv wlndlng connecLed LogeLher and glven 73 of 28 kv (for 11kv Lransformer) for 1 mlnuLe. V IIgI VoILuge LesL: Pv wlndlng connecLed LogeLher and earLhed. Lv wlndlng connecLed LogeLher and glven 73 of 3 kv for 1 mlnuLe. EquIpmenL used: High Voltage tester (100KV & 3KV)
lHPulSF TFST lHPulSF TFST lHPulSF TFST lHPulSF TFST This test is made to prove that the transformer insulation will withstand voltage surges which may be caused by lightning or switching; this includes insulation to ground, insulation between turns and windings, and the flashover value of the associated bushings. A high-voltage wave of standard values, and approximating a lightning surge, is imposed on the unit to be tested. The surge generator usually consists of a number of capacitors connected so that they be charged in parallel from a relatively low-voltage source and discharged in series to give a high voltage across the test piece. A standard impulse wave is illustrated below;
The standard wave reaches its peak voltage value in 1.5 microseconds and reduces to half the voltage value in 40 microseconds. The value of the voltage applied depends on the rating of the insulation, and may vary from 5 to 30 times the voltage rating of the insulation. Since rather elaborate and costly equipment is needed, impulse tests are usually performed only on large station-type power transformers, and rarely made after they leave the factory.
Motor Generutor Set This test setup is generally used to perform induced voltage test on the transformers. This set up consists of the used motor and generator combination to develop the required voltage and frequency. It is used to find the insulation break down of the conductors from turns to turns and layers to layers. It is an insulation test for the transformers. For an 11KV/433V transformer, 866 Volts are applied at the 433V winding with the help of a Generator for 1 minute. This induces 22KV on 11KV side. The frequency of the 866V supply is also increased to 100HZ. EquIpmenL used: MO1Ok CNkA1Ok 51 Technicul SpeciIicutions motor set Input to Output Output Capacity : Depending upon KVA rating of the under test Transformer Direction of the Dimmer
0ll 0v TFST 0ll 0v TFST 0ll 0v TFST 0ll 0v TFST
Oil breakdown voltage is checked as per IS 100 mm L X 70 mm B X 80 mm Ht. glass pot. 500ml Oil sample. Spherical electrodes with gap of 2.5 mm Recommended EquIpmenL
Technicul SpeciIicutions motor set: Input to motor: Output voltage: Output frequency : Double of Input Capacity : Depending upon KVA rating of the under test Transformer Direction of the Dimmer stat: 0ll 0v TFST 0ll 0v TFST 0ll 0v TFST 0ll 0v TFST Oil breakdown voltage is checked as per IS 100 mm L X 70 mm B X 80 mm Ht. glass pot. 500ml Oil sample. Spherical electrodes with gap of 2.5 mm Recommended vuIue: EquIpmenL used:
Technicul SpeciIicutions motor: 415 V three phase, 50 Hz. voltage: 100 to 900 V AC. frequency : Double of Input Capacity : Depending upon KVA rating of the under test Transformer Direction of the motor: Should be clockwise. Apply dimmer stat to the generator terminals. Oil breakdown voltage is checked as per IS 100 mm L X 70 mm B X 80 mm Ht. glass pot. Spherical electrodes with gap of 2.5 mm vuIue: 6oKV used: DIL DV TEST SET Technicul SpeciIicutions oI u typicul 415 V three phase, 50 Hz. 100 to 900 V AC. frequency : Double of Input Capacity : Depending upon KVA rating of the Should be clockwise. Apply dimmer stat to the generator terminals. Oil breakdown voltage is checked as per IS-335. 100 mm L X 70 mm B X 80 mm Ht. glass pot. Spherical electrodes with gap of 2.5 mm 6oKV DIL DV TEST SET oI u typicul 415 V three phase, 50 Hz. Frequency Capacity : Depending upon KVA rating of the Should be clockwise. Apply dimmer stat to the generator terminals. 335. 100 mm L X 70 mm B X 80 mm Ht. glass pot. DIL DV TEST SET.
Apply dimmer stat to the generator terminals. A Sumple dutu sheet oI Testing Ior u g KVA 11[.q KV TrunsIormer is given here:- Resistance Test
H.T. Side
129.7 129.1 130.0 L.T. Side 55.3m 55.3m 56.7m
High Voltage Test
Side Voltage Given Time period of Observation H.T. Side 21 KV (75% of 28 KV) 1 min L.T. Side 2250 V (75% of 3 KV) 1 min.
DVDF Test Voltage Given Frequency given Time period of Observation 866V (2x433 V) 100 HZ (2x50 HZ) 1 min.
Turns Ratio Test Ratio=1:44 Deviation (0.5%) Centridian (0.1%) -0.2 0.04 -0.29 0.07 -0.09 0.08
No-Load Test
V(Volt) I(Ampere) W1(Watt) W2(Watt) mf 433 V 0.2 A 32 W 8 W 2x2
Load Test
V1(H.V.) V2(L.V) I1(H.V.) I2(L.V.) W1 W2 mf 500 V 1.31 V 0.65A 33.3 A 0 W 70 W 4x2 So preciselg Tronsformers Testing con he dioided into
So preciselg Tronsformers Testing con he dioided into
So preciselg Tronsformers Testing con he dioided into
8ouLlne 1esL ConLlnulLy 1esL no Load 1esL Load 1esL 1urns 8aLlo 1esL Wlndlng 8eslsLance 1esL uvul 1esL Plgh volLage 1esL Cll 8uv 1esL So preciselg Tronsformers Testing con he dioided into
1ransformers 1esLlng 8ouLlne 1esL ConLlnulLy 1esL no Load 1esL Load 1esL 1urns 8aLlo 1esL Wlndlng 8eslsLance 1esL uvul 1esL Plgh volLage 1esL Cll 8uv 1esL 1ype 1esL lmpulse 1esL 1emperaLure 8lse So preciselg Tronsformers Testing con he dioided into
1ransformers 1esLlng 1ype 1esL LlghLenlng lmpulse 1esL 1emperaLure 8lse 1esL So preciselg Tronsformers Testing con he dioided into
1emperaLure 8lse Speclal 1esL ShorL ClrculL MagneLlc 8alance 1esL So preciselg Tronsformers Testing con he dioided into Speclal 1esL ShorL ClrculL 1esL MagneLlc 8alance 1esL So preciselg Tronsformers Testing con he dioided into: